5 th 500 kVAr3 481 Amps 480 Volts 384.9 Amps 4.7 th 0.7200 2.1600 0.0326 403.2 Amps 503.9 Amps 1500 kVA3 6.00 % 30.00 % Fund 42.7 Amps
Power System Fundamental Frequency: Capacitor Bank Voltage Rating: Capacitor Unit Frequency Rating: Derated Capacitor Bank Rating: Total Harmonic Nonlinear Load: Filter Tuning Frequency (x Fundamental): Capacitor Bank Capacitance (wye): Capacitor Bank Capacitance (delta): Harmonic Filter Reactor Inductance: Fundamental Frequency Compensation: Utility Side Voltage Distortion (Vh): (Utility Harmonic Voltage Source) Nonlinear Load Harmonic Current: Maximum Total Harmonic Current:
60 Hz 600 Volts 60 Hz 320 kVAr3 500 kVA3 282 Hz 3684.15 F 1228.05 F 0.0865 mH 335 kVAr3 1.00 % 180.4 Amps 223.1 Amps
CAPACITOR BANK DUTY CALCULATIONS: Harmonic Filter Bank RMS Current: Harmonic Capacitor Bank Voltage: RMS Capacitor Bank Voltage: 460.8 Amps 55.6 Volts 32.1 VoltsG 505.8 Volts 292.0 VoltsG Capacitor Bank Voltage (Fundamental): Maximum Peak Voltage (Fundamental): 502.8 Volts 290.3 VoltsG 558.4 Volts 322.4 VoltsG 626.2 Amps
480 Volt Bus
CAPACITOR LIMITS: (IEEE Standard 18-2002) Peak Voltage: RMS Current: KVAr: RMS Voltage: Limit 100% 100% 100% 100% Contingency 120% 135% 135% 110% Actual 93.1% 95.8% 80.7% 84.3%
Xl =
0.0326
HARMONIC FILTER REACTOR DESIGN SPECIFICATIONS: Filter Reactor Reactance: Fundamental Frequency Current: RMS Current Requirement: 0.0326 403.2 Amps 460.8 Amps Filter Reactor Inductance: Harmonic Current: Voltage Requirement: 0.0865 mH 223.1 Amps 277.1 VoltsG
TOLERANCE EVALUATION, QUALITY FACTOR, AND PARALLEL RESONANCE CHECK: Capacitor Tolerance: Reactor Tolerance: Filter Reactor X/R Ratio: 0.00 2.50 4.00 + 10.00 2.50
ftuned fno min al 1 (1 t r )(1 t c )
Information contained in this document is subject to change without notice. Electrotek assumes no responsibility for any damages resulting from use of the information contained within. Copyright 2000-2012 Electrotek Concepts, Inc. All rights reserved.