You are on page 1of 133

Universidad de San Carlos de Guatemala Facultad de Ingeniera Escuela de Ingeniera Mecnica Elctrica

METODOLOGA DE PLANIFICACIN Y EXPANSIN PARA EL DISEO DE REDES ELCTRICAS DE DISTRIBUCIN RADIALES-URBANAS.

Alex Vicente Girn Castillo Asesorado por el Ing. Juan Fernando Castro Martnez

Guatemala, mayo de 2006

UNIVERSIDAD DE SAN CARLOS DE GUATEMALA

FACULTAD DE INGENIERA

METODOLOGA DE PLANIFICACIN Y EXPANSIN PARA EL DISEO DE REDES ELCTRICAS DE DISTRIBUCIN RADIALES-URBANAS.

TRABAJO DE GRADUACIN PRESENTADO A LA JUNTA DIRECTIVA DE LA FACULTAD DE INGENIERA POR ALEX VICENTE GIRON CASTILLO ASESORADO POR EL ING. JUAN FERNANDO CASTRO MARTNEZ AL CONFERRSELE EL TTULO DE INGENIERO ELECTRICISTA

GUATEMALA, MAYO DE 2006

UNIVERSIDAD DE SAN CARLOS DE GUATEMALA FACULTAD DE INGENIERA

NMINA DE JUNTA DIRECTIVA


DECANO VOCAL I VOCAL II VOCAL III VOCAL IV VOCAL V SECRETARIA Ing. Murphy Olympo Paiz Recinos Lic. Amahn Snchez lvarez Ing. Julio David Galicia Celada Br. Kenneth Issur Estrada Ruiz Br. Elisa Yazminda Vides Leiva Inga. Marcia Ivonne Vliz Vargas

TRIBUNAL QUE PRACTIC EL EXAMEN GENERAL PRIVADO


DECANO EXAMINADOR EXAMINADOR EXAMINADOR SECRETARIO Ing. Sydney Alexander Samuels Milson Ing. Ing. Carlos Francisco Gressi Lpez Ing. Marvin Marino Hernndez Fernndez Ing. Guillermo Antonio Puente Romero Ing. Pedro Antonio Aguilar Polanco

HONORABLE TRIBUNAL EXAMINADOR

Cumpliendo con los preceptos que establece la ley de la Universidad de San Carlos de Guatemala, presento a su consideracin mi trabajo de graduacin titulado: METODOLOGA DE PLANIFICACIN Y EXPANSIN PARA EL DISEO DE REDES ELCTRICAS DE DISTRIBUCIN RADIALES-URBANAS,

tema que me fuera asignado por la Direccin de Escuela de Ingeniera Mecnica Elctrica, con fecha 7 de abril de 2005. Ref. EIME 76. 2005.

Alex Vicente Girn Castillo

DEDICATORIA A

Dios

Porque mejor es la sabidura que las piedras preciosas y todo cuanto se puede desear, no es de compararse con ella. Prov. 8:11. Cristbal Alfredo Girn, Dina Ester de Girn, a mi padrino Miguel ngel Azaba Trabanino (Q.E.P.D.) que me han apoyado esforzndose siempre por darnos un futuro mejor a m y a mi hermano. Siendo el instrumento que Dios ha usado para bendecirnos. Cristian Eduardo Girn Castillo. Vicente Girn, Secundina Lpez, Imelda y Leopoldo(Q.E.P.D.) Elda Alcira de Girn, por su apoyo y amor Alessandro Alfredo Girn Navas, por ser mi inspiracin Luis F. Mazariegos, por ser el impulsador de este sueo. Giovanni de Len, Eddy Flores, Rodolfo Agustn, Carlos Fuentes, Edgar Manso, Omar, Milgen, Patricia, nuestro jefe Fernando Castro Marvn Monzn, por considerarlo como un hermano.

Mis padres

Mi hermano Mi Abuelos Mi Esposa Mi Hijo

Mi Amigo Mis compaeros de estudio

Mis compaeros de trabajo Mi Primo

AGRADECIMIENTOS

A la Universidad de San Carlos de Guatemala, por ser el medio que hizo posible mi visin. Al claustro de catedrticos de la Escuela de Ingeniera Mecnica Elctrica, por su dedicacin en la enseanza y apoyo hacia mi persona y formacin profesional. Al asesor de este trabajo de graduacin, por su ayuda para la realizacin del trabajo de graduacin.

NDICE GENERAL

NDICE DE ILUSTRACIONES.................................................................. VII GLOSARIO................................................................................................... XIII RESUMEN ...................................................................................................XVII OBJETIVOS .................................................................................................XIX INTRODUCCIN ........................................................................................XXI

1. CONCEPTOS INTRODUCTORIOS..................................................... 1
1.1 Generalidades ....................................................................................... 1 1.2 Sistemas de distribucin........................................................................ 2 1.2.1 Componentes de los sistemas de distribucin.............................. 4 1.3 Topologas de las redes de distribucin en media tensin. .................... 4 1.3.1 Sistemas radiales .......................................................................... 5 1.3.2 Sistemas en anillo.......................................................................... 5 1.3.3 Sistemas mallados......................................................................... 6 1.4 Densidad del servicio elctrico .............................................................. 7 1.5 Consideraciones para el diseo de lneas de distribucin. ..................... 8

1.5.1 Lneas elctricas de distribucin................................................... 9 1.5.1.1 Conductores ..................................................................... 9 1.5.1.1.1 Propiedades de los conductores........................ 9 1.5.1.1.2 Limite trmico de los conductores ACSR......... 10 1.5.1.1.3 Seleccin de calibre de los conductores.......... 11 1.6 Flujo de Carga en sistemas de distribucin ......................................... 12 1.7 Calidad del servicio suministrado ........................................................ 14

2. METODOLOGA DE PLANIFICACIN Y EXPANSIN DE REDES DE DISTRIBUCIN URBANAS-RADIALES ....... 15


2.1 Introduccin ......................................................................................... 15 2.2 Metodologa de planificacin de sistemas de distribucin radiales radiales-urbanas .................................................................................. 16 2.2.1 Reglas de la Metodologa ............................................................ 16 2.2.1.1 Lnea principal ................................................................ 17 2.2.1.2 Lneas derivadas ............................................................ 17 2.2.1.3 Lneas subderivadas........................................................ 18 2.2.1.4 Tipos de redes de distribucin ......................................... 20 2.2.1.4.1 Zonas urbanas: ......................................... 20 2.2.1.5 Subestaciones ................................................................. 21 2.2.1.6 Elementos de maniobra ................................................... 22 2.2.1.6.1 Seccionador monopolar: ................................... 22

II

2.2.1.7 Elementos de Compensacin .......................................... 23 2.2.1.7.1 Capacitares en MT:............................................ 23 2.2.1.7.2 Regulador de tensin en MT:............................. 23 2.2.1.8 Elementos de sealizacin .............................................. 25 2.2.1.8.1 Detector de paso de falta ........................... 25 2.2.1.9 Elementos de proteccin .................................................. 26 2.2.1.9.1 Reconectador (recloser) ..................................... 26 2.2.1.9.2 Cortacircuitos fusibles de expulsin................... 28 2.2.1.10 Consideraciones econmicas ......................................... 32 2.3. Metodologa de Expansin de sistemas de distribucin urbanos radiales ................................................................................................ 34 2.3.1 Horizonte del tiempo de planificacin ................................................ 34 2.3.2 Caractersticas de la demanda .......................................................... 35 2.3.2.1 Factor de carga.................................................................... 36 2.3.2.2 Factor de utilizacin.............................................................. 36

3.

APLICACIN DE LA METODOLOGA DE PLANIFICACIN Y EXPANSIN DE REDES DE DISTRIBUCIN PARA LA PROBLACIN URBANA DE ESQUIPULAS ....................... 37
3.1 Sistema de distribucin actual de la poblacin de Esquipulas.............. 37 3.1.1 Clasificacin y cuantificacin de clientes en la red urbana de Esquipulas. ................................................................................ 38 III

3.1.2 Demanda del circuito de Esquipulas 13.8 KV ............................. 38 3.1.3 Diagnostico de la red de media tensin de Esquipulas 13.8 kV 40 3.1.4 Comportamiento de desbalance del ramal Esquipulas............... 49 3.1.5 Clculo y anlisis de resultados de ndices de confiabilidad ..... 53 3.1.5.1 ndices de calidad de servicio (interrupciones) ............. 53 3.1.5.2 ndices de calidad del producto ................................... 54 3.2 Aplicacin de la Metodologa de Planificacin y Expansin para la red urbana de Esquipulas .............................................................. 54 3.2.1 Sistema de distribucin propuesto............................................ 54 3.2.2 Remodelacin de red de distribucin de Esquipulas ................ 56 3.2.3 Clculo y anlisis de flujo de carga de la red Esquipulas 13.8 kV propuesto..................................................................... 61 3.2.3.1 Comportamiento de desbalance del ramal Esquipulas72 3.2.4 Agrupacin de derivadas y suberivadas con su respectiva proteccin ................................................................ 73

4.

ANLISIS TCNICO-ECONMICO .............................................. 81


4.1 Inversin en la Aplicacin de la metodologa de planificacin y expansin de redes .............................................................................. 81 4.1.1 Inversin en remodelacin de lneas de distribucin ................... 81 4.1.2 Inversin en instalacin de equipos de maniobras y proteccin.. 82 4.2 Ahorros en la aplicacin de la metodologa de planificacin y expansin de redes ............................................................................... 83 IV

4.2.1 Clculo del ahorro de prdidas de potencia activa ....................... 83 4.2.2 Clculos en ahorros de perdidas por corriente de neutro ............. 84

4.3 Anlisis y clculos de penalizaciones por mala regulacin e interrupciones ...................................................................................... 86 4.3.1 Penalizaciones por TTIK y FMIK ................................................ 86 4.3.2 Penalizaciones por mala regulacin ........................................... 87 4.4 Evaluacin econmica......................................................................... 88 4.5 Tiempo de recuperacin de Capital. ..................................................... 90

CONCLUSIONES ........................................................................................ 91 RECOMENDACIONES .............................................................................. 93 BIBLIOGRAFA ............................................................................................ 95 ANEXO.. ......................................................................................................... 97

VI

NDICE DE ILUSTRACIONES

FIGURAS
1 Sistema elctrico en Guatemala 2 Red de distribucin tpica 3 Red de distribucin tpica radial 4 5 6 7 8 9 Red de distribucin tpica en anillo Red de distribucin tpica en mallada Red de distribucin Cuchillas Porta fusible por una barra de cobre (SXS) Diagrama del regulador de tensin
1 3 5 6 7 19 22 23 24 25 26 28 29 30 35 37 39 47 48 49 50 50 51 55 59

10 Regulador de tensin 11 Detector de paso de falla 12 Reconectador 13 Cortacircuitos fusibles de expulsin 14 Coordinacin de protecciones 15 Curva de duracin de carga horaria 16 Diagrama unifilar del sistema actual 17 Demanda horaria Esquipulas 18 Diagrama unifilar Esquipulas (demanda mxima) 19 Diagrama unifilar Esquipulas (demanda media) 20 Diagrama unifilar Esquipulas (demanda minima) 21 Grfica del comportamiento de desbalance del ramal Esquipulas 22 Diagrama topolgico de la lnea de Esquipulas 13.8 kV 23 Diagrama unifilar del sistema propuesto 24 Diagrama topolgico propuesto VII

25 Diagrama unifilar Esquipulas (demanda mxima) 26 Diagrama unifilar Esquipulas (demanda media) 27 Diagrama unifilar Esquipulas (demanda baja) 28 Grfica del comportamiento de desbalance del ramal Esquipulas 29 Grafica de coordinacin de protecciones 30 Diagrama topolgico de agrupacin y proteccin 31 Flujo econmico del proyecto

70 71 71 73 73 74 79 88

VIII

TABLAS

I II III IV V VI VII VII IX X XI

Los conductores y sus caracterstica Parmetros de lneas Criterio de salidas de subestaciones de distribucin Total de usuarios registrados por sector de consumo en Esquipulas Demanda horaria Esquipulas 13.8 kV Flujo de carga actual (demanda Mxima) Flujo de carga actual (demanda mxima) Flujo de carga actual (demanda media) Comportamiento de desbalance del ramal Esquipulas Tramos a reconductorado Tramos a convertir de monofsica a trifsica

12 19 21 38 39 41 47 48 48 49 56 57 57 61 70 70 71 72 75 76 77 78 82

VIII Flujo de carga actual (demanda minima)

XII Tramos a nuevos y lnea nueva XIII Flujo de carga propuesto (demanda mxima) XIV Flujo de carga propuesto (demanda mxima). XV Resultado de flujo de carga propuesto (demanda media) XVI Resultado de flujo de carga propuesto (demanda baja). XVI Comportamiento de desbalance del ramal Esquipulas XVII Agrupacin y proteccin Esquipulas 1 Segmento 1 XVIII Agrupacin y proteccin Esquipulas 1 Segmento 2 XIX Agrupacin y proteccin Esquipulas 2 Segmento 1 XIX Agrupacin y proteccin Esquipulas 2 Segmento 2 XX Cuantificacin de la inversin en la remodelacin IX

XXI

Cuantificacin de la inversin de equipos de maniobras y proteccin

82 87 98 98

XXII Registros penalizados por mala regulacin XXIII ndices de calidad de servicio suministrado exigidos XXIV Tolerancias de los ndices de regulacin de tensin XXV Valorizacin de la energa segn el grado de desviacin a las tolerancias establecidas

99

LISTA DE SMBOLOS

CEMS ENS CP Fs T.T. n TTIK CT CNEE KV Km KVA kWh SE MT BT FU Q VPN VP % f.p. US$ Urb Rur Q

Costo de energa Costo de la energa no suministrada Costo de prdidas Factor de simultaneidad Transformador de tensin 20.000-15.000/220 V Tiempo de recuperacin de capital Tiempo medio de interrupcin por KVA Centro de transformacin de MT a BT Comisin Nacional de Energa Elctrica Kilovoltio Kilmetro Kilo voltios amperios Kilovatios hora Subestacin Media tensin Baja tensin Factor de utilizacin Quetzal, moneda de la Repblica de Guatemala Valor presente neto Valor presente Porcentaje Factor de potencia Dlar de los Estados Unidos de Amrica Urbano Rural Quetzal, moneda de la Repblica de Guatemala

XI

P/A I NC NA kV SSEE SMT INIG NTSD FC

Valor presente a partir de un valor futuro Inters mensual a plazo fijo Elemento de corte o seccionamiento normalmente cerrado Elemento de corte o seccionamiento normalmente abierto Kilovoltio Subestacin Elctrica Salida de media tensin Indemnizacin para ser distribuida globalmente entre los usuarios Normas Tcnicas del Servicio de Distribucin Flujo de carga

XII

GLOSARIO

Alta tensin

Nivel de tensin superior a sesenta mil voltios (60,000 V).

Baja tensin

Nivel de tensin menor o igual a mil voltios (1,000 V).

Beneficio

Cambio a favor en el estado de las condiciones distribuidora. econmicas de una

Cliente-Usuario

Persona individual o jurdica que recibe el servicio de energa elctrica del distribuidor, en media o baja tensin.

Distribuidora

Ente privado o estatal que se dedica a la distribucin de la energa elctrica.

Incidencia

Interrupcin del suministro de energa elctrica.

XIII

Indicador de calidad

ndices normados por la CNEE para determinar la calidad del servicio tcnico de una distribuidora.

Factor de potencia

Es el coseno del ngulo que existe entre la potencia activa y la potencia aparente.

Media tensin

Nivel de tensin superior a mil voltios (1,000 V) y menor o igual a sesenta mil voltios (60,000 V).

Penalizacin

Sancin que se aplica al distribuidor por haber sobrepasado los lmites de los indicadores de calidad.

ndices

Son valores normados por la Comisin Nacional de Energa Elctrica para medir la calidad del servicio de una empresa.

Empresa distribuidora

Empresa que se dedica a suministrar la energa elctrica al usuario final.

Potencia

Es el trabajo o transferencia de energa por unidad de tiempo.

XIV

Factor de potencia Trifsico

Es el coseno del ngulo que existe entre la potencia activa y la potencia aparente. Sistema compuesto por tres fases de voltaje y corriente alterna.

Monofsico

Sistema compuesto por una fase de voltaje y corriente alterna.

Transformador de distribucin

Componente

de

las

instalaciones

elctricas de una empresa distribuidora cuya funcin es la de convertir el voltaje a niveles comerciales de consumo. Transformador de distribucin Componente de las instalaciones

elctricas de una empresa distribuidora cuya funcin es la de convertir el voltaje a niveles comerciales de consumo.

XV

XVI

RESUMEN

La realizacin de este trabajo de graduacin esta influenciado por la carencia de informacin acerca de este tema en nuestro medio. Esto podra ayudar a mejorar los conceptos acerca del control del nivel de voltaje, fiabilidad, energa sin suministrar, elementos de proteccin y la rentabilidad de los mismos. Los mayores beneficiarios de un trabajo como ste serian todos los usuarios de electricidad, puesto que al poner en prctica los conceptos se podr mejorar la calidad de voltaje en toda la lnea, as como, todas sus cargas. El primer captulo se enfoca en la descripcin de los conceptos generales tales como: Sistemas de Distribucin, sus configuraciones, las topologas existentes, flujo de carga y al final los ndices de calidad de servicio . El segundo captulo describe la metodologa de planificacin y expansin de sistemas de distribucin, sus reglas, los elementos de maniobra y proteccin, as como tambin el calculo y localizacin adecuada de los mismos en funcin de la demanda de cada lugar.

XVII

El tercer captulo es la aplicacin de la metrologa el cual se escogi la la red urbana de la poblacin de Esquipulas, como primer paso se simulo la red existente por medio de un flujo de carga donde se encontraron los paramentos de prdidas de potencia, corriente de neutro y el porcentaje de cada de tensin, el siguiente paso fue la aplicacin de la metrologa, donde se propone una nueva configuracin de la red, y para finalizar se simula nuevamente para encontrar los paramentos anteriores, tambin se calculan los ndices de calidad (con y sin la metodologa), para luego compararlos y encontrar los ahorros con esto la rentabilidad. El cuarto captulo se analiza la rentabilidad de la nueva configuracin de la red, se cuantifica la inversin, se comparan los paramentos del flujo de carga actual y propuesto para encontrar los ahorros que se trasladarn a dinero, con los datos de inversin y beneficios se trasladan a valores presentes para encontrar el tiempo de recuperacin de la inversin.

XVIII

OBJETIVOS

General Resolver el problema de planificacin y expansin de sistemas de distribucin elctricos minimizando el costo de inversin y operando del mismo sistema con una configuracin que mejore la calidad del producto y del servicio de acuerdo con los requerimientos de demanda de energa

Especficos 1. Definir la configuracin en funcin de la carga. 2. Mejorar y ubicar los elementos de proteccin para liberar las fallas. 3. Evaluar econmicamente las remodelaciones para encontrar la rentabilidad de las mismas. 4. Implementar la metodologa de solucin en un modelo de planificacin.

XIX

XX

INTRODUCCIN

Los sistemas de distribucin de energa tienen gran importancia en todos los pases del mundo, ya que son los encargados de llevar hasta el usuario la energa elctrica. La energa es un ndice infalible del desarrollo econmico y del bienestar social, ya que sin esta no se pueden realizar las actividades productivas y de servicios de la vida moderna. Cuanta ms energa consuma un pas, ms alto es su nivel socioeconmico. El crecimiento de una red de distribucin sin ningn tipo de criterio, representa un desarrollo no uniforme de la misma a lo largo del tiempo. Este desarrollo se ha debido principalmente a la necesidad de satisfacer puntualmente los nuevos suministros y de garantizar el servicio frente al progresivo aumento de la demanda, lo que ha dado lugar a un crecimiento desordenado de la misma. Esta situacin da lugar a problemas de todo tipo como: como desbalances (debido a la existencia de derivaciones bifsicas y monofsicas grandes), alimentacin de zonas urbanas y rurales a travs de una misma salida de media tensin, la proteccin coordinacin. Se presenta en este trabajo de graduacin una metodologa de planificacin y expansin de redes elctricas de distribucin radiales-urbanas, con el fin establecer las reglas para el anlisis y ordenamiento de la explotacin de la red de distribucin actual y de las redes que se planifiquen en el futuro. no responde porque no existe un criterio de

XXI

1.

CONCEPTOS INTRODUCTORIOS

1.1 Generalidades

El abastecimiento elctrico se provee a travs de tres etapas, generacin transmisin y distribucin, siendo esta ltima la encargada de llevar la energa elctrica a los consumidores finales en forma eficiente y bajo estndares de calidad de servicio. Este proceso, realizado va redes de alimentacin y subestaciones. En general, distribucin incluye todas las partes de un sistema pblico de energa elctrica, entre las voluminosas fuentes de la energa y los equipos de la entrada de servicio de los consumidores En la siguiente figura se muestra el abastecimiento de la energa elctrica en Guatemala. Figura 1. Sistema elctrico en Guatemala

1-Generacin 2-Transmisin 3-Distribucin

El problema de planificacin de la red nace de la necesidad de satisfacer la creciente demanda de energa por medio de la ampliacin de la capacidad de las redes, las subestaciones, transferencia de carga a otras subestaciones con capacidad, o bien constituyendo nuevas instalaciones. Sumando a ello se tiene los futuros centros de carga, que involucran un aserie de factores que dificultan las decisiones a seguir para realizar una expansin optima. La Planificacin tanto de la operacin y desarrollo de los sistemas de distribucin elctricos, es una tarea altamente completa, que involucra altos costo de inversin y una diversidad de alternativas posibles. La construccin de una metodologa se muestra en un sistema elctrico existente donde se han definido las cargas, con demandas futuras conocidas, considerando factores de carga y dems teniendo en cuenta las consideraciones tcnicas y econmicas. De esta forma, la expansin que se busca obtener debe abastecer las demandas al mnimo costo posible, es decir, el problema tiene un enfoque econmico, considerando costos de inversin, operacin, de calidad de servicio, seguridad y confiabilidad.

1.2 Sistemas de distribucin

Los sistemas de distribucin presentan caractersticas muy particulares que los diferencian de los sistemas de transmisin, entre los cuales se puede mencionar:

Topologas radiales Topologas en Anillo Topologas Anillo-Radiales Mltiples conexiones (monofsicas, bifsicas y trifsicas) Cargas de distinta naturaleza (comerciales, industriales, residenciales o mixtas).

El que tpicamente sean radiales, significa que el flujo de potencia nace en un solo nodo. Este nodo corresponde a la subestacin que alimenta al resto de la red o salida de media tensin, en la siguiente figura se muestra un diagrama tpico de una salida de media tensin y su carga distribuida a lo largo de ella, sin importar su nivel de tensin. Figura 2. Red de distribucin tpica

Subestaci

Lne

Cargas

La distribucin se efecta en niveles de media tensin para la conduccin primaria y en baja tensin la conduccin secundaria, siendo los valores tpicos en Guatemala los siguientes:

Media tensin: 13.8 kV, 34.5 kV (Conduccin primaria) Baja tensin: 120 V, 240 V, 208 V. (Conduccin Secundaria) Los clientes residenciales y comerciales se alimentan en baja tensin, los

clientes industriales se alimentan en media tensin o baja tensin, segn los requerimientos particulares de cada uno de ellos.

1.2.1 Componentes de los sistemas de distribucin

En todo sistema de distribucin suele encontrarse los siguientes elementos: subestaciones, red primaria, transformadores, red secundaria, equipos de compensacin, equipos de proteccin, acometidas y equipos de medida. Partiendo de la fuente de generacin, esta se lleva a travs de lneas de transmisin, hasta la subestacin, donde la tensin disminuye para la distribucin en una determinada rea.

1.3 Topologas de las redes de distribucin en media tensin

Uno de los objetivos claves de un servicio de distribucin es disear una red que permita minimizar los cortes de energa a los usuarios. Para ello, existen distintas topologas de redes que condicionan la forma normal de explotar los sistemas elctricos y las posibilidades de salvar el servicio en caso de falla o perturbaciones. Bsicamente se pueden encontrar tres tipos de topologas: los sistemas radiales, sistemas de anillo y sistemas mallados. 4

1.3.1 Sistemas radiales

Los sistemas radiales son aquellos en que desde una subestacin salen uno o mas alimentadores. Cada uno de ellos puede o no ramificarse, pero jams vuelven a encontrarse en un punto comn. Estos sistemas, son sencillos y fciles de controlar y proteger, a continuacin se muestra un diagrama donde describe lo mencionado. Figura 3. Red de distribucin tpica radial

Carga

S E
P roteccin

P roteccin P roteccin P roteccin

Carga

Carga
1.3.2 Sistemas en anillo

Carga

Carga

Los sistemas en anillo permiten mejorar la confiabilidad al ser alimentados en paralelo desde dos fuentes a la vez, mediante lneas continuas, sin interrupciones. El numero de anillos as formados es siempre reducido y cada uno puede contener derivaciones ms o menos importantes y ramificaciones. Ahora bien, en caso de problemas con una fuente( subestacin), es posible mantener la alimentacin de los consumidores desde las fuentes restantes.

Si falla uno de los anillos, puede aislarse el segmento fallado y alimentar desde lados en forma radial. Mientras mayor sea el numero de trozos en que pueda dividirse el anillo, mayor ser la seguridad, pero tambin el costo. A continuacin se muestra un diagrama donde se ilustra lo antes mencionado Figura 4. Red de distribucin tpica en anillo
Carga
Proteccin

Carga
P roteccin

Carga
Proteccin

S E
P roteccin Proteccin Proteccin

Punto de Apoyo

Carga

Carga

Carga

1.3.3 Sistemas mallados

Finalmente, los sistemas mallados son aquellos en que todas la lneas forman anillos, obteniendo una estructura similar a un malla. Esa disposicin exige que todos los tramos de lnea de soporte sobrecargas permanentes, y que estn unidos a equipos de desconexin en ambas extremos. Se obtiene as la mxima seguridad, aunque tambin el mayor costo. A continuacin se muestra un diagrama donde se ilustra lo antes mencionado

Figura 5. Red de distribucin tpica en mallada


Carga
P rotec c in P rotec c in P rotec c in

Carga

Carga

Carga

S E
P rotec c in

Carga

Carga Carga

Carga

P unto de Apoyo

P rotec c in P rotec c in

Carga

Carga

Carga

1.4 Densidad del servicio elctrico

Las compaas distribuidoras DEORSA y DEOCSA miden el alcance de su servicio a travs de ciertos cocientes llamados parmetros de densidad. Estos parmetros indican qu tipo de reas son abastecidas. Por ejemplo, en zonas rurales, las redes son ms extensas y sirven menos clientes por kilmetro que en zonas urbanas. Los parmetros de densidad mas comunes son: el cociente de la demanda mxima del sistema y los kilmetros de red de propiedad de la distribuidora as como tambin, el cociente entre el nmero de clientes asociados a la red y los kilmetros de red de propiedad de la compaa. Ejemplos: La lnea de Media tensin de Cabrican 13.8 kV 13,275.5 kVA/376.80 km.= 35 kVA/km. 18,973 Clientes/376.80 km = 50 Clientes/ km 7

La lnea de Media tensin de Concepcin Las Minas 13.8 KV 4077.5 kVA/148.84 km= 27.4 kVA/km 4378 kVA/148.84 km= 29.4 Clientes /km Otro Cociente es el numero de clientes urbanos con relacin a la

superficie total servida por una distribuidora expresado en clientes urbanas por kilmetro cuadrado, y la relacin entre la energa vendida a clientes regulados y el nmero de habitantes totales en el rea de concesin, expresada en kWh por habitante. Ejemplos: La red urbana de Chiquimula 34.5 KV 10190 Clientes/ 372 km2 = 27.3 Clientes/ km2 4863.67 kW/62894 habitantes =0.07 kW/habitantes La red urbana de Esquipulas 13.8 KV 5889 Clientes/ 188 km2 =31.32 Clientes/ km2 3492 Clientes 18368 km2=0.190 Clientes/ km2

1.5 Consideraciones para el diseo de lneas de distribucin

Es importante aclarar que para realizar un estudio elctrico para la construccin de lneas de distribucin, como primer paso se debe planificar (objetivo de esta tesis) y luego entra en la etapa de diseo (que no entraremos en detalles), pero en estos dos pasos tiene un factor comn el cual es el conductor, que es importante analizar en la etapa de planificacin.

A continuacin se analizarn todos lo parmetros de los conductores.

1.5.1 Lneas elctricas de distribucin

La Red de distribucin de la republica de Guatemala opera con dos tipos de niveles de tensin las cuales son 13.8 KV y 34.5 KV, estos se transportan generalmente en lneas areas, muy escasamente con lneas subterrneas.

1.5.1.1 Conductores Los conductores a emplear sern desnudos, de aluminio, con alma de acero ACSR (Aluminium Conductor Steel Reinforced) que oscilan de No. 2 ACSR hasta el 477 MCM.

1.5.1.1.1 Propiedades de los conductores

Para evaluar un conductor, debe considerarse las propiedades trmicas del material y las cualidades ambientales. Entre las propiedades trmicas se pueden mencionar: La Absorcin solar y la emisividad de la superficie conductores La Resistencia del conductor con la temperatura, La variacin longitudinal del conductor La Velocidad del viento (cualidad ambiental) La presin atmosfrica (cualidad ambiental) de los

Otro aspecto que debe evaluarse , pero que en este caso no es tema de estudio es el efecto de las fuerzas mecnicas causadas por la circulacin de la corriente en el conductor. El deterioro causado a un conductor como consecuencia de ser sometido a calentamiento indebido es muchas veces irreversible, pudiendo reducirse la vida til de un conductor en forma considerable e incluso puede presentarse dao total, un ejemplo de esto es el llamado CREEP que es el alargamiento no elstico de los cables con el tiempo. El CREEP es el resultado de: -Un alargamiento inicial no elstico debido a la estabilizacin de los haces de alambres, este es un proceso corto que dura unos pocas ciertas horas. -Distorsin en el punto de contacto de las diferentes capas. -Un deslizamiento puramente metalrgico causado por la tensin mecnica. Evidentemente el CREEP se manifiesta como un aumento de la longitud del conductor y el consiguiente aumento de la flecha. Si se deben mantener alturas libres dictadas por normas nacionales o municipales, es de gran importancia conocer el comportamiento del cable a largo plazo. El CREEP afecta al conductor a lo largo de toda su vida, es obvio que la adquisicin de la informacin es tambin un trabajo de largo plazo.

1.5.1.1.2 Limite trmico de los conductores ACSR

La capacidad de transporte de una lnea de distribucin se refiere a la potencia mxima que puede fluir en un conductor sin producir dao a la estructura molecular del mismo y est condicionada a los siguientes factores:

10

Tipo de conductor voltaje de operacin carga caractersticas de la carga longitud de la lnea. Con relacin a los conductores , la limitante mas importante se tiene en los incrementos de temperatura que llegan a superar la temperatura critica del material existen un valor mximo de temperatura que puede ser considerado limite en la operacin de los conductores y sirve para fijar un valor mximo de corriente elctrica que puede transmitirse por los conductores durante cierta etapa de su operacin, esta corriente est definida en tablas de conductores. La primera evaluacin en la capacidad de transmisin es la temperatura ambiente a que deber ser sometida el conductor; temperatura que varia durante el transcurso del da, con las dos estaciones del ao y con la altitud sobre el nivel del mar. Para el calculo de la corriente elctrica en la lneas de distribucin, se considera que la temperatura del medio ambiente varia razonablemente entre 25oC y 40oC y se fija una temperatura mxima para la operacin del conductor, que como norma de uso comn se puede establecer en 75oC , siendo sta la temperatura limite del conductor.

1.5.1.1.3 Seleccin de calibre de los conductores

La Seleccin del calibre de los conductores econmicos, ampacidad, propiedades mecnicas utilizados, es decir condiciones de temperatura y de viento.

atienden criterios

y ambientes donde sern

11

No analizaremos estas caractersticas por separado, sin embargo continuacin se describe una tabla donde muestra lo antes mencionado. Tabla I. Los conductores y sus caractersticas

En importante mencionar la parte de planificacin es distinta a la parte de diseo, por esta razn no se detallan las normas.

1.6 Flujo de Carga en sistemas de distribucin

El flujo de carga es un algoritmo matemtico que simula la operacin de redes de distribucin elctricas y en el cual se obtienen resultados tales como magnitudes de regulacin de tensin, perdidas de potencia, niveles de desbalances (corriente de neutro).

12

La naturaleza desbalanceada de impedancias y cargas de los sistemas de distribucin no hace atractiva la transformacin a componentes simtricas. En efecto, la imposibilidad de desacoplar y modelar el sistema como una red de una secuencia, hace ms complejo el anlisis de flujo de potencia. Las dos razones por la que nos interesa desarrollar flujos de potencia especializados para sistemas de distribucin son: Las herramientas de anlisis utilizadas hasta el momento no son las ms adecuadas. La tendencia a una futura automatizacin de los sistemas de distribucin. Hasta el momento las principales herramientas de anlisis que se disponen para resolver redes de distribucin son los flujos de potencia monofsicos desarrollados para sistemas de transmisin. El problema principal con los mtodos tradicionales es que tienen malas caractersticas de convergencia. El mtodo de NewtonRaphson en sus versiones desacopladas es el menos idneo para la distribucin dado el amplio rango de variacin de la razn X/R. Por otro lado las tcnicas de la matriz de impedancia de barra, GaussSeidel directo, se muestran ms rpidas, pero tienen un excesivo uso de memoria. En definitiva, estos resultados no satisfactorios son causa directa de las caractersticas ya mencionadas de los sistemas de distribucin, especialmente de la topologa radial y del amplio rango de la razn X/R.

13

Simulando

una condicin especfica de carga, se puede determinar

cules son las prdidas en las redes de media tensin.

1.7 Calidad del servicio suministrado

La Calidad del Servicio Suministrado, es un aspecto importante en la Planificacin y expansin de sistemas de distribucin debido a que la comisin nacional de energa elctrica (CNEE), establece ndices de calidad del servicio que al no cumplirse, sta impone penalizaciones a las empresas distribuidoras. En general la parte de planificacin analiza los siguientes aspectos: Frecuencia Media de Interrupcin por kVA (FMIK) Tiempo Total de Interrupcin por kVA (TTIK); La Regulacin de Tensin. Penalizaciones Estos ndices de calidad se definen en el anexo 1

14

2. METODOLOGA DE PLANIFICACIN Y EXPANSIN DE REDES DE DISTRIBUCIN URBANAS-RADIALES

2.1 Introduccin

Un sistema elctrico de distribucin est construido normalmente de un numero de subestaciones, cada una de las cuales tiene cierta cantidad de salidas de media tensin que distribuyen la energa a los consumidores. La zona servida por la totalidad de las salidas de media tensin de una subestacin se denomina radio de influencia de la subestacin. Debido al normal crecimiento del consumo elctrico, la carga total en una rea podra llegar a exceder la capacidad de una subestacin. Esta podra expandirse o, en forma alternativa, el exceso de carga podra ser transferido a una subestacin vecina y en el ultimo de los casos, seria necesario definir la ubicacin de una nueva subestacin. Del mismo modo la aleatoriedad del crecimiento geogrfico del consumo, conlleva continuos cambios en al configuracin de las redes. Motivo por el cual el planificador, se enfrenta con el frecuente problema de determinar la mejor estrategia de expansin de los sistemas de distribucin de manera de mantenerlo permanentemente adaptado.

15

La metodologa para la planificacin de la expansin de los sistemas de distribucin radial, teniendo como parte integrante los sistemas elctricos rurales y urbanos; el mtodo en si cae en el mbito de la simulacin ya que en l se propone la determinacin y posterior anlisis de cada una de las posibles configuraciones radiales, la viabilidad de cada una de estas en cuanto a limites de capacidad y cadas de voltaje se examinan utilizando un programa de flujo de carga(metodo descrito en el inciso 1.6) este determina los lugares con dficit de capacidad, excesiva cada de voltaje, las perdidas de potencia activa.

2.2 Metodologa de planificacin de sistemas de distribucin radiales radiales-urbanas

La metodologa de planificacin de sistemas de distribucin tiene como fin establecer las reglas para el anlisis de la explotacin de la red de distribucin. De esta manera se podr disear y planificar una red ordenada, con capacidad de absorber el crecimiento de la demanda, sencilla de operar, con una calidad de servicio acorde con las exigencias regulatorias. La aplicacin de la metodologa en una red de distribucin tiene una inversin, inversin que se debe justificar con una evaluacin economica para encontrar la rentabilidad.

2.2.1 Reglas de la Metodologa

Las reglas tiene por propsito el ordenamiento de las redes existente y futuras, con el objetivo de tener agrupada la carga instalada en un ramal.

16

2.2.1.1Lnea principal

Debe ser lneas trifsicas con neutro aterrizado que tiene su origen en una salida de la subestacin y constituye el eje elctrico de una zona geogrfica de distribucin. De la lnea principal parten las lneas derivadas, subderivadas y/o transformadores de distribucin independientes (conectados en la linea principal), para lo cual se tendr en cuenta lo siguiente: La lnea trifsica de media tensin que tiene la mayor carga. La lnea trifsica con conductor de mayor capacidad. Las lneas principales deben estar libres de elementos de proteccin pero pueden contener elementos de maniobra y sealizacin (con el objetivo de localizar fallas), la seccin del conductor debe ser uniforme para lneas principales.

2.2.1.2 Lneas derivadas

Lneas derivadas son aquellas que parten de la lnea principal a travs de un elemento de proteccin, y alimentan a subderivadas. Las lneas subderivadas tienen su origen en lneas derivadas, a travs de otro elemento de proteccin. Derivadas y subderivadas podrn ser trifsicas, bifsicas o monofsicas, tambin estas tiene una lnea principal que se llamar lnea principal de derivada o subderivada.

17

La seccin de una derivacin no podr ser mayor que la de la lnea principal o derivacin de mayor rango. Por lo tanto, en conjunto la red deber ser telescpica . El nmero mximo de derivaciones en serie en el diseo no podr ser mayor de dos: derivada y subderivada o lo que indique su rentabilidad.

2.2.1.3

Lneas subderivadas

Son agrupamientos de lneas y bifsicos o monofsicos.

transformadores de distribucin que

comparten un mismo elemento de proteccin y maniobra. Pueden ser trifsicos,

Para limitar el desbalance de cargas la potencia instalada en cada derivada monofsica o bifsica, estas no podrn superar el 5% de la potencia total instalada en el circuito en el cual pertenece, esto aplicar para todas las salidas de media tensin dentro de cualquier subestacin, de esta manera se tendr un nivel de desbalance aceptable y de acuerdo a las exigencias regulatorias. A continuacin se representan grficamente lo antes mencionado:

18

Figura 6. Red de distribucin


Linea Derivad a

Linea S ubderivada
Elemento de P roteccion

S ubestac ion

Elemento de P roteccion

Linea Principal
Linea Derivad a

Elemento de P roteccion

Linea S ubderivada
Elemento de P rotec cion

La potencia y la longitud son factores que tambin determina el tipo de lnea, y describen en el cuadro siguiente. Tabla II. Parmetros de lneas

Dentro de las redes de Unin Fenosa existen ramales, derivadas y subderivadas que no cumplen con estos paramentos con es le caso de la lnea de San Marcos 34.5 KV que tiene una derivada con 1235 kVA y 36 Km. Todos los valores descritos en la tabla II fueron calculados con los resultados de flujos de carga para lograr obtener niveles de perdidas y regulacin aceptables, esto aplica para cualquier configuracin.

19

2.2.1.4 Tipos de redes de distribucin

Los criterios de diseo de redes se definen segn las caractersticas de las redes que a su vez estarn asociados al mercado que atiendan. La segmentacin del mercado la fijan normalmente las regulaciones vigentes del mercado elctrico de cada pas, al establecer distintos ndices de calidad del servicio y del producto tcnico tomando en consideracin las caractersticas del cliente. Segn su tipo de construccin pueden clasificar en: Redes areas. Redes subterrneas. Redes mixtas areo-subterrneas. Segn su mbito geogrfico en: Redes urbanas (alto factor de carga) Redes rurales. (bajo factor de carga) Para efectos de este trabajo se analizarn redes areas en las zonas urbanas.

2.2.1.4.1 Zonas urbanas

Constituidas por ncleos de poblacin importantes por su tamao o por su categora administrativa y densidades de carga mayores que en zonas rurales Las zonas urbanas pueden a su vez subdividirse en dos tipos: reas de alto consumo, caracterizadas por tener edificacin elevada, centros comerciales, zonas bancarias y/o administrativas. reas de bajo consumo, con edificaciones de pocas plantas, pequeos locales comerciales, y zonas residenciales,

20

Estas dos reas sern medidas por su factor de carga.

2.2.1.5 Subestaciones

La demanda de potencia elctrica requerida por los consumidores define la capacidad y ubicacin de una subestacin. Al definir el mbito de una subestacin se define tambin el rea de influencia de cada salida de la subestacin, que debe estar claramente delimitada evitndose cruzamientos de lneas. Esta definicin debe permitir que la operacin de la misma se haga sin problemas de cada de tensin, sin sobrecargas y que soporte el crecimiento de la demanda de la zona sin necesidad de realizar inversiones adicionales dentro del perodo comprendido entre el establecimiento de la explotacin y el ao horizonte considerado en el estudio, que normalmente es de 15 aos. El modelo de red urbana debe disearse con el criterio de que las lneas tengan socorro, la demanda determinara el numero de salidas en el cuadro siguiente se describe esto. Tabla III. Criterio de salidas de subestaciones de distribucin

Salidas Potencia (KVA) 13.8 KV 34.5 KV 20000 3 2 30000 4 3 40000 3 4

21

El cuadro anterior describe que para una potencia instalada de 20 mVA es necesario tener 3 salidas de media tensin para un nivel de tensin de 13.8 kV y para 34.5 kV 2 salidas, estos datos estan sustentados por estudios de flujos de carga.

2.2.1.6 Elementos de maniobra

Los elementos de maniobra se instalaran en puntos estratgicos con el fin de traslado de carga, seccionamiento temporal de carga, socorro entre lneas de la misma tensin, tambin sirven para aislar las zonas donde se va a actuar, o se ha producido una falta 2.2.1.6.1 Seccionador monopolar

Aparato mecnico de accionamiento monofsico capaz de abrir un circuito sin carga y cerrar sobre corrientes de cortocircuito. Existen dos tipos de seccionadores: los de cuchillas y los basados en los seccionadores fusibles de expulsin, en los que se ha sustituido el tubo porta fusible por una barra de cobre (SXS) En ambos casos su diseo permitir la apertura en carga mediante prtiga "Load-Booster". Debe garantizar nivel de aislamiento. Figura 7. Cuchillas

22

Figura 8. Porta fusible por una barra de cobre (SXS)

2.2.1.7 Elementos de compensacin 2.2.1.7.1 Capacitares en MT

Conjunto de capacitores que se instalan para la compensacin de la potencia reactiva en la red de MT. Se instalan en puntos intermedios de circuitos de MT. Pueden ser fijos o con conexin y desconexin automtica, este equipo se instala con el objetivo de mejorar el porcentaje de regulacin.

2.2.1.7.2 Regulador de tensin en MT

Equipo con caractersticas comunes a los autotransformadores, con determinada capacidad de regulacin automtica de la tensin de la red para la intensidad nominal especificada, las unidades monofsicas que se conecten en serie, estrella delta.

23

La conexin de la polaridad del secundario en forma aditiva, de tal modo que la tensin en l se sume a la tensin del primario, hacen al regulador funcionar como elevador de la tensin. Esta configuracin se muestra en la figura 9. La insercin de un regulador en esta configuracin en un determinado punto de la lnea de distribucin regenera el valor de la tensin al nominal de la lnea a partir de ese punto; por supuesto el valor de voltaje regenerado puede ser mayor en cierto porcentaje al nominal si as lo requieren las condiciones de carga y la longitud del tendido. Figura 9. Diagrama del regulador de tensin

24

Figura 10. Regulador de tensin

2.2.1.8 Elementos de sealizacin Son elementos que indican la existencia de una falla aguas debajo de su ubicacin los cuales describiremos a continuacin

2.2.1.8.1 Detector de paso de falta

Es un elemento que se activa al paso de una corriente de defecto ocasionada por una falla (de suma utilidad para que la brigada de operacin ubique rpidamente el punto por donde ha pasado la falla) La indicacin puede ser del tipo luminoso o bandera reflectante, y del tipo telesealizable. La reposicin de la seal del detector a su estado normal se puede dar por presencia de tensin, corriente o tiempo.

25

Figura 11. Detector de paso de falla

2.2.1.9 Elementos de proteccin La funcin de estos elementos es la actuar en el momento de falla, estos se deben instalar en cabeceras de salidas de media tensin en la subestacin, en cabecera de derivadas y subderivadas.

2.2.1.9.1 Reconectador (recloser)

Elemento de proteccin y maniobra capaz de abrir y cerrar sobre corrientes de cortocircuito equipado con rels de apertura ajustables, que protege la lnea contra cortocircuitos y sobreintensidades, y que se sita en puntos intermedios de la lnea. Debe actuar en coordinacin con el interruptor de cabecera de la subestacin. Tiene la funcin de reenganche automtico, con el mismo funcionamiento que el indicado para el interruptor de cabecera y puede tener telecontrol.

26

Con respecto a la realidad accional de este dispositivo sobre los los tiempos de respuestas estn referidas para validar la seal de entrada en la interfase de entradas y salidas digitales entre un rango de 20mseg-200ms, luego esta informacin es procesada por la CPU del interruptor Cooper F5 en un periodo de 500 mseg, tomando en cuenta la velocidad de respuesta del Hardware y del Software, por lo que la actuacin del interruptor despues de validar la seal es de 500 mseg (ejecucin de software+hardware), para esto se tienen los siguientes valores: Detencin del Nivel Mnimo................................................. 8 Vac (50 o 60Hz) 10 Vdc Mximo voltaje de Operacin..........................................135 Vac (50 r 60Hz) 175 Vdc Impedancia de Entrada......................................................................10 k Minimo Mxima Carga de ...................................................................2 mA por entrada Rechazo de fuga maxima............................................................................ 1 mA El tiempo Mximo de realidad accional...................10 msec(no cuenta el tiempo de respuesta del control) Tiempo de entrada de pu....................................................................... 100 msec Tiempo minimo de transicin entre las entradas de los pulso.................200msec Estos valores son para el reconectador COOPER que es el que utiliza Union Fenosa, en las salidas de media tensin.

27

Se encuentra en cabecera de las lneas, ejerciendo las mismas funciones de interruptor automtico, estos deben estar coordinados con los corta-circuitos en la lnea que atiende, mas informacin se detallaran mas adelante, otro aspecto importante mencionar que el reconectados tiene diferentes curvas de proteccin siendo las principales la de curva de disparo por neutro, curva de disparo por sobre intensidad de fase, las cuales son programables en funcin de la corriente, el tiempo de respuesta. A continuacin se ilustra este elemento.

Figura 12. Reconectador

2.2.1.9.2 Cortacircuitos fusibles de expulsin Aparato mecnico de proteccin y seccionamiento capaz de abrir un circuito con corrientes de intervencin que incluye un elemento fusible que al fundir provoca la apertura de derivadas y subderivada cuando existe una falla dentro de las mismas. El cual se ilustra acontinuacin.

28

Figura 13. Cortacircuitos fusibles de expulsin

Con la coordinacin de las protecciones se trata de minimizar los efectos de las faltas en los distintos elementos que componen la lnea elctrica. Para i dejar fuera de servicio la menor porcin de lnea posible, la proteccin que primero debe actuar es la que se encuentra ms prxima a la falta aguas arriba de esta. En la siguiente figura se muestran la curvas de tiempo inverso de los cortacircuitos coordinadas con la del reconectador en cabecera en la subestacin.

29

Figura 14. Coordinacin de protecciones

Fusible Tipo K: 10 Amp. Fusible Tipo K: 15 Amp

Fusible Tipo K: 25 Amp. Fusible Tipo K: 40 Amp

Fusible Tipo K: 65 Amp.

Recloser Esquipulasl 320 Fusible Tipo K: 6 Amp

Las curvas de actuacin de los corta-circuitos estn coordinadas al 60 %, unas con otras, adems debe actuar mas rpidamente que la curva de disparo por sobre corriente del reconectador. El clculo de la proteccin con fusibles depender de la capacidad acumulada por fase de carga nominal instalada estimndose: (Max(R, S, T)/tension*facto de potencia * factor de seguridad * factor de Coincidencia (trafo-trafo) *factor de Coincidencia (baja tensin).

30

Donde: R, S, T= Capacidad instalada en KVA/fase Tensin= Nivel de Tensin (para el caso de 34.5 kV es 19.9 kV, 13.8 kV es 7.6 kV.) Facto de Potencia depender de la lnea Factor de Seguridad 1.5 Factor de Coincidencia(trafo-trafo)= que es igual a 0.71 Factor de Coincidencia (baja tensin)= que es igual a 0.71 El factor de coincidencia no es mas que la coididencia que usuarios de energa elctrica la consuman al mismo tiempo, este dato es una probabilidad donde se tiene una muestra y se evala con la potencia de los clientes con la demanda de los mismos, y con la energa consumida por ellos en un periodo de tiempo. Para la seleccin de los fusibles y obtener una buena coordinacin se tienen las siguientes consideraciones: Si el resultado es menor de 20 A se instalara 10 A Si el resultado es menor de 30 A se instalara 15 A Si el resultado es menor de 50 A se instalara 25 A Si el resultado es menor 80 A se instalara 40 A Si el resultado es menor de 120 A se instalara 60 A Si el resultado es mayor a 160 A, se debe instalar un Reconectador En muchas salidas de media tensin donde se aplicarn estas

consideraciones se ha logrado reducir las incidencias por fallas.

31

2.2.1.10 Consideraciones econmicas

La metodologa describe bsicamente una reestructuracin de las redes existentes pero es importante encontrar la rentabilidad de las mismas para lo cual se tiene las siguientes consideraciones: Para lograr encontrar la recuperacin de capital es importante encontrar el valor presente de las inversiones y de los beneficios, los cuales se calculan de la siguiente manera: VPN = VP(beneficios) VP(costos) - inversin En donde: VPN VP(beneficios) Es el valor presente neto del proyecto o plan a evaluarse. Es el valor presente de los beneficios que se obtendrn del proyecto o plan. VP(costos) Es el valor presente de los costos que se tendrn que realizar para ejecutar el proyecto o plan. Los costos sern la inversin necesaria para la implementacin de la red. Los beneficios sern los ahorros de perdidas de potencia activa y los ahorros de perdidas por corriente de neutro los cuales se calculan de la siguiente manera: C.p = Costes prdidas de potencia Activa

32

Donde,
Cp= Potencia Perdidas x(FpxCosto de Energia+12xFsxCosto de potencia) Donde:

Fp= 8760(0.15Fc+0.85Fc2) FC = factor de carga El Factor de simultaneidad con la demanda mxima del sistema que es 0.4 C.p.i = Costes prdidas por corriente de neutro

Potencia prdidas =
donde:

2 * r * L * I2 3

r, rn, es la resistencia del conductor de fase y de neutro. Unidades: /km L, longitud del conductor, para este estudio 1 km. Unidades: km. I, intensidad de lnea, siendo el subndice el indicador de la fase (a, b o c) o del neutro (n). Unidades: A. Luego es necesario encontrar el tiempo de recuperacin de capital el cual ser con la siguiente expresin:

A ___ Ln ( A iP ) n = _______________ Ln (i + 1) Datos: P = VP Inversin A = VP Beneficio i = inters.

33

2.3. Metodologa de Expansin de sistemas de distribucin urbanos radiales

La expansin de las redes de distribucin debe contemplar modelos de simulacin propios de los sistemas elctricos, con el fin de recrear las situaciones de forma tal que se acerque lo ms que se pueda a la realidad, en el modelo se debe representar: Horizonte del tiempo de planificacin Caractersticas de la demanda Caractersticas tcnicas y econmicas de las redes de distribucin

2.3.1 Horizonte del tiempo de planificacin

El rpido crecimiento y constante evolucin del sistema elctrico de distribucin hace difcil determinar con exactitud las demandas y las localizaciones futuras de los centros de carga. Por esta razn, la metodologa de planificacin y expansin considera un horizonte de tiempo finito, para el cual se han dado como variables conocidas, la localizacin geogrfica de las cargas y las demandas para cada uno de los aos del perodo en estudio. Esta simplificacin transforma el problema aleatorio en uno determinstico, con lo que es posible determinar la ubicacin cronolgica de las obras manteniendo el sistema permanentemente adaptado. Por otra parte, el perodo de planificacin debe ser considerado en la evaluacin econmica, producto de la vida til de los elementos y estructuras del sistema elctrico, estos pueden ser de 10 a15 aos .

34

2.3.2 Caractersticas de la demanda

La metodologa a plantear debe considerar las modificaciones y reestructuraciones que sufren las redes de distribucin, producto de los constantes cambios en la demanda. As, para mantener el sistema adaptado es necesario poder predecir la demanda con la mayor exactitud posible; pero la gran cantidad de variables involucradas y la aleatoriedad de stas, hacen de la estimacin un subproblema igualmente complejo. La demanda es entonces la potencia media correspondiente a un intervalo de medida adoptado. La demanda mxima en una hora resulta ser la potencia media mayor de quince minutos que todas las potencias medias registradas en intervalo de tiempo adoptado a lo largo de esa hora. La demanda mxima del da ser la mayor de todas las demandas mximas obtenidas en cada una de las horas del da, la demanda mxima del mes, es la mayor de las demandas mximas obtenidas en cada uno de los das del mes, etc. Curva de carga diaria tpica se denomina con este nombre a la forma en que varia la demanda a lo largo de un da. La figura muestra un ejemplo. Figura 15. Curva de duracin de carga horaria Dmax

Dmed 6 12 18 24

35

Esta curva tpica de carga tiene variaciones de acuerdo al rea de anlisis .

2.3.2.1 Factor de carga

El factor de carga tiene importancia comercial pues indirectamente. Nos da una relacin entre los KMH de energa consumida, ( res decir cobrara por la empresa) y los KWH de potencias, que la empresa debe tener disponibles para responder a la demanda del publico, Es decir la carga promedio entre la carga en hora pico. Fc = Energa (kWh)/ (Potencia (kW)*Tiempo (horas))

2.3.2.2 Factor de utilizacin

Es el ndice del porcentaje en que esta siendo utilizando un sistema respecto a su 100%. Puede ser fraccin de la unidad o mayor que ella (cuando la carga sobrepasa a la capacidad nominal del circuito

36

3.

APLICACIN DE LA METODOLOGA DE PLANIFICACIN Y EXPANSIN DE REDES DE DISTRIBUCIN PARA LA PROBLACIN URBANA DE ESQUIPULAS

3.1 Sistema de distribucin actual de la poblacin de Esquipulas.

En el presente caso practico de estudio se analizara la red urbana de Esquipulas, departamento de Chiquimula, esta red de distribucin es suministrada por la subestacin de Esquipulas 34.5kV/13.8KV, y la lnea de media tensin del mismo nombre, Esquipulas 13.8 kV, la alimentacin de dicha subestacin proviene de la subestacin Quezaltepeque 69 kV/34.5kV y esta es parte del sistema nacional interconectado, lo cual se describe a continuacin. Figura 16. Diagrama unifilar del sistema actual
69 kV

SE Quezaltepeque

34.5 kV

69/34.5 kV

Linea 34.5 kV

S Esquipulas E

34.5/13.8 kV 34.5 kV 13.8 kV

Carga E squipulas

37

3.1.1 Clasificacin y cuantificacin de clientes en la red urbana de Esquipulas.

El casco urbano de Esquipulas tiene un total de habitantes hasta diciembre/2005 de 62, 894 de los cuales 5,tiene servicio elctrico. Tabla IV. Total de usuarios registrados por sector de consumo en Esquipulas.
SECTOR DE CONSUMO Residencial Comercial Industrial Gubernamental Diverso Trifsicos TOTAL TOTAL DE USUARIOS REGISTRADOS 4224 1542 12 9 80 22 5889 PORCENTAJE 71.72% 26.18% 0.20% 0.15% 1.37% 0.38% 100%

3.1.2 Demanda del circuito de Esquipulas 13.8 KV

La demanda de Esquipulas 13.8 KV, se divide en tres partes, demanda mnima que comprende un factor de utilizacin del 15%, la demanda media que tambin comprende un factor de utilizacin del 25% y por ultimo la demanda mxima que tiene un factor de 41%, estos factores de 15%,25% y 41% es el porcentaje de lo que se esta utilizando durante las tres etapas de demanda.

38

A continuacin se describe la potencia utilizada cada hora durante el da viernes 16 de diciembre del 2005 uno de los das de demanda mxima as como tambin su respectiva grafica. Tabla V. Demanda horaria Esquipulas 13.8 kV

Figura 17. Demanda horaria Esquipulas

39

3.1.3 Diagnstico de la red de media tensin de Esquipulas 13.8 kV

La red de distribucin de Esquipulas tiene una potencia instalada de 10,450 kVA y una longitud de lnea de 50.5 Km. actualmente este circuito se encuentra con una diversidad de tramos de calibres de conductor diferentes los cuales tienen el 60% de 1/0, el 35% No.2 y el 5% No.4 intercalados en la toda la lnea, aunque este 5% no sea significativo tiene localizados una buena concertacin de carga, estos tramos estn identificados en el cuadro de calculo y anlisis de flujo de carga actual( cuadro VI) y identificados en el diagrama topolgico de la red de distribucin elctrica de Esquipulas figura 21. La falta de uniformidad del conductor representa un porcentaje considerable de perdidas de potencia activa y mala regulacin.

3.1.4 Clculo y anlisis de flujo de carga del ramal Esquipulas 13.8 kV actual El anlisis de flujo de potencia, consiste en simular las magnitudes de tensin en los transformadores y en los tramos de lnea que une los mismos de un sistema de distribucin , as como tambin, las perdidas de potencia activa. Los estudios de flujo de potencia son de gran importancia, tanto en sistemas ya existentes (buscando resolver problemas de operacin econmica, regulacin de tensin, et.), como en la planificacin y expansin de nuevos sistemas.

40

Con un factor de utilizacin de 41% respecto a la carga instalada en la salida de media tensin en demanda mxima, un factor de potencia de 0.873 en la misma lnea y apoyados con el programa que calcula flujo de carga propiedad de Unin Fenosa llamado OPEN-ESTUDIOS se obtuvo los clculos de regulacin y perdidas en transformadores y tramos. Tabla VI. Flujo de carga actual (demanda mxima)

No. Trafo 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47

KVA KVA KVA S S T 15 50 50 50 37.5 25 25 15 25 25 25 37.5 37.5 50 10 50 50 10

Tensin % Perdidas Nominal Tensin R Tensin S Tensin T Regulacin (kW) 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.5 7.5 7.5 7.5 7.5 7.5 7.4 7.4 7.5 7.5 7.5 7.4 7.6 7.6 7.6 7.6 0 0 0 0 1 1 1 1 1 1 2 2 1 1 1 2 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 1 1 1 1 1 1 3 3 0.1 0.1 0.1 0.1 0.2 0.1 0.3 0.3 0.4 0.1 0.2 0.1 0.3 0.3 0.4 0.4 0.5 0.6 0.7 0.6 0.8 0.9 0.5 0.6 0.7 0.6 0.8 0.9 0.9 0.5 0.6 0.7 0.6 0.8 1.123 0.3 1.3 0 0.2 0.2 0.4 0.3 0.2 0.2 0.4 0.3 0.2

Codigo del Conductor 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47

Conductor 1/0 AWG ASCR 1/0 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR 1/0 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR 1/0 AWG ASCR 1/0 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No.4 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR

Longitud (km) 0.8 0.379 0.557 0.102 0.525 0.122 0.033 0.06 0.037 0.038 0.034 0.095 0.135 0.029 0.009 0.395 0.115 0.266 0.352 1.163 0.69 0.364 0.209 1.148 0.374 0.006 0.222 0.067 0.078 0.1 0.038 0.05 0.721 0.023 0.025 0.045 0.035 0.141 0.05 0.077 0.107 0.041 0.037 0.001 0.001 0.001 0.001

OHMIO S/KM 0.71 0.71 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 0.71 1.09 1.09 1.09 0.71 0.71 1.09 1.09 1.09 1.7 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09

25

50

25 10 37.5 50 25 25 25 25 25 25 25 10 25 25 25 25 25 25 25 25 25 37.5 37.5 25 25 25

7.5

7.4

7.5 7.5 7.5 7.4 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3

25 10 25 25 25 37.5 25 40 25

7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.3 7.3

41

No. Trafo 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113

KVA KVA KVA S S T 25 25 15 25 25 62.5 37.5 25 25 25 25 25 25 10 15 25 25 25 25 25 25 25 25 25 25 25 25 50 50 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 15 15 25 75 25 25 25 15

Tensin % Perdidas Nominal Tensin R Tensin S Tensin T Regulacin (kW) 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.5 7.5 7.5 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.5 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.4 7.4 7.4 7.5 7.5 7.5 7.5 3 3 3 3 3 3 3 3 3 3 3 3 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 2 2 1 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 0.2 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.3 0.2 0.4 0.3 0.2 0.4 0.3 0.2 0.2 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.3 0.2 0.4 0.2 0.4 0.2 0.2 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.3 0.2 0.4 0.2 0.4 0.3 0.2 0.4 0.2 0.4 0.3 0.2 0.4 0.3 0.2 0.4 0.2 0.4 0.5 0.3 0.4 0.6

Codigo del Conductor 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113

Conductor No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR 1/0 AWG ASCR 1/0 AWG ASCR 3/0 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR 3/0 AWG ASCR 3/0 AWG ASCR No. 2 AWG ASCR 3/0 AWG ASCR 3/0 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR 1/0 AWG ASCR 1/0 AWG ASCR 1/0 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR 1/0 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR 1/0 AWG ASCR No.4 AWG ASCR 1/0 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR

Longitud (km) 0.001 0.001 0.001 0.001 0.057 0.153 0.072 0.066 0.065 0.063 0.027 0.088 0.022 0.11 0.202 0.066 0.065 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.06 0.063 0.148 0.18 0.073 0.567 0.129 0.081 0.035 0.085 0.113 0.345 0.211 0.014 0.1 0.062 0.077 0.237 0.038 0.038 0.111 0.095 0.036 0.065 0.046 0.127 0.199 0.045 0.134 0.127 0.104 0.12 0.226 0.005 0.102 0.1 0.008 0.14 0.07 0.149 0.059

OHMIO S/KM 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 0.71 0.71 0.472 1.09 1.09 0.472 0.472 1.09 0.472 0.472 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 0.71 0.71 0.71 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 0.71 1.09 1.09 1.09 1.09 0.71 1.7 0.71 1.7 1.7

42

No. Trafo 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179

KVA KVA KVA S S T 62.5 25 25 25 25 35

Tensin % Perdidas Nominal Tensin R Tensin S Tensin T Regulacin (kW) 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.3 7.3 7.3 7.3 7.3 7.3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 5 5 5 5 5 5 5 5 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 7 7 7 7 7 7 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 0.8 0.7 0.6 0.5 0.7 0.8 0.6 0.6 0.8 0.7 0.6 0.5 0.7 0.6 0.8 0.7 1.2 1.5 2.2 2.3 0.9 0.8 0.7 0.9 2.3 2.5 2.6 2.4 2.3 2.5 2.6 2.4 2.3 2.2 2.9 2.8 2.7 3.1 3.3 3.4 3.5 3.6 4.3 4.2 4.5 4.6 4 4.5 5.5 5.6 5.4 6.5 6.5 7.2 7.3 7.3 7.4 7.5 7.6 7.5 8.6 8.6 8.5 8.6 8.4 8.6

Codigo del Conductor 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179

Conductor No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR 1/0 AWG ASCR 1/0 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR

Longitud (km) 0.103 0.238 0.222 0.039 0.26 0.242 0.043 0.058 0.04 0.251 0.023 0.145 0.206 0.065 0.015 0.068 0.107 0.021 0.063 0.731 0.568 0.001 0.038 0.031 0.06 0.104 0.063 0.12 0.044 0.149 0.15 0.109 0.026 0.033 0.047 0.107 0.219 0.042 0.032 0.041 0.12 0.246 0.07 0.02 0.167 0.087 0.205 0.13 0.009 0.236 0.073 0.122 0.047 0.05 0.044 0.049 0.041 0.053 0.06 0.158 0.038 0.026 0.036 0.068 0.036 0.028

OHMIO S/KM 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.09 1.09 1.09 0.71 0.71 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09

25 35 25

7.3 7.3 7.3

10 25 25 25 50 50

50 50

50 50 35 10 62.5 50 37.5 25 75 45 15 50 50 37.5

7.3 7.3 7.3 7.3 7.3 7.3

7.3 7.3

7.3 7.3 7.3 7.3 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7 7 7

25

7.1

37.5 25

37.5 25

7.1 7.3

7.1 7.3

25 50 37.5 37.5 50 50 25 37.5

7 7 7 7 7 7 7 7

25 25 10 62.5 25 25 10 50 15 25 50 50 50 15 10 15 25 25 25 25 25 25 10 25 50 25 25 50 50 50 50 25 50 75 50 15 10 20 10 50 75 15

7 7 7 7 7 7 7 7 6.9 6.9 6.9 6.9 6.9 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.9 6.9 6.9 6.8 6.8 6.8 6.9 6.9 6.9 6.9 6.8

50

50 10

6.8

6.8 6.8

43

No. Trafo 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 243 244 245 246

KVA KVA KVA S S T 50 50 50 25 37.5 35 37.5 20 25 10 25 37.5 50 50 50 50 50 10 25 25 25 15 50 62.5 62.5 25 50 25 25 50 25 25 25 15 50 50 25 25 35 25 15 25 25 25 25 25 10 25 25 25 25 25 25 15 37.5 25 10 75 25 15 25 15 15 25 15 37.5 75 25 10 37.5

Tensin % Perdidas Nominal Tensin R Tensin S Tensin T Regulacin (kW) 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 6.8 6.8 6.8 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.3 7.3 7.3 7.3 7.3 8 8 8 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 8.5 8.4 8.2 0.6 0.8 0.7 0.6 0.5 0.7 0.6 0.8 0.7 1.2 1.5 2.2 2.3 0.6 0.8 0.7 0.6 0.5 0.7 0.6 0.8 0.7 0.6 0.8 0.7 0.6 0.5 0.7 0.6 0.8 0.7 1.2 1.5 2.2 2.3 0.9 0.8 1.8 2.3 2.4 2.5 2.9 2.3 2.4 2.5 2.9 2.5 2.9 2.3 2.5 2.9 2.3 2.4 2.5 2.9 2.3 2.5 2.9 2.3 2.5 2.9 2.3 2.5

Codigo del Conductor 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245

Conductor No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR

Longitud (km) 0.04 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.033 4.054 1.517 0.065 0.097 0.518 0.089 0.034 0.063 0.161 0.078 0.205 0.228 0.558 0.526 0.348 0.164 0.1 0.026 0.095 0.051 0.059 0.033 0.027 0.203 0.048 0.201 0.111 0.048 0.184 0.177 0.07 0.245 0.001 0.061 0.16 0.236 0.14 0.038 0.073 0.081 0.079 0.033 0.519 0.089 0.027 0.179 0.053 0.038 0.039 0.071 0.118 0.118 0.009 0.102 0.519 0.109

OHMIO S/KM 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7

25 10

7.3 7.3

47.5

7.3

44

No. Trafo 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 Total

KVA KVA KVA S S T 50 37.5 25 25 25 25 37.5 10 25 25 37.5 50 25 100 100 100 15 25 25 25 25 25 25 25 25 50 25 50 10

Tensin % Perdidas Nominal Tensin R Tensin S Tensin T Regulacin (kW) 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 2.9 2.3 2.5 2.9 2.3 2.5 2.9 2.3 2.5 2.9 2.3 2.4 2.5 2.9 2.3 2.5 2.9 2.3 2.4 2.5 2.9 2.3 2.5 2.9 2.3 2.5 2.9 2.3 2.5 2.9 2.3 2.4 2.5 2.9 2.3 2.5 2.9 2.3 2.4 2.5 2.6 2.4 502.023

Codigo del Conductor 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 304 305 306 307 308 309 310

Conductor No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR No.4 AWG ASCR 1/0 AWG ASCR 1/0 AWG ASCR 1/0 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR 1/0 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR 1/0 AWG ASCR No. 2 AWG ASCR 1/0 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR 1/0 AWG ASCR 1/0 AWG ASCR 1/0 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR 1/0 AWG ASCR 1/0 AWG ASCR 1/0 AWG ASCR 1/0 AWG ASCR No. 2 AWG ASCR

Longitud (km) 0.122 0.033 0.06 0.037 0.038 0.034 0.095 0.135 0.029 0.122 0.033 0.06 0.037 0.038 0.034 0.095 0.135 0.029 0.009 0.395 0.115 0.266 0.122 0.033 0.06 0.037 0.038 0.034 0.095 0.135 0.029 0.009 0.395 0.115 0.122 0.033 0.06 0.037 0.038 0.034 0.095 0.135 0.029 0.009 0.395 0.115 0.266 0.122 0.033 0.06 0.037 0.038 0.034 0.095 0.135 0.029 0.009 0.395 0.115 0.266 0.122 0.033 0.06 0.037 0.038

OHMIO S/KM 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 0.71 0.71 0.71 1.09 1.09 1.09 0.71 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 0.71 1.09 0.71 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 0.71 0.71 0.71 1.09 1.09 1.09 1.09 0.71 0.71 0.71 0.71 1.09

37.5 10 10 25 10 15 25 25 15 25 75 50 10 25 25 25 3170 3313 3968

7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2

75 50 10

75 50

7.2 7.2 7.2

7.2 7.2

45

No. Trafo

KVA KVA KVA S S T

Tensin % Perdidas Nominal Tensin R Tensin S Tensin T Regulacin (kW)

Codigo del Conductor 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 351 352 353 354 355 356 357 358 359 360 361 362 363 364 365 366 367 368 369 370 371 372 373 374 375 376

Conductor No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR 1/0 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR 1/0 AWG ASCR 1/0 AWG ASCR 1/0 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR 1/0 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR 1/0 AWG ASCR 1/0 AWG ASCR 1/0 AWG ASCR 1/0 AWG ASCR No. 2 AWG ASCR 1/0 AWG ASCR 1/0 AWG ASCR No. 2 AWG ASCR 1/0 AWG ASCR No. 2 AWG ASCR 1/0 AWG ASCR No. 2 AWG ASCR

Longitud (km) 0.034 0.095 0.135 0.029 0.009 0.395 0.115 0.266 0.122 0.033 0.06 0.037 0.038 0.034 0.095 0.135 0.029 0.009 0.395 0.115 0.266 0.122 0.033 0.06 0.037 0.038 0.034 0.095 0.135 0.029 0.009 0.395 0.115 0.266 0.122 0.033 0.06 0.037 0.038 0.034 0.095 0.135 0.029 0.009 0.395 0.122 0.033 0.06 0.037 0.038 0.034 0.095 0.135 0.029 0.009 0.395 0.122 0.033 0.06 0.037 0.038 0.034 0.095 0.135 0.029 0.009

OHMIO S/KM 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 0.71 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 0.71 0.71 0.71 1.09 1.09 1.09 0.71 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 0.71 1.09 1.09 0.71 1.09 0.71 1.09 0.71

46

No. Trafo

KVA KVA KVA S S T

Tensin % Perdidas Nominal Tensin R Tensin S Tensin T Regulacin (kW)

Codigo del Conductor 377 378 379 380 381 382 383 384 385 386 387 388 389 390 391 Total

Conductor 1/0 AWG ASCR 1/0 AWG ASCR No. 2 AWG ASCR 1/0 AWG ASCR 1/0 AWG ASCR 1/0 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR No. 2 AWG ASCR

Longitud (km) 0.395 0.115 0.266 0.122 0.033 0.06 0.037 0.038 0.034 0.095 0.135 0.029 0.009 0.395 0.115 50.526

OHMIO S/KM 1.09 1.09 0.71 1.09 1.09 1.09 0.71 0.71 0.71 0.71 0.71 0.71 0.71 0.71 0.71

Tabla VII. Resultados de flujo de carga actual (demanda mxima)


Flujo de Carga 10,450.0 kVA Instalado: 4,329.4 kVA Utilizado: 3,680.0 kW Utilizado: 50.5 Longitud (kms): 502.0 kW Prdidas: 13.6% % Prdidas: 8.0% % Regulacin:

Figura 18. Diagrama unifilar Esquipulas (demanda mxima)

S E

R egulac in 13.6% P erdidas 502. KW P Utilizada 3680 kW .

47

Tabla VII. Resultados de flujo de carga actual (demanda media)


Flujo de Carga 10,450.0 kVA Instalado: 2,612.5 kVA Utilizado: 2,220.6 kW Utilizado: 50.5 Longitud (kms): 202.3 kW Prdidas: 9.1% % Prdidas: 5.0% % Regulacin:

Figura 19. Diagrama unifilar Esquipulas (demanda media)

S E

Regulac in 9.1% Perdidas 202.3 KW P Utilizada 2202.6 kW .

Tabla VIII. Resultados de flujo de carga actual (demanda mnima)


Flujo de Carga 10,450.0 kVA Instalado: 1,567.5 kVA Utilizado: 1,332.4 kW Utilizado: 50.5 Longitud (kms): 102.3 kW Prdidas: 7.7% % Prdidas: 3.0% % Regulacin:

48

Figura 20. Diagrama unifilar Esquipulas (demanda mnima)

S E

Regulac in 7.7% Perdidas 102.3KW P Utilizada 1332.4 kW .

3.1.4. Comportamiento de desbalance del ramal Esquipulas

En la siguiente tabla se muestra la corriente de neutro que representa el nivel de desbalance en demanda mxima, este alcanza un valor mximo 39.71 A y un valor mnimo 5.45 A, que de acuerdo a las exigencia regulatorias no debe exceder en 3 A. Tabla IX. Comportamiento de desbalance del ramal Esquipulas

49

En la siguiente figura se muestra el comportamiento de las corrientes en cada fase y la corriente de neutro durante las horas del da, la fase R es la mas baja y la fase T es la mas alta.

Figura 21. Grfica del comportamiento de desbalance del ramal Esquipulas

A continuacin se presenta el diagrama topolgico de la red urbana de Esquipulas donde ilustra los cdigos de los transformadores y de los tramos descritos en las tablas de flujo de carga.

50

Figura 22. Diagrama topolgico de la lnea de Esquipulas 13.8 kV

51

52

3.1.5 Clculo y anlisis de resultados de ndices de confiabilidad

3.1.5.1 ndices de calidad de servicio (interrupciones)

La calidad del servicio tcnico o continuidad del suministro hace referencia a la existencia o no de tensin en el punto de conexin. Cuando falla la continuidad del servicio. Todas las interrupciones de suministro se caracterizan por su duracin, y solamente se toman en cuenta las interrupciones largas, que exceden ms de tres minutos. FMIK = j Qkfsj/Qki Tenemos 20 Interrupciones en el ao (enero-Diciembre 2005) 5530 kVA interrumpidos en el semestre(enero-Diciembre 2005) 10450 kVA Instalados
FMIK = (20)*5530/10450= 10.58 interrupciones / ao

TTIK = TIK = j Qkfsj*Tfsj/Qki Tenemos 20 Interrupciones en el ao(enero-Diciembre 2005) 5530 kVA interrumpidos en el semestre(enero-Diciembre 2005) 23.6 horas de interrupcin 10450 kVA Instalados
TTIK = (20)*5530*23.6/10450= 249.77 interrupciones-Horas / ao

53

3.1.5.2 ndices de calidad del producto

Las interrupciones breves, o menores de tres minutos(lo exigido por la Comisin Nacional de Energa Elctrica), se consideran un problema de calidad de onda, ya que se deben a la operacin de los sistemas de proteccin de las redes: reenganches rpidos debidos a fallas transitorias o fugitivas, operacin de aislamiento de tramos con falla, etc. El control para la Regulacin de Tensin se realizo por medio del sistema flujo de carga de la lnea en anlisis, debido a que se ha logrado identificar que son aproximadamente iguales.

3.2 Aplicacin de la Metodologa de Planificacin y Expansin para la red urbana de Esquipulas.

3.2.1 Sistema de distribucin propuesto

La metodologa de planificacin y expansin de redes analiza diferentes puntos, que dependiendo del caso en anlisis sern aplicados. Con el flujo de carga descrito anteriormente se termino que existe un porcentaje de perdidas de 13.6% y un 8% de regulacin, tambin los registros de fallas registran un FMIK y TTIK alto por no tener un criterio de proteccin objetivo es mejorar las condiciones de la red. confiable nuestro

54

En la figura 22 se describe el diagrama unifilar correspondiente a la red a modificar, en la adecuacin se crear otro circuito , con el objetivo de dividir la carga y que cada ramal tenga aproximadamente el 50% del total instalado, separado con el elemento de maniobra, y cada ramal de dividir en dos segmentos, tambin separados por un elemento de maniobra, es decir que entre cada seccionamiento se tenga el 25% de lo instalado, esto mejorara la confiabilidad de la red, porque cuando exista una falla solo se perder el 25% de la carga instalada, esto se describe en la figura siguiente. Figura 23. Diagrama unifilar del sistema propuesto

69 kV

S Quezaltepeque E

34.5 kV

69/34.5 kV

Linea 34.5 kV

S E E squipulas

25%
Esquipulas 1

25%
Elemento de Maniobra N.A

Elemento de maniobra N.C.

34.5/13.8 kV 34.5 kV 13.8 kV

25%
E squipulas 2

25%

55

3.2.2 Remodelacin de red de distribucin de Esquipulas De acuerdo a la metodologa se debe definir una lnea principal, y luego de ella debern salir derivadas y de estas saldrn subderivadas, con una proteccin en cabecera que coordine con la proteccin de la subestacin. En la configuracin propuesta (figura 23) se define una lnea principal, la cual ser reconductorado debido a que ser el eje principal del ramal, continuacin se describe el tramo y conductor a instalar: Tabla X. Tramos a reconductorado
Tramos 1 12 17 58 59 60 64 66 67 217 219 253 254 298 299 300 304 305 306 307 Total Longitud Conductor a instalar 0.8 4/0 AWG ASCR 0.095 4/0 AWG ASCR 0.115 4/0 AWG ASCR 0.027 4/0 AWG ASCR 0.088 4/0 AWG ASCR 0.022 4/0 AWG ASCR 0.065 4/0 AWG ASCR 0.001 4/0 AWG ASCR 0.001 4/0 AWG ASCR 0.048 4/0 AWG ASCR 0.177 4/0 AWG ASCR 0.135 4/0 AWG ASCR 0.029 4/0 AWG ASCR 0.034 4/0 AWG ASCR 0.095 4/0 AWG ASCR 0.135 4/0 AWG ASCR 0.115 4/0 AWG ASCR 0.266 4/0 AWG ASCR 0.122 4/0 AWG ASCR 0.033 4/0 AWG ASCR 2.403

56

Con la definicin de la lnea principal se debe convertir de lnea monofsica a trifsica los siguientes tramo; con el fin de obtener derivaciones con carga instalada al menos 5%.

Tabla XI. Tramos a Convertir de monofsica a trifsica


Tramos 77 121 223 224 123 Total Longitud Conductor a instalar 0.073 4/0 AWG ASCR 0.058 4/0 AWG ASCR 0.061 4/0 AWG ASCR 0.16 4/0 AWG ASCR 0.251 4/0 AWG ASCR 0.603

Como se describi en la figura 22 se crear un nuevo ramal al cual tambin, se debe definir un eje principal, la definicin de la lnea principal la constituirn tramos nuevos, los cuales se describen a continuacin:

Tabla XII. Tramos a nuevos y lnea Nueva


Tramos 392 393 394 Lnea Nueva Total Longitud Conductor a instalar 0.6 4/0 AWG ASCR 0.4 4/0 AWG ASCR 1.3 4/0 AWG ASCR 4.3 4/0 AWG ASCR 6.6

57

Con la creacin de nuevos tramos y la remodelacin de otros se crea una nueva topologa la cual se describe a continuacin donde muestra los tramos mencionados en las tablas X, XI, XII. Con la nueva configuracin topolgica se desmantelaran los siguientes tramos 36,38,39,92,140,190,285, a continuacin se describe el nuevo diagrama topolgico, en la figura 23, en el siguiente diagrama topolgico propuesto.

58

Figura 24. Diagrama topolgico propuesto

59

60

Luego del

diagrama topolgico propuesto se agruparn todas las

derivadas que parten de la lnea principal y las subderivadas que arranquen de las derivadas, con el objetivo de calcular la proteccin en cabeceras de las mismas.

3.2.3 Clculo y anlisis de flujo de carga de la red Esquipulas 13.8 kV propuesto.

En el apartado 3.1.4 muestra el anlisis de flujo de carga actual, ahora se presenta el flujo de carga propuesto, con las modificaciones antes mencionados. Tabla XII. Flujo de carga propuesta (demanda mxima)
Codigo del Fase Fase Fase Tensin Trafo. R S T Nominal 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 50 25 25 10 37.5 50 25 25 25 25 25 25 15 25 25 25 37.5 37.5 50 50 50 37.5 25 25 50 10 50 50 10 15 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.6 7.6 7.6 7.6 7.6 Tension Tension Tensin % Perdida R S T Regulacin s (kW) 7.6 0 0 0 0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0.1 0.1 0.1 0.1 0.2 0.1 0.3 0.3 0.4 0.1 0.2 0.1 0.3 0.3 0.4 0.4 0.5 0.6 0.7 0.6 0.8 0.9 Codigo del Conductor Conductor 14/0 AWG ASCR 24/0 AWG ASCR 34/0 AWG ASCR 4No. 2 AWG ASCR 54/0 AWG ASCR 6No. 2 AWG ASCR 74/0 AWG ASCR 8No. 2 AWG ASCR 9No. 2 AWG ASCR 10No. 2 AWG ASCR 114/0 AWG ASCR 12No. 2 AWG ASCR 134/0 AWG ASCR 14No. 2 AWG ASCR 15No. 2 AWG ASCR 16No. 2 AWG ASCR 174/0 AWG ASCR 184/0 AWG ASCR 19No. 2 AWG ASCR 20No. 2 AWG ASCR 21No. 2 AWG ASCR 22No.4 AWG ASCR Longitud (km) 0.8 0.379 0.557 0.102 0.525 0.122 0.033 0.06 0.037 0.038 0.034 0.095 0.135 0.029 0.009 0.395 0.115 0.266 0.352 1.163 0.69 0.364 OHMIOS CAPACIDAD /KM (AMPERIOS) 1.25 1.25 1.25 1.09 1.25 1.09 1.25 1.09 1.09 1.09 1.25 1.09 1.25 1.09 1.09 1.09 1.25 1.25 1.09 1.09 1.09 1.25 385 385 385 184 385 184 385 184 184 184 385 184 385 184 184 184 385 385 184 184 184 385

61

Codigo del Fase Fase Fase Tensin Trafo. R S T Nominal 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 25 25 25 25 25 25 25 25 10 15 15 25 25 25 40 25 25 25 15 25 25 62.5 37.5 25 25 25 25 25 25 37.5 25 10 25 25 25 10 25 25 25 25 25 25 25 25 25 37.5 37.5 25 25 25 25 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6

Tension Tension Tensin % Perdida R S T Regulacin s (kW) 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0.5 0.6 0.7 0.6 0.8 0.9 0.9 0.5 0.6 0.7 0.6 0.8 1.123 0.3 1.3 0 0.2 0.2 0.4 0.3 0.2 0.2 0.4 0.3 0.2 0.2 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.3 0.2 0.4 0.3 0.2 0.4 0.3 0.2 0.2 0.4 0.2 0.4 0.2 0.4

Codigo del Conductor Conductor 23No. 2 AWG ASCR 24No. 2 AWG ASCR 25No. 2 AWG ASCR 26No. 2 AWG ASCR 27No. 2 AWG ASCR 28No. 2 AWG ASCR 29No. 2 AWG ASCR 30No. 2 AWG ASCR 31No. 2 AWG ASCR 32No. 2 AWG ASCR 33No. 2 AWG ASCR 34No. 2 AWG ASCR 35No. 2 AWG ASCR 36No. 2 AWG ASCR 37No. 2 AWG ASCR 40No. 2 AWG ASCR 41No. 2 AWG ASCR 42No. 2 AWG ASCR 43No. 2 AWG ASCR 44No. 2 AWG ASCR 45No. 2 AWG ASCR 46No. 2 AWG ASCR 47No. 2 AWG ASCR 48No. 2 AWG ASCR 49No. 2 AWG ASCR 50No. 2 AWG ASCR 51No. 2 AWG ASCR 52No. 2 AWG ASCR 53No. 2 AWG ASCR 54No. 2 AWG ASCR 55No. 2 AWG ASCR 56No. 2 AWG ASCR 57No. 2 AWG ASCR 584/0 AWG ASCR 594/0 AWG ASCR 604/0 AWG ASCR 614/0 AWG ASCR 62No. 2 AWG ASCR 63No. 2 AWG ASCR 644/0 AWG ASCR 654/0 AWG ASCR 664/0 AWG ASCR 674/0 AWG ASCR 684/0 AWG ASCR 69No.4 AWG ASCR 70No.4 AWG ASCR 71No.4 AWG ASCR 72No.4 AWG ASCR 73No.4 AWG ASCR

Longitud (km) 0.209 1.148 0.374 0.006 0.222 0.067 0.078 0.1 0.038 0.05 0.721 0.023 0.025 0.045 0.035 0.077 0.107 0.041 0.037 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.057 0.153 0.072 0.066 0.065 0.063 0.027 0.088 0.022 0.11 0.202 0.066 0.065 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.06

OHMIOS CAPACIDAD /KM (AMPERIOS) 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.25 1.25 1.25 1.25 0.71 0.472 1.25 1.25 1.25 1.25 1.25 0.472 0.472 1.7 1.7 1.7 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 385 385 385 385 242 315 385 385 385 385 385 315 315 140 140 140

62

Codigo del Fase Fase Fase Tensin Trafo. R S T Nominal 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 25 25 25 25 35 25 35 25 25 25 25 25 25 25 25 15 62.5 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 15 25 75 25 25 25 25 25 50 50 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6

Tension Tension Tensin % Perdida R S T Regulacin s (kW) 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0.2 0.4 0.2 0.4 0.2 0.4 0.3 0.2 0.4 0.2 0.4 0.2 0.2 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.3 0.2 0.4 0.2 0.4 0.3 0.2 0.4 0.2 0.4 0.3 0.2 0.4 0.3 0.2 0.4 0.2 0.4 0.5 0.3 0.4 0.6 0.8 0.7 0.4 0.2 0.4 0.2 0.4

Codigo del Conductor Conductor 74No.4 AWG ASCR 75No.4 AWG ASCR 76No.4 AWG ASCR 774/0 AWG ASCR 78No.4 AWG ASCR 79No.4 AWG ASCR 80No.4 AWG ASCR 81No.4 AWG ASCR 82No.4 AWG ASCR 83No.4 AWG ASCR 84No.4 AWG ASCR 85No.4 AWG ASCR 86No.4 AWG ASCR 87No.4 AWG ASCR 881/0 AWG ASCR 891/0 AWG ASCR 901/0 AWG ASCR 91No. 2 AWG ASCR 93No. 2 AWG ASCR 94No. 2 AWG ASCR 95No. 2 AWG ASCR 96No. 2 AWG ASCR 97No. 2 AWG ASCR 98No. 2 AWG ASCR 99No. 2 AWG ASCR 100No. 2 AWG ASCR 101No. 2 AWG ASCR 102No. 2 AWG ASCR 103No. 2 AWG ASCR 1041/0 AWG ASCR 105No. 2 AWG ASCR 106No. 2 AWG ASCR 107No. 2 AWG ASCR 108No. 2 AWG ASCR 1091/0 AWG ASCR 110No.4 AWG ASCR 1111/0 AWG ASCR 112No.4 AWG ASCR 113No.4 AWG ASCR 114No.4 AWG ASCR 115No.4 AWG ASCR 116No.4 AWG ASCR 117No.4 AWG ASCR 118No.4 AWG ASCR 119No.4 AWG ASCR 120No.4 AWG ASCR 1214/0 AWG ASCR 122No.4 AWG ASCR 123No.4 AWG ASCR

Longitud (km) 0.063 0.148 0.18 0.073 0.567 0.129 0.081 0.035 0.085 0.113 0.345 0.211 0.014 0.1 0.062 0.077 0.237 0.038 0.111 0.095 0.036 0.065 0.046 0.127 0.199 0.045 0.134 0.127 0.104 0.12 0.226 0.005 0.102 0.1 0.008 0.14 0.07 0.149 0.059 0.103 0.238 0.222 0.039 0.26 0.242 0.043 0.058 0.04 0.251

OHMIOS CAPACIDAD /KM (AMPERIOS) 1.7 1.7 1.7 1.25 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 0.71 0.71 0.71 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 0.71 1.09 1.09 1.09 1.09 0.71 1.7 0.71 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 140 140 140 385 140 140 140 140 140 140 140 140 140 140 140 140 242 242 242 184 184 184 184 184 184 184 184 184 184 184 184 184 242 184 184 184 184 242 140 242 140 140 140 140 140 140 140 140 140

63

Codigo del Fase Fase Fase Tensin Trafo. R S T Nominal 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 25 25 25 25 10 15 25 25 15 50 50 15 25 50 25 50 75 50 15 10 15 50 75 20 10 25 10 50 10 62.5 25 37.5 37.5 50 25 25 50 50 25 37.5 37.5 25 50 50 37.5 25 37.5 25 25 62.5 50 37.5 25 75 45 15 10 25 25 25 50 50 50 50 50 50 35 10 25 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6

Tension Tension Tensin % Perdida R S T Regulacin s (kW) 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0.2 0.4 0.3 0.2 0.2 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.4 0.2 0.4

Codigo del Conductor Conductor 124No.4 AWG ASCR 125No.4 AWG ASCR 126No.4 AWG ASCR 127No.4 AWG ASCR 128No.4 AWG ASCR 129No.4 AWG ASCR 130No.4 AWG ASCR 131No.4 AWG ASCR 132No.4 AWG ASCR 133No. 2 AWG ASCR 134No. 2 AWG ASCR 135No. 2 AWG ASCR 1361/0 AWG ASCR 1371/0 AWG ASCR 138No. 2 AWG ASCR 139No. 2 AWG ASCR 141No. 2 AWG ASCR 142No. 2 AWG ASCR 143No. 2 AWG ASCR 144No. 2 AWG ASCR 145No. 2 AWG ASCR 146No. 2 AWG ASCR 147No. 2 AWG ASCR 148No. 2 AWG ASCR 149No. 2 AWG ASCR 150No. 2 AWG ASCR 151No. 2 AWG ASCR 152No. 2 AWG ASCR 153No. 2 AWG ASCR 154No. 2 AWG ASCR 155No. 2 AWG ASCR 156No. 2 AWG ASCR 157No. 2 AWG ASCR 158No. 2 AWG ASCR 159No. 2 AWG ASCR 160No. 2 AWG ASCR 161No. 2 AWG ASCR 162No. 2 AWG ASCR 163No. 2 AWG ASCR 164No. 2 AWG ASCR 165No. 2 AWG ASCR 166No. 2 AWG ASCR 167No. 2 AWG ASCR 168No. 2 AWG ASCR 169No. 2 AWG ASCR 170No. 2 AWG ASCR 171No. 2 AWG ASCR 172No. 2 AWG ASCR 173No. 2 AWG ASCR

Longitud (km) 0.023 0.145 0.206 0.065 0.015 0.068 0.107 0.021 0.063 0.731 0.568 0.001 0.038 0.031 0.06 0.104 0.12 0.044 0.149 0.15 0.109 0.026 0.033 0.047 0.107 0.219 0.042 0.032 0.041 0.12 0.246 0.07 0.02 0.167 0.087 0.205 0.13 0.009 0.236 0.073 0.122 0.047 0.05 0.044 0.049 0.041 0.053 0.06 0.158

OHMIOS CAPACIDAD /KM (AMPERIOS) 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.09 1.09 1.09 0.71 0.71 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 140 140 140 140 140 140 140 140 140 140 140 140 184 184 184 242 242 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184

64

Codigo del Fase Fase Fase Tensin Trafo. R S T Nominal 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 25 25 25 50 25 25 25 15 50 50 20 25 10 25 37.5 50 50 50 50 50 10 25 25 25 15 50 62.5 62.5 25 50 47.5 25 10 25 10 35 37.5 37.5 75 37.5 50 50 10 25 25 50 50 50 50 50 50 50 25 37.5 10 25 50 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6

Tension Tension Tensin % Perdida R S T Regulacin s (kW) 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0.2 0.4 0.2 0.4 0.3 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.3 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.3 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.3 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.4 0.2 0.4 0.2 0.4 0.2

Codigo del Conductor Conductor 174No. 2 AWG ASCR 175No. 2 AWG ASCR 176No. 2 AWG ASCR 177No. 2 AWG ASCR 178No. 2 AWG ASCR 179No. 2 AWG ASCR 180No. 2 AWG ASCR 181No. 2 AWG ASCR 182No. 2 AWG ASCR 183No. 2 AWG ASCR 184No. 2 AWG ASCR 185No. 2 AWG ASCR 186No. 2 AWG ASCR 187No. 2 AWG ASCR 188No.4 AWG ASCR 189No.4 AWG ASCR 191No.4 AWG ASCR 192No.4 AWG ASCR 193No.4 AWG ASCR 194No.4 AWG ASCR 195No.4 AWG ASCR 196No.4 AWG ASCR 197No.4 AWG ASCR 198No.4 AWG ASCR 199No.4 AWG ASCR 200No.4 AWG ASCR 201No.4 AWG ASCR 202No.4 AWG ASCR 203No.4 AWG ASCR 204No.4 AWG ASCR 205No.4 AWG ASCR 206No.4 AWG ASCR 207No.4 AWG ASCR 208No.4 AWG ASCR 209No.4 AWG ASCR 210No.4 AWG ASCR 211No.4 AWG ASCR 212No.4 AWG ASCR 213No.4 AWG ASCR 214No.4 AWG ASCR 215No.4 AWG ASCR 216No.4 AWG ASCR 217No.4 AWG ASCR 2184/0 AWG ASCR 219No.4 AWG ASCR 2204/0 AWG ASCR 2214/0 AWG ASCR 222No.4 AWG ASCR 223No.4 AWG ASCR

Longitud (km) 0.038 0.026 0.036 0.068 0.036 0.028 0.04 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.033 1.517 0.065 0.097 0.518 0.089 0.034 0.063 0.161 0.078 0.205 0.228 0.558 0.526 0.348 0.164 0.1 0.026 0.095 0.051 0.059 0.033 0.027 0.203 0.048 0.201 0.111 0.048 0.184 0.177 0.07 0.245 0.001 0.061

OHMIOS CAPACIDAD /KM (AMPERIOS) 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140

65

Codigo del Fase Fase Fase Tensin Trafo. R S T Nominal 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 25 100 15 25 25 25 25 25 100 100 37.5 25 25 25 25 37.5 10 25 25 37.5 50 50 50 15 25 50 10 25 25 15 37.5 25 10 75 25 15 25 15 15 25 10 25 25 25 25 25 35 25 15 25 25 25 25 25 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6

Tension Tension Tensin % Perdida R S T Regulacin s (kW) 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0.4 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.3 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.3 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.4 0.2 0.4 0.2 0.4 0.2

Codigo del Conductor Conductor 2244/0 AWG ASCR 225No.4 AWG ASCR 226No.4 AWG ASCR 227No.4 AWG ASCR 228No.4 AWG ASCR 229No.4 AWG ASCR 230No.4 AWG ASCR 231No.4 AWG ASCR 232No.4 AWG ASCR 233No.4 AWG ASCR 234No.4 AWG ASCR 235No.4 AWG ASCR 236No.4 AWG ASCR 237No.4 AWG ASCR 238No.4 AWG ASCR 239No.4 AWG ASCR 240No.4 AWG ASCR 241No.4 AWG ASCR 242No.4 AWG ASCR 243No.4 AWG ASCR 244No.4 AWG ASCR 245No.4 AWG ASCR 246No.4 AWG ASCR 247No.4 AWG ASCR 248No.4 AWG ASCR 249No.4 AWG ASCR 250No.4 AWG ASCR 251No.4 AWG ASCR 252No.4 AWG ASCR 2534/0 AWG ASCR 2544/0 AWG ASCR 255No.4 AWG ASCR 256No.4 AWG ASCR 257No.4 AWG ASCR 258No.4 AWG ASCR 259No.4 AWG ASCR 2601/0 AWG ASCR 2611/0 AWG ASCR 2621/0 AWG ASCR 263No. 2 AWG ASCR 264No. 2 AWG ASCR 265No. 2 AWG ASCR 2661/0 AWG ASCR 267No. 2 AWG ASCR 268No. 2 AWG ASCR 269No. 2 AWG ASCR 270No. 2 AWG ASCR 271No. 2 AWG ASCR 272No. 2 AWG ASCR

Longitud (km) 0.16 0.236 0.14 0.038 0.073 0.081 0.079 0.033 0.519 0.089 0.027 0.179 0.053 0.038 0.039 0.071 0.118 0.118 0.009 0.102 0.519 0.109 0.122 0.033 0.06 0.037 0.038 0.034 0.095 0.135 0.029 0.122 0.033 0.06 0.037 0.038 0.034 0.095 0.135 0.029 0.009 0.395 0.115 0.266 0.122 0.033 0.06 0.037 0.038

OHMIOS CAPACIDAD /KM (AMPERIOS) 1.25 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.25 1.25 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 0.71 0.71 0.71 1.09 1.09 1.09 0.71 1.09 385 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 385 385 140 140 140 140 140 140 140 140 140 140 242 242 242 184 184 184 242 184

66

Codigo del Fase Fase Fase Tensin Trafo. R S T Nominal 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 Total 10 25 25 25 3460 3545 3445 75 50 10 15 25 25 15 25 75 50 10 75 50 10 25 25 25 25 37.5 10 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6

Tension Tension Tensin % Perdida R S T Regulacin s (kW) 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0.4 0.3 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.4 0.2 0.4 0.2 0.4 0.2 0.4 0.3 0.2 0.1 0.2 95.623

Codigo del Conductor Conductor 273No. 2 AWG ASCR 274No. 2 AWG ASCR 275No. 2 AWG ASCR 276No. 2 AWG ASCR 277No. 2 AWG ASCR 278No. 2 AWG ASCR 279No. 2 AWG ASCR 280No. 2 AWG ASCR 281No. 2 AWG ASCR 2821/0 AWG ASCR 283No. 2 AWG ASCR 2841/0 AWG ASCR 286No. 2 AWG ASCR 287No. 2 AWG ASCR 288No. 2 AWG ASCR 289No. 2 AWG ASCR 290No. 2 AWG ASCR 291No. 2 AWG ASCR 292No. 2 AWG ASCR 293No. 2 AWG ASCR 294No. 2 AWG ASCR 295No. 2 AWG ASCR 296No. 2 AWG ASCR 297No. 2 AWG ASCR 2984/0 AWG ASCR 2994/0 AWG ASCR 3004/0 AWG ASCR 3014/0 AWG ASCR 302No. 2 AWG ASCR 303No. 2 AWG ASCR 3044/0 AWG ASCR 3054/0 AWG ASCR 3064/0 AWG ASCR 3074/0 AWG ASCR 3084/0 AWG ASCR 3091/0 AWG ASCR 310No. 2 AWG ASCR 311No. 2 AWG ASCR 312No. 2 AWG ASCR 313No. 2 AWG ASCR 314No. 2 AWG ASCR 315No. 2 AWG ASCR 316No. 2 AWG ASCR 317No. 2 AWG ASCR 318No. 2 AWG ASCR 319No. 2 AWG ASCR 320No. 2 AWG ASCR 321No. 2 AWG ASCR 322No. 2 AWG ASCR

Longitud (km) 0.034 0.095 0.135 0.029 0.009 0.395 0.115 0.122 0.033 0.06 0.037 0.038 0.095 0.135 0.029 0.009 0.395 0.115 0.266 0.122 0.033 0.06 0.037 0.038 0.034 0.095 0.135 0.029 0.009 0.395 0.115 0.266 0.122 0.033 0.06 0.037 0.038 0.034 0.095 0.135 0.029 0.009 0.395 0.115 0.266 0.122 0.033 0.06 0.037

OHMIOS CAPACIDAD /KM (AMPERIOS) 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 0.71 1.09 0.71 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.25 1.25 1.25 1.25 1.09 1.09 1.25 1.25 1.25 1.25 1.25 1.09 1.09 1.09 0.71 0.71 0.71 0.71 1.09 1.09 1.09 1.09 1.09 1.09 1.09 184 184 184 184 184 184 184 184 184 184 184 184 184 184 242 184 242 184 184 184 184 184 184 184 385 385 385 385 184 184 385 385 385 385 385 184 184 184 242 242 242 242 184 184 184 184 184 184 184

67

Codigo del Fase Fase Fase Tensin Trafo. R S T Nominal

Tension Tension Tensin % Perdida R S T Regulacin s (kW)

Codigo del Conductor Conductor 323No. 2 AWG ASCR 324No. 2 AWG ASCR 325No. 2 AWG ASCR 326No. 2 AWG ASCR 327No. 2 AWG ASCR 328No. 2 AWG ASCR 3291/0 AWG ASCR 330No. 2 AWG ASCR 331No. 2 AWG ASCR 332No. 2 AWG ASCR 333No. 2 AWG ASCR 334No. 2 AWG ASCR 335No. 2 AWG ASCR 336No. 2 AWG ASCR 337No. 2 AWG ASCR 3381/0 AWG ASCR 3391/0 AWG ASCR 3401/0 AWG ASCR 341No. 2 AWG ASCR 342No. 2 AWG ASCR 343No. 2 AWG ASCR 3441/0 AWG ASCR 345No. 2 AWG ASCR 346No. 2 AWG ASCR 347No. 2 AWG ASCR 348No. 2 AWG ASCR 349No. 2 AWG ASCR 350No. 2 AWG ASCR 351No. 2 AWG ASCR 352No. 2 AWG ASCR 353No. 2 AWG ASCR 354No. 2 AWG ASCR 355No. 2 AWG ASCR 356No. 2 AWG ASCR 357No. 2 AWG ASCR 358No. 2 AWG ASCR 359No. 2 AWG ASCR 360No. 2 AWG ASCR 361No. 2 AWG ASCR 362No. 2 AWG ASCR 363No. 2 AWG ASCR 364No. 2 AWG ASCR 3651/0 AWG ASCR 3661/0 AWG ASCR 3671/0 AWG ASCR 3681/0 AWG ASCR 369No. 2 AWG ASCR 3701/0 AWG ASCR 3711/0 AWG ASCR

Longitud (km) 0.038 0.034 0.095 0.135 0.029 0.009 0.395 0.115 0.266 0.122 0.033 0.06 0.037 0.038 0.034 0.095 0.135 0.029 0.009 0.395 0.115 0.266 0.122 0.033 0.06 0.037 0.038 0.034 0.095 0.135 0.029 0.009 0.395 0.122 0.033 0.06 0.037 0.038 0.034 0.095 0.135 0.029 0.009 0.395 0.122 0.033 0.06 0.037 0.038

OHMIOS CAPACIDAD /KM (AMPERIOS) 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 0.71 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 0.71 0.71 0.71 1.09 1.09 1.09 0.71 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 1.09 184 184 184 184 184 184 184 184 184 184 184 184 242 184 184 184 184 184 184 184 184 242 242 242 184 184 184 242 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 184 242

68

Codigo del Fase Fase Fase Tensin Trafo. R S T Nominal

Tension Tension Tensin % Perdida R S T Regulacin s (kW)

Codigo del Conductor Conductor 372No. 2 AWG ASCR 3731/0 AWG ASCR 374No. 2 AWG ASCR 3751/0 AWG ASCR 376No. 2 AWG ASCR 3771/0 AWG ASCR 3781/0 AWG ASCR 379No. 2 AWG ASCR 3801/0 AWG ASCR 3811/0 AWG ASCR 3821/0 AWG ASCR 383No. 2 AWG ASCR 384No. 2 AWG ASCR 385No. 2 AWG ASCR 386No. 2 AWG ASCR 387No. 2 AWG ASCR 388No. 2 AWG ASCR 389No. 2 AWG ASCR 390No. 2 AWG ASCR 391No. 2 AWG ASCR 3924/0 AWG ASCR 3934/0 AWG ASCR 3944/0 AWG ASCR 3934/0 AWG ASCR 3944/0 AWG ASCR 3954/0 AWG ASCR 3964/0 AWG ASCR 3974/0 AWG ASCR 3984/0 AWG ASCR 3994/0 AWG ASCR 4004/0 AWG ASCR 4014/0 AWG ASCR 4024/0 AWG ASCR 4034/0 AWG ASCR 4044/0 AWG ASCR 4054/0 AWG ASCR 4064/0 AWG ASCR 4074/0 AWG ASCR 4084/0 AWG ASCR 4094/0 AWG ASCR 4104/0 AWG ASCR Total

Longitud (km) 0.034 0.095 0.135 0.029 0.009 0.395 0.115 0.266 0.122 0.033 0.06 0.037 0.038 0.034 0.095 0.135 0.029 0.009 0.395 0.115 0.6 0.4 1.3 0.723 0.62 0.015 0.321 0.215 0.352 0.02 0.214 0.214 0.281 0.182 0.181 0.154 0.22 0.14 0.153 0.15 0.21 52.811

OHMIOS CAPACIDAD /KM (AMPERIOS) 1.09 1.09 1.09 0.71 1.09 1.09 0.71 1.09 0.71 1.09 0.71 1.09 1.09 0.71 1.09 1.09 1.09 0.71 0.71 0.71 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 242 242 242 184 242 242 184 242 184 242 184 242 242 184 242 242 242 184 184 184 385 385 385 385 385 385 385 385 385 385 385 385 385 385 385 385 385 385 385 385 385

69

Tabla XIV. Resultado de flujo de carga propuesta (demanda mxima).


Flujo de Carga 10,450.0 kVA Instalado: 4,329.4 kVA Utilizado: 3,680.0 kW Utilizado: 52.8 Longitud (kms): 95.6 kW Prdidas: 2.6% % Prdidas: 2.0% % Regulacin:

Figura 25. Diagrama unifilar Esquipulas (demanda mxima)

S E

R egulac in 2% P erdidas 2.6 KW P Utilizada 3680 kW .

Tabla XV. Resultado de flujo de carga propuesta (demanda media).


Flujo de Carga 10,450.0 kVA Instalado: 2,612.5 kVA Utilizado: 2,220.6 kW Utilizado: 52.8 Longitud (kms): 55.0 kW Prdidas: 2.5% % Prdidas: 1.0% % Regulacin:

70

Figura 26. Diagrama unifilar Esquipulas (demanda media)

S E

Regulac in 1% Perdidas 2.5 KW P Utilizada 2202.6 kW .

Tabla XVI. Resultado de flujo de carga propuesta (demanda baja).


Flujo de Carga 10,450.0 kVA Instalado: 1,567.5 kVA Utilizado: 1,332.4 kW Utilizado: 58.2 Longitud (kms): 23.0 kW Prdidas: 1.7% % Prdidas: 1.0% % Regulacin:

Figura 27. Diagrama unifilar Esquipulas (demanda baja)

S E

Regulac in 1% Perdidas 1.7KW P Utilizada 1332.4 kW .

71

3.2.3.1 Comportamiento de desbalance del ramal Esquipulas

En la siguiente tabla se muestra la corriente de neutro que representa el nivel de desbalance en diferentes horarios en la barra de la subestacin, que de acuerdo a la aplicacin de la metodologa se logra alcanzar la corriente de neutro a niveles regulatorios. Tabla XVI. Comportamiento de desbalance del ramal Esquipulas
Hora 00:00 01:00 02:00 03:00 04:00 05:00 06:00 07:00 08:00 09:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 Fase R (A) Fase S (A) Fase T (A) Neutro (A) 56.4 61.9 68.5 68.9 69.3 70.0 70.4 70.8 73.5 73.5 74.0 73.9 79.9 87.0 92.9 97.7 111.7 123.8 154.8 160.3 154.8 81.5 63.9 58.0 57.8 63.4 70.2 70.6 71.0 71.8 72.2 72.6 75.3 75.3 75.8 75.7 81.9 89.1 95.2 100.1 114.4 126.9 158.6 164.3 158.6 83.5 65.5 59.5 56.1 61.7 68.2 68.6 69.0 69.7 70.1 70.5 73.2 73.2 73.7 73.6 79.6 86.6 92.5 97.3 111.2 123.3 154.1 159.6 154.1 81.1 63.7 57.8 1.5 1.7 1.8 1.9 1.9 1.9 1.9 1.9 2.0 2.0 2.0 2.0 2.2 2.3 2.5 2.6 3.0 3.3 4.2 4.3 4.2 2.2 1.7 1.6

72

Figura 28 Grfica del comportamiento de desbalance del ramal Esquipulas

Grafica Corriente/fase
200.0 Corriente (A) 150.0 100.0 50.0 0.0 Fase R Fase S Fase T Neutro

00

00

00

00

00

00

00 18 :

00 :

03 :

06 :

09 :

En la grafica anterior se muestra el comportamiento de la corriente de neutro que bajo considerablemente.

3.2.4 Agrupacin de derivadas y suberivadas con su respectiva proteccin

Como se describi en la figura 12, y de acuerdo a la metodologa de planificacin y expansin de sistemas de distribucin se hicieron las siguientes modificaciones en la red de distribucin de Esquipulas: Se reparti la carga instalada en dos ramales, los cuales les llamaremos Esquipulas 1 & Esquipulas 2, los cuales se unirn en un elemento de maniobra que estar normalmente abierto y que se le llamara punto de reflexin.

12 :

hora

73

15 :

21 :

00

Cada ramal tambin se dividi en dos segmentos y unidos por medio de un elemento de maniobra que estar normalmente cerrado. Cada ramal tienen un eje llamada lnea principal, de esta saldrn todas las derivaciones y cuando estas sean muy grandes tambin tendrn una lnea principal la cual saldrn las subderivaciones. Cada subderivada tendrn un corta-circuito en cabecera y debe

coordinar con el fusible de cabecera en la derivada de origen y luego este debe coordinar con el reconectador de cabecera en la subestacin . A continuacin se muestra las grafica de tiempo inverso de los fusibles y las curvas de disparo del recloser de la subestacin. Figura 29. Grfica de coordinacin de protecciones

74

Tabla XVII. Agrupacin y proteccin Esquipulas 1 segmento 1

Agrupacin Derivada 1 Derivada 2 Derivada 3 Derivada 4 Derivada 5 Derivada 6 Derivada 7 Derivada 8 Derivada 9 principal Subderivada a Derivada 10 Derivada 11 principal Subderivada a Subderivada b Subderivada c Subderivada d Subderivada e Subderivada f Subderivada g Derivada 12 principal Subderivada a Subderivada b Subderivada c Subderivada d Subderivada e Subderivada f Subderivada g Subderivada h Principal Total / fase

Fase R 15 50

Fase S

Fase T

225 125 10 175 50 150 50 100 375 100 150 75 15 15 50 75 75 25 352.5 75

Imax*1.5 Proteccin 10 1.97 Fusible 10 2.96 Fusible 11 9.87 Fusible 12 35.53 Fusible 40 24.67 Fusible 25 1.97 Fusible 10 34.54 Fusible 40 50 9.87 Fusible 10 23.68 Fusible 25 15.79 Fusible 15 4.93 Fusible 10 59.21 Fusible 60 25 4.93 29.61 14.80 4.93 4.93 19.74 44.90 130.26 4.93 4.93 22.20 58.22 1.97 19.74 4.93 22.70 Fusible Fusible Fusible Fusible Fusible Fusible Fusible Fusible Fusible Fusible Fusible Fusible Fusible Fusible Fusible Fusible 10 10 10 10 10 10 15 40 10 10 10 15 10 10 10 10

125 25

25 25 100 25 390 55 25 72.5 62.5 100 25 50 215 1245 227.5 660 62.5 25 25 37.5 295 100 115 65 1247.5

445 60 25 112.5 87.5 10 100 25 25 85 1245

75

Tabla XVIII. Agrupacin y proteccin Esquipulas 1 segmento 2

Agrupacin Derivada 13 Derivada 14 Derivada 15 principal Subderivada a Subderivada b Subderivada c Subderivada d Subderivada e Subderivada f Subderivada g Subderivada h Subderivada i Subderivada j Subderivada k Subderivada l Subderivada m Subderivada n Subderivada Principal Total / fase

Fase R

Fase S 225 732.5 47.5 90 50 25 225 150 10 550

Fase T

122.5 87.5

150

10

125 75 807.5 35 810

65 125

Imax*1.5 Proteccin 35.53 Fusible 40 50 9.87 Fusible 10 730 106.02 Fusible 65 50 307.5 44.51 Fusible 40 14.21 Fusible 15 0 24.18 Fusible 25 17.27 Fusible 15 4.93 Fusible 10 38.49 Fusible 40 150 25.66 Fusible 25 25 4.93 Fusible 10 1.97 Fusible 10 37.5 7.40 Fusible 10 1.97 Fusible 10 10 1.97 Fusible 10 25 4.93 Fusible 10 12.83 Fusible 10 125 24.67 Fusible 25 25 805

76

Tabla XIX. Agrupacin y proteccin Esquipulas 2 segmento 1

Agrupacin Derivada 1 Derivada 2 Derivada 3 Derivada 4 Derivada 5 Derivada 6 Derivada 7 Derivada 8 Derivada 9 Derivada 10 Derivada 11 Derivada 12 Derivada 13 Derivada 14 Derivada 15 Derivada 16 Derivada 17 Derivada 18 principal Subderivada a Subderivada b Principal Total / fase

Fase R

Fase S 87.5 47.5 50 25 25 25 90 65

Fase T

45

162.5 25 50 265 0 25 0 50 250 25 112.5 112.5 150 865

210 25 87.5 97.5 100 882.5

Imax*1.5 Proteccin 13.82 Fusible 40 50 7.89 Fusible 10 75 11.84 Fusible 10 175 27.63 Fusible 25 3.95 Fusible 10 3.95 Fusible 10 3.95 Fusible 10 14.21 Fusible 15 10.26 Fusible 10 25.66 Fusible 25 3.95 Fusible 10 25 3.95 Fusible 10 140 22.11 Fusible 25 3.95 Fusible 10 47.5 41.84 Fusible 40 25 3.95 Fusible 10 50 7.89 Fusible 10 222.5 39.47 Fusible 40 60 137.5 21.71 Fusible 25 25 17.76 Fusible 15 75 885

77

Tabla XIX. Agrupacin y proteccin Esquipulas 2 segmento 2

Agrupacin Derivada 19 principal Subderivada a Subderivada b Subderivada c Subderivada d Derivada 20 Derivada 21 Derivada 22 Derivada 23 Derivada 24 Derivada 25 Derivada 26 Principal Total / fase

Fase R 50 50

Fase S 95 50 10

Fase T 475 50 425 25 10 50

Imax*1.5 Proteccin 62.50 Fusible 60 1.32 55.92 3.29 1.32 6.58 1.97 3.29 29.61 37.83 7.89 1.32 Fusible Fusible Fusible Fusible Fusible Fusible Fusible Fusible Fusible Fusible Fusible 10 40 10 10 10 10 10 25 40 10 10

15 25 115 287.5 10 50 552.5 20 480 625 20 225 60 10 140

10

En la figura siguiente se describe los ramales, derivadas y subderivadas con la numeracin que se les asigno, tambin la localizacin de la proteccin

78

Figura 30. Diagrama topolgico de agrupacin y proteccin

79

80

4.

ANLISIS TCNICO-ECONMICO

4.1 Inversin en la Aplicacin de la metodologa de planificacin y expansin de redes

En los captulos anteriores se describi la metodologa, tambin se eligi una poblacin para la aplicacin de la misma. La realizacin del proyecto representa una inversin, porque una red PLANIFICADA con criterios de crecimiento y proteccin , es una red con bajas perdidas , un ndice de interrupcin bajo y buena regulacin . En el presente capitulo se analizaran las variables que intervienen para encontrar la rentabilidad.

4.1.1 Inversin en remodelacin de lneas de distribucin

Debido al mal estado de la red con una diversidad de calibres de conductores fue necesario plantear el reconductorado, la construccin de tramos nuevos para el nuevo ramal, la definicin del nuevo ramal que significo la reconversin de monofsico a trifsico y otros tramos nuevos para unir los dos ramales como se describi en la figura 12 donde muestra los tramos antes mencionados.

81

En el siguiente cuadro se muestra la magnitud de la obra:

Tabla XX. Cuantificacin de la inversin en la remodelacin

Descripcin Lneas a Reconductorar Lneas a Reconvertir de mono. a tri. Lneas Nuevas Total de la Inversin

Costo (Q/km) Cantidad (km) Q58,953.45 Q78,604.61 Q119,620.30 0.603

Total Q47,398.58 Q978,557.69

2.403 Q141,665.14 6.6 Q789,493.97

Los costos de reconductorar y reconversiones ya tienen incluido el costo de mano de obra del desmontado del material a sustituir.

4.1.2 Inversin en instalacin de equipos de maniobras y proteccin

En la siguiente tabla se muestra la cuantificacin de los equipos de maniobra y proteccin que se deben instalar en los ramales.

Tabla XXI. Cuantificacin de la inversin de equipos de maniobras y proteccin

Elementos Corta-Circuito Cuchillas Monopolares Posicin en Subestacin Total

Cantidad 134 9 1

Costo (Q/unidad)

836.4 1436.2 152000

Total 112077.6 12925.8 152000 Q277,003.4

82

En los costos de los corta-circuitos estn incluidos los costos de mano de obra, de igual manera para las cuchillas . En el desarrollo de un nuevo ramal tambin es necesario instalar los equipos de proteccin ubicados en la subestacin. En el cuadro anterior le llamamos costo de posicin en subestacin

4.2 Ahorros en la aplicacin de la metodologa de planificacin y expansin de redes

En esta seccin analizaremos los ahorros que se obtendrn con la nueva red de distribucin, para luego determinar el tiempo de recuperacin del capital.

4.2.1 Clculo del ahorro de prdidas de potencia activa

Con los resultados del flujo de carga con la red actual tenemos unas perdidas de potencia activa de 502 kW y con y con una red propuesta perdidas de 95.6 kW, la diferencia es el ahorro y quedara 406.4 kW. Para el calculo del costo de perdidas de potencia activa se utilizar siguiente ecuacin: Cp= Potencia Prdidas x(FpxCosto de Energia+12xFsxCosto de potencia) Donde: Fp= 8760(0.15Fc+0.85Fc2) FC = factor de carga 8 760: horas/ ao. 83 la

12: Cantidad de meses de un ao. Fs = Factor de simultaneidad con la demanda mxima del sistema valor 0.85 Costo de Energa = 0.057736 US$-kWh Costo de Potencia 0.394 US$-kW mes Entonces, Fp= [8760(0.15*0.41)+(0.85*0.412)]= 1790.41 horas Pedidas Actuales:
Cp= 502 kW [(1790.41horasX0.057736 US$-kWh+12 meseX0.85X0.394 US$-kW mes) Cp= US$53,894.11

Pedidas Propuestas:
Cp= 95.6 kW [(1790.41horasX0.057736 US$-kWh+12 meseX0.85X0.394 US$-kW mes) Cp= US$10262.66 El Ahorro ser Actuales-Propuestas US$53,894.11- US$10262.66= US$43,631.45

Con el cambio a Q7.67 por US$1 tenemos Q331,599.02 anuales

4.2.2 Clculos en ahorros de perdidas por corriente de neutro

Con los resultados del flujo de carga red actual tenemos una corriente de neutro de 39.1 A y con la remodelacin una corriente de neutro 4.3 A ( en la barra de la subestacin ) Para el calculo del costo de perdidas por corriente de neutro se utilizar la siguiente ecuacin: Potencia de perdidas por corriente de neutro = 2/3[(r*l*i2)]*[ (FpxCosto de Energia+12xFsxCosto de potencia) ] 1000

84

r, es la resistencia del conductor de fase y de neutro. Unidades: /km L, longitud del conductor de la lnea principal. Unidades: km. I, intensidad de lnea de neutro (n). Entonces, r, conductor 1/0 AWG ACSR 0.71 /km L, 15.506 km Iactual, 39.1 Amp Fp= [8760(0.15*0.41)+(0.85*0.412)]= 1790.41 horas Costo de Energa = 0.057736 US$-kWh Costo de Potencia 0.394 US$-kW mes Fs = Factor de simultaneidad con la demanda mxima del sistema valor 0.85 1000 = Para uniformizar las unidades Actuales: Potencia de perdidas por corriente de neutro = (2/3[(0.71 /km *15.506 km *39.1 Amp2)* [(1790.41horasX0.057736 US$-kWh+12 1000
meseX0.85X0.394 US$-kW mes)]

Unidades: Amp.

Potencia de perdidas por corriente de neutro = US$1,181.2 Propuesta: Dentro de la propuesta se crearon dos salidas de media tensin las cuales tendrn conductor 4/0 ACSR r= 1.25 /km Ramal 1 con una longitud de lnea principal de 12.3 km, con corriente de neutro de 2.1 amperios. Potencia de perdidas por corriente de neutro = (2/3[(1.25 /km *12.3 km *2.1 Amp2)* [(1790.41horasX0.057736 US$-kWh+12 1000
meseX0.4X0.394 US$-kW mes)]

Potencia de perdidas por corriente de neutro = US$ 4.75 Ramal 2 tiene una longitud de lnea principal de 6.4 km, con corriente de neutro de 3.1 amperios.

85

Ramal 1 Potencia de perdidas por corriente de neutro = (2/3[(1.25 /km *6.4km *3.1Amp2)* [(1790.41horasX0.057736 US$-kWh+12 1000
meseX0.85X0.394 US$-kW mes)]=

Potencia de perdidas por corriente de neutro = US$ 2.39


El Ahorro ser Actuales-Propuestas US$1,181.2- US$ 4.75- US$ 2.39= US$1,874 .06

Con el cambio a Q7.67 por US$1 tenemos Q9,058.73 anuales

4.3 Anlisis y clculos de penalizaciones por mala regulacin e interrupciones

4.3.1 Penalizaciones por TTIK y FMIK

Para el Calculo de las penalizaciones se tomarn los datos calculados de en la seccin 3.1.5.1 la forma de calculo es de siguiente manera. Penalizacin = ENS sistemas CEMS Donde: ENSsistema= Demanda del sistema[(FMIKcalculado-KMIKlimite)*(TTIK/FMIK)]/8760 CEMS = 10 veces la BTS donde BTS=1.4326 Q/kWh Tenemos Demanda del sistema = 4285.4 kW/h FMIKcalculado =10.58 TTIK = 249.7 KMIKlimite= 2.5

86

ENSsistema=4285.4 kW/h [(10.58-2.5)*(249.7/10.58)]/8760 = 93.58 Penalizacin = 93.58 kWh*14.326 Q/kWh= Q1336.46 Tenemos unas Penalizaciones de Q1,336.46 anuales

4.3.2 Penalizaciones por mala regulacin

Para el calculo de las penalizaciones por mala regulacin se tomarn los datos calculados en el flujo de carga, para este caso se penalizarn todos los transformadores que registren una regulacin mayor del 6% y el calculo ser de la siguiente manera: Penalizacin = registros(KVA*factor de utilizacin*CENS) Factor de utilizacin es 41% En el siguiente cuatro se muestra lo antes mencionado: Tabla XXII. Registros penalizados por mala regulacin
No. Trafo 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 25 25 10 25 25 10 15 25 25 15 50 50 KVA R 15 25 50 25 50 75 50 15 10 15 50 75 20 10 KVA S KVA T % de Regulacin 7 7 7 7 7 7 8 8 8 8 8 8 8 8 8 8 8 8 Penalizaciones Q88.10 Q264.31 Q352.42 Q146.84 Q881.05 Q1,174.73 Q293.68 Q264.31 Q58.74 Q58.74 Q88.10 Q146.84 Q146.84 Q146.84 Q146.84 Q146.84 Q146.84 Q58.74

87

No. Trafo 171 172 173 174 175 176 177 178 179 180 181 182 Total

KVA R 50

KVA S 50 10

KVA T 25 50 25 25 50 50 50 50 50 50 50

% de Regulacin 8 8 8 8 8 8 8 8 8 8 8 8

Penalizaciones Q146.84 Q881.05 Q58.74 Q146.84 Q146.84 Q293.68 Q293.68 Q293.68 Q293.68 Q293.68 Q293.68 Q293.68 Q8,046.91

Tenemos unas Penalizaciones de Q8,046.91 anuales

4.4 Evaluacin econmica

El objetivo de elaborar evaluacin econmica es encontrar la rentabilidad del proyecto. Figura 31. Flujo econmico del proyecto

Beneficios

i = tasa de inters mensual

Inversin

Tiempo

88

En este diagrama observamos que para un perodo de tiempo determinado representado por la lnea horizontal ms gruesa, lo que est por encima de ella es ingreso y por debajo es egreso, todo esto evaluado por un inters. Tenemos: VPN = VP(beneficios) VP(costos) - inversin En donde: VPN VP(beneficios) Es el valor presente neto del proyecto o plan a evaluarse. Es el valor presente de los beneficios que se obtendrn del proyecto o plan. VP(costos) Es el valor presente de los costos que se tendrn que realizar para ejecutar el proyecto o plan. Entonces para el clculo del valor presente neto se tiene: Inversin: Q1,255,561.09 Beneficios con la metodologa : Q35,0041.12 (ahorros en perdidas de potencia activa, ahorros por corriente de neutro y penalizaciones) Inters del 10% en 30 aos VPN = VPN (Beneficios) - VPN (Costos) - Inversin VPN = Q (10%, 30aos,Q35,0041.12) Q (10%,30 aos; Q1,255,561.09) - Q1,255,561.09 VPN = Q 3,254,308.32 Q 11,836,067.00 - Q1,255,561.09 VPN = Q 7,326,197.60 Para el clculo de beneficio costo:

89

Beneficios Costos

= Relacin costo beneficio

Beneficios / Inversin = B / C B / C = Q 11,836,067.00/ Q 3,254,308.32= 27.5 %

4.5 Tiempo de recuperacin de Capital.

Segn la ecuacin siguiente tenemos que el tiempo en que se recupera la inversin seria de: A ___ Ln ( A iP ) n = _______________ Ln (i + 1) Datos: P = VP Inversin = Q 11,836,067.00 A = VP Beneficio = Q 3,254,308.32 i = 10 %. El resultado seria n = 4.7aos. Este dato indica que en 4 aos siete meses se estar recuperando la inversin.

90

CONCLUSIONES

1. La aplicacin de la metodologa nos dar una red calidad del servicio.

ordenada que

permitirn una explotacin ms fcil y gil apuntando a la mejora en la

2. Las industrias y los usuarios son totalmente favorecidos cuando las empresas distribuidoras cuentan con sistemas de distribucin confiable, debido que se reduce el tiempo de recuperacin de la energa cuando ocurren fallas. 3. Con la herramienta del flujo de carga se pueden determinar los parmetros de regulacin, prdidas de potencia activa aproximadas de los sistemas de distribucin y, es de uso obligatorio en planificacin de redes. 4. La Rentabilidad de la inversin de la inversin se basa en la recuperacin de capital, por las mejoras.

91

92

RECOMENDACIONES

1. Usar flujo de carga para simular eventos en la red. 2. Se debe tener separada la carga urbana y rural. 3. La Proyeccin de la demanda se realiza en funcin de la demanda histrica y modelos estadsticos. 4. Con los resultados de flujo de carga , al combinar dos escenarios de la red se obtiene la informacin para el anlisis econmicas y rentabilidad.

93

94

BIBLIOGRAFA

1. Balance energtico de las instalaciones de DEORSA, Union Fenosa, 2004. 2. BLANK, Leland y Anthony Tarqun. Mxico, McGraw-Hill, 1992. Ingeniera econmica. 3 ed.;

3. Informacin alfanumrica de incidencias del Centro de Operaciones de Red de DEORSA. Unin Fenosa, 2004. 4. Informacin alfanumrica de instalaciones elctricas de la Base de Datos de Instalaciones de DEORSA. Unin Fenosa, 2004. 5. TANEMBAUM, Andrew, Redes de computadoras, 3 ed.; Mxico, 6. GROCC, G Planificacin y Operacin Econmica de sistemas de Potencia. 7. Garca Trasancos, Jos. Instalaciones Elctricas en Media y Baja Tensin Espaa: Editorial Paraninfo, 2001. 392pp. 8. Pinto, P. R. Planificacin de sistemas elctricos de distribucin, Universidad Catlica de Chile, Escuela de Ingeniera, Departamento de Ingeniera Elctrica, curso tutorial, Chile. Noviembre 1989.

95

96

ANEXO

ndices de calidad
Frecuencia media de Interrupcin por kVA (FMIK) Representa la cantidad de veces que el kVA promedio de distribucin sufri una interrupcin de servicio. FMIK = j Qkfsj/Qki Donde: j: semestre. Qkfsj : Cantidad de kVA fuera de servicio en la interrupcin j. Qki : Cantidad de kVA instalados. Sumatoria de todas las interrupciones del servicio durante el

Tiempo total de interrupcin por kVA (TTIK). Representa el tiempo total, en horas, en que cada kVA promedio estuvo fuera de servicio. TIK = j Qkfsj*Tfsj/Qki Donde: j : Sumatoria de todas las interrupciones del servicio durante el semestre. Qkfsj : Cantidad de kVA fuera de servicio en la interrupcin j. Qki : Cantidad de kVA instalados

97

Tfsj :

Tiempo, en horas, que han permanecido fuera de servicio los kVA en la interrupcin j.

Tabla XXIII. ndices de calidad de servicio suministrado exigidos.


FMIK TTIK

INTERRUPCIONES URBANO RURAL URBANO RURAL Interrupciones Atribuibles a Distribucin 2.5 3.5 8 10 Interrupciones Atribuibles a Causas Externas a la Distribucin 4 12

Regulacin de tensin. El ndice para evaluar la tensin en el punto de entrega del Distribuidor al Usuario, en un intervalo de medicin (k), ser el valor absoluto de la diferencia (Vk) entre la media de los valores eficaces (RMS) de tensin (Vk) y el valor de la tensin nominal (Vn), medidos en del mismo punto, expresado como un porcentaje de la tensin nominal: Tabla XXIV. Tolerancias de los ndices de regulacin de tensin

TENSION

TOLERANCIA ADMISIBLE RESPECTO DEL VALOR NOMINAL, EN %


SERVICIO URBANO SERVICIO RURAL 10 7 5 8 6

BAJA MEDIA ALTA

98

Indemnizaciones y penalizaciones Indemnizacin y penalizaciones por mala regulacin de tensin

Para el caso de incumplimiento en la Regulacin de Tensin, la indemnizacin se calcular con base en la valorizacin de la totalidad de la energa suministrada en malas condiciones de calidad, de acuerdo a lo especificado en la Tabla, indicada a continuacin: Tabla XXV. Valorizacin de la energa segn el grado de desviacin a las tolerancias establecidas
VkSUP superior al admisible en (%):
1 2 3 4 5 6 7 8 9 10 > 10 VALORIZACION DE LA ENERGIA CE(B) (% de CENS) 4 8 15 20 30 36 49 56 72 84 100

Se define a VkSUP como el porcentaje de desviacin superior del Valor admisible. CENS: Costo de la Energa No Suministrada, [Q / kWh]. El Costo de Energa No Suministrada es diez veces el valor del Cargo Unitario por energa de la Tarifa simple para Usuarios conectados en baja tensin sin cargo por demanda (BTS).

99

Indemnizacin y penalizaciones por KMIK y TTIK

Para el caso de incumplimiento a los ndices o indicadores globales, la Indemnizacin ser la siguiente:
ETF * FEECB * CEB * FEBPB * CENS / 100 B = BP Indemnizacin Global =

Donde: (B=BP) : ETF: FEBPB: Sumatoria sobre las Bandas fuera de las tolerancias establecidas segn corresponda con la Etapa considerada. Energa Total Facturada por el Distribuidor en el perodo controlado, en kWh. Frecuencia Equivalente por Banda de Tensin B fuera de las tolerancias establecidas. FEECB: Frecuencia Equivalente por Energa Consumida desagregada por Banda de Tensin B. Valorizacin de la energa suministrada fuera de las tolerancias CEB: establecidas por banda de Tensin B.

100