MINISTRY OF ENERGY

IRAN POWER DEVELOPMENT COMPANY


I.P.D.C
PROJECT:
PROJECT : SHIRVAN 6159 M.W. GAS TURBINE POWER PLANT
STEAM & CONDENSATE DESIGN AND
PIPE SIZING CALCULATION
IN-HOUSE REVISIONS DOCUMENT REVISIONS
B B
A FOR APPROVAL A.M APR.05 A.S.M APR.05 E.A APR.05 A FOR APPROVAL A.M APR.05 A.S.M APR.05 E.A APR.05
0 FOR APPROVAL A.M DEC.04 A.S.M DEC.04 E.A DEC.04 0 FOR APPROVAL A.M DEC.04 A.S.M DEC.04 E.A DEC.04
REV. DESCRIPTION DESG. DATE CHK. DATE APP. DATE REV. DESCRIPTION DESG. Date CHK. Date APP. Date
VENDOR:
KHERAD WATER TREATMENT CO.
MAPNA
CO.
(PRIVATE JOINT STOCK)
IRAN POWER PLANT PROJECT MANACEMENT CO.
DOCUMENT NO.:
MP-SVG-20ME-08-SB3-001
Rev:
A
PROJECT:
SHIRVAN GAS TURBIN POWER PLANT
ORIG. NO.: REV.
A
CONTRACT
NO.:

FILE NO.:
STEAM &
CONDENSATE DESIGN
PAGE:
1 of 22


MINISTRY OF ENERGY
IRAN POWER DEVELOPMENT COMPANY
I.P.D.C
PROJECT:
PROJECT : SHIRVAN 6159 M.W. GAS TURBINE POWER PLANT
PAGE REVISION REMARKS PAGE REVISION REMARKS
0 A B C D E F G 0 A B C D E F G
1 X 37
2 X 38
3 X 39
4 X 40
5 X 41
6 X 42
7 X 43
8 X 44
9 X 45
10 X 46
11 X 47
12 X 48
13 X 49
14 X 50
15 X 51
16 X 52
17 X 53
18 X 54
19 X 55
20 X 56
21 X 57
22 X 58
23 59
24 60
25 61
26 62
27 63
28 64
29 65
30 66
31 67
32 68
33 69
34 70
35 71
36 72
37 73
38 74
39 75
40 76
41 77
42 78
43 79
44 80
45 81
46 82
47 83
48 84
49 85
50 86
51 87
52 88
53 89
VENDOR:
KHERAD WATER TREATMENT CO.
MAPNA
CO.
(PRIVATE JOINT STOCK)
IRAN POWER PLANT PROJECT MANACEMENT CO.
DOCUMENT NO.:
MP-SVG-20ME-08-SB3-001
Rev:
A
PROJECT:
SHIRVAN GAS TURBIN POWER PLANT
ORIG. NO.: REV.
A
CONTRACT
NO.:

FILE NO.:
STEAM &
CONDENSATE DESIGN
PAGE:
2 of 22


MINISTRY OF ENERGY
IRAN POWER DEVELOPMENT COMPANY
I.P.D.C
PROJECT:
PROJECT : SHIRVAN 6159 M.W. GAS TURBINE POWER PLANT
Introduction
For supply of steam to heat the gasoil storage tanks in this project a steam with a pressure of 6 bar(a)
& temperature of 180 C is considered.(that is 20C super heated)
Aux. steam consumption is mainly considered for following purposes:
- Heating and keeping temperature of two gas oil storage tanks at 12 C.
- Heat tracing of gasoil lines.
Gas oil storage tanks are always kept at 12 C. The volume storage of each gas oil tank is 20,000 m
3
.
Note: For an optimum calculation of steam consumption, all calculations are based on minimum mean
daily ambient air temperature of -12

C.
General Conditions:
T
a
= Ambient temperature = 10.4
o
F
T
o
= Steam temperature = 356
o
F
P
o
= Steam pressure 6 bar (abs)
T
w
= Wall temperature of tank
T
g
= Gas oil temperature = 53.6
o
F
D = Gas oil tank diameter = 150 ft
H = Gas oil tank height = 42 ft
Gas oil properties at 12
o
C
: Density = 52.68 lb/ft
3
C : Specific heat capacity = 0.45 Btu/lb
o
F
: Viscosity = 13.31 lb/ft.hr
= 0.0004 1/
o
F
K : Thermal conductivity = 0.0798 Btu/ft.hr.
o
F
h
fg
(at 6 bar(a) pressure)=896 Btu/lb
h
i
= inside convectional heat transfer coefficient (Btu/hr.ft
2
.
o
F)
VENDOR:
KHERAD WATER TREATMENT CO.
MAPNA
CO.
(PRIVATE JOINT STOCK)
IRAN POWER PLANT PROJECT MANACEMENT CO.
DOCUMENT NO.:
MP-SVG-20ME-08-SB3-001
Rev:
A
PROJECT:
SHIRVAN GAS TURBIN POWER PLANT
ORIG. NO.: REV.
A
CONTRACT
NO.:

FILE NO.:
STEAM &
CONDENSATE DESIGN
PAGE:
3 of 22


MINISTRY OF ENERGY
IRAN POWER DEVELOPMENT COMPANY
I.P.D.C
PROJECT:
PROJECT : SHIRVAN 6159 M.W. GAS TURBINE POWER PLANT
Components of correlations
Q = Tank heat loss
m = Mass flow rate
A' = Heat transfer surface of steam coil
U' = Overall heat transfer coefficient
U = corrected overall heat transfer coefficient
h= Convectional heat transfer coefficient
F=Fouling factor 0.003 [(hr)(ft
2
)(

F) /Btu)]
References:
[1] : Introduction to heat transfer by Frank Incropera-Free convection chapter
[2] : ASHRAE , Fundamental Free Convection Section
[3] : Introduction to heat transfer by J.P.Holman-Free convection chapter
[4] : Process Heat Transfer by Kern
[5] : Introduction to heat transfer by Frank Incropera-Free convection chapter
[6] : Piping Handbook by Mohinder L. Nayyer
[7] : Flow of fluids by CRANE Co.
[8] : Heating, Ventilation and Air Conditioning Design Manual , CAPITOLINE
Properties of gas oil are taken from : Petroleum Refinery Engineering by W.L Nelson
Scope of work
This document deals with the calculation details of auxiliary steam system of Shirvan power plant. As it
will be mentioned, the steam is used for heating the gasoil system. In the next sections the calculation
for steam part of system which include calculation of heat loss of storage tank and estimating the
required
steam consumption for this purpose, sizing of tank coil heater, calculation of the heat loss of gasoil lines,
their acoompanying tracers will be shown.
VENDOR:
KHERAD WATER TREATMENT CO.
MAPNA
CO.
(PRIVATE JOINT STOCK)
IRAN POWER PLANT PROJECT MANACEMENT CO.
DOCUMENT NO.:
MP-SVG-20ME-08-SB3-001
Rev:
A
PROJECT:
SHIRVAN GAS TURBIN POWER PLANT
ORIG. NO.: REV.
A
CONTRACT
NO.:

FILE NO.:
STEAM &
CONDENSATE DESIGN
PAGE:
4 of 22


MINISTRY OF ENERGY
IRAN POWER DEVELOPMENT COMPANY
I.P.D.C
PROJECT:
PROJECT : SHIRVAN 6159 M.W. GAS TURBINE POWER PLANT

Calculation
There is natural convectional heat transfer between warm gas oil & cold tank wall. Free convection heat
transfer coefficient on a vertical plate with length (L) can be written as follow:
2
27 / 8 16 / 9
6 / 1
}
] Pr) / 492 . 0 ( 1 [
387 . 0
825 . 0 {
+
+
L
gasoil
i
Ra
Nu
K
L h
[1]

Where Ra
L
= Gr
L
. Pr or
K
L T T Cg
Ra
wall gasoil
L


3 2
) (

It is noted that Ra, Gr, Pr and Nu are Rayleigh, Grashof, Prantel and Nusselt numbers respectively.
For tanks heat loss calculation, external surface temperature should be calculated. It should be
mentioned that as portion of D (Tank diameter) to H (Height of tank) is much greater than (35/Gr
H
1/4
), so
according to ref. [5] tanks can be considered as vertical plates. Of course this condition will be checked
in each part.
Internal free convection heat transfer coefficient (hi) on the basis of tank height can be calculated via the
formula as follow:
2
27 / 8 16 / 9
6 / 1
}
] Pr) / 492 . 0 ( 1 [
387 . 0
825 . 0 {
+
+
H
gasoil
i
Ra
Nu
K
H h
Where
2
3 2
) (

H T T g
Gr
wall gasoil
H

K
C
Pr
VENDOR:
KHERAD WATER TREATMENT CO.
MAPNA
CO.
(PRIVATE JOINT STOCK)
IRAN POWER PLANT PROJECT MANACEMENT CO.
DOCUMENT NO.:
MP-SVG-20ME-08-SB3-001
Rev:
A
PROJECT:
SHIRVAN GAS TURBIN POWER PLANT
ORIG. NO.: REV.
A
CONTRACT
NO.:

FILE NO.:
STEAM &
CONDENSATE DESIGN
PAGE:
5 of 22


MINISTRY OF ENERGY
IRAN POWER DEVELOPMENT COMPANY
I.P.D.C
PROJECT:
PROJECT : SHIRVAN 6159 M.W. GAS TURBINE POWER PLANT
Where (g=32.2 ft/sec
2
) is acceleration of gravity.Other parameters have been identified in the pages
before. As T
wall
is going to be calculated therefore at first a temperature is assumed as tank wall
temperature, say 45 F, so Gr
H
and Pr will be calculated as follow:
2
3 2 2
) 31 . 13 (
42 ) 68 . 52 ( ) 45 6 . 53 ( 0004 . 0 ) 3600 ( 2 . 32

H
Gr
0798 . 0
31 . 13 45 . 0
Pr

So
12
10 66 . 1
H
Gr & Pr = 75.05
Noted that [(35/Gr
H
1/4
) << (150/42)]
14
10 25 . 1
H
Ra
So
2
27
8
16
9
6
1
14
}
] )
05 . 75
492 . 0
( 1 [
) 10 25 . 1 ( 387 . 0
825 . 0 {
+

+
H
Nu
Therefore 8 . 7379
K
hiH
Nu
H
Or
F ft hr
Btu
hi

. .
02 . 14
42
0798 . 0 7379
2
There is free convectional heat transfer between warm tank wall & ambient which heat transfer
coefficient of this phenomenon can be written as follow:
33 . 0
) ( 19 . 0 T h
out convection
[2]

out convection
h
F ft hr
Btu


. .
612 . 0 ) 4 . 10 45 ( 19 . 0
2
33 .. 0

In addition there is radiation heat transfer between tank wall & ambient:
) 4 . 10 45 (
)
100
460 4 . 10
( )
100
460 45
(
17134 . 0 8 . 0
4 4

+

radiation
h
VENDOR:
KHERAD WATER TREATMENT CO.
MAPNA
CO.
(PRIVATE JOINT STOCK)
IRAN POWER PLANT PROJECT MANACEMENT CO.
DOCUMENT NO.:
MP-SVG-20ME-08-SB3-001
Rev:
A
PROJECT:
SHIRVAN GAS TURBIN POWER PLANT
ORIG. NO.: REV.
A
CONTRACT
NO.:

FILE NO.:
STEAM &
CONDENSATE DESIGN
PAGE:
6 of 22


MINISTRY OF ENERGY
IRAN POWER DEVELOPMENT COMPANY
I.P.D.C
PROJECT:
PROJECT : SHIRVAN 6159 M.W. GAS TURBINE POWER PLANT
F ft hr
Btu
h
radiation

. .
637 . 0
2
With definition h
out
& alfa as follow
h
out
= h
radiation
+ h
convection

out

And
) (
out i
h h
hi
alfa
+

And with consideration heat balance equation as follow:


hi (T
gasoil
T
wall
) = h
out
(T
wall
T
ambient
)
T
wall
can be written as:
T
wall
= T
ambient
+ (alfa) (T
gasoil
T
ambient
)
h
out
= 1.248
F ft hr
Btu
. .
2
alfa = 0.918
So T
wall
= 10.4 + 0.918 (53.6-10.4)
Or T
wall
= 50.06F
In the second try 50.06F is a assumed as wall temperature, so:
11
10 86 . 6
H
Gr
13
10 147 . 5
H
Ra
F ft hr
Btu
h
Nu
i
H

. .
46 . 10
54 . 5506
2
F ft hr
Btu
h
F ft hr
Btu
h
F ft hr
Btu
h
out
out convection
radiation

. .
287 . 1
. .
64 . 0
. .
647 . 0
2
2
2
alfa = 0.89
VENDOR:
KHERAD WATER TREATMENT CO.
MAPNA
CO.
(PRIVATE JOINT STOCK)
IRAN POWER PLANT PROJECT MANACEMENT CO.
DOCUMENT NO.:
MP-SVG-20ME-08-SB3-001
Rev:
A
PROJECT:
SHIRVAN GAS TURBIN POWER PLANT
ORIG. NO.: REV.
A
CONTRACT
NO.:

FILE NO.:
STEAM &
CONDENSATE DESIGN
PAGE:
7 of 22


MINISTRY OF ENERGY
IRAN POWER DEVELOPMENT COMPANY
I.P.D.C
PROJECT:
PROJECT : SHIRVAN 6159 M.W. GAS TURBINE POWER PLANT
T
wall
= 48.86F
In the third try 48.86F is assumed as wall temperature, so
F ft hr
Btu
h
F ft hr
Btu
h
F ft hr
Btu
h
Nu
Ra
Gr
out
radiation
i
H
H
H



. .
278 . 1
. .
644 . 0
. .
519 . 11
8 . 6062
10 89 . 6
10 18 . 9
2
2
2
13
11
alfa = 0.9
T
wall
= 49.28 F
After a few try and errors 49.2F is achieved as tank wall temperature. Therefore three kind of main heat
transfer can be calculated using above wall temperature.
1. Radiation heat transfer from tank wall to ambient
Using formula:

+
] )
100
460
( )
100
460
[( 17134 . 0 8 . 0
4 4 ambient wall
radiation
T T
Q Surface of heat transfer
Q
radiation
= 0.8 0.17134 [672.3-489.6] 3.14 150 42 or Q
radiation
= 495,317
hr
Btu
2. Free convection heat transfer from tank external surface to ambient.
There is free convection heat transfer from external surface of tank to ambient due to temperature
difference. This heat transfer can be written as
Q= h
convection

out
(T
wall
T
ambient
) (Heat transfer surface) where h
convection

out
= 0.19 (T
wall
T
ambient
)
0.33

F ft hr
Btu
. .
2
VENDOR:
KHERAD WATER TREATMENT CO.
MAPNA
CO.
(PRIVATE JOINT STOCK)
IRAN POWER PLANT PROJECT MANACEMENT CO.
DOCUMENT NO.:
MP-SVG-20ME-08-SB3-001
Rev:
A
PROJECT:
SHIRVAN GAS TURBIN POWER PLANT
ORIG. NO.: REV.
A
CONTRACT
NO.:

FILE NO.:
STEAM &
CONDENSATE DESIGN
PAGE:
8 of 22


MINISTRY OF ENERGY
IRAN POWER DEVELOPMENT COMPANY
I.P.D.C
PROJECT:
PROJECT : SHIRVAN 6159 M.W. GAS TURBINE POWER PLANT
So Q
convection

out
= 0.19 (49.2-10.4)
1.33
(3.14 150 42) or Q
convection

out
= 487,719
hr
Btu
3. Total heat transfer in the case of heating one tank
Total heat transfer from tank to the surrounding is
Q
radiation
+ Q
convection

out
= 983036
hr
Btu
select 1,000,000 Btu/hr
4. Calculation of heat load to preheat of cold gasoil.
Suppose that gas oil enters into the tank with 30F (-1C) and bottom heater should warm this cold
gasoil up to 53.6F (+12C) during 60 hours. Gasoil is subjected to pervious different kinds of heat
transfer as mentioned on the pages before.
Point the finger that tank wall is supposed to be thin layered so equation can be written as
Q
input
(Btu) = Q
convection

out
(Btu) + Q
radiation
(Btu)+ (Mass of gasoil) C (T
final
T
initial
) (Btu)
5. Q convection out during 60 hours
Q
convention out
= h
convention out
*area of heat transfer *T * 60 hrs
Q
convection out
= ( ) 60 42 150 14 . 3 4 . 10
2
2 . 49 30
19 . 0
33 . 1

,
_

+
Or Q
convection out
= 20,050,917 Btu
6. Q
radiation
during 60 hours
Q radiation =
( ) 60 42 150 14 . 3
100
460 4 . 10
100
460 6 . 39
17134 . 0 8 . 0
4 4

1
1
]
1

,
_

,
_

+

VENDOR:
KHERAD WATER TREATMENT CO.
MAPNA
CO.
(PRIVATE JOINT STOCK)
IRAN POWER PLANT PROJECT MANACEMENT CO.
DOCUMENT NO.:
MP-SVG-20ME-08-SB3-001
Rev:
A
PROJECT:
SHIRVAN GAS TURBIN POWER PLANT
ORIG. NO.: REV.
A
CONTRACT
NO.:

FILE NO.:
STEAM &
CONDENSATE DESIGN
PAGE:
9 of 22


MINISTRY OF ENERGY
IRAN POWER DEVELOPMENT COMPANY
I.P.D.C
PROJECT:
PROJECT : SHIRVAN 6159 M.W. GAS TURBINE POWER PLANT
So Q radiation =21,698,596 (Btu)
7. Gas oil pre heat load
Mass of gas oil = (volume of tank) *
gas oil
= 39,079,341 lb
Q = 39,079,341 * 0.45 * (53.6 - 30) = 415,022,601 (Btu)

8. Total heat load to preheat:
Q
total
= Q
convection

out
+Q
radiation
+ Q
warming gasoil

So Q
total
= 20050917 (Btu) + 21698596 (Btu ) + 415022601 (Btu)
Or Q
total
= 456,772,115 (Btu)
Heat rate =
,
_

hr
Btu Qtotal
869 , 612 , 7
60

As the heat rate of pre heating is greater than of the heating load so bottom heater coils will be sized
according to pre heating load (7,612,869 select 7,700,000
hr
Btu
)
9. Coil u calculation
There is natural convection from bottom heater of tank to gas oil. On the basis of Mc Adams
Formula natural convection coefficient from a cylinder to its surroundings can be calculated as follow:
25 . 0
53 . 0
d d
Ra Nu [3]
Suppose ( ) " 5 D pipes to be used as bottom heaters so
VENDOR:
KHERAD WATER TREATMENT CO.
MAPNA
CO.
(PRIVATE JOINT STOCK)
IRAN POWER PLANT PROJECT MANACEMENT CO.
DOCUMENT NO.:
MP-SVG-20ME-08-SB3-001
Rev:
A
PROJECT:
SHIRVAN GAS TURBIN POWER PLANT
ORIG. NO.: REV.
A
CONTRACT
NO.:

FILE NO.:
STEAM &
CONDENSATE DESIGN
PAGE:
10 of 22


MINISTRY OF ENERGY
IRAN POWER DEVELOPMENT COMPANY
I.P.D.C
PROJECT:
PROJECT : SHIRVAN 6159 M.W. GAS TURBINE POWER PLANT
K
TD Cg
Ra
D


2 3
.


so
( )
9
2
3
2
10 53 . 5
0798 . 0 31 . 13
68 . 52
12
56 . 5
0004 . 0 ) 6 . 53 337 ( 3600 2 . 32 45 . 0


,
_

oF oF
D
Ra

Point the finger that 337
o
F is average of super heated steam temperature (356
o
F) and saturated steam at
88 psi a (318
o
F)
So
25 . 0
53 . 0
d d
Ra Nu =144
8 . 24
12
56 . 5
0798 . 0 * 144
144

,
_

h
K
hD

F ft hr
Btu

. .
2

As steam inside the pipe is distilling to saturated water so heat transfer coefficient is so high in this case
[ ] 4
. .
1500
2 1
]
1

F ft hr
Btu

(Chapter 7 , page No. 164)


Point the finger that this coefficient can be calculated by Chato formula as follow:
( )
( )
where
D T
h K g
H
fg v l
D
2
1
1
3
1
555 . 0
1
1
]
1


( )
s sat pl fg
T T C hfg h +
8
3
[ ] 5

Mention that
steam tion freeconvec
h h u
1 1
'
1
+
so
4 . 24
1
1500
1
8 . 24
1 1
+
u
VENDOR:
KHERAD WATER TREATMENT CO.
MAPNA
CO.
(PRIVATE JOINT STOCK)
IRAN POWER PLANT PROJECT MANACEMENT CO.
DOCUMENT NO.:
MP-SVG-20ME-08-SB3-001
Rev:
A
PROJECT:
SHIRVAN GAS TURBIN POWER PLANT
ORIG. NO.: REV.
A
CONTRACT
NO.:

FILE NO.:
STEAM &
CONDENSATE DESIGN
PAGE:
11 of 22
K
C
pr
TD g
Gr
D

&
2
2 3


MINISTRY OF ENERGY
IRAN POWER DEVELOPMENT COMPANY
I.P.D.C
PROJECT:
PROJECT : SHIRVAN 6159 M.W. GAS TURBINE POWER PLANT
so 4 . 24 u there for u= 7 . 22
4 . 24 003 . 0 1
4 . 24

+

F ft hr
Btu

. .
2

10. Calculation of bottom heater coil length.
As the heat rate of pre heating is greater than the heating load so bottom heater coils should be sized
according to pre heating load
hr
But
7700000
T Area U
hr
Btu
Q
coil coil SUPPLY

,
_

. .

f ft hr
Btu
U
coil

. .
7 . 22
2

7700000 ( ) F Area
hr
Btu
o
coil
6 . 53 337 * * 7 . 22
So Area=
2
1196
4 . 283 7 . 22
7700000
ft

(for 2 branches)
This Area should be supplied by coil length. Suppose the bottom coils are 5
"
pipe so length of pipe (each
branch) will be:

" 5
2
D
Area
l

(Each branch)
ft l 411
12
56 . 5
* 14 . 3
2
1196

(Each branch) [equal to 120m]

With consideration 15%for safety factor the length of each branch will be: 140 m.
11. Heat loss along with steam flow through steam pipes:
VENDOR:
KHERAD WATER TREATMENT CO.
MAPNA
CO.
(PRIVATE JOINT STOCK)
IRAN POWER PLANT PROJECT MANACEMENT CO.
DOCUMENT NO.:
MP-SVG-20ME-08-SB3-001
Rev:
A
PROJECT:
SHIRVAN GAS TURBIN POWER PLANT
ORIG. NO.: REV.
A
CONTRACT
NO.:

FILE NO.:
STEAM &
CONDENSATE DESIGN
PAGE:
12 of 22


MINISTRY OF ENERGY
IRAN POWER DEVELOPMENT COMPANY
I.P.D.C
PROJECT:
PROJECT : SHIRVAN 6159 M.W. GAS TURBINE POWER PLANT
There is heat loss from steam pipes to surrounding along with steam flows through pipes. The maximum
length of mentioned pipes are as follow:
6
"
:370 meters
4
"
:130 meters
2
2
1
"
:260 meters
Heat loss rate per foot of mentioned pipes are as follow :
38
ft
watt
for 6
"
pipelines,
28.3

ft
watt
for 4
"
pipelines
and 21
ft
watt
for 2
2
1
"
pipes. [6]
So heat loss from above pipes will be 76112 watt or 259760
hr
Btu
(select 260000
hr
Btu
)
12-Heat tracers consumption
The fuel pipelines should be warm enough to protect the gas oil from freezing.
This duty can be supplied by steam tracing. Approximately length of gasoil and their heat loss rate per
foot of pipe are as follow:
16
"
:615 meters, 8.9 watt/ft heat loss [6]
12
"
:110 meters, 7.3 watt/ft heat loss [6]
10
"
:135 meters, 6.3 watt/ft heat loss [6]
8
"
:135 meters, 5.2 watt/ft heat loss [6]
5
"
:2000 meters, 3.5 watt/ft heat loss [6]
4
"
:430 meters, 3.1 watt/ft heat loss [6]
So total loss from above pipes is 53000 watt or 180800 (
hr
Btu
) (select 200000
hr
Btu
)
13. Total steam consumption:
VENDOR:
KHERAD WATER TREATMENT CO.
MAPNA
CO.
(PRIVATE JOINT STOCK)
IRAN POWER PLANT PROJECT MANACEMENT CO.
DOCUMENT NO.:
MP-SVG-20ME-08-SB3-001
Rev:
A
PROJECT:
SHIRVAN GAS TURBIN POWER PLANT
ORIG. NO.: REV.
A
CONTRACT
NO.:

FILE NO.:
STEAM &
CONDENSATE DESIGN
PAGE:
13 of 22


MINISTRY OF ENERGY
IRAN POWER DEVELOPMENT COMPANY
I.P.D.C
PROJECT:
PROJECT : SHIRVAN 6159 M.W. GAS TURBINE POWER PLANT
On the basis that one tank is going to be preheated and one tank is heating and heat loss from pipes total
heat loss can be calculated as follow:
Q
total
= 1000000 + 7700000 + 260000 + 200000 = 9160000
hr
Btu
. (select 10000000
hr
Btu
)
So total steam consumption for doing the action said before can be calculated as follow:
Enthalpy of superheated steam at(88 psia & 356 F): 1206
lb
Btu

Enthalpy of saturated steam at(88 psia): 1185
lb
Btu

Latent heat of saturated steam at(88psia): 896
lb
Btu
specific volume of superheated steam (s.v=0.335 m
3
/kg)

m =
( ) [ ]
hr
kg
hr
lb
lb
Btu
hr
Btu
Q
TOTAL
4907 10905
896 1185 1206
) (

+
Select 5000
hr
kg
(5ton/hr)
14. Pressure drop calculation and pipe sizing
Following the piping distribution of steam lines and condensate collecting system with their sizing have
been shown which pipe sizes shall be checked using their flow rates and then pressure drop of flow
will be calculated through each lines.
VENDOR:
KHERAD WATER TREATMENT CO.
MAPNA
CO.
(PRIVATE JOINT STOCK)
IRAN POWER PLANT PROJECT MANACEMENT CO.
DOCUMENT NO.:
MP-SVG-20ME-08-SB3-001
Rev:
A
PROJECT:
SHIRVAN GAS TURBIN POWER PLANT
ORIG. NO.: REV.
A
CONTRACT
NO.:

FILE NO.:
STEAM &
CONDENSATE DESIGN
PAGE:
14 of 22


MINISTRY OF ENERGY
IRAN POWER DEVELOPMENT COMPANY
I.P.D.C
PROJECT:
PROJECT : SHIRVAN 6159 M.W. GAS TURBINE POWER PLANT
Line C-D :
This line supplies the steam for bottom heater and gasoil lines tracers in the mentioned zone(from point
C to point D). So there are two heat loss cases:
A) Bottom heating of gasoil tank : 7,700,000 Btu/hr (according to section 8)
B) Tracers of gasoil lines which include as follow (approximately lengths):
16: 180 meters (8.9 watt/ft heat loss) => 5255 watt (17930 Btu/hr )
VENDOR:
KHERAD WATER TREATMENT CO.
MAPNA
CO.
(PRIVATE JOINT STOCK)
IRAN POWER PLANT PROJECT MANACEMENT CO.
DOCUMENT NO.:
MP-SVG-20ME-08-SB3-001
Rev:
A
PROJECT:
SHIRVAN GAS TURBIN POWER PLANT
ORIG. NO.: REV.
A
CONTRACT
NO.:

FILE NO.:
STEAM &
CONDENSATE DESIGN
PAGE:
15 of 22


MINISTRY OF ENERGY
IRAN POWER DEVELOPMENT COMPANY
I.P.D.C
PROJECT:
PROJECT : SHIRVAN 6159 M.W. GAS TURBINE POWER PLANT
4 : 90 meters (3.1 watt/ft heat loss) => 915 watt(3120 Btu/hr)
total heat loss: 7,700,000 + 17,930 + 3,120 = 7,721,050 Btu/hr

m
line C-D
=
( ) [ ]
hr
kg
hr
lb
lb
Btu
hr
Btu
Q
D neC HeatLossli
3790 8420
896 1185 1206
) (

+

d=5 (128mm inside diameter) => Velocity=3790(kg/hr) x 0.335(m3/kg)/[3.14*0.128


2
/4] or
Velocity=98720 m/hr = 27 m/sec
Re
d
= 354 * W(kg/hr) / (d*) [7]
Where d and are pipe diameter(mm) and absolute viscosity(centipoises) respectively that d=128mm
and =0.016 centipoises [7]
So Re
d
= 655110 so f(friction factor)=0.016 [7]
Calculating pressure drop of 100 meter of pipe via formula [7] :
steam
d
fW
P

5
2
100
62530
where
steam
= 1/(s.v)=2.985 kg/m
3
so pascal P 14 . 0
985 . 2 * 128
3790 * 016 . 0
62530
5
2
100

as length of line C-D is 90 meter and with consideration 20% additional length for fittings and valves so
pressure drop along with line C-D will be :
0.14 * 90*1.2/100=0.15pascal
Line L-M :
This line supplies the steam for gasoil lines tracers so there is one heat loss case:
Gasoil lines which subjected to heat tracing are as follow (approximately lengths):
16: 445 meters (8.9 watt/ft heat loss) => 12995 watt (44332 Btu/hr )
5 : 2000 meters(3.5 watt/ft heat loss) =>22965 watt(78355 Btu/hr)
4 : 480 meters (3.1 watt/ft heat loss) => 4880 watt(16655 Btu/hr)
VENDOR:
KHERAD WATER TREATMENT CO.
MAPNA
CO.
(PRIVATE JOINT STOCK)
IRAN POWER PLANT PROJECT MANACEMENT CO.
DOCUMENT NO.:
MP-SVG-20ME-08-SB3-001
Rev:
A
PROJECT:
SHIRVAN GAS TURBIN POWER PLANT
ORIG. NO.: REV.
A
CONTRACT
NO.:

FILE NO.:
STEAM &
CONDENSATE DESIGN
PAGE:
16 of 22


MINISTRY OF ENERGY
IRAN POWER DEVELOPMENT COMPANY
I.P.D.C
PROJECT:
PROJECT : SHIRVAN 6159 M.W. GAS TURBINE POWER PLANT
total heat loss: 44,332 + 78,355 + 16,655 = 139,342 Btu/hr

m
line L-M
=
( ) [ ]
hr
kg
hr
lb
lb
Btu
hr
Btu
Q
M neL HeatLossli
68 150
896 1185 1206
) (

+

d=2 1/2 (63mm inside diameter) => Velocity=68(kg/hr) x 0.335(m3/kg)/[3.14*0.063


2
/4] or
Velocity=7311 m/hr = 2 m/sec
Re
d
= 354 * W(kg/hr) / (d*) [7]
Where d and are pipe diameter(mm) and absolute viscosity(centipoises) respectively that d=63mm
and =0.016 centipoises [7]
So Re
d
= 23880 so f(friction factor)=0.028 [7]
Calculating pressure drop of 100 meter of pipe via formula [7] :
steam
d
fW
P

5
2
100
62530
where
steam
= 1/(s.v)=2.985 kg/m
3
so pascal P 0027 . 0
985 . 2 * 63
68 * 028 . 0
62530
5
2
100

as length of line L-M is 415 meters and with consideration 20% additional length for fittings and valves
so pressure drop along with line C-D will be :
0.0027 * 415*1.2/100=0.013pascal
Line C-K :
This line supplies the steam for gasoil lines tracers in section C-K ,L-M and Forwarding pump house
piping. There are three heat loss cases:
A) Gasoil lines which subjected to heat tracing between C and K are as follow (approximately lengths):
16: 112 meters (8.9 watt/ft heat loss) => 3270 watt (11160 Btu/hr )
4 : 56 meters(3.5 watt/ft heat loss) =>645 watt(2195 Btu/hr)
VENDOR:
KHERAD WATER TREATMENT CO.
MAPNA
CO.
(PRIVATE JOINT STOCK)
IRAN POWER PLANT PROJECT MANACEMENT CO.
DOCUMENT NO.:
MP-SVG-20ME-08-SB3-001
Rev:
A
PROJECT:
SHIRVAN GAS TURBIN POWER PLANT
ORIG. NO.: REV.
A
CONTRACT
NO.:

FILE NO.:
STEAM &
CONDENSATE DESIGN
PAGE:
17 of 22


MINISTRY OF ENERGY
IRAN POWER DEVELOPMENT COMPANY
I.P.D.C
PROJECT:
PROJECT : SHIRVAN 6159 M.W. GAS TURBINE POWER PLANT
B) Gasoil lines which subjected to heat tracing between L and M which has been calculated in the
previous section which the amount of heat loss is 139,342 Btu/hr
C) Forwarding pump house piping tracers which include piping as follow (approximately lengths):
16
"
: 8 meters(8.9 watt/ft heat loss) => 233 watt ( 800 Btu/hr)
12
"
: 9 meters(7.3 watt/ft heat loss) => 215 watt( 743 Btu/hr)
10
"
: 4 meter(6.3 watt/ft heat loss) => 82 watt( 285 Btu/hr)
8
"
: 4 meters(5.2 watt/ft heat loss) => 68 watt( 234 Btu/hr)
5
"
: 60 meters(3.5 watt/ft heat loss) => 690 watt( 2375 Btu/hr)
total heat loss: 11,160+2,195+139,342+800+743+285+234+2375 = 157134 Btu/hr

m
line C-K
=
( ) [ ]
hr
kg
hr
lb
lb
Btu
hr
Btu
Q
K neC HeatLossli
75 171
896 1185 1206
) (

+

d=4 (102mm inside diameter) => Velocity=75(kg/hr) x 0.335(m3/kg)/[3.14*0.102


2
/4] or
Velocity=3079 m/hr = 0.8 m/sec
Re
d
= 354 * W(kg/hr) / (d*) [7]
Where d and are pipe diameter(mm) and absolute viscosity(centipoises) respectively that d=102mm
and =0.016 centipoises [7]
So Re
d
= 16268 so f(friction factor)=0.028 [7]
Calculating pressure drop of 100 meter of pipe via formula [7] :
steam
d
fW
P

5
2
100
62530
where
steam
= 1/(s.v)=2.985 kg/m
3
so pascal P 0003 . 0
985 . 2 * 102
75 * 028 . 0
62530
5
2
100

as length of line C-K is 60 meters and with consideration 20% additional length for fittings and valves
so pressure drop along with line C-K will be :
VENDOR:
KHERAD WATER TREATMENT CO.
MAPNA
CO.
(PRIVATE JOINT STOCK)
IRAN POWER PLANT PROJECT MANACEMENT CO.
DOCUMENT NO.:
MP-SVG-20ME-08-SB3-001
Rev:
A
PROJECT:
SHIRVAN GAS TURBIN POWER PLANT
ORIG. NO.: REV.
A
CONTRACT
NO.:

FILE NO.:
STEAM &
CONDENSATE DESIGN
PAGE:
18 of 22


MINISTRY OF ENERGY
IRAN POWER DEVELOPMENT COMPANY
I.P.D.C
PROJECT:
PROJECT : SHIRVAN 6159 M.W. GAS TURBINE POWER PLANT
0.0003 * 60*1.2/100=0.0002 pascal
Line C-B :
This line supplies the steam for gasoil lines tracers in section C-M ,C-D and two tanks bottom heaters
which one tank is going only to be kept and another is preheating which steam consumption of all cases
have been calculated and they are defined.
A) Steam consumption of line C-K which its loss is 157,000 Btu/hr (75kg/hr )
B) Keeping of one: 1,000,000 Btu/hr
C) Preheating of one tank is 7,700,000 Btu/hr
D) Heat tracing of tank yard piping and pipes between point B and D 21,050 Btu/hr
total heat loss: 157,000+1,000,000+7,700,000+21,050 = 8,878,050 Btu/hr

m
line C-B
=
( ) [ ]
hr
kg
hr
lb
lb
Btu
hr
Btu
Q
HeatLoss
4353 9675
896 1185 1206
) (

+
d=8 (203mm inside diameter) => Velocity=4353(kg/hr) x 0.335(m3/kg)/[3.14*0.203
2
/4]( m
2
) or
Velocity=45078 m/hr = 12.5 m/sec
Re
d
= 354 * W(kg/hr) / (d*) [7]
Where d and are pipe diameter(mm) and absolute viscosity(centipoises) respectively that d=203mm
and =0.016 centipoises [7]
So Re
d
= 474,435 so f(friction factor)=0.016 [7]
Calculating pressure drop of 100 meter of pipe via formula [7] :
steam
d
fW
P

5
2
100
62530
where
steam
= 1/(s.v)=2.985 kg/m
3
VENDOR:
KHERAD WATER TREATMENT CO.
MAPNA
CO.
(PRIVATE JOINT STOCK)
IRAN POWER PLANT PROJECT MANACEMENT CO.
DOCUMENT NO.:
MP-SVG-20ME-08-SB3-001
Rev:
A
PROJECT:
SHIRVAN GAS TURBIN POWER PLANT
ORIG. NO.: REV.
A
CONTRACT
NO.:

FILE NO.:
STEAM &
CONDENSATE DESIGN
PAGE:
19 of 22


MINISTRY OF ENERGY
IRAN POWER DEVELOPMENT COMPANY
I.P.D.C
PROJECT:
PROJECT : SHIRVAN 6159 M.W. GAS TURBINE POWER PLANT
so pascal P 018 . 0
985 . 2 * 203
4353 * 016 . 0
62530
5
2
100

as length of line B-C is 45 meters and with consideration 20% additional length for fittings and valves
so pressure drop along with line B-C will be :
0.018 * 45*1.2/100=0.01 pascal
Line A-B :
This line supplies the steam for all of gasoil systems included tanks and heat tracers. As it is shown in
the previous sections the pressure drop of lines is too low so only heat loss of line B-H and B-F is
calculated.
A) Steam consumption of line C-M and C-D and tanks heaters which its loss is 8,878,050 Btu/hr
(4353kg/hr )
B) Steam consumption of lines located between points B-F and F-J which their lengths are as follow:
12
"
:110 meters,(7.3 watt/ft heat loss ) => 2634 watt (9,100 Btu/hr)
10
"
:135 meters,(6.3 watt/ft heat loss) => 2790 watt (9,600 Btu/hr)
8
"
: 135 meters,(5.2 watt/ft heat loss)=> 2300 watt (7,950 Btu/hr)
total heat loss: 8,878,050+9,100+9,600+7,950 = 8,904,700 Btu/hr

m
line A-B
=
( ) [ ]
hr
kg
hr
lb
lb
Btu
hr
Btu
Q
HeatLoss
4370 9705
896 1185 1206
) (

+
d=8 (203mm inside diameter) => Velocity=4370(kg/hr) x 0.335(m3/kg)/[3.14*0.203
2
/4]( m
2
) or
Velocity=45255 m/hr = 12.6 m/sec
Re
d
= 354 * W(kg/hr) / (d*) [7]
Where d and are pipe diameter(mm) and absolute viscosity(centipoises) respectively that d=203mm
and =0.016 centipoises [7]
VENDOR:
KHERAD WATER TREATMENT CO.
MAPNA
CO.
(PRIVATE JOINT STOCK)
IRAN POWER PLANT PROJECT MANACEMENT CO.
DOCUMENT NO.:
MP-SVG-20ME-08-SB3-001
Rev:
A
PROJECT:
SHIRVAN GAS TURBIN POWER PLANT
ORIG. NO.: REV.
A
CONTRACT
NO.:

FILE NO.:
STEAM &
CONDENSATE DESIGN
PAGE:
20 of 22


MINISTRY OF ENERGY
IRAN POWER DEVELOPMENT COMPANY
I.P.D.C
PROJECT:
PROJECT : SHIRVAN 6159 M.W. GAS TURBINE POWER PLANT
So Re
d
= 476,286 so f(friction factor)=0.016 [7]
Calculating pressure drop of 100 meter of pipe via formula [7] :
steam
d
fW
P

5
2
100
62530
where
steam
= 1/(s.v)=2.985 kg/m
3
so pascal P 019 . 0
985 . 2 * 203
4370 * 016 . 0
62530
5
2
100

as length of line A-B is 30 meters and with consideration 20% additional length for fittings and valves
so pressure drop along with line A-B will be :
0.019 * 30*1.2/100=0.006 pascal
As it is seen all the pipe sizes for steam lines are sufficient and they are in safe side fluid velocity,
maximum pressure drop is occurs in line A-B-D which its amount is (0.15 + 0.01 + 0.006 = 0.166 )
pascal which is negligible so there is sufficient steam pressure to carry out the condensate through
pipes, as an example through line M-L there is only 150 lb/hr which size 1 1/4 is sufficient for this
purpose[8].
As the maximum flow rate occurs through line C-D an D-B-A so calculation is done only for this case.
Point the finger that heat loss and flow rate for line C-D in the worst condition is 8400 lb/hr and by
using the condensate lines sizing table [8] via interpolation it is seen that pipe size 2 can carry out
9750 lb/hr flow rate of condense with pressure drop 1 psi per 100 ft of pipe. The length of piping
between points C and D is 82 meters so pressure drop of this line will be [82 / 0.3048 / 100 x 1 = 2.7 psi
] that is too low to hold up the flow.
As it is calculated in the pages before , in the worst condition maximum flow rate through the line
D-B-A is 9500 lb/hr and as it is said before pipe size 2 can carry out 9750 lb/hr flow rate of
condense with pressure drop 1 psi per 100 ft of pipe[8]. The length of piping between points D and A is
68 meters so pressure drop of this line is maximum [68 / 0.3048 / 100 x 1 = 2.2 psi ]. So total pressure
drop of condensate line will be 2.7 + 2.2 = 4.9 psi (as it is calculated pressure drop of steam is too low to
enter the total pressure drop) which this amount is negligible too.
VENDOR:
KHERAD WATER TREATMENT CO.
MAPNA
CO.
(PRIVATE JOINT STOCK)
IRAN POWER PLANT PROJECT MANACEMENT CO.
DOCUMENT NO.:
MP-SVG-20ME-08-SB3-001
Rev:
A
PROJECT:
SHIRVAN GAS TURBIN POWER PLANT
ORIG. NO.: REV.
A
CONTRACT
NO.:

FILE NO.:
STEAM &
CONDENSATE DESIGN
PAGE:
21 of 22


MINISTRY OF ENERGY
IRAN POWER DEVELOPMENT COMPANY
I.P.D.C
PROJECT:
PROJECT : SHIRVAN 6159 M.W. GAS TURBINE POWER PLANT

VENDOR:
KHERAD WATER TREATMENT CO.
MAPNA
CO.
(PRIVATE JOINT STOCK)
IRAN POWER PLANT PROJECT MANACEMENT CO.
DOCUMENT NO.:
MP-SVG-20ME-08-SB3-001
Rev:
A
PROJECT:
SHIRVAN GAS TURBIN POWER PLANT
ORIG. NO.: REV.
A
CONTRACT
NO.:

FILE NO.:
STEAM &
CONDENSATE DESIGN
PAGE:
22 of 22