Protection of transformers

Sn

[kVA]

500

630

800

1000

1250

1600

2000

2500

3150

Ucc (1)

6,25

6,25

6,25

6,25

In (2)

[A]

722

909

1154

1443

1804

2309

2887

3608

4547

Isc (2)

[kA]

18

22.7

23.1

28.9

36.1

37

46.2

57.7

72.7

E1B12

E1B12

E2B16

E2B20

E3B25

E3B32

E4S40

E6H50

SACE Emax

E1B08

(1) For values of the percent short circuit voltage Ucc% different from the Ucc% values as per table, the rated three-phase short
circuit current Icn becomes:

Isc = Isc

Ucc %

Ucc %
(2) The calculated values refer to a U20 voltage of 400 V. for different U20 values, do multiply In and Isc the following k times:

U20

[V]

ABB SACE

220

380

400

415

440

480

500

660

690

1.82

1.05

0.96

0.91

0.83

0.8

0.606

0.580