What is a load break switch?

Posted SEP 8 2011 by EDVARD in HIGH VOLTAGE , MEDIUM VOLTAGE with 3 COMMENTS

SF6 Insulated Load Break Switch for the use in medium voltage switchboards for secondary distribution networks.

A load break switch is a disconnect switch that has been designed to provide making or breaking of specified currents.This is accomplished by addition of equipment that increases the operating speed of the disconnect switch blade and the addition of some type of equipment to alter the arcing phenomena and allow the safe interruption of the arc resulting when switching load currents. Disconnect switches can be supplied with equipment to provide a limited load switching capability. Arcing horns, whips, and spring actuators are typical at lower voltages.These switches are used to de-energize or energize a circuit that possesses some limited amount of magnetic orcapacitive current , such as transformer exciting current or line charging currents. An air switch can be modified to include a series interrupter (typically vacuum or SF6 ) for higher voltage and current interrupting levels. These interrupters increase the load break capability of the disconnect switch and can be applied for switching load or fault currents of the associated equipment.

Apakah suis rehat beban?


Posted SEP 8 2011 oleh EDVARD dalam VOLTAN TINGGI , VOLTAN SEDERHANA dengan 3 KOMEN

SF6 tertebat Beban Switch Cuti untuk digunakan dalam papan suis voltan sederhana untuk rangkaian pengedaran menengah.

Satu suis beban rehat putus suis yang telah direka untuk menyediakan membuat atau melanggar arus dinyatakan. Ini dicapai dengan penambahan peralatan yang meningkatkan kelajuan operasi bilah suis putus dan penambahan beberapa jenis peralatan untuk mengubah fenomena pengarkaan dan membenarkan gangguan selamat arka yang terhasil apabila menukar arus beban. Suis putus boleh dibekalkan dengan peralatan untuk menyediakan pensuisan beban keupayaan terhad. Tanduk pengarkaan, memukul, dan penggerak spring biasa pada voltan yang lebih rendah. Suis ini telah digunakan untuk de-tenaga atau tenaga litar yang mempunyai beberapa jumlah terhad magnet atau semasa kapasitif , seperti pengubah arus menarik mengecas semasa atau talian. Suis udara boleh diubahsuai termasuk interrupter siri (biasanya vakum atau SF6 ) untuk voltan yang lebih tinggi dan tahap semasa mengganggu. Interrupters ini meningkatkan keupayaan beban berehat suis putus dan boleh digunakan bagi menukar arus beban atau kesilapan peralatan yang berkaitan.

Erection Procedures For Medium Voltage Switchgear


Po s t ed A PR 3 2 0 1 2 by E DVA RD in M A INTENA NC E , M EDIU M VOLTA GE w it h 1 C O M M ENT

Translate

PDF

ABB's Unigear medium voltage switchgear

Before commencing erection of medium voltage (MV) switchgear check that all connections are tight on busbars and on main and auxiliary circuits. Examine the insulation carefully, because there have been cases of burned out connections due to failure to observe this precaution. Obvious faults such as distorted panel work, broken meter glass and damaged packing cases should be noted and immediate steps taken to rectify the damage or to return the switchgear to the supplier. After erection, steps must be taken to prevent deterioration of the switchgear due to damp, dust or casual damage. Substations should be cleared out and locked fast and

should not be used as a site office, store or workshop after the switchgear has been installed. When all erection and jointing work is complete the medium voltage switchgear must be inspected and thoroughly cleaned to remove cuttings of cable, spare nuts, washers, accumulations of dust orcopper filings and tools which may have been left behind. However, it is dangerous to blow out equipment because dust, filings, light metal scraps, rags and sawdust can be blown into positions where they become inaccessible and may pass unnoticed. It is better to clean manually and vacuum the plant. An important point to remember is the removal of all packing materials particularly in moving parts, and of course make sure that oil circuit breakers receive their first filling of water-free oil (If you have this kind of CBs). In the erection of the switchgear the following points should be emphasised. Where steel channels are used as foundations, ensure that they are correctly laid to an accuracy of about 1 mm in 3 m. Use a masking strip to prevent fouling by the floor materials. Read and apply the manufacturers erection instructions and use the correct tools such as torque spanners to obtain the appropriate tightness of nuts. Make sure switchgear is properly aligned. This means vertically and horizontally in both longitudinal and lateral directions. Incorrect alignment causes problems during operation of mechanical linkages and cableconnections, difficulty in removing and replacing circuit breakers and other withdrawable parts and puts stress on interpanel connections such as busbars and earth bars. When the floor is being laid and there are no steel inset channels, it should be level both front to back and should not vary by more than a millimetre or so between cubicle centres. When the floor is being laid it is common practice to form pockets at the foundation hole positions in order to avoid having to cut them out of the solid floor at installation time. The floor should be marked out in accordance with the switchgear assembly drawings usually provided by the manufacturer to ensure that the switchgear is correctly located with respect to cable trenches, building walls and other equipment in the room. A datum line requires to be established usually along the rear foundation bolts, and using normal geometric methods the switchboard and foundation bolt holes can be located. The method of positioning theswitchgear is dependent on a number of factors such as switchgear size, building location, site accessibility and lifting tackle available. Lifting eyes are often either incorporated into switchboards or can be screwed into pre-machined holes, but generally slinging is necessary and this should be done strictly in accordance with the manufacturers recommendations. Without the use of cranes, however, the traditional manual methods utilising jacks and roller bars are effective.

Care must be taken not to exert pressure on weak parts such as control handles during this manhandling. Positioning of the cubicles should start near to the centre of the switchboard, installing as early as possible the enclosures associated with any special chambers or trunking. The first enclosure should be positioned and checked to ensure the side sheets are plumb and that any runner rails are level in both planes. When the first enclosure panel is correctly set the remaining enclosures should be positioned successively on alternate sides of this panel to make the front form an unbroken line. Adjacent enclosures should be bolted together after they have been correctly aligned using whatever shimming proves necessary to make sure that the cubicles are vertically and horizontally true. The fixing bolts should be positioned in the foundation holes and cemented in leaving adequate time for the cement to set before tightening up.

Checking of cable and other connections

Siemens metal clad switchgear SIMOSEC - Cable connection in cable panel

The switchgear may now be connected up and cable joints made. In particular one must confirm that the earthing of the switchgear has been carried out using the recommended cross-section of material and satisfactory terminations. The LV system must then be proved for continuity, preferably by using a hand generator or other portable device and with a current of about 1.5 times the design current. A further examination of all incoming and outgoing circuit and auxiliary cables, including a test of the correctness of the connections at the remote ends, should be done; this should include measuring the insulation resistance and continuity of all cables and wiring including internal and auxiliary connections. Where appropriate, phase rotation checks must be made before three-phase drives are energised. All moving parts must be inspected to ensure they are all operative. Dashpots must be filled to the correct level with the right grade of fluid, and the operation and accuracy of meters and relays by secondary or primary injection tests should be checked. All settings should be agreed with the clients engineers. All cable boxes must be properly topped up and compound filling spouts capped off. All insulators and spouts must be clean and dry and cover plates securely bolted up with all screws in position and tightened and breather vents clear of obstruction. Ensure that the top of the switchgear is free from all dirt and rubbish. A final check on all incoming and outgoing cable connections to terminals ensures that they are tight and have adequate clearance. High voltage testing can then be carried out to the test figures laid down in the appropriate BS switchgear specification or as specified by the clients engineers who should witness the tests and sign the test r esults. After testing, precautions must be taken to discharge any static and remove the test connections before bolting up any covers removed for testing. Before energising, the operation of all circuit breakers and relays should be confirmed manually and electrically to ensure that no sticking or malfunction is present, particular attention being given to manual trip and close operations and to the operation of overcurrent relays and residual current devices.

Going Alive
When the switchgear is ready to make alive all circuits not in service shall be locked off at each end and safety operation procedures adopted. All switching operations should be carried out by a competent person. 1 The substations entry and emergency exist doors must be operative and kept clear and free from obstruction. 2 All substations should be kept locked when the switchgear is live, and access restricted to authorised personnel only.

3 Danger, safety, shock cards and any statutory notices must be prominently displayed. 4 Tools required for operating switchgear should be stored adjacent to the equipment in
proper racks or cabinets. 5 Circuit and interlock keys should also be contained in special cabinets under the control of authorised personnel and no spare keys must be allowed to abort the safety of the system. 6 Batteries should be examined to ensure that they have received their first charge and the electrolyte is at the correct level and of appropriate specific gravity. 7 The fire-fighting requirement should be checked and if it is CO2 it must be confirmed that the safety lock-off procedure is understood by the personnel authorised to enter the substation. 8 External warning notices must be fixed to protect any strangers from inadvertently suffocating.

Prosedur ereksi Untuk Switchgear Voltan Sederhana


Posted APR 3 2012 oleh EDVARD PENYELENGGARAAN , VOLTAN SEDERHANA dengan 1 COMMENT

Menterjemahkan

PDF

ABB, suis voltan sederhana Unigear

Sebelum memulakan pendirian voltan sederhana (MV) cek suis semua sambungan adalah ketat pada palang bas dan litar utama dan tambahan. Memeriksa penebat dengan teliti, kerana terdapat kes-kes sambungan yang dibakar keluar disebabkan kegagalan untuk mematuhi langkah berjaga-jaga ini.Kerosakan yang ketara seperti kerja panel yang diputarbelitkan, kaca meter pecah dan rosak kes pembungkusan perlu diambil perhatian dan langkah segera yang diambil untuk membetulkan kerosakan atau kembali suis kepada pembekal. Selepas ereksi, langkah-langkah yang perlu diambil untuk mengelakkan kemerosotan suis kerana lembap, habuk atau kerosakan kasual. Pencawang perlu dibersihkan dan yang dikunci cepat dan tidak harus digunakan sebagai sebuah kedai tapak pejabat, atau bengkel selepas suis telah dipasang. Apabila semua pembinaan dan kerja-kerja penyambungan lengkapkan suis voltan sederhana perlu diperiksa dan dibersihkan secara menyeluruh untuk membuang keratan kabel, kacang ganti, sesendal, pengumpulan habuk atau tembaga pemfailan dan alat-alat yang mungkin telah ketinggalan. Walau bagaimanapun, ia adalah merbahaya untuk meniup peralatan kerana debu, pemfailan, memo logam yang ringan, habuk papan dan kain boleh ditiup ke dalam kedudukan di mana mereka menjadi tidak boleh diakses dan

boleh lulus tanpa disedari. Adalah lebih baik untuk membersihkan secara manual dan vakum loji. Satu perkara yang penting untuk diingati ialah penyingkiran semua bahan pembungkusan terutamanya dalam bahagian yang bergerak, dan sudah tentu memastikan bahawa pemutus litar minyak menerima pengisian pertama mereka bebas minyak air (Jika anda mempunyai jenis ini bank perdagangan). Dalam pendirian suis perkara-perkara berikut perlu diberi penekanan. Jika saluran keluli digunakan sebagai asas, memastikan bahawa mereka betul dibentangkan ketepatan mengenai mm 1 dalam 3 m. Gunakan jalur masking untuk mencegah pengotoran oleh bahan lantai.Baca dan memohon arahan pendirian pengilang dan menggunakan alat yang betul seperti sepana tork untuk mendapatkan ketat sesuai kacang. Pastikan suis yang betul sejajar. Ini bermakna melintang dan menegak dalam kedua-dua arah membujur dan sisi. Penjajaran yang tidak betul menyebabkan masalah semasa operasi hubungan mekanikal dan sambungan kabel , kesukaran untuk mengeluarkan dan menggantikan pemutus litar dan lain-lain bahagian dikeluarkan dan meletakkan tekanan pada sambungan interpanel seperti palang bas dan bar bumi. Apabila lantai sedang dibentangkan dan tidak ada saluran keluli Inset, ia harus menjadi peringkat kedua-dua depan ke belakang dan tidak harus berbeza-beza mengikut lebih daripada milimeter atau antara pusat kubikel. Apabila lantai sedang dibentangkan ia adalah amalan biasa untuk membentuk poket di kedudukan lubang asas bagi mengelakkan memotong mereka keluar dari tingkat pepejal pada masa pemasangan. Lantai perlu ditanda mengikut lukisan pemasangan suis yang biasanya disediakan oleh pengilang untuk memastikan bahawa suis dengan betul terletak berkenaan parit kabel, dinding bangunan dan peralatan lain di dalam bilik. Satu garis datum memerlukan ditubuhkan biasanya sepanjang bolt asas belakang, dan menggunakan kaedah geometri biasa papan suis dan asas bolt lubang boleh ditempatkan. Kaedah kedudukan daripada theswitchgear adalah bergantung kepada beberapa faktor seperti saiz suis, lokasi bangunan, kemudahan tapak dan takal mengangkat disediakan. Mengangkat mata sering kali sama ada dimasukkan ke dalam papan suis atau boleh diskru ke dalam lubang pra-dimesin, tetapi umumnya slinging adalah perlu dan ini harus dilakukan dengan ketat selaras dengan saranan pengeluar. Tanpa penggunaan kren, bagaimanapun, kaedah manual tradisional yang menggunakan bicu dan bar roller berkesan. Perhatian perlu diambil tidak mengenakan tekanan ke atas bahagian-bahagian yang lemah seperti kawalan mengendalikan semasa manhandling ini. Kedudukan daripada gubuk harus bermula dekat ke pusat papan suis itu, memasang seawal mungkin lampiran yang berkaitan dengan mana-mana dewan khas atau Trunking. Penutup pertama harus diletakkan dan diperiksa untuk memastikan lembaran sampingan adalah alat pengukur dan bahawa mana-mana rel pelari adalah peringkat di kedua-dua

pesawat. Apabila panel kepungan pertama dengan betul lampiran baki perlu diletakkan berturut-turut bersilang panel ini untuk membuat borang depan talian tak terputus-putus. Kandang bersebelahan perlu diperketatkan bersama selepas mereka telah betul sejajar yang menggunakan apa sahaja shimming membuktikan perlu untuk memastikan bahawa gubuk menegak dan mendatar benar. Bolt menetapkan harus diletakkan dalam lubanglubang asas dan yang disimenkan dalam meninggalkan masa yang mencukupi untuk simen untuk menetapkan sebelum mengetatkan.

Semakan sambungan kabel dan lain-lain

Siemens logam berpakaian suis SIMOSEC - sambungan kabel dalam panel kabel

Suis sekarang boleh disambung sehingga dan sendi kabel yang dibuat. Khususnya seseorang mesti mengesahkan bahawa pembumian suis telah dijalankan menggunakan yang disyorkan keratan rentas bahan dan penamatan memuaskan. Sistem LV mesti dibuktikan untuk kesinambungan, sebaik-baiknya dengan menggunakan penjana tangan atau peranti mudah alih lain dan dengan semasa kira-kira 1.5 kali semasa reka bentuk. Pemeriksaan lanjut litar semua masuk dan keluar dan kabel tambahan, termasuk ujian ketepatan sambungan di hujung jauh, perlu dilakukan; ini harus termasuk mengukur rintangan penebat dan kesinambungan semua kabel dan pendawaian yang termasuk sambungan dalaman dan tambahan . Di mana sesuai, cek giliran fasa mesti dibuat sebelum pemacu tiga fasa bertenaga. Semua bahagian yang bergerak mesti diperiksa

untuk memastikan mereka semua operatif. Peredam mesti diisi ke tahap yang betul dengan gred kanan cecair, dan operasi dan ketepatan meter dan geganti oleh ujian suntikan menengah atau rendah perlu diperiksa. Semua tetapan perlu bersetuju dengan jurutera pelanggan. Semua kotak kabel mesti ditokok dan mengisi spouts kompaun dihadkan off. Semua penebat dan spouts yang mesti bersih dan kering dan plat penutup selamat diperketatkan dengan semua skru di dalam kedudukan dan mengetatkan dan bolong seketika jelas halangan. Memastikan bahawa atas peralatan suis yang bebas dari semua kotoran dan sampah. Semakan akhir ke atas semua sambungan kabel masuk dan keluar kepada terminal memastikan bahawa mereka adalah ketat dan mempunyai pelepasan yang mencukupi. Ujian voltan tinggi kemudiannya boleh dijalankan dengan angka ujian yang ditetapkan dalam spesifikasi BS suis yang sesuai atau sebagaimana yang dinyatakan oleh jurutera pelanggan yang harus menyaksikan ujian dan menandatangani keputusan ujian. Selepas ujian, langkah berjaga-jaga yang perlu diambil untuk melepaskan mana-mana statik dan keluarkan sambungan ujian sebelum hal mengunci mana-mana perlindungan yang dikeluarkan kerana ujian. Sebelum bertenaga operasi semua pemutus litar dan geganti perlu disahkan secara manual dan elektrik untuk memastikan bahawa tiada lekatan atau kepincangan hadir, perhatian khusus diberikan kepada perjalanan manual dan operasi rapat dan operasi geganti arus lebih dan peranti arus baki.

Melangkah Hidup
Apabila suis bersedia untuk membuat hidup semua litar tidak dalam perkhidmatan hendaklah dikunci pada setiap hujung dan prosedur operasi keselamatan yang diterima pakai. Semua operasi pensuisan perlu dijalankan oleh orang kompeten. 1 entry pencawang dan kecemasan wujud pintu mestilah kuasa dan disimpan jelas dan bebas daripada halangan. 2 pencawang Semua perlu sentiasa dikunci apabila suis hidup, dan akses terhad kepada kakitangan yang dibenarkan sahaja. Bahaya 3, keselamatan, kad kejutan dan sebarang notis berkanun mesti dipaparkan dengan ketara. 4 Alatan yang diperlukan untuk suis operasi perlu disimpan bersebelahan dengan peralatan dalam rak atau kabinet yang betul. 5 Circuit dan kunci berpaut juga perlu terkandung di dalam kabinet khas di bawah kawalan kakitangan yang dibenarkan dan tiada kekunci ganti mesti dibenarkan untuk keselamatan membatalkan sistem. 6 Bateri perlu diperiksa untuk memastikan bahawa mereka telah menerima tuduhan pertama dan elektrolit mereka adalah pada tahap yang betul dan graviti tentu yang sesuai. 7 Keperluan memadam kebakaran perlu diperiksa dan jika ia adalah CO2 ia mesti mengesahkan bahawa keselamatan kunci-prosedur difahami oleh kakitangan yang diberi kuasa untuk memasuki pencawang.

8 amaran notis Luar mesti ditetapkan untuk melindungi mana-mana orang yang tidak
dikenali daripada secara tidak sengaja merimaskan. Rujukan: Geoffrey Stokes - Buku amalan elektrik

Complete overview of lightning arresters (part 1)


Po s t ed S E P 2 3 2 0 11 by J I GU PA RM A R in POWER S U BS TA TION , PRO TEC TIO N w i t h 5 C OM M ENTS

Translate

PDF

Top

Lighting and Voltage Surge

Rod arrester

Lightning can create voltage surges in several of the following ways. Lightning can score a direct hit on your house. It can strike the overhead power line which enters your house, or a main power line that is blocks away from your home. Lightning can strike branch circuitry wiring in the walls of your house. Lightning can strike an object near your home such as a tree or the ground itself and cause a surge. Voltage surges can be created by cloud to cloud lightning near your home. A highly charged cloud which passes over your home can also induce a voltage surge. Voltage surges can also be caused by standard on and off switching activities of large electric motors or pieces of equipment. These surges can be created by a neighbor, or by a business or manufacturing facility some distance from your house. These surges are insidious and for the most part are silent. They can occur with little or no warning.
Top

Methodology to Suppress Lighting and Voltage Surge:


When a voltage surge is created, it wants to equalize itself and it wants to do it as quickly as possible. These things seem to have very little patience. The surges will do whatever it takes to equalize or neutralize themselves, even if it means short circuiting all of your electronic equipment. The method of providing maximum protection for equipment is quite simple. Create a pathway for the voltage surge (electricity) to get to and into the ground outside your house as quickly as possible. This is not, in most cases, a difficult task.

The first step is simple. Create an excellent grounding system for your household electrical system. The vast majority of homes do not have an excellent grounding system. Many homes have a single grounding rod and /or a metallic underground water pipe which are part of the electrical grounding system. In most cases, this is inadequate. The reason is somewhat easy to explain. Imagine putting a two inch fire hose into your kitchen sink and opening the nozzle to the full on position. I doubt that the drain in your sink could handle all of the water. Your grounding system would react in the same way to a massive voltage surge. Just as the water jumps out of the sink, the electricity jumps from the grounding system and looks for places to go. Frequently it looks for the microchips in your electronic devices. They are an easy target. They offer a path of least resistance. Voltage surges want to be directed to the grounding system, and when they do, they want to get into the ground around your house in a hurry. You can achieve this by driving numerous grounding rods into virgin soil around your house. These rods should be UL approved and connected by a continuous heavy solid copper wire which is welded to each grounding rod. This solid copper wire begins on the grounding bar inside of your electrical panel and terminates at the last grounding rod. Avoid using clamps if at all possible. Over time, the connection at the clamp can corrode or become loose creating tremendous resistance. This will act as a roadblock to the electricity trying to get into the ground around your home. The grounding rods should be at least ten feet apart from one another. They should be located in soil which readily accepts electricity. Moist clay soils are very desirable. Rocky, sandy, or soils with gravel generally have high resistance factors. Electricity has a tough time dissipating into them. Resistance readings should be in the range of 10 to 30 ohms. The lower the better. The second step in household surge protection is to install a lightning arrester inside of your electric service panel. These devices can be extremely effective in intercepting large voltage surges which travel in the electric power lines. These devices capture the voltage surges and bleed them off to the grounding wire which we just spoke of. If for some reason you do not have a large enough grounding wire, or enough ground rods, the arrester cannot do its job. It must be able to send the surge quickly to the ground outside of your house. These arresters range in price from $50.00 to $175.00. Almost every manufacturer of circuit breakers makes one to fit inside their panel. They can be installed by a homeowner who is experienced in dealing with high voltage panels. If you do not have this capability, have an experienced electrician install it for you. The final step in the protection plan is to install point of use surge suppression devices. Often you will see these called transient voltage surge suppressors. These are your last line of defense. They are capable of only stopping the leftover voltage surge which got past the grounding system and the lightning arrester. They cannot protect your electronic devices by themselves. They must be used in conjunction with the grounding system and

the lightning arresters. Do not be lulled into a false sense of security if you merely use one of these devices! The point of use surge suppression devices are available in various levels of

quality.Some are much better than others. What sets them apart are several things. Generally speaking, you look to see how fast their response time is. This is often referred to as clamping speed. Also, look to see how high of a voltage surge they will suppress. Make sure that the device has a 500 volt maximum UL rated suppression level. Check to see if it has an indicator, either visual or audio, which lets you know if it is not working. The better units offer both, in case you install the device out of sight. Check to see if it offers a variety of modes with respect to protection. For example, does the device offer protection for surges which occur betwee n the hot and neutral, between hot and ground, as well as between neutral and ground. There is a difference! Check to see if it monitors the normal sine waves of regular household current. Surges can cause irregularities in these wave patterns. Good transient surge suppression devices devour these voltage spikes. Finally, check the joule rating. Attempt to locate a device which has a joule rating of 140 or higher. Electrical supply houses often are the best place to look for these high quality devices. Some devices can also protect your phone equipment at the same time. This is very important for those individuals who have computer modems. Massive voltage surges can come across phone lines as well. These surges can enter your computer through the telephone line! Dont forget to protect this line as well. Also, be sure the telephone ground wire is tied to the upgraded electrical grounding system.

Gambaran lengkap kilat arresters (bahagian 1)


Posted SEP 23 2011 oleh JIGUPARMAR di PENCAWANG KUASA , PERLINDUNGAN dengan 5 KOMEN

Menterjemahkan

PDF

Top

Luruan pencahayaan dan Voltan

Penangkap rod

Kilat boleh membuat voltan pusuan dalam beberapa cara yang berikut. Kilat boleh menjaringkan hit langsung ke atas rumah anda. Ia boleh menyerang talian kuasa overhed yang memasuki rumah anda, atau talian kuasa utama yang blok jauh dari rumah anda. Kilat boleh menyerang cawangan pendawaian litar di dinding rumah anda. Kilat boleh menyerang objek yang berdekatan rumah anda seperti pokok atau tanah itu sendiri dan menyebabkan lonjakan. Voltan pusuan boleh diwujudkan dengan awan kilat awan berhampiran rumah anda. Awan yang dikenakan yang merentasi rumah anda juga boleh mendorong lonjakan voltan. Voltan pusuan juga boleh disebabkan oleh standard dalam dan di luar aktiviti penukaran motor elektrik yang besar atau keping peralatan. Ini pusuan boleh diwujudkan oleh jiran,

atau oleh kemudahan perniagaan atau pengilangan beberapa jarak dari rumah anda. Ini luruan adalah berbahaya dan bagi sebahagian besar adalah senyap. Mereka boleh berlaku dengan amaran sedikit atau tiada langsung.
Top

Metodologi untuk Mengurangkan Surge Lampu dan Voltan:


Apabila lonjakan voltan diwujudkan, ia mahu menyamakan dirinya sendiri dan mahu melakukannya secepat mungkin.Perkara-perkara ini seolah-olah mempunyai kesabaran yang sangat sedikit. Yang mendadak akan buat apa sahaja untuk menyamakan atau meneutralkan diri mereka, walaupun ia bermakna pendek pintas semua peralatan elektronik anda. Kaedah menyediakan perlindungan maksimum untuk peralatan adalah agak mudah. Buat laluan untuk gelombang voltan (elektrik) untuk mendapatkan dan ke dalam tanah di luar rumah anda secepat mungkin. Ini tidak, dalam kebanyakan kes, tugas yang sukar. Langkah pertama adalah mudah. Mewujudkan satu sistem asas yang sangat baik untuk sistem elektrik rumah anda. Majoriti rumah tidak mempunyai sistem pembumian yang cemerlang. Kebanyakan rumah mempunyai satu rod grounding dan / atau paip air bawah tanah logam yang merupakan sebahagian daripada sistem pembumian elektrik. Dalam kebanyakan kes, ini adalah tidak mencukupi. Sebab agak mudah untuk menerangkan. Bayangkan meletakkan hos api 2 inci ke dalam sink dapur anda dan membuka muncung penuh ke atas kedudukan. Saya ragu-ragu bahawa parit dalam sink anda boleh mengendalikan semua air. Sistem pembumian yang anda akan bertindak balas dengan cara yang sama melonjak voltan besar-besaran. Sama seperti air melompat keluar dari singki, elektrik melompat dari sistem pembumian dan mencari tempat untuk pergi. Kerap ia kelihatan untuk mikrocip dalam alat-alat elektronik anda. Mereka merupakan sasaran mudah. Mereka akan menawarkan laluan yang paling kurang rintangan. Voltan pusuan mahu ditujukan kepada sistem pembumian , dan apabila mereka berbuat demikian, mereka mahu mendapatkan kembali ke dalam tanah di sekitar rumah anda terburu-buru. Anda boleh mencapai ini dengan memandu rod asas yang banyak ke dalam tanah dara di sekeliling rumah anda.Rod ini harus menjadi UL diluluskan dan dihubungkan dengan wayar kuprum pepejal berterusan berat yang dikimpal pada setiap rod grounding. Ini wayar kuprum pepejal bermula pada bar bumi di dalam panel elektrik anda dan akan tamat pada rod asas yang terakhir. Elakkan menggunakan pengapit jika boleh. Dari masa ke masa, sambungan pada pengapit boleh mengakis atau menjadi longgar mewujudkan rintangan yang besar. Ini akan bertindak sebagai roadblock kepada bekalan elektrik yang cuba untuk mendapatkan ke dalam tanah di sekeliling rumah anda. Rod bumi harus sekurang-kurangnya sepuluh kaki dari satu sama lain. Mereka harus terletak di tanah yang sedia menerima elektrik. Tanah liat lembab adalah sangat

wajar. Berbatu, berpasir atau tanah dengan batu kelikir umumnya mempunyai faktor daya ketahanan yang tinggi. Elektrik mempunyai masa yang sukar yang melesapkan kepada mereka. Bacaan rintangan yang perlu berada dalam lingkungan 10-30 ohm. Yang lebih rendah lebih baik. Langkah kedua dalam perlindungan pusuan isi rumah adalah untuk memasang penangkap kilat di dalam panel perkhidmatan elektrik anda. Alat-alat ini boleh menjadi sangat berkesan dalam memintas voltan besar luruan yang perjalanan dalam talian kuasa elektrik. Alat-alat ini menawan voltan yang mendadak dan 'berdarah' mereka kepada dawai pembumian yang kita hanya bercakap mengenai. Jika atas sebab-sebab tertentu, anda tidak mempunyai wayar grounding yang cukup besar, atau rod alasan yang cukup, penangkap tidak boleh melakukan pekerjaan. Ia mesti berupaya untuk menghantar melonjak dengan cepat ke tanah di luar rumah anda. Arresters ini antara harga dari $ 50.00 pada $ 175,00. Hampir setiap pengilang pemutus litar membuat satu hingga dimuatkan di dalam panel mereka. Ia boleh dipasang oleh pemilik rumah yang berpengalaman dalam berurusan dengan panel voltan tinggi. Jika anda tidak mempunyai keupayaan ini, mempunyai juruelektrik berpengalaman memasang untuk anda. Langkah terakhir di dalam pelan perlindungan adalah titik penggunaan 'untuk memasang peranti penindasan lonjakan. Kerap anda akan melihat 'penebat voltan lonjakan fana' ini dipanggil. Ini adalah garis pertahanan terakhir anda. Mereka mampu hanya berhenti lonjakan tinggalan voltan yang dapat melepasi sistem pembumian dan penangkap kilat. Mereka tidak boleh melindungi peranti elektronik anda dengan sendiri. Ia mestilah digunakan bersama-sama dengan sistem pembumian dan arresters kilat. Tidak lulled ke dalam erti kata palsu keselamatan jika anda hanya menggunakan satu peranti ini!

'Titik peranti penindasan lonjakan penggunaan' boleh didapati dalam pelbagai tahap kualiti.Ada yang lebih baik daripada yang lain. Apa yang menetapkan mereka selain beberapa perkara. Secara umum, anda melihat melihat betapa cepat masa tindak balas mereka. Ini sering dirujuk sebagai pengapit kelajuan. Juga, melihat untuk melihat berapa tinggi lonjakan voltan mereka akan menindas. Pastikan bahawa peranti mempunyai 500 maksimum volt UL Tertinggi penindasan tahap. Periksa untuk melihat jika ia mempunyai penunjuk, sama ada visual atau audio, yang membolehkan anda tahu jika ia tidak berfungsi. Unit-unit yang lebih baik menawarkan kedua-duanya, jika anda memasang peranti penglihatan.Periksa untuk melihat jika ia menawarkan pelbagai kaedah berkenaan kepada perlindungan. Sebagai contoh, adakah perlindungan peranti tawaran yang luruan yang berlaku antara 'panas' dan neutral, antara 'panas' dan tanah, serta antara neutral dan bumi. Terdapat perbezaan! Periksa untuk melihat jika ia memantau gelombang sinus normal semasa isi rumah biasa. Mendadak boleh menyebabkan penyelewengan dalam corak gelombang ini. Penindasan peranti lonjakan baik fana 'memakan' pancang voltan ini. Akhir sekali, periksa penarafan joule. Cuba untuk mencari peranti yang mempunyai penarafan joule daripada 140 atau lebih tinggi. Rumah bekalan elektrik sering adalah tempat terbaik untuk mencari peranti ini berkualiti tinggi.

Sesetengah peranti juga boleh melindungi peralatan telefon anda pada masa yang sama. Ini adalah sangat penting bagi individu-individu yang mempunyai modem komputer. Voltan secara besar-besaran luruan boleh mencari talian telefon juga. Ini pusuan boleh memasuki komputer anda melalui talian telefon!Jangan lupa untuk melindungi garisan ini sebagai. Juga, pastikan wayar telefon alasan terikat kepada sistem pembumian elektrik yang dinaik taraf.

Complete overview of lightning arresters (part 2)


Po s t ed S E P 2 9 2 0 11 by J I GU PA RM A R in POWER S U BS TA TION , PRO TEC TIO N w i t h 1 C OM M ENT

Translate

PDF

Top

Continued from article Complete overview of lightning arresters (part 1)

What is a surge arrester?


Surge arresters are devices that help prevent damage to apparatus due to high voltages. The arrester provides a low-impedance path to ground for the current from a lightning strike or transient voltage and then restores to a normal operating conditions. A surge arrester may be compared to a relief valve on a boiler or hot water heater. It will release high pressure until a normal operating condition is reached. When the pressure is returned to normal, the safety valve is ready for the next operation. When a high voltage (greater than the normal line voltage) exists on the line, the arrester immediately furnishes a path to ground and thus limits and drains off the excess voltage. The arrester must provide this relief and then prevent any further flow of current to ground. The arrester has two functions; it must provide a point in the circuit at which an overvoltage pulse can pass to ground and second, to prevent any follow-up current from flowing to ground.
Top

Causes of over voltages


Internal causes External causes

Internal causes
Switching surge
The overvoltages produced on the power system due to switching are known as switching surge.

Insulation failure
The most common case of insulation failure in a power system is the grounding of conductors (i.e. insulation failure between line and earth) which may cause overvoltage in the system.

Arcing ground
The phenomenon of intermittent arc taking place in line to ground fault of a 3phase system with consequent production of transients is known as arcing ground.

Resonance
It occurs in an electrical system when inductive reactance of the circuit becomes equal to capacitive reactance. under resonance , the impedance of the circuit is equal to resistance of the circuit and the p.f is unity.
Top

Types of lightning strokes


1. Direct stroke 2. Indirect stroke

(1) Direct stroke


In direct stroke, the lightning discharge is directly from the cloud to the subject equipment. From the line, the current path may be over the insulator down the pole to the ground.

(2) Indirect stroke


Indirect stroke results from the electro statically induced charges on the conductors due to the presence of charge clouds.
Top

Harmful effects of lightning


The traveling waves produced due to lightning will shatter the insulators. If the traveling waves hit the windings of a transformer or generator it may cause considerable damage.

Protection against lightning


Different types of protective devices are: 1. Earthing screen 2. Overhead ground wires 3. Lightning arresters

(1) The Earthing screen


The power station & sub-station can be protected against direct lightning strokes by providing earthing screens. On occurrence of direct stroke on the station ,screen provides a low resistance path by which lightning surges are conducted to ground.

Limitations: It does not provide protection against the traveling waves which may reach the equipments in the station.

(2) Overhead ground wires


It is the most effective way of providing protection to transmission lines against direct lightning strokes. It provides damping effect on any disturbance traveling along the lines as it acts as a short-circuited secondary. Limitations:

It requires additional cost. There is a possibility of its breaking and falling across the line conductors, thereby causing a short-circuit fault.

(3) Lightning Arresters

It is a protective device which conducts the high voltage surge on the power system to ground. The earthing screen and ground wires fail to provide protection against traveling waves. The lightning arrester provides protection against surges.
Top

AC Power Surge Arrester


Type 1 Surge Protectors
Type 1 surge protectors are designed to be installed where a direct lightning strike risk is high, especially when the building is equipped with external lightning protection system (LPS or lightning rod). In this situation IEC 61643-11 standards require the Class I test to be applied to surge protectors : this test is characterized by the injection of 10/350 s impulse current in order to simulate the direct lightning strike consequence. Therefore these Type 1 surge protectors must be especially powerful to conduct this high energy impulse current.

Type 2 surge protectors


Type 2 surge protectors are designed to be installed at the beginning of the installation, in the main switchboard, or close to sensitive terminals, on installations without LPS (lightning rods). These protectors are tested following the Class II test from IEC61643-11 based on 8/20 s impulse current injection.

Type 3 surge protectors


In case of very sensitive or remote equipment, secondary stage of surge protectors is required : these low energy SPDs could be Type 2 or Type 3. Type 3 SPDs are tested with a combination waveform (1,2/50 s 8/20 s) following Class III test.
Top

Types of Lightning Arrestors according to Class


1. Station Class

Station class arrestors are typically used in electrical power stations or substations and other high voltage structures and areas. These arrestors protect against both lightning and over-voltages, when the electrical device has more current in the system than it is designed to handle. These arrestors are designed to protect equipment above the 20 mVA range.

2. Intermediate Class

Like station class arrestors, intermediate class arrestors protect against surges from lightning and over-voltages, but are designed to be used in medium voltage equipment areas, such as electrical utility stations, substations, transformers or other substation equipment.

These arrestors are designed for use on equipment in the range of 1 to 20 mVA.

3. Distribution Class

Distribution class arrestors are most commonly found on transformers, both drytype and liquid-filled. These arrestors are found on equipment rated at 1000 kVA or less. These arrestors are sometimes found on exposed lines that have direct connections to rotating machines.

4. Secondary Class

Secondary class lightning arrestors are designed to protect most homes and businesses from lightning strikes, and are required by most electrical codes, according to, Inc., an electrical power protection company.

These arrestors cause high voltage overages to ground, though they do not short all the over voltage from a surge. Secondary class arrestors offer the least amount of protection to electrical systems, and typically do not protect solid state technology, or anything that has a microprocessor.
Top

Choosing the right AC Power Surge Arrester


AC power surge protectors is designed to cover all possible configurations in low voltage installations. They are available in many versions, which differ in:

Type or test class ( 1 , 2 or 3) Operating voltage ( Uc) AC network configuration ( Single/3-Phase) Discharge currents (Iimp, Imax, In) Protection level (Up) Protection technology ( varistors, gas tube-varistor, filter) Features (redundancy, differential mode, plug-in, remote signaling).

The surge protection selection must be done following the local electrical code requirements (i.e. minimum rating for In) and specific conditions (i.e. high lightning density).
Top

Working Principle of Lightning Arrester


The earthing screen and ground wires can well protect the electrical system against direct lightning strokes but they fail to provide protection against traveling waves, which may reach the terminal apparatus. The lightning arresters or surge diverts provide protection against such surges. A lightning arrester or a surge diverted is a protective device, which conducts the high voltage surges on the power system to the ground. The earthing screen and ground wires can well protect the electrical system against direct lightning strokes but they fail to provide protection against traveling waves, which may reach the terminal apparatus. The lightning arresters or surge diverters provide protection against such surges. A lightning arrester or a surge diverted is a protective device, which conducts the high voltage surges on the power system to the ground. Fig below shows the basic form of a surge diverter.

Basic form of a surge diverter

It consists of a spark gap in series with a non-linear resistor. One end of the diverter is connected to the terminal of the equipment to be protected and the other end is effectively grounded. The length of the gap is so set that normal voltage is not enough to cause an arc but a dangerously high voltage will break down the air insulation and form an arc. The property of the non-linear resistance is that its resistance increases as the voltage (or current) increases and vice-versa. This is clear from the volt/amp characteristic of the resistor shown in Figure above. The action of the lightning arrester or surge diverter is as under: 1. Under normal operation, the lightning arrester is off the line i.e. it conducts no current to earth or the gap is non-conducting 2. On the occurrence of over voltage, the air insulation across the gap breaks down and an arc is formed providing a low resistance path for the surge to the ground. In this way, the excess charge on the line due to the surge is harmlessly conducted through the arrester to the ground instead of being sent back over the line. 3. It is worthwhile to mention the function of non-linear resistor in the operation of arrester. As the gap sparks over due to over voltage, the arc would be a shortcircuit on the power system and may cause power-follow current in the arrester. Since the characteristic of the resistor is to offer low resistance to high voltage (or current), it gives the effect of short-circuit. After the surge is over, the resistor offers high resistance to make the gap non-conducting.

Gambaran lengkap kilat arresters (bahagian 2)


Posted SEP 29 2011 oleh JIGUPARMAR di PENCAWANG KUASA , PERLINDUNGAN dengan 1 COMMENT

Menterjemahkan

PDF

Top

Sambungan dari artikel gambaran lengkap kilat arresters (bahagian 1)

Adalah penangkap lonjakan?


Arresters lonjakan peranti yang membantu mencegah kerosakan kepada radas disebabkan voltan tinggi .Penangkap menyediakan laluan-galangan rendah ke tanah semasa dari kilat atau voltan fana dan kemudian mengembalikan kepada keadaan operasi biasa. Penangkap lonjakan boleh berbanding dengan injap pelega pada dandang atau pemanas air panas . Ia akan melepaskan tekanan tinggi sehingga keadaan operasi normal dicapai. Apabila tekanan kembali kepada normal, injap keselamatan sedia untuk operasi seterusnya. Apabila voltan tinggi (lebih besar daripada voltan talian biasa) wujud secara on-line, penangkap segera memberikan laluan ke tanah dan dengan itu menghadkan dan parit daripada voltan berlebihan. Penangkap mesti memberi kelegaan ini dan kemudian menghalang mana-mana aliran arus ke bumi. Penangkap mempunyai dua fungsi, ia mesti menyediakan satu titik dalam litar di mana denyutan voltan berlebihan boleh lulus ke tanah dan kedua, untuk menghalang mana-mana susulan daripada mengalir ke tanah.
Top

Punca lebihan voltan


Sebab-sebab dalaman Faktor-faktor luaran

Sebab-sebab dalaman
Lonjakan pensuisan
Overvoltages yang dihasilkan pada sistem kuasa kerana pensuisan dikenali sebagai penukaran lonjakan.

Kegagalan penebat
Kes paling biasa kegagalan penebat dalam sistem kuasa adalah pembumian yang konduktor (kegagalan penebat iaitu antara garis dan bumi) yang boleh menyebabkan voltan lampau dalam sistem.

Tanah pengarkaan
Fenomena arka-sekala berlaku selaras kesalahan alasan sistem 3phase dengan pengeluaran berbangkit fana ini dikenali sebagai alasan pengarkaan.

Resonans
Ia berlaku dalam sistem elektrik apabila regangan induktif litar menjadi sama dengan regangan kapasitif.di bawah resonans, galangan litar adalah sama dengan rintangan litar dan pf adalah perpaduan.
Top

Jenis-jenis strok kilat


1. Strok langsung 2. Strok tidak langsung

(1) strok langsung


Dalam strok langsung, menunaikan kilat terus dari awan ke peralatan subjek. Dari garisan, laluan semasa mungkin lebih penebat turun tiang ke tanah.

(2) strok Tidak Langsung


Tidak langsung keputusan strok daripada caj statik didorong elektro pada konduktor yang disebabkan oleh kehadiran awan caj.
Top

Kesan-kesan bahaya petir


Ombak perjalanan yang dikeluarkan akibat kilat akan memecahkan penebat. Jika gelombang perjalanan melanda belitan pengubah atau penjana ia boleh menyebabkan kerosakan yang besar.

Perlindungan terhadap kilat


Pelbagai jenis peranti perlindungan adalah seperti berikut: 1. Skrin pembumian 2. Tanah wayar overhed 3. Kilat arresters

(1) skrin pembumian


Stesen kuasa & sub-stesen boleh dilindungi terhadap sebatan kilat langsung dengan menyediakan skrin pembumian. Apabila berlakunya strok langsung di stesen, skrin menyediakan laluan rintangan rendah yang kilat luruan dijalankan ke tanah.

Batasan: Ia tidak memberi perlindungan terhadap gelombang perjalanan yang boleh mencapai peralatan di dalam stesen.

(2) Overhed wayar bumi


Ia adalah cara yang paling berkesan untuk memberi perlindungan kepada talian penghantaran terhadap sebatan kilat langsung. Ia memberikan kesan redaman ke atas apa-apa gangguan perjalanan di sepanjang garis kerana ia bertindak sebagai menengah pendek litar. Batasan:

Ia memerlukan kos tambahan. Ada kemungkinan menarik semasa dan jatuh merentasi konduktor sejajar, dengan itu menyebabkan kerosakan litar pendek.

(3) Kilat Arresters


Ia adalah alat perlindungan yang mengendalikan lonjakan voltan pada sistem kuasa yang tinggi ke bumi.Skrin pembumian dan wayar bumi gagal untuk memberi perlindungan terhadap perjalanan gelombang.Penangkap kilat memberikan perlindungan terhadap peningkatan.
Top

AC Power Surge Penangkap


Taip 1 Pelindung Luruan
Pelindung jenis lonjakan 1 direka untuk dipasang di mana risiko kilat langsung adalah tinggi, terutamanya apabila bangunan itu dilengkapi dengan sistem perlindungan kilat luar (LPS atau kilat rod). Dalam keadaan ini IEC 61643-11 Piawaian tersebut memerlukan Kelas I menguji akan digunakan untuk pelindung pusuan: ujian ini dicirikan dengan suntikan 10/350 s impuls semasa supaya dapat merangsangkan kilat akibat langsung. Oleh itu, 1 pelindung ini lonjakan Jenis mestilah lebih kuat untuk menjalankan ini impuls tenaga semasa yang tinggi.

Taip 2 pelindung pusuan


Pelindung jenis lonjakan 2 direka untuk dipasang pada awal pemasangan, dalam papan suis utama, atau dekat dengan terminal sensitif, pemasangan tanpa LPS (rod kilat). Pelindung ini telah diuji berikutan ujian Kelas II dari IEC61643-11 pada 8/20 s impuls suntikan semasa.

Taip 3 pelindung pusuan


Dalam kes peralatan yang sangat sensitif atau jauh, peringkat menengah pelindung pusuan diperlukan: SPD tenaga rendah boleh menjadi Jenis 2 atau Jenis 3. Jenis 3 SPD diuji dengan gelombang gabungan (s 1,2 / 50 - 8/20 s) berikutan ujian Kelas III.
Top

Jenis-jenis penangkap kilat menurut Kelas


1. Kelas stesen

Penangkap kelas stesen biasanya digunakan di stesen-stesen kuasa atau pencawang elektrik dan lain-lain struktur voltan tinggi dan kawasan. Ini penangkap melindungi daripada kedua-dua kilat dan berlebihan voltan, apabila peranti elektrik mempunyai lebih semasa dalam sistem daripada direkabentuk untuk menangani.

Penangkap ini telah direka untuk melindungi peralatan di atas julat 20 MVA. Seperti penangkap kelas stesen, penangkap kelas pertengahan melindungi mendadak dari kilat dan berlebihan voltan, tetapi direka untuk digunakan di kawasan peralatan voltan sederhana, seperti stesen utiliti elektrik, substesen, transformer atau peralatan pencawang yang lain. Penangkap ini telah direka untuk digunakan pada peralatan dalam lingkungan 1-20 MVA.

2. Kelas pertengahan

3. Kelas pengedaran

Penangkap kelas pengagihan yang paling biasa ditemui pada transformer, keduadua kering jenis dan berisi cecair. Penangkap ini telah ditemui pada peralatan yang diberi nilai pada 1000 kVA atau kurang. Penangkap kadang-kadang dijumpai pada baris yang terdedah yang mempunyai sambungan terus ke mesin berputar.

4. Kelas Menengah

Penangkap kilat kelas menengah yang bertujuan untuk melindungi kebanyakan rumah-rumah dan perniagaan dari kilat, dan dikehendaki oleh kebanyakan kod elektrik, mengikut, Inc, syarikat perlindungan kuasa elektrik.

Penangkap ini menyebabkan overages voltan tinggi ke tanah, walaupun mereka tidak melakukan pendek semua voltan alih daripada melonjak. Penangkap kelas menengah menawarkan jumlah sekurang-kurangnya perlindungan kepada sistem elektrik, dan lazimnya tidak melindungi teknologi keadaan pepejal, atau apa-apa yang mempunyai mikropemproses.
Top

Memilih Power Surge Penangkap AC kanan


Pelindung lonjakan kuasa AC direka untuk meliputi semua konfigurasi mungkin dalam pepasangan voltan rendah. Mereka terdapat dalam banyak versi, yang berbeza dalam:

Jenis atau kelas ujian (1, 2 atau 3) Voltan operasi (U c) AC konfigurasi rangkaian (Single/3-Phase) Pelepasan arus (imp saya, saya
max,

I n)

Tahap perlindungan (U p) Perlindungan teknologi (varistors, gas tiub varistor, penapis) Ciri-ciri (pemberhentian, perbezaan mod, di dalam palam, isyarat jauh ...).

Pemilihan perlindungan lonjakan mesti dilakukan berikutan keperluan kod elektrik tempatan (iaitu penarafan minimum untuk saya n) dan keadaan tertentu (iaitu kilat kepadatan tinggi).
Top

Prinsip Kerja Penangkap Kilat


Skrin pembumian dan wayar bumi dan boleh melindungi sistem elektrik terhadap sebatan kilat langsung tetapi mereka gagal untuk memberi perlindungan terhadap perjalanan gelombang, yang boleh mencapai radas terminal. Arresters kilat atau alihan lonjakan memberi perlindungan terhadap apa-apa peningkatan.Penangkap kilat atau melonjak dialihkan adalah alat perlindungan, yang mengendalikan voltan tinggi peningkatan pada sistem kuasa ke tanah. Skrin pembumian dan wayar bumi dan boleh melindungi sistem elektrik terhadap sebatan kilat langsung tetapi mereka gagal untuk memberi perlindungan terhadap perjalanan gelombang, yang boleh mencapai radas terminal. Yang arresters kilat atau diverters lonjakan memberi perlindungan terhadap apa-apa peningkatan. Penangkap kilat atau melonjak dialihkan adalah alat perlindungan, yang mengendalikan voltan tinggi peningkatan pada sistem kuasa ke tanah. Rajah di bawah menunjukkan bentuk yang asas diverter lonjakan.

Bentuk asas diverter lonjakan

Ia terdiri daripada jurang pencucuh dalam siri dengan perintang bukan linear. Satu hujung diverter yang disambungkan kepada terminal peralatan untuk dilindungi dan hujung berkesan dibumikan. Panjang jurang begitu menetapkan bahawa voltan yang normal tidak cukup untuk menyebabkan arka tetapi voltan yang terlalu tinggi akan memecahkan penebatan udara dan membentuk arka. Harta rintangan bukan linear adalah bahawa rintangannya meningkat apabila meningkat (atau semasa) voltan dan sebaliknya. Ini adalah jelas daripada ciri-ciri volt / amp perintang yang ditunjukkan dalam Rajah di atas.

Tindakan penangkap kilat atau diverter lonjakan adalah seperti di bawah: 1. Di bawah operasi normal, penangkap kilat garisan iaitu ia menjalankan tiada semasa ke bumi atau jurang adalah tidak-menjalankan 2. Apabila berlaku lebih voltan, penebatan udara merentasi jurang rosak dan arka terbentuk menyediakan satu laluan rintangan rendah untuk melonjak ke tanah. Dengan cara ini, caj berlebihan dalam talian disebabkan lonjakan secara tidak dijalankan melalui penangkap ke tanah bukannya dihantar semula melalui talian. 3. Ia berbaloi untuk menyebut fungsi perintang bukan linear dalam operasi penangkap. Ini disebabkan oleh perbezaan percikan lebih disebabkan oleh voltan lebih, arka akan menjadi litar pintas pada sistem kuasa dan boleh menyebabkan kuasa-ikut semasa dalam penangkap. Sejak ciri perintang adalah untuk menawarkan rintangan yang rendah kepada voltan yang tinggi (atau semasa), ia memberi kesan litar pendek. Selepas lonjakan berakhir, perintang menawarkan rintangan yang tinggi untuk membuat jurang yang tidak menjalankan.

Complete overview of lightning arresters (part 3)


Po s t ed OC T 8 2 0 1 1 by J IG U PA RM A R in POWER SU BSTA TIO N , PR OTEC T ION w it h 0 C OM M ENTS

Translate

PDF

Top

Continued from article Complete overview of lightning arresters (part 2)

Types of Lightning Arresters for outdoor application


There are several types of lightning arresters in general use. They differ only in constructional details but operate on the same principle, providing low resistance path for the surges to the round. 1. Rod arrester 2. Horn gap arrester 3. Multi gap arrester 4. Expulsion type lightning arrester 5. Valve type lightning arrester

(1) Rod gap arrester


It is a very simple type of diverter and consists of two 1.5 cm rods, which are bent at right angles with a gap in between as shown in Fig. One rod is connected to the line circuit and the other rod is connected to earth. The distance between gap and insulator (i.e. distance P) must not be less than one third of the gap length so that the arc may not reach the insulator and damage it.

Generally, the gap length is so adjusted that breakdown should occur at 80% of sparkvoltage in order to avoid cascading of very steep wave fronts across the insulators. The string of insulators for an overhead line on the bushing of transformer has frequently a rod gap across it. Fig 8 shows the rod gap across the bushing of a transformer. Under normal operating conditions, the gap remains non-conducting. On the occurrence of a high voltage surge on the line, the gap sparks over and the surge current is conducted to earth. In this way excess charge on the line due to the surge is harmlessly conducted to earth

Typical rod gap arrester

Limitations
1. After the surge is over, the arc in the gap is maintained by the normal supply voltage, leading to short-circuit on the system. 2. The rods may melt or get damaged due to excessive heat produced by the arc. 3. The climatic conditions (e.g. rain, humidity, temperature etc.) affect the performance of rod gap arrester. 4. The polarity of the f the surge also affects the performance of this arrester. Due to the above limitations, the rod gap arrester is only used as a back-up protection in case of main arresters.

(2) Horn gap arrester


Fig shows the horn gap arrester. It consists of a horn shaped metal rods A and B separated by a small air gap. The horns are so constructed that distance between them gradually increases towards the top as shown. The horns are mounted on porcelain insulators. One end of horn is connected to the line through a resistance and choke coil L while the other end is effectively grounded.

The resistance R helps in limiting the follow current to a small value. The choke coil is so designed that it offers small reactance at normal power frequency but a very high reactance at transient frequency. Thus the choke does not allow the transients to enter the apparatus to be protected. The gap between the horns is so adjusted that normal supply voltage is not enough to cause an arc across the gap.

Typical horn gap arrester

Under normal conditions, the gap is non-conducting i.e. normal supply voltage is insufficient to initiate the arc between the gap. On the occurrence of an over voltage, spark-over takes place across the small gap G. The heated air around the arc and the magnetic effect of the arc cause the arc to travel up the gap. The arc moves progressively into positions 1, 2 and 3. At some position of the arc (position 3), the distance may be too great for the voltage to maintain the arc; consequently, the arc is extinguished. The excess charge on the line is thus conducted through the arrester to the ground.

(3) Multigap arrester


Fig shows the multi gap arrester. It consists of a series of metallic (generally alloy of zinc) cylinders insulated from one another and separated by small intervals of air gaps. The first cylinder (i.e. A) in the series is connected to the line and the others to the ground through a series resistance. The series resistance limits the power arc. By the inclusion of series resistance, the degree of protection against traveling waves is reduced. In order to overcome this difficulty, some of the gaps (B to C in Fig) are shunted by resistance. Under normal conditions, the point B is at earth potential and the normal supply voltage is unable to break down the series gaps. On the occurrence an over voltage, the breakdown of series gaps A to B occurs.

The heavy current after breakdown will choose the straight through path to earth via the shunted gaps B and C, instead of the alternative path through the shunt resistance.

Typical multigap arrester

Hence the surge is over, the arcs B to C go out and any power current following the surge is limited by the two resistances (shunt resistance and series resistance) which are now in series. The current is too small to maintain the arcs in the gaps A to B and normal conditions are restored. Such arresters can be employed where system voltage does not exceed 33kV.

(4) Expulsion type arrester


This type of arrester is also called protector tube and is commonly used on system operating at voltages up to 33kV. Fig shows the essential parts of an expulsion type lightning arrester. It essentially consists of a rod gap AA in series with a second gap enclosed within the fiber tube. The gap in the fiber tube is formed by two electrodes. The upper electrode is connected to rod gap and the lower electrode to the earth. One expulsion arrester is placed under each line conductor. Fig shows the installation of expulsion arrester on an overhead line.

Typical expulsion arrester

On the occurrence of an over voltage on the line, the series gap AA spanned and an arc is stuck between the electrodes in the tube. The heat of the arc vaporizes some of the fiber of tube walls resulting in the production of neutral gas. In an extremely short time, the gas builds up high pressure and is expelled through the lower electrode, which is hollow. As the gas leaves the tube violently it carries away ionized air around the arc. This deionizing effect is generally so strong that the arc goes out at a current zero and will not be re-established.

Advantages
1. They are not very expensive. 2. They are improved form of rod gap arresters as they block the flow of power frequency follow currents 3. They can be easily installed.

Limitations

1. An expulsion type arrester can perform only limited number of operations as during each operation some of the fiber material is used up. 2. This type of arrester cannot be mounted on enclosed equipment due to discharge of gases during operation. 3. Due to the poor volt/am characteristic of the arrester, it is not suitable for protection of expensive equipment

(5) Valve type arrester


Valve type arresters incorporate non linear resistors and are extensively used on systems, operating at high voltages. Fig shows the various parts of a valve type arrester. It consists of two assemblies (i) series spark gaps and (ii) non-linear resistor discs in series. The non-linear elements are connected in series with the spark gaps. Both the assemblies are accommodated in tight porcelain container. The spark gap is a multiple assembly consisting of a number of identical spark gaps in series. Each gap consists of two electrodes with fixed gap spacing. The voltage distribution across the gap is line raised by means of additional resistance elements called grading resistors across the gap. The spacing of the series gaps is such that it will withstand the normal circuit voltage. However an over voltage will cause the gap to break down causing the surge current to ground via the non-linear resistors. The non-linear resistor discs are made of inorganic compound such as thyrite or metrosil. These discs are connected in series. The non-linear resistors have the property of offering a high resistance to current flow when normal system voltage is applied, but a low resistance to the flow of high surge currents. In other words, the resistance of these non-linear elements decreases with the increase in current through them and vice-versa.

Non-linear resistor discs

Under normal conditions, the normal system voltage is insufficient to cause the break down of air gap assembly. On the occurrence of an over voltage, the breakdown of the series spark gap takes place and the surge current is conducted to earth via the non-linear resistors. Since the magnitude of surge current is very large, the non-linear elements will offer a very low resistance to the passage of surge. The result is that the surge will rapidly go to earth instead of being sent back over the line. When the surge is over, the non-linear resistors assume high resistance to stop the flow of current.

(6) Silicon carbide arresters


A great number of silicon carbide arresters are still in service. The silicon carbide arrester has some unusual electrical characteristics. It has a very high resistance to low voltage, but a very low resistance to high-voltage. When lightning strikes or a transient voltage occurs on the system, there is a sudden rise in voltage and current. The silicon carbide resistance breaks down allowing the current to be conducted to ground. After the surge has passed, the resistance of the silicon carbide blocks increases allowing normal operation. The silicon carbide arrester uses nonlinear resistors made of bonded silicon carbide placed in series with gaps. The function of the gaps is to isolate the resistors from the normal steady-state system voltage. One major drawback is the gaps require elaborate design to ensure consistent spark-over level and positive clearing (resealing) after a surge passes. It should be recognized that over a period of operations that melted particles of copper might form which could lead to a reduction of the breakdown voltage due to the pinpoint effect. Over a period of time, the arrester gap will break down at small over voltages or even at normal operating voltages. Extreme care should be taken on arresters that have failed but the over pressure relief valve did not operate.

(7) Metal Oxide Arrestor:


The MOV arrester is the arrester usually installed today. The metal oxide arresters are without gaps, unlike the SIC arrester. This gap -less design eliminates the high heat associated with the arcing discharges. The MOV arrester has two-voltage rating: duty cycle and maximum continuous operating voltage, unlike the silicon carbide that just has the duty cycle rating. A metal-oxide surge arrester utilizing zinc-oxide blocks provides the best performance, as surge voltage conduction starts and stops promptly at a precise voltage level, thereby improving system protection. Failure is reduced, as there is no air gap contamination possibility; but there is always a small value of leakage current present at operating frequency. It is important for the test personnel to be aware that when a metal oxide arrester is disconnected from an energized line a small amount of static charge can be retained by the arrester. As a safety precaution, the tester should install a temporary ground to discharge any stored energy.

Duty cycle rating: The silicon carbide and MOV arrester have a duty cycle rating in KV, which is determined by duty cycle testing. Duty cycle testing of an arrester is performed by subjecting an arrester to an AC rms voltage equal to its rating for 24 minutes. During which the arrester must be able to withstand lightning surges at 1-minute intervals. Maximum continuous operating voltage rating: The MCOV rating is usually 80 to 90% of the duty cycle rating.
Top

Installation of Lightning Arresters


The arrester should be connected to ground to a low resistance for effective discharge of the surge current. The arrester should be mounted close to the equipment to be protected & connected with shortest possible lead on both the line & ground side to reduce the inductive effects of the leads while discharging large surge current.
Top

Maintenance of Lightning Arresters


Cleaning the outside of the arrester housing. The line should be de-energized before handling the arrester. The earth connection should be checked periodically. To record the readings of the surge counter. The line lead is securely fastened to the line conductor and arrester The ground lead is securely fastened to the arrester terminal and ground.

Gambaran lengkap kilat arresters (part 3)


Posted 8 OKT 2011 oleh JIGUPARMAR di PENCAWANG KUASA , PERLINDUNGAN dengan 0 COMMENTS

Menterjemahkan

PDF

Top

Sambungan dari artikel gambaran lengkap kilat arresters (bahagian 2)

Jenis Arresters Kilat bagi permohonan luar


Terdapat beberapa jenis arresters kilat dalam kegunaan umum. Mereka hanya berbeza dalam butir-butir pembinaan tetapi beroperasi pada prinsip yang sama, menyediakan laluan rintangan rendah untuk luruan untuk pusingan. 1. Penangkap rod 2. Tanduk jurang penangkap 3. Multi jurang penangkap 4. Penangkap kilat jenis pengusiran 5. Penangkap kilat jenis injap

(1) Rod jurang penangkap


Ia adalah sejenis diverter yang sangat mudah dan terdiri daripada dua cm rod 1.5, yang dibengkokkan pada sudut tepat dengan jurang di antara seperti yang ditunjukkan dalam Rajah. Satu rod disambungkan kepada talian litar dan rod lain disambungkan ke bumi. Jarak di antara jurang dan penebat (iaitu jarak P) mestilah tidak kurang daripada satu pertiga daripada panjang jurang supaya arka tidak boleh mencapai penebat dan merosakkan.

Umumnya, panjang jurang yang diselaraskan bahawa pecahan sepatutnya berlaku pada 80% pencucuh voltan untuk mengelakkan Cascading front gelombang yang sangat curam di seluruh penebat . Rentetan penebat untuk overhed pada sesendal pengubah mempunyai kerap jurang rod merentasinya.Rajah 8 menunjukkan jurang rod merentasi sesendal pengubah. Di bawah keadaan operasi biasa, jurang kekal tidak menjalankan. Pada berlakunya lonjakan voltan yang tinggi dalam talian, jurang percikan alih dan semasa lonjakan dijalankan ke bumi Dengan cara ini caj lebihan dalam talian disebabkan melonjak secara tidak dijalankan ke bumi

Penangkap jurang rod tipikal

Batasan
1. Selepas lonjakan berakhir, arka dalam jurang dikekalkan oleh bekalan voltan normal, menyebabkan litar pintas pada sistem. 2. Rod boleh mencairkan atau rosak disebabkan kepanasan yang berlebihan yang dihasilkan oleh arka. 3. Keadaan iklim (contohnya hujan, kelembapan, suhu dan lain-lain) menjejaskan prestasi penangkap jurang rod. 4. Polariti f lonjakan juga memberi kesan kepada prestasi penangkap ini. Disebabkan batasan di atas, penangkap rod jurang hanya digunakan sebagai perlindungan yang back-up dalam kes arresters utama.

(2) Horn jurang penangkap


Rajah menunjukkan penangkap tanduk jurang. Ia terdiri daripada logam berbentuk rod tanduk A dan B yang dipisahkan oleh jurang udara yang kecil. Tanduk begitu dibina bahawa jarak di antara mereka secara beransur-ansur meningkat ke arah atas seperti yang ditunjukkan. Tanduk yang dipasang pada penebat porselin. Satu hujung tanduk disambungkan ke baris melalui rintangan dan L gegelung pencekik manakala hujung berkesan dibumikan.

Rintangan R membantu dalam menghadkan semasa susulan kepada nilai kecil. Gegelung pencekik direka bentuk supaya ia menawarkan regangan kecil pada frekuensi kuasa yang normal tetapi regangan sangat tinggi pada frekuensi fana. Oleh itu, pencekik tidak membenarkan fana untuk memasuki radas untuk dilindungi. Jurang antara tanduk begitu diselaraskan bahawa bekalan voltan normal tidak cukup untuk menyebabkan arka merentasi jurang.

Penangkap jurang tanduk tipikal

Di bawah keadaan biasa, jurang bukan menjalankan voltan bekalan biasa iaitu tidak mencukupi untuk memulakan arka antara jurang. Pada berlakunya voltan berlebihan, percikan api-over berlaku merentasi G jurang kecil. Udara panas di sekitar arka dan kesan magnet arka menyebabkan arka untuk perjalanan jurang. Lengkok bergerak secara progresif ke dalam kedudukan 1, 2 dan 3. Pada kedudukan beberapa arka (kedudukan 3), jarak yang mungkin terlalu besar untuk voltan untuk mengekalkan arka; akibatnya, arka dipadamkan. Caj berlebihan dalam talian itu dijalankan melalui penangkap ke bumi.

(3) penangkap Multigap


Rajah menunjukkan penangkap jurang pelbagai. Ia terdiri daripada satu siri silinder logam (biasanya aloi zink) terlindung daripada satu sama lain dan dipisahkan oleh selang kecil jurang udara. Silinder pertama (iaitu A) dalam siri ini disambungkan ke baris dan lainlain alasan melalui rintangan siri.Rintangan siri menghadkan lengkok kuasa. Dengan kemasukan rintangan siri, tahap perlindungan terhadap gelombang perjalanan dikurangkan. Dalam usaha untuk mengatasi kesukaran ini, sebahagian daripada jurang (B ke C dalam Rajah) shunted oleh rintangan. Di bawah keadaan biasa, titik B adalah pada potensi bumi dan voltan bekalan yang normal tidak dapat memecahkan jurang siri. Apabila berlaku voltan lebih, pecahan siri jurang A, B untuk berlaku. Semasa berat selepas runtuhan akan memilih lurus melalui jalan ke bumi melalui jurang shunted B dan C, dan bukannya laluan alternatif melalui rintangan pirau.

Multigap penangkap tipikal

Oleh itu, lonjakan alih, B lengkuk kepada C keluar dan apa-apa kuasa semasa berikutan lonjakan dihadkan oleh kedua-dua rintangan (rintangan pirau dan rintangan siri) yang kini dalam siri. Semasa adalah terlalu kecil untuk mengekalkan lengkok dalam jurang A ke B dan keadaan biasa dipulihkan. Arresters seperti ini boleh digunakan di mana voltan sistem tidak melebihi 33kV.

(4) jenis penangkap Pemecatan


Jenis ini penangkap juga dikenali sebagai 'tiub pelindung' dan biasanya digunakan pada sistem operasi pada voltan sehingga 33kV. Rajah menunjukkan bahagian penting penangkap kilat pengusiran jenis. Ia pada dasarnya terdiri daripada rod jurang AA 'dalam siri dengan jurang yang kedua dan dimasukkan ke dalam tiub gentian. Jurang dalam tiub gentian yang dibentuk oleh dua elektrod. Elektrod atas disambungkan untuk jurang rod dan elektrod yang lebih rendah ke bumi. Satu pengusiran penangkap diletakkan di bawah konduktor setiap baris. Rajah menunjukkan pemasangan penangkap pengusiran secara on-line overhed.

Pengusiran penangkap tipikal

Pada berlakunya voltan berlebihan on-line, siri jurang AA 'membentang dan arka terperangkap antara elektrod dalam tiub. Haba arka vaporizes beberapa gentian dinding tiub yang menyebabkan pengeluaran gas neutral. Dalam masa yang sangat singkat, gas

membina tekanan tinggi dan dibuang melalui elektrod yang lebih rendah, yang berongga. Sebagai gas meninggalkan tiub ganas ia menjalankan jauh udara terion sekitar arka. Ini kesan deionizing umumnya begitu kuat bahawa arka padam pada sifar semasa dan tidak akan ditubuhkan semula.

Kelebihan
1. Mereka tidak sangat mahal. 2. Mereka memperbaiki bentuk arresters jurang rod kerana ia menyekat aliran kekerapan kuasa mengikut arus 3. Mereka boleh mudah dipasang.

Batasan
1. Seorang penangkap pengusiran jenis boleh melakukan hanya bilangan yang terhad operasi semasa operasi setiap beberapa bahan gentian yang digunakan. 2. Jenis ini penangkap tidak boleh dipasang pada kelengkapan tertutup kerana melepaskan gas semasa operasi. 3. Disebabkan volt / pagi ciri penangkap miskin, ia tidak sesuai untuk perlindungan peralatan mahal

(5) jenis penangkap Valve


Arresters jenis injap menggabungkan perintang bukan linear dan meluas digunakan ke atas sistem, yang beroperasi pada voltan tinggi. Rajah menunjukkan pelbagai bahagian penangkap jenis injap. Ia terdiri daripada dua perhimpunan (i) jurang pencucuh siri dan (ii) cakera perintang bukan-linear dalam siri.Unsur-unsur non-linear disambung secara siri dengan jurang pencucuh. Kedua-dua majlis ditempatkan di dalam bekas porselin ketat. Jurang pencucuh adalah pemasangan pelbagai yang terdiri daripada beberapa jurang bibit siri yang serupa dalam. Jurang setiap terdiri daripada dua elektrod dengan jarak jurang tetap. Pengagihan voltan merentasi jurang selaras yang dibangkitkan oleh cara unsur-unsur rintangan tambahan yang dipanggil perintang penggredan merentasi jurang. Jarak jurang siri itu bahawa ia akan menahan voltan litar biasa.Walau bagaimanapun voltan berlebihan akan menyebabkan jurang untuk memecahkan menyebabkan lonjakan semasa ke tanah melalui perintang bukan linear. Cakera perintang non-linear dibuat sebatian tak organik seperti thyrite atau metrosil. Cakera disambung secara siri. Perintang bukan linear mempunyai harta menawarkan rintangan tinggi kepada aliran arus apabila voltan sistem normal dikenakan, tetapi rintangan rendah kepada aliran arus melonjak tinggi. Dalam erti kata lain, rintangan elemen-elemen ini bukan linear menurun dengan peningkatan dalam arus yang melalui mereka dan sebaliknya.

Perintang cakera bukan linear

Di bawah keadaan biasa, sistem voltan normal tidak mencukupi untuk menyebabkan rehat berhimpun jurang udara. Pada berlakunya voltan terlebih, pecahan jurang pencucuh siri berlaku dan arus lonjakan dijalankan ke bumi melalui perintang bukan linear. Sejak magnitud arus lonjakan yang sangat besar, elemen-elemen bukan-linear akan menawarkan rintangan yang sangat rendah untuk laluan lonjakan. Hasilnya adalah bahawa lonjakan pesat akan pergi ke bumi bukan dihantar semula melalui talian. Apabila melonjak ke atas, perintang bukan linear mengandaikan rintangan yang tinggi untuk menghentikan aliran arus.

(6) Silikon karbida arresters


Sebilangan besar silikon karbida arresters adalah masih dalam perkhidmatan. Penangkap silikon karbida mempunyai beberapa ciri-ciri elektrik yang luar biasa. Ia mempunyai rintangan yang sangat tinggi kepada voltan rendah, tetapi rintangan yang sangat rendah kepada voltan tinggi. Apabila kilat atau voltan fana berlaku ke atas sistem, terdapat peningkatan mendadak dalam voltan dan arus. Rintangan silikon karbida memecahkan membenarkan arus dijalankan ke tanah. Selepas lonjakan telah diluluskan, rintangan blok silikon karbida meningkatkan membenarkan operasi normal. Penangkap silikon karbida menggunakan perintang tak linear yang dibuat terikat silikon karbida yang diletakkan di dalam siri dengan jurang. Fungsi jurang tersebut adalah untuk mengasingkan perintang dari voltan sistem biasa keadaan-mantap. Satu kelemahan utama adalah jurang memerlukan reka bentuk yang rumit untuk memastikan konsisten mencetuskan-tahap dan penjelasan positif (resealing) selepas melonjak pas. Ia perlu diiktiraf bahawa sepanjang tempoh operasi bahawa zarah cair tembaga mungkin membentuk yang boleh membawa kepada pengurangan voltan pecahan disebabkan kesan Mengenalpasti. Tempoh masa, jurang penangkap akan memecahkan pada voltan

lebih kecil atau walaupun pada voltan operasi biasa. Sangat berhati-hati perlu diambil arresters yang telah gagal tetapi injap pelega tekanan ke atas tidak beroperasi.

(7) Logam Oksida penangkap:


Penangkap MOV adalah penangkap biasanya dipasang hari ini. Arresters oksida logam tanpa jurang, tidak seperti penangkap SIC. Ini "jurang-kurang" reka bentuk menghilangkan haba yang tinggi yang berkaitan dengan melepaskan pengarkaan. Penangkap MOV mempunyai dua voltan rating: kitar tugas dan maksimum voltan operasi yang berterusan, tidak seperti Silikon karbida yang hanya mempunyai penarafan kitar tugas. A penangkap logam oksida lonjakan menggunakan blok zink-oksida memberikan prestasi yang terbaik, sebagai lonjakan konduksi voltan mula dan berhenti segera pada tahap voltan tepat, dan dengan itu memperbaiki sistem perlindungan. Kegagalan dikurangkan, kerana ada kemungkinan pencemaran tiada jurang udara; tetapi sentiasa ada nilai kecil hadir arus bocor pada frekuensi operasi. Ia adalah penting untuk kakitangan ujian sedar bahawa apabila suatu penangkap oksida logam terputus dari talian bertenaga sedikit caj statik boleh disimpan oleh penangkap. Sebagai langkah keselamatan, penguji perlu memasang alasan yang sementara untuk menunaikan mana-mana tenaga yang tersimpan. Kedudukan kitar tugas: Silikon karbida dan penangkap MOV mempunyai penarafan kitar tugas di KV, yang ditentukan oleh ujian kitar tugas. Kewajipan ujian kitaran penangkap dilakukan dengan menundukkan penangkap voltan rms AC sama rating selama 24 minit. Semasa yang penangkap mestilah mampu menghadapi kilat luruan pada sela masa 1-minit. Voltan maksimum operasi berterusan rating: Kedudukan MCOV biasanya 80-90% daripada Kadar kitaran tugas.
Top

Pemasangan Kilat Arresters


Penangkap tersebut perlu disambungkan ke tanah untuk rintangan yang rendah untuk melaksanakan semasa lonjakan. Penangkap perlu dipasang berhampiran dengan peralatan untuk dilindungi & yang berkaitan dengan plumbum terpendek didapati di kedua-dua baris & sampingan alasan untuk mengurangkan kesan induktif penyambung semasa menunaikan lonjakan besar semasa.
Top

Penyelenggaraan Kilat Arresters


Membersihkan bahagian luar rumah penangkap. Baris perlu dinyahtenagakan sebelum mengendalikan penangkap. Sambungan bumi perlu diperiksa dari semasa ke semasa. Untuk merakam bacaan kaunter lonjakan.

Menerajui selaras dengan kejap pada konduktor garis dan penangkap Menerajui bumi kejap ke terminal penangkap dan tanah.