You are on page 1of 2

Description

Function and application


The signal amplifier DIM SA in combination with 1...10V control units is used for the control of electronic ballasts (ECG) with a 1...10V interface. The following applications are available, depending on the connection (see the connection diagram): Increase in the number of electronic ballasts and luminaires that can be connected to the control unit. Increase in the permissible control line length. Configuration of lighting with daylight-dependent control or daylight- and motion-dependent control (in combination with a suitable light sensor or light and motion sensor).

DIM SA

Connections
The signal amplifier has the following connections: Power supply (A) 110V input (B) 110V output (C)

Signal amplifier Fitting instructions

Installation

Safety instructions
The signal amplifier must only be installed and put into operation by a qualified electrician. The applicable safety regulations and accident prevention regulations must be observed. WARNING! Exposed, live cables. Danger of electric shock! Only work on the signal amplifier when it is de-energised. CAUTION! Destruction of the signal amplifier and other devices through incorrect mounting! Do not connect the control outputs of multiple signal amplifiers in parallel. Only use ballasts with a 1...10V interface. Do not exceed the maximum number of connectable components. Only supply signal amplifiers with an AC operating voltage, especially in networks with UPS systems.

L N PE

Connecting the signal amplifier


H

1...10V

DIM SA

1...10V

~ 230V ~ 50-60Hz

in +

1...10V out

~ 230V / ~ 50Hz +

- 1...10V
. . .

1...10V EVG

DIM SA

1...10V

~ 230V ~ 50-60Hz
. . .

1...10V out

in +

~ 230V / ~ 50Hz +

D  Increase in the number of electronic ballasts and luminaires that can be connected to the control unit(H) Connect the control output of the control unit with the 1...10V inputs of the signal amplifier. Connect the 1...10V outputs of the signal amplifier with the 1...10V control inputs of the electronic ballast. Note: Ensure that the configuration is symmetric:  As far as possible, distribute the number of electronic ballasts evenly among the signal amplifiers.  Connect all electronic ballasts to the signal amplifiers if possible. If some of the electronic ballasts are connected directly to the control unit, dim settings and dim speeds may vary within the system.

- 1...10V
. . .

1...10V EVG

Page 1 of 2

Installation (cont.)
E
L N PE

1...10V

E  Increase in the permissible control line length of the control unit(H) Maximum line length between the distributors of the signal amplifiers: 300m.

DIM SA
max. 300 m

1...10V

~ 230V ~ 50-60Hz

in +

1...10V out

~ 230V / ~ 50Hz +

- 1...10V
. . .

1...10V EVG

DIM SA
max. 300 m

1...10V

~ 230V ~ 50-60Hz
. . .

in -

+ +

1...10V out

~ 230V / ~ 50Hz +

- 1...10V
. . .

1...10V EVG

L N PE

DIM MICO

F  Configuration of lighting with daylight-dependent control Suitable light sensor: DIM MICO

~ 230V / ~ 50Hz +

DIM SA

1...10V

~ 230V ~ 50-60Hz

1...10V out

in +

- 1...10V

1...10V EVG

~ 230V / ~ 50Hz +

- 1...10V
. . .

1...10V EVG

L N PE

N L
DIM MULTI

G  Configuration of lighting with daylight- and motiondependent control Suitable light and motion combination sensor: DIM MULTI

DIM SA

1...10V

~ 230V ~ 50-60Hz

in -

+ +

1...10V 1...10V out

~ 230V / ~ 50Hz +

- 1...10V

1...10V EVG

~ 230V / ~ 50Hz +

- 1...10V
. . .

1...10V EVG

Appendix

Technical data
Operating voltage Supply connection Power consumption Load capacity 230V; 50-60Hz (no DC operation) L, N, PE Approx. 2W 110V input: max. 1.5mA 110V output: max. 100mA or 100 OSRAM 110V ECG Protection class Protection type Operating temperature Dimensions (L x W x H) I IP 20 0C +50C 189 x 30 x 28mm 180mm

IV 2009 DIM_SA_ma0904en_we1.01.indd OSRAM GmbH Kunden Service Center Customer-Service-Center (CSC) Steinerne Furt 62 86167 Augsburg Germany Tel : +49 (0) 1803 677 - 200 (kostenpflichtig / charges apply) Fax.: +49 (0) 1803 677 - 202 www.osram.com www.osram.de

Hole distance for mounting

The EMC requirements to EN 61547, EN 61347-11 and EN 55015 are fulfilled. Conformity with the relevant EU directives is confirmed by the CE symbol.

40083210970958
4008321097095

Page 2 of 2