Docente: Ing.

Flix Enrique Zamarrn Gaona


Alumno: Genaro Macias Feliciano
Matricula: 1128689
HORA: V1 SABATINO

A.- CARGA CALENTADOR DE AIRE


Pnom =5kw
F.P= 1.0pu
Faces= 1F-1N (2 hilos)
Vnom= 277vca

C.-TABLERO DE DISTRIBUCIN Y ALUMBRADO


Pnom= 8Kw
F.P= 0.9 (-)
Faces= 4 hilos (A, B, C, N)

B.-MOTORES DE FUERZA
5nom= 10kva
F.P= 0.80 (-) pu en atras
Vnom= 480vca = 277
Faces= 3 (A, B, C-3hilos)

D.- SISTEMA P NEUMTICO


Pnom= 10 Kw
F.P= 0.9 (-)
Face= 2 (2 hilos F1, F2)
Vop= 480vca

TRANSFORMADOR
= 1.1 [FU1xKVA1+FU2xKVA2+FU3xKVA3+FU4xKVA4+FUNxKVAN]
= 1.1 [1.0

+ 0.7

+ 1.0

= 1.1 (5KVA + 7KVA + 8.88KVA + 11.11KVA)


= 1.1 (31.99KVA)
= 33.198KVA) 45KVA

CORRIENTE EN ALTA
IHTr=

IHTr = 1.88Amp

CORRIENTE EN BAJA
IHTr=
IHTr = 55Amp

=
3x70Amp

APARTA RAYOS
=

3Amp =

= 8KV

CARGAS
ICFN =

ICFF 2f =

IC 3f =
ICB =
ICC =

= 18.05Amp
= 23.14 Amp
= 4.334 Amp

=
=
= 11Amp

= 9Amp

TCPD

(18)

(24)

(30)

(36)

(48)

(72)

TCPD

(12)
A

TC

Acond EF = 0.4 A
A

C#12

= 0.78in2
TC

= 503mm2

= 0.4 x 503mm2 = 201mm2

= 3.31mm2 =

= 17.34

12 calibre del cable


#

= 11

40%
1in = 25mm2
1in2 = (25mm) 2 = 645mm2

Dext=4.70 mm

(96)

(in)

FACTOR DE CORRECCIN DE TEMPERATURA (FCT)


Cal#12, CU, 75C

Factor de Correccin Agrupamiento (FCA)


Tubos
conduit

INOM COREGIDO = FCT (INOM 30)


INOMC = 0.58 (25)
INOMC = 15A

#Conductores
4-6
7-24
24-42
43

FCA
0.8
0.7
0.6
0.5

CAL#10
75C,
35A

INOM COREGIDO = FCT (INOM 30)


INOMC = 0.8 (35A)
INOMC = 28A