GE N E RA L N O TE S

1. This drawing to be read in conjuction with all relevant Architect's Drawings and Engineer's Drawings 2. Dimensions must not be Scaled or Assumed, After Notification, Discrepancies or Missing Dimensions will be corrected in writing by the Engineer
3. All Elements of the Building to be constructed within the tolerances laid down in SABS 0155 "Accuracy in Building" with the following Clasification:

Foundation Grade II Slabs and Columns Grade II FOUNDATION NOTES 1. Found below loose top soil horizon in medium dense clayey Gravel or Firm to Stiff Sandy Clay at a Bearing Pressure of 150 KPa 2. Levels shown are Approximate and must be verified on site. All Foundation excavations ate to be approved by the Enginner and cleaned prior to pouring 3. All strip foundation to be 600 x 250 deep U.O.N 4. All Excavations to have 50mm minimum Blinding Layer 5. All cavities to cavity brick walls to be filled with 10MPa Mass Concrete below D.P.C Level
CO N C RE TE N O TE S 1. A ll con crete w ork is to b e d one in a ccorda nce w ith S A B S 12 0 0G an d Project S pecifica tion 2. CO N C RE TE S TR EN G TH S

Element

Concr. Strength/ Aggregate Size (Mpa/mm) 10/38 30/19 30/19 30/19 30/19

Blinding Foundations Surface Beds Columns Beams

Cover (mm) UON on Schedule 50 40 35 30

Max. Water/ Cement Ratio 0.53 0.53 0.53 0.53

3. Finish to concrete to be as follows

A
150x65x20x2.5 PURLIN

Surface Bed Slab Columns

Top Soffit Square Round

150x65x20x2.5 PURLIN

Beams

Powerfloat Rough Smooth Rough Smooth Smooth

4. Where brickwork is built into concrete structure, shot fire hoop straps onto structure at every 5th brick course 5. Legend:

150x65x20x2.5 PURLIN

150x65x20x2.5 PURLIN

u/s denotes U/S denotes D/D denotes UON denotes COS denotes

Underside Upstand Beam Downstand Beam Unless Otherwise Noted Check On Site

Beam size shown as Width x Depth


6. Loadings

150x65x20x2.5 PURLIN

Finishes Partitions Imposed


150x65x20x2.5 PURLIN

Utilities 2.0 kN/m 2.0 kN/m 2.0 kN/m

Office 1.5 kN/m 1.5 kN/m 1.5 kN/m

Office Roof 2.0 kN/m 2.0 kN/m 2.0 kN/m

7. Test cub es a re to be ta ke n ev ery 50 m or for e a ch con crete pour (W hiche ve r is the L ea st) or a s req uired by E ngin e er

150x65x20x2.5 PURLIN

8. A ll ca vitie s to be brick w a lls to be filled w ith 1 0 M Pa m a ss Con crete b elow D .P .C Le ve l

C
150x65x20x2.5 PURLIN 50x50x3mm SAG BARS 50x50x3mm SAG BARS 50x50x3mm SAG BARS 50x50x3mm SAG BARS

REN ca
D EVELOPERS
C iv il, S tru ctu ral & Electrica l E ngin eers Architect

150x65x20x2.5 PURLIN

150x65x20x2.5 PURLIN

150x65x20x2.5 PURLIN

150x65x20x2.5 PURLIN

150x65x20x2.5 PURLIN

Clien t
10 11
12 13 14 15 16 17

150x65x20x2.5 PURLIN

150x65x20x2.5 PURLIN

E1

150x65x20x2.5 PURLIN

133.182mm

F
150x65x20x2.5 PURLIN

150x65x20x2.5 PURLIN

150x65x20x2.5 PURLIN

PRO JECT G
150x65x20x2.5 PURLIN

X ANO M A S H O PPIN G & O FFIC E C O M PLE X


ROOF OVER SUPERMARKET
O N ER VE N 31 3 5, 3 1 3 6 11 7 TSO LO M HLO N TLO M U N ICIPA L A REA E A STE RN CA PE
DRAWING TITLE

150x65x20x2.5 PURLIN

150x65x20x2.5 PURLIN

150x65x20x2.5 PURLIN

RO O F A: LAYO U T
150x65x20x2.5 PURLIN

150x65x20x2.5 PURLIN 406 X 140 X 39 CASTELLETED RAFTER ( GRADE 350W) 406 X 140 X 39 CASTELLETED RAFTER ( GRADE 350W) 406 X 140 X 39 CASTELLETED RAFTER ( GRADE 350W) 406 X 140 X 39 CASTELLETED RAFTER ( GRADE 350W) 406 X 140 X 39 CASTELLETED RAFTER ( GRADE 350W) 406 X 140 X 39 CASTELLETED RAFTER ( GRADE 350W)

A,B,C.../ : BEFORE TENDER 0 Z / : TENDER DRAWING / : AS BUILT 1,2,3...../ : AFTER TENDER

/A : BY CLIENT /B : BY ARCHITECT /C : BY MECHANICAL OR ELECTRICAL /D : BY RENCA DEVELOPERS /E : BY OTHER ( )

150x65x20x2.5 PURLIN

REVISION No
60 x6 0x 4m m G AN L EE LE

DESCRIPTION

DATE

60 x6 0x 4m m

ST EE LA NG

LE

x6 60

0x

m 4m

EE ST

LE NG A L

150x65x20x2.5 PURLIN

ST EE LA

150x65x20x2.5 PURLIN

NG LE

mm x4 0 x6 60

ST

150x65x20x2.5 PURLIN 150x65x20x2.5 PURLIN

Checked

Date

dm
Designed

2013-04-24
Date

rn
Drawn

2013-04-24
Date

rn
Scale

2013-04-24
File No.

As Shown

1304-01
Rev.

ROOF A : LAYOUT
SCALE 1:100

Drawing Number

PROPOSED XANOMA SHOPPING AND OFFICE COMPLEX | ON ERVEN 3135, 3136 AND 117 TSOLO | MHLONTLO MUNICIPAL AREA | EASTERN CAPE

EC-344