Circular Silencer
Rigid and flexible construction
Type CA CB CF CS

TROX GmbH
Heinrich-Trox-Platz
D-47504 Neukirchen-Vluyn

Telephone +49/28 45/2 02-0


Telefax
+49/28 45/2 02-2 65
e-mail trox@trox.de
www.troxtechnik.com

Contents Description CA CB
Description CA CB
Description CF CS
Construction Dimensions CA CB
Construction Dimensions CF CS
Insertion loss CA
Insertion loss CB

2
3
4
5
6
7

Type CA

TROX circular silencers type CA CB CF CS are intended for


use in room air conditioning systems.
In air distribution systems they can be used to attenuate fan
noise and to reduce the air-regenerated noise of air terminal
units.
To avoid sound transmission through ventilation ducting
between adjacent rooms they can be integrated into the
duct system as so called cross talk silencers.
Further, current information on application, selection as well as
silencers available can be found in the Technical Documents
download area of our website.
Also available on the internet is the on-line design programme
silencers for the design and selection of our units.

Special constructions
Due to the technical co-ordination necessary, special constructions are only available on request.

Air-regenerated noise Pressure differential CB


Insertion loss CF CS
Order details CA CB
Order details CF CS

8
10
11
12

Type CB

Circular silencer Type CA


The outer casing and perforated inner duct of circular silencers
type CA are galvanised sheet steel. The non-combustible
acoustic material is available in insulation thicknesses of 50 mm
or 100 mm.
Inlet and outlet connection options available:
Spigots with groove for lip seal
Spigots with lip seal
Flanges according to DIN EN 12220

Circular silencer Type CB


Type CB attenuators are the same as the type CA models,
but have an additional sound-absorbing pod for higher insertion
loss.
The sound-absorbing pod fitted in the centre has a galvanised,
perforated sheet covering and a coned end to reduce pressure
drop.

Description CF CS

Type CF

Type CS

Circular silencer Type CS

Circular silencer Type CF

The outer casing and perforated inner duct of circular silencers


Type CS are aluminium.

The circular silencer Type CF is the flexible construction of Type


CS.

The non-combustible acoustic material is available in insulation


thicknesses of 25 mm or 50 mm.

The circular silencer with a high degree of flexibility means that


they can be fitted in complicated duct systems and in restricted
spaces.

Inlet and outlet connection options available:


Spigots with groove for lip seal
Spigots with lip seal
Socket type spigots
Spigots with raised edges for quick locking system

Construction Dimensions CA CB
Construction

Constructional features

The table below shows weights and the sizes of silencers


available.

Circular silencer in rigid construction


Insertion loss tested according to DIN EN ISO 7235
Casing air leakage complies with DIN EN 1751, class A
Construction with spigot connections suitable for circular
connecting ducts to DIN EN 1506 or DIN EN 13180 with
groove for lip seal (if lip seals are required, these will be
factory fitted)
Flange construction with flange drilling to DIN 12220

Materials
Casing, perforated inner duct and pod (CB only) galvanised
sheet steel.
Lining is mineral wool conforming to DIN 4102, fire rating
class A2, with RAL quality mark RAL-GZ 388, bio-degradable
as defined by TRGS 905 and EU directive 97/69/EG
Mineral wool faced with fibreglass as protection against
erosion suitable for air velocities up to 20 m/s

Type CA CB (Type CB shown)


Construction with plug type spigots (standard)

Construction with
lip seal (VD2)

Flange construction (VF) 1)


s

d

k

d

D

9.5

60

Insulation thickness 50 mm:  D =  d + 100 mm


Insulation thickness 100 mm:  D =  d + 200 mm

Casing air leakage complies


with DIN EN 1751, class A

1) Reduced length for flange construction 10 mm (VF1) or 20 mm (VF2)

22
28
34

6
7
9
9
11
14
18

11
13
16
17
20
25
30

1500

7
9
12
13
16
20
25

1000

4
5
7
7
9
12
15

500

100
125
160
200
250
315
400
450
500
560
630
710
800
900
1000

1500

4
4
6
6
6
8
8
8
8
12
12
12
16
16
16

1000

25 x 3
25 x 3
25 x 4
25 x 4
25 x 4
30 x 4
30 x 4
30 x 4
30 x 4
35 x 4
35 x 4
35 x 4
35 x 4
35 x 4
35 x 4

CB100
L in mm

500

132
157
192
233
283
352
438
488
538
600
670
750
840
940
1041

CB050
L in mm
1500

99
124
159
199
249
314
399
448
498
558
628
708
798
898
998

No. of
holes

1000

bxs
in mm

500

k
in mm

CA100
L in mm
1500

d
in mm

CA050
L in mm
1000

Plain flange to
DIN EN 12220

500

100
125
160
200
250
315
400
450
500
560
630
710
800
900
1000

Weight in kg
Nominal
size

Nominal
size

Dimensions in mm

29
35
42
46
52
55
62
68
76

10
13
16

17
21
27

24
30
38

12
15
19
21
22
26
30
33
37
40
45

21
26
32
35
38
44
49
55
61
68
75

31
37
46
50
56
62
69
77
86
95
106

Construction Dimensions CF CS
Construction

Constructional features

The table below shows weights and the sizes of silencers


available. (Type CS max length: 1500 mm).

Circular silencer in rigid (CS) or flexible (CF) construction


Insertion loss tested according to DIN EN ISO 7235
Casing air leakage complies with DIN EN 1751, class A.
Construction with spigot connections suitable for circular
connecting ducts to DIN EN 1506 or DIN EN 13180 with
groove for lip seal (if lip seals are required, these will be factory fitted)

Materials
Outer casing and inner duct are aluminium
Lining is mineral wool conforming to DIN 4102, fire rating
class A2, with RAL quality mark RAL-GZ 388, bio-degradable
as defined by TRGS 905 and EU directive 97/69/EG
Mineral wool faced with fibreglass as protection against
erosion suitable for air velocities up to 20 m/s

Type CF CS (Type CF shown)


Construction with lip seal (VD2)

75

D

da

Construction with plug type spigots (standard)

75 1)

55

Construction with raised edges for quick locking system (BK2)

 di

Construction with socket type spigots (AS2)

55

Casing air leakage complies with DIN EN 1751, class A

1) 69 mm for construction with raised edges

Dimensions in mm

Weight in kg

1000

1500

2000

500

1000

1500

500

1000

80
100
125
160
200
250
315
400

0.6
0.8
0.9
1.1
1.3
1.6
1.9
2.5

1.0
1.3
1.5
1.8
2.2
2.7
3.2
4.1

1.5
1.7
2.1
2.5
3.0
3.7
4.5
5.6

1.9
2.2
2.7
3.2
3.9
4.7
5.7
7.2

0.9
1.1
1.2
1.4
1.7
2.1
2.4
3.1

1.5
1.8
2.0
2.4
2.9
3.5
4.0
5.1

2.2
2.5
2.9
3.3
4.0
4.8
5.6
7.1

2.8
3.2
3.7
4.3
5.1
6.2
7.2
9.1

1.0
1.2
1.4
1.6
2.0
2.5
2.9
3.7

1.8
2.1
2.5
2.9
3.6
4.4
5.2
6.6

2.6
3.1
3.7
4.2
5.2
6.2
7.5
9.4

1.4
1.6
1.9
2.1
2.6
3.1
3.5
4.5

2.6 3.7
2.9 4.2
3.3 4.7
3.8 5.4
4.6 6.5
5.5 7.8
6.2 8.9
7.9 11.3

1500

500

191
211
235
271
311
366
426
511

2000

135
160
191
221
261
311
376
461

79
99
124
159
199
249
314
399

CS050
L in mm

1500

80
100
125
160
200
250
315
400

in mm

CS025
L in mm

1000

in mm

50 mm
D
in mm

di

CF050
L in mm

500

80
100
125
160
200
250
315
400

25 mm
D
in mm

da

CF025
L in mm

Nominal
size

Nominal
size

Insulation thickness

Insertion Loss CA
Insertion loss De

Example

From the test conditions described in DIN EN ISO 7235, the


duct/reverberation chamber method was chosen. This method
involves an empty duct being exposed to a noise, the third
octave levels of which are measured in the connecting reverberation chamber under defined conditions. The silencer to be
tested is then inserted in the empty duct and the measurement
repeated. The difference between the two measurements is the
insertion loss De

Given:

The octave values are calculated from the third octave measurements.
Laboratory measurements exceeding 50 dB are indicated as
50 dB, in line with common practice.

Pressure drop; Air-regenerated noise

TVR nominal size 315 for supply air


V = 410 l/s or 1480 m3/h
Total pressure differential: 200 Pa
Required sound pressure level in the room 45 dB(A)

Calculation procedure
fm in Hz

63 125 250 500

1k

2k

4k 8k

TVR nominal size 315 *)


to ISO 5135-1999 LW in dB

68

55

CA050 / L = 1500 mm De in dB
End reflection attenuation
nominal size 315 in dB
Room attenuation in dB

Pressure drop and air-regenerated noise do not vary significantly from the values of the air flowing in circular ducts.

A-weighting

66

55

52

56

17

35

17

63

52

38

17

39

46

39

12

23

35

35

29

12

35

42

33

Sound pressure level of air-regenerated noise LpA = 45 dB(A)


*) Data from leaflet 5/3/EN/...

Insertion loss De, oct. in dB


Type CA050 (without pod); Insulation thickness = 50 mm
Nominal
size
100
125
160
200
250
315
400

Nominal
size
100
125
160
200
250
315
400

Nominal
size
250
315
400

63

125

3
3
2
1
1
1
1

5
4
3
2
2
1
1

63

125

4
4
3
2
2
1
1

9
7
5
4
3
2
2

63

125

2
2
1

4
3
2

Length L = 500 mm
fm in Hz
250 500
1k
2k
8
7
6
5
4
3
3

14
12
10
9
8
7
6

23
21
18
16
14
12
11

30
23
17
13
10
7
6

Length L = 1000 mm
fm in Hz
250 500
1k
2k
15
12
9
8
6
5
4

27
23
19
16
14
12
10

42
38
34
31
28
25
22

50
42
30
22
17
13
10

Length L = 1500 mm
fm in Hz
250 500
1k
2k
8
7
6

19
17
14

39
35
31

23
17
13

Type CA100 (without pod); Insulation thickness = 100 mm

4k

8k

18
12
8
5
3
2
1

13
10
8
6
4
3
2

4k

8k

43
29
18
12
8
5
3

25
20
15
11
9
6
5

4k

8k

13
9
6

12
9
7

Nominal
size
100
125
160
200
250
315
400

Nominal
size
100
125
160
200
250
315
400
450
500

Nominal
size
250
315
400
450
500
560
630
710
800

63

125

4
4
3
3
2
2
1

9
7
6
5
4
3
3

63

125

5
5
5
4
3
3
2
2
2

17
14
11
9
8
6
5
5
4

63

125

4
3
3
2
2
2
2
2
2

11
9
7
6
6
5
5
5
4

Length L = 500 mm
fm in Hz
250 500
1k
2k

4k

8k

33
26
20
16
13
10
8

26
19
13
9
6
4
3

14
11
8
7
5
4
3

Length L = 1000 mm
fm in Hz
250 500
1k
2k

12
10
9
8
7
6
6

18
17
15
15
14
13
12

35
31
28
25
21
18
17

4k

8k

50
44
33
26
21
16
12
11
10

47
33
22
16
11
8
5
4
4

25
20
15
12
9
7
5
5
4

Length L = 1500 mm
fm in Hz
250 500
1k
2k

4k

8k

15
10
7
6
5
4
4
3
2

12
9
7
6
6
5
4
4
3

24
21
18
16
14
12
11
10
10

21
18
16
15
14
13
12
11
11

48

66

26 16

Corrected level

59

35
32
30
28
26
24
23
22
21

37
34
32
31
30
29
28
27
26

50
48
42
38
33
29
25
23
22

41
35
31
29
27
25
23
22
20

27
21
16
14
13
11
10
9
8

Insertion Loss CB
Nomenclature
fm

in Hz: Octave band centre frequency

in mm: Length

LW

in dB: Sound power level of the air-regenerated noise

L WA in dB(A): A-weighted sound power level of air-regenerated


noise
L pA

in dB(A): A-weighted sound pressure level of


air-regenerated noise

Lp

in dB: Sound pressure level

De, oct.

in dB: Insertion loss

v tot

in m/s: Air velocity based on cross-sectional area

 pg

in Pa: Total pressure differential

All sound power levels are based on 1 pW, all sound pressure
levels on 20 Pa.

Insertion loss De, oct. in dB


Type CB050 (with pod); Insulation thickness = 50 mm
Nominal
size
250
315
400

Nominal
size
250
315
400

Nominal
size
250
315
400

63

125

1
1
1

3
3
2

63

125

3
2
2

5
5
4

63

125

5
5
5

7
6
5

Length L = 500 mm
fm in Hz
250 500
1k
2k
6
5
5

11
10
8

17
15
13

20
17
15

Length L = 1000 mm
fm in Hz
250 500
1k
2k
9
8
6

18
15
12

42
40
38

48
42
35

Length L = 1500 mm
fm in Hz
250 500
1k
2k
10
8
7

23
19
15

50
50
50

50
50
50

Type CB100 (with pod); Insulation thickness = 100 mm

4k

8k

23
18
14

23
18
13

4k

8k

47
36
28

35
27
20

4k

8k

50
50
39

44
34
25

Nominal
size
250
315
400
450
500
560
630
710
800
900
1000

Nominal
size
250
315
400
450
500
560
630
710
800
900
1000

Nominal
size
250
315
400
450
500
560
630
710
800
900
1000

63

125

2
2
1
1
1
1
1
1
1
1
1

5
5
4
4
3
3
3
3
2
2
2

63

125

5
4
3
3
2
2
2
2
2
2
2

10
9
7
7
6
6
5
5
5
4
4

63

125

7
7
6
5
5
4
4
4
3
3
3

14
12
10
9
9
8
8
7
6
6
6

Length L = 500 mm
fm in Hz
250 500
1k
2k

4k

8k

23
20
17
16
15
14
13
12
11
10
10

26
21
16
14
13
11
10
9
8
7
6

24
18
14
12
11
10
9
8
7
6
5

Length L = 1000 mm
fm in Hz
250 500
1k
2k

10
9
8
7
7
6
6
6
5
5
5

17
16
14
14
13
13
12
12
11
10
10

24
21
18
16
16
15
15
14
13
13
12

4k

8k

50
45
38
35
33
31
29
27
25
23
22

50
39
29
26
24
21
19
17
14
13
12

36
27
21
18
17
15
13
12
10
9
8

Length L = 1500 mm
fm in Hz
250 500
1k
2k

4k

8k

50
50
40
36
33
29
26
23
20
17
16

44
34
26
23
21
19
16
14
12
11
10

17
15
13
12
12
11
11
10
9
9
8

22
20
17
16
16
15
14
13
13
12
11

30
27
25
24
23
22
21
20
19
18
17

41
37
33
31
30
30
29
28
26
24
23

47
44
40
39
38
36
34
33
31
30
29

50
50
50
50
50
50
50
50
49
47
45

50
50
50
50
50
48
44
41
37
34
33

Air-regenerated Noise Pressure Differential CB


Air-regenerated noise

Pressure differential

The sound power levels stated for regenerated noise in the


silencer were measured in the TROX laboratory to
DIN EN ISO 7235 and evaluated to ISO 5135.

The pressure losses stated were calculated in the TROX


laboratory by measuring the difference in pressure between
entering and exiting the silencer, with the unit installed in
smooth straight ducting.

The evaluation allows for the end reflection losses from the
connection duct when the sound exits into the reverberation
chamber.

The values apply to an silencer length of 1000 mm.


See table below for correction factors for other lengths.

The values listed below show the actual regenerated noise in


duct.
To calculate the sound power level radiating into the space, the
end reflection from the duct connecting to the space or the end
reflection from the grille or diffuser must be subtracted from the
listed values.

Pressure drop-correction factor


for length  1000 mm
Nominal size

Length
in mm

250

315

400

450

500

560

500

0.72

0.76

0.80

0.82

0.82

0.83

1500

1.28

1.24

1.20

1.18

1.18

1.17

Air-regenerated noise Pressure differential

34
39
44
47
51
53
56
58
60

in l/s
306
382
459
535
612
688
765
841
917

in m3/h in m/s
1101
1376
1651
1927
2202
2477
2752
3028
3303

4
5
6
7
8
9
10
11
12

<15
<15
<15
19
24
27
31
34
37

36
41
45
49
52
55
58
60
62

in l/s
628
785
942
1099
1255
1412
1569
1726
1883

vtot

in m3/h in m/s
2260
2825
3390
3955
4520
5085
5649
6214
6779

4
5
6
7
8
9
10
11
12

40
44
48
51
54
56
59
61
62

36
41
45
49
51
54
56
58
60

30
36
40
44
48
50
53
55
57

21
28
33
38
41
45
47
50
52

<15
18
24
29
33
37
40
43
45

<15
<15
<15
19
23
27
30
33
36

36
41
46
50
53
56
58
61
63

<15
18
24
29
33
36
39
42
45

<15
<15
<15
18
23
26
30
33
36

36
42
46
50
53
56
59
61
63

46
51
55
58
62
65
67
70
72

43
48
52
55
58
60
63
65
67

41
46
49
53
55
58
60
62
64

36
42
46
49
53
55
57
59
61

29
36
40
45
48
51
53
56
58

20
27
33
37
41
44
47
50
52

<15
17
23
28
32
36
39
42
45

<15
<15
<15
18
22
26
29
32
35

37
42
46
50
53
56
59
61
63

LW in dB
fm in Hz

pg

in l/s

in m3/h in m/s

in Pa

975
1218
1462
1706
1949
2193
2437
2680
2924

3509
4386
5263
6140
7018
7895
8772
9649
10527

13
21
30
41
53
67
83
101
120

4
5
6
7
8
9
10
11
12

LWA in dB(A)

21
28
33
38
41
45
47
50
52

8000

29
36
40
44
48
51
53
55
57

4000

36
41
46
49
52
55
57
59
61

2000

40
45
49
52
55
57
59
61
63

vtot

1000

8000

LWA in dB(A)

43
47
51
54
57
60
62
64
66

.
V

500

4000

14
22
31
42
55
70
86
104
124

14
22
32
44
57
72
89
108
128

250

2000

45
50
54
58
61
65
67
70
73

LW in dB
fm in Hz

in Pa

42
47
50
54
57
59
62
64
66

in Pa

63

1000

4
5
6
7
8
9
10
11
12

45
50
54
58
61
65
68
70
73

LW in dB
fm in Hz

pg

Nominal size 560 mm

500

2794
3492
4190
4889
5587
6286
6984
7682
8381

35
40
45
48
52
54
57
59
61

LWA in dB(A)

<15
19
25
29
33
37
40
43
45

250

in m3/h in m/s

<15
<15
16
21
25
29
32
35
37

8000

22
28
33
38
41
45
47
50
52

63
776
970
1164
1358
1552
1746
1940
2134
2328

<15
20
25
30
34
37
40
43
45

4000

30
36
40
44
47
50
52
55
56

pg

22
29
34
38
41
44
47
49
51

2000

35
40
45
48
51
53
55
57
59

125

in l/s

vtot

29
35
39
43
46
49
51
53
55

1000

39
44
47
51
53
56
58
60
62

.
V

Nominal size 500 mm


.
V

34
39
43
46
49
52
54
56
58

500

8000

LWA in dB(A)

15
23
33
46
60
75
93
113
134

37
42
46
49
52
54
56
58
60

250

4000

41
46
50
53
56
59
61
64
66

in Pa

40
44
48
52
55
58
61
63
65

63

2000

44
49
54
58
61
65
68
71
74

LW in dB
fm in Hz

pg

16
26
37
50
66
83
102
124
147

125

1000

4
5
6
7
8
9
10
11
12

500

1783
2228
2674
3119
3565
4011
4456
4902
5348

250

in m3/h in m/s

495
619
743
867
990
1114
1238
1362
1485

63
in l/s

vtot

43
49
54
58
62
66
69
73
76

in Pa

Nominal size 450 mm

125

Nominal size 400 mm


.
V

LWA in dB(A)

<15
<15
17
21
26
29
32
35
38

8000

<15
21
26
30
34
37
40
43
45

4000

22
28
33
37
41
44
46
48
50

2000

29
34
38
42
45
47
50
52
53

1000

33
38
42
45
48
50
52
54
56

LW in dB
fm in Hz

pg

125

18
28
41
56
73
92
114
138
164

500

36
40
44
47
50
53
55
57
59

in Pa

vtot

250

8000

LWA in dB(A)

38
43
47
51
54
57
60
63
66

pg

.
V

63

4000

42
48
54
59
63
67
71
75
79

LW in dB
fm in Hz

125

2000

4
5
6
7
8
9
10
11
12

1000

690
862
1035
1207
1380
1552
1725
1897
2070

500

in m3/h in m/s

192
240
287
335
383
431
479
527
575

250

in l/s

vtot

Nominal size 315 mm

63

.
V

125

Nominal size 250 mm

Air-regenerated Noise Pressure Differential CB

Pressure drop-correction factor


for length  1000 mm
Nominal size

Length
in mm

630

710

800

900

1000

500

0.85

0.86

0.88

0.89

0.89

1500

1.15

1.14

1.12

1.11

1.11

Air-regenerated noise Pressure differential

29
35
40
45
48
51
54
56
58

20
27
32
37
41
44
47
50
52

<15
16
22
27
32
35
39
41
44

<15
<15
<15
17
21
25
28
31
34

37
42
47
50
54
57
59
61
64

1570
1963
2355
2748
3141
3533
3926
4318
4711

in Pa

5653
7066
8480
9893
11306
12720
14133
15546
16959

12
20
28
38
50
63
78
94
112

4
5
6
7
8
9
10
11
12

<15
16
22
27
31
35
38
41
44

<15
<15
<15
16
20
24
28
31
34

37
43
47
51
54
57
59
62
64

28
35
40
44
48
51
54
56
59

18
25
31
36
40
43
47
49
52

<15
15
21
26
30
34
37
40
43

<15
<15
<15
15
20
23
27
30
33

37
43
47
51
54
57
60
62
64

2528
3160
3792
4424
5056
5687
6319
6951
7583

in Pa

9100
11375
13650
15925
18200
20475
22750
25025
27300

12
18
27
36
47
60
74
90
107

4
5
6
7
8
9
10
11
12

36
42
47
51
54
57
59
61
63

28
34
40
44
48
51
54
56
59

18
25
30
35
39
43
46
49
51

<15
<15
20
25
29
33
37
40
42

<15
<15
<15
<15
19
23
26
29
32

38
43
48
51
54
57
60
62
64

LW in dB
fm in Hz

pg

in m3/h in m/s

LWA in dB(A)

36
42
47
50
54
56
59
61
63

8000

LWA in dB(A)

42
47
51
54
57
60
62
64
66

4000

8000

45
50
54
57
60
62
64
66
68

vtot

2000

4000

12
19
27
37
49
61
76
92
109

4
5
6
7
8
9
10
11
12

19
26
32
36
40
44
47
50
52

500

2000

in Pa

7184
8980
10776
12572
14368
16164
17960
19756
21552

29
35
40
44
48
51
54
56
58

1000

1000

in m3/h in m/s

1996
2494
2993
3492
3991
4490
4989
5488
5987

.
V

250

500

in l/s

41
47
51
54
57
59
61
63
65

125

250

in l/s

48
52
56
60
62
65
68
70
72

LW in dB
fm in Hz

pg

45
49
53
56
59
62
64
66
68

63

125

vtot

47
52
56
59
62
65
67
70
72

Nominal size 900 mm

63

Nominal size 800 mm


.
V

36
42
46
50
53
56
58
61
62

LW in dB
fm in Hz

pg

in m3/h in m/s

LWA in dB(A)

36
42
46
50
53
56
58
60
62

8000

41
46
50
53
56
58
61
63
64

4000

LWA in dB(A)

13
20
29
39
52
65
81
97
116

4
5
6
7
8
9
10
11
12

2000

8000

in Pa

4446
5558
6669
7781
8892
10004
11115
12227
13339

500

4000

in m3/h in m/s

1235
1544
1853
2161
2470
2779
3088
3396
3705

1000

2000

in l/s

vtot

250

1000

44
49
52
56
58
61
63
65
67

pg

.
V

125

500

in l/s

47
51
55
59
62
65
67
70
72

LW in dB
fm in Hz

63

250

vtot

Nominal size 710 mm

125

.
V

63

Nominal size 630 mm

48
53
57
60
63
66
68
70
72

46
51
54
58
60
63
65
67
69

42
47
51
55
58
60
63
65
66

250

500

1000

2000

4000

8000

LWA in dB(A)

49
54
57
61
63
66
68
70
72

46
51
55
58
61
63
65
67
69

42
47
52
55
58
61
63
65
67

36
42
47
51
54
57
59
62
64

27
34
39
44
48
51
54
56
59

17
24
30
35
39
42
46
49
51

<15
<15
19
24
29
33
36
39
42

<15
<15
<15
<15
18
22
25
29
31

38
43
48
51
55
57
60
62
64

LW in dB
fm in Hz

pg

in l/s

in m3/h in m/s

in Pa

3123
3903
4684
5465
6246
7026
7807
8588
9368

11242
14052
16863
19673
22484
25294
28105
30915
33726

12
18
26
36
46
59
72
88
104

4
5
6
7
8
9
10
11
12

125

vtot

63

Nominal size 1000 mm


.
V

Insertion Loss CF CS
Insertion loss De

Pressure drop; Air-regenerated noise

From the test conditions described in DIN EN ISO 7235, the


duct/reverberation chamber method was chosen. This method
involves an empty duct being exposed to a noise, the third
octave levels of which are measured in the connecting reverberation chamber under defined conditions. The silencer to be
tested is then inserted in the empty duct and the measurement
repeated. The difference between the two measurements is the
insertion loss De

Pressure drop and air-regenerated noise do not vary significantly from the values of the air flowing in circular ducts.

The octave values are calculated from the third octave measurements.
Laboratory measurements exceeding 50 dB are indicated as
50 dB, in line with common practice.

Insertion loss De, oct. in dB


Type CF025.../CS025; Insulation thickness = 25 mm
Nominal
size
80
100
125
160
200
250
315
400

Nominal
size
80
100
125
160
200
250
315
400

Nominal
size
80
100
125
160
200
250
315
400

Nominal
size
80
100
125
160
200
250
315
400

10

63

125

1
1
1
1
1
0
0
0

2
1
1
1
1
1
1
0

63

125

3
2
2
1
1
1
0
0

5
3
3
1
1
1
1
1

63

125

3
2
2
2
2
1
1
1

5
4
3
2
2
2
2
1

63
3
2
2
2
1
1
1
1

Length L = 500 mm
fm in Hz
250 500
1k
2k
4
4
3
2
2
2
1
1

9
8
8
5
5
5
4
3

20
17
15
14
14
13
9
6

16
14
11
10
9
8
7
5

Length L = 1000 mm
fm in Hz
250 500
1k
2k
10
8
7
4
3
3
3
3

21
17
17
12
11
11
9
8

44
44
43
40
35
30
21
16

46
34
30
27
22
19
10
8

Length L = 1500 mm
fm in Hz
250 500
1k
2k
13
12
10
6
5
5
4
4

28
24
22
16
15
15
12
10

47
47
45
42
41
38
27
23

48
41
34
30
27
25
19
17

Type CF050 .../CS 050; Insulation thickness = 50 mm

4k

8k

15
12
9
8
6
5
4
3

10
9
7
6
5
4
3
3

4k

8k

37
28
24
20
16
12
12
8

23
21
17
16
13
10
8
7

4k

8k

44
34
28
25
19
14
13
11

31
26
20
19
15
11
10
8

Length L = 2000 mm (only type CF)


fm in Hz
125 250 500
1k
2k
4k
6
5
4
3
3
3
2
2

15
15
12
8
7
6
6
4

35
30
28
20
19
17
14
10

50
50
48
47
47
43
32
23

50
49
37
34
32
30
27
22

50
41
32
28
20
15
13
11

8k
39
31
23
21
16
13
11
9

Nominal
size
80
100
125
160
200
250
315
400

Nominal
size
80
100
125
160
200
250
315
400

Nominal
size
80
100
125
160
200
250
315
400

Nominal
size
80
100
125
160
200
250
315
400

63

125

4
3
2
2
1
1
1
1

5
4
3
2
2
2
1
1

63

125

8
7
5
4
3
2
1
0

14
10
7
5
5
4
4
4

8k

16
12
11
8
6
5
4
4

12
10
9
6
5
4
3
3

Length L = 1000 mm
fm in Hz
250 500
1k
2k

20
17
14
12
12
12
9
7

30
24
20
17
16
15
12
9

4k

8k

44
29
25
20
16
12
12
10

27
22
22
16
13
10
8
7

Length L = 1500 mm
fm in Hz
250 500
1k
2k

4k

8k

47
37
33
24
18
14
12
11

37
30
27
19
15
11
10
8

Length L = 2000 mm (only type CF)


fm in Hz
125 250 500
1k
2k
4k

8k

125

11
10
7
5
4
3
2
2

14
11
9
7
6
5
4
4

15
12
9
6
5
4
3
3

4k

27
21
16
14
11
8
6
6

11
9
7
6
5
4
3
3

50
50
42
34
26
19
13
11

63

63

Length L = 500 mm
fm in Hz
250 500
1k
2k

15
12
11
9
8
6
4
3

23
21
16
12
11
9
8
8

33
27
21
17
14
11
10
9

42
34
27
22
18
15
12
9

47
38
32
26
25
25
22
18

48
44
41
37
37
35
26
20

50
50
50
48
47
45
33
22

50
50
50
47
45
40
28
23

50
50
50
48
48
45
35
26

50
50
50
50
50
50
41
29

50
50
46
42
34
25
19
17

50
50
50
50
42
30
27
22

50
46
40
29
22
16
14
11

47
37
31
21
18
13
11
9

Order Details CA CB
Specification text Type CA050 or CA100

Specification text Type CB050 or CB100

Type CA circular silencer for ventilation systems; insertion


loss tested to DIN EN ISO 7235.

Type CB circular silencer for ventilation systems; insertion


loss, sound power level of air-regenerated noise and pressure drop tested to DIN EN ISO 7235.

Absorption material non-combustible mineral wool with


RAL quality mark RAL-GZ 388, to DIN 4102, fire rating
class A2; with glass fibre scrim facing covered with
perforated plate as protection against erosion suitable for air
velocities up to 20 m/s. Casing and perforated inner duct
galvanised sheet steel.
Spigot connections suitable for circular connecting ducts to
DIN EN 1506 or DIN EN 13180 with groove for lip seal.
Casing air leakage complies with DIN EN 1751, class A

Sound-absorbing pod for better acoustic performance.


Coned end upstream to reduce pressure drop. Absorption
material non-combustible mineral wool with RAL quality
mark RAL-GZ 388, to DIN 4102, fire rating class A2; with
glass fibre scrim facing covered with perforated plate as
protection against erosion suitable for air velocities up to
20 m/s. Casing and perforated inner duct galvanised sheet
steel.
Spigot connections on both ends suitable for circular
connecting ducts to DIN EN 1506 or DIN EN 13180 with
groove for lip seal.
Casing air leakage complies with DIN EN 1751, class A

Dimensions:

Dimensions:

Nominal size
Length in mm
Insulation thickness in mm
Flow rate in m3/h (in l/s)
Insertion loss in dB
at 250 Hz octave band centre frequency

Nominal size
Length in mm
Insulation thickness in mm
Flow rate in m3/h (in l/s)
Insertion loss in dB
at 250 Hz octave band centre frequency
Max. permitted flow resistance in Pa (pressure differential)
Item
Type (in accordance with order code; see below)
CBMake
TROX

Item
Type (in accordance with order code; see below)
Make

CATROX

Order code
CB100

315 x 1000

GE

VF1

Type
CA (without pod)
CB (with pod)
Insulation thickness in mm 1)

Connection variations
000
= Plug type spigot
VF1
= Flange one end 2)
VF2
= Flange both ends
VD2
= Lip seal both ends

Nominal size
Matching flange 3)
no entry
= without
GE
= one end
GZ
= both ends

Length

1) 50 mm up to size 400 possible. (If insulation details are missing from the order, standard delivery is 100 mm.)
2) In type CB.../VF1: Standard flange and cone at the same end
3) Connection variation VF1 and VF2 only

Connection variations

Plug type - 000 -

Flange one end - VF1 -

Flange both ends - VF2 -

Lip seal - VD2 -

11

Order Details CF CS

Specification text Type CF025 or CF050

Specification text Type CS025 or CS050

Flexible circular silencer Type CF for ventilation systems;


Suitable for attenuation of air-regenerated noise and reduction of sound transmission to adjacent rooms. Insertion loss
tested to DIN EN ISO 7235. Absorption material non-combustible mineral wool with RAL quality mark RAL-GZ 388,
to DIN 4102, fire rating class A1. Outer casing and inner
duct are aluminium.

Circular silencer Type CS for ventilation systems; Suitable


for attenuation of air-regenerated noise and reduction of
sound transmission to adjacent rooms. Insertion loss tested
to DIN EN ISO 7235. Absorption material non-combustible
mineral wool with RAL quality mark RAL-GZ 388, to
DIN 4102, fire rating class A1. Outer casing and inner duct
are aluminium.

Spigot connections suitable for circular connecting ducts to


DIN EN 1506 or DIN EN 13180 with groove for lip seal.

Spigot connections suitable for circular connecting ducts to


DIN EN 1506 or DIN EN 13180 with groove for lip seal.

Casing air leakage complies with DIN EN 1751, class A

Casing air leakage complies with DIN EN 1751, class A

Dimensions:

Dimensions:

Nominal size
Length in mm
Insulation thickness in mm
Flow rate in m3/h (in l/s)
Insertion loss in dB
at 250 Hz octave band centre frequency
Item
Type (in accordance with order code; see below)
Make

Nominal size
Length in mm
Insulation thickness in mm
Flow rate in m3/h (in l/s)
Insertion loss in dB
at 250 Hz octave band centre frequency
Item
Type (in accordance with order code; see below)
Make

CFTROX

Order code
CF050

Design changes reserved All rights reserved TROX GmbH (08/2008)

Type
CF (flexible)
CS (rigid)
Insulation thickness in mm 1)

315 x 1000

VD2

Connection variations
000 = Plug type spigots
VD2 = Lip seal both ends
AS2 = Socket type spigots both ends
BK2 = Raised edges both ends
for quick locking system

Nominal size
Length 2)

1) 25 mm and 50 mm available. (If insulation details are missing from the order, standard delivery is 50 mm.)
2) Type CS maximum length 1500 mm. Type CF maximum length 2000 mm.

Connection variations (Type CF shown)

Plug type - 000 -

12

Lip seal - VD2 -

Socket type spigots - AS2 -

Raised edge - BK2 -

CSTROX