You are on page 1of 6

www.hilti.co.uk Company: Specifier: Address: Phone I Fax: E-Mail: Specifier's comments: HLGS Page: Project: Sub-Project I Pos. No.

: Date:

PROFIS Anchor 2.0.7


1 Dubai Pearl 3/6/2012

-|-

1. Input data

Anchor type and diameter: Effective embedment depth: Material: Evaluation Service Report:: Issued I Valid: Proof: Stand-off installation: Anchor plate: Profile Base material: Installation: Reinforcement:

HIT-HY 150 MAX + HIT-V (8.8), M20 h ef,opti = 124 mm (hef,limit = 400 mm) 8.8 -|design method Engineering judgement SOFA BOND - after ETAG BOND testing with clamping (anchor); restraint level (anchor plate): 1.0; e b = 50 mm; t = 30 mm S355(St52); lx x l y x t = 700 x 900 x 30 mm (Recommended plate thickness: not calculated) Square hollow; (L x W x T) = 600 mm x 600 mm x 25 mm uncracked concrete , C50/60, f cc = 60.00 N/mm; h = 10000 mm, Temp. short/long: 0/0C hammer drilled hole, installation condition: dry reinforcement spacing < 150 mm (any ) or < 100 mm ( <= 10 mm) with longitudinal edge reinforcement d >= 12 mm + close mesh (stirrups, hangers) s <= 100 mm Reinforcement to control splitting according to EOTA TR 029, 5.2.2.6 present.

Geometry [mm] y z 700 3 800 5 4 x 900 t=30 e b=50 h ef =124 x

200

h = 10000

200

1 275

6 350

2 275

lx = 700

Loading [kN, kNm] Resulting loads Design loads (Load case 1) N Vx Vy Mx My Mz 0.000 12.000 0.000 0.000 35.000 0.000

Eccentricity (structural section) [mm] e x = 0; e y = 0

Input data and results must be checked for agreement with the existing conditions and for plausibility! PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

www.hilti.co.uk Company: Specifier: Address: Phone I Fax: E-Mail: HLGS Page: Project: Sub-Project I Pos. No.: Date:

PROFIS Anchor 2.0.7


2 Dubai Pearl 3/6/2012

-|-

2. Load case/Resulting anchor forces


Load case (Design loads): Anchor reactions [kN] Tension force: (+Tension, -Compression) Anchor 1 2 3 4 5 6 Tension force 50.000 -50.000 50.000 -50.000 0.000 0.000 Shear force 2.000 2.000 2.000 2.000 2.000 2.000 Shear force x 2.000 2.000 2.000 2.000 2.000 2.000 Shear force y 0.000 0.000 0.000 0.000 0.000 0.000 Tension Compression x 3 5 y 4

max. concrete compressive strain []: 0.00 max. concrete compressive stress [N/mm]: 0.00 resulting tension force in (x/y)=(-175/0) [kN]: 100.000 resulting compression force in (x/y)=(175/0) [kN]: 100.000

3. Tension load (EOTA TR 029, Section 5.2.2)


Proof Steel Strength* Combined pullout-concrete cone failure** Concrete Breakout Strength** Splitting failure** 100.000 N/A 143.872 N/A 70 N/A OK N/A Load [kN] 50.000 100.000 Capacity [kN] 130.667 135.962 Utilization bN [%] 38 74 Status OK OK

* most unfavorable anchor **anchor group (anchors in tension) Steel Strength NRk,s [kN] 196.000 g M,s 1.500 NRd,s [kN] 130.667 NSd [kN] 50.000

Combined pullout-concrete cone failure Ap,N [mm ] 276350 yc 1.091 e c1,N [mm] 0 NRk,p [kN] 101.971
0 2

Ap,N [mm ] 138175 t Rk,ucr [N/mm ] 13.10 y ec1,Np 1.000 NRk,p [kN] 203.943
2

t Rk,ucr,25 [N/mm ] 12.00 k 3.200 e c2,N [mm] 0 g M,p 1.500

s cr,Np [mm] 372 y g,Np 1.031 y ec2,Np 1.000 NRd,p [kN] 135.962
0

c cr,Np [mm] 186 y g,Np 1.000 y s,Np 1.000 NSd [kN] 100.000

c [mm] 200

h ef [mm] 124

y re,Np 1.000

Input data and results must be checked for agreement with the existing conditions and for plausibility! PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

www.hilti.co.uk Company: Specifier: Address: Phone I Fax: E-Mail: HLGS Page: Project: Sub-Project I Pos. No.: Date:

PROFIS Anchor 2.0.7


3 Dubai Pearl 3/6/2012

-|-

Concrete Breakout Strength Ac,N [mm ] 276350 e c1,N [mm] 0 NRk,c [kN] 107.904
0 2

Ac,N [mm ] 138175 y ec1,N 1.000 g M,c 1.500

c cr,N [mm] 186 e c2,N [mm] 0 NRd,c [kN] 143.872

s cr,N [mm] 372 y ec2,N 1.000 NSd [kN] 100.000

h ef [mm] 124 y s,N 1.000 y re,N 1.000 k1 10.100

Input data and results must be checked for agreement with the existing conditions and for plausibility! PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

www.hilti.co.uk Company: Specifier: Address: Phone I Fax: E-Mail: HLGS Page: Project: Sub-Project I Pos. No.: Date:

PROFIS Anchor 2.0.7


4 Dubai Pearl 3/6/2012

-|-

4. Shear load (EOTA TR 029, Section 5.2.3)


Proof Steel Strength (without lever arm)* Steel failure (with lever arm)* Pryout Strength** Concrete edge failure in direction x+** * most unfavorable anchor **anchor group (relevant anchors) Steel Strength (without lever arm) VRk,s [kN] 98.000 g M,s 1.250 V Rd,s [kN] 78.400 VSd [kN] 2.000 Load [kN] 2.000 2.000 12.000 12.000 Capacity [kN] 78.400 3.941 527.959 113.047 Utilization bV [%] 3 51 2 11 Status OK OK OK OK

Steel failure (with lever arm) l [mm] 65 NSd / N Rd,s 0.383


M

aM 1.00 1 - NSd/ N Rd,s 0.617 M Rk,s [kNm] 0.519 gM,s,b 1.250 VRd,s [kN] 3.941
M 0

M Rk,s=MRk,s (1 - NSd/NRd,s) [kNm] 0.320 VSd [kN] 2.000

VRk,s= aM * MRk,s / l [kN] 4.927 Pryout Strength (bond relevant) Ap,N [mm ] 536553 yc 1.091 y s,Np 1.000 NRk,p [kN] 101.971
0 2

Ap,N [mm ] 138175 t Rk,ucr [N/mm ] 13.10 e c1,V [mm] 0 NRk,p [kN] 395.969
2

t Rk,ucr,25 [N/mm ] 12.00 k 3.200 y ec1,Np 1.000 gM,c,p 1.500

s cr,Np [mm] 372 k-factor 2.000 e c2,V [mm] 0 VRd,c1 [kN] 527.959

c cr,Np [mm] 186 y g,Np 1.109 y ec2,Np 1.000 VSd [kN] 12.000
0

c [mm] 200 y g,Np 1.000 y re,Np 1.000

h ef [mm] 124

Concrete edge failure in direction x+ h ef [mm] 124 c 1 [mm] 275 y s,V 0.845 VRk,c [kN] 137.890
0

d nom [mm] 20 Ac,V [mm ] 495000 y h,V 1.000 g M,c 1.500


2

k1 2.400 A c,V [mm ] 340313 y a,V 1.000 V Rd,c [kN] 113.047


0 2

a 0.067

b 0.059

e c,V [mm] 0 VSd [kN] 12.000

y ec,V 1.000

y re,V 1.000

Input data and results must be checked for agreement with the existing conditions and for plausibility! PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

www.hilti.co.uk Company: Specifier: Address: Phone I Fax: E-Mail: HLGS Page: Project: Sub-Project I Pos. No.: Date:

PROFIS Anchor 2.0.7


5 Dubai Pearl 3/6/2012

-|-

5. Combined tension and shear loads (EOTA TR 029, Section 5.2.4)


bN 0.736 bN + b V <= 1
a a

bV 0.507

a 1.5

Utilization bN,V [%] 99

Status OK

6. Displacements
The displacement of the highest loaded anchor should be calculated according to the relevant approval under the effect of the following characteristic loads. NSk VSk = = 37.040 [kN] 4.440 [kN]

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

7. Warnings
The design method SOFA assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by filling the gap with mortar of sufficient compressive strength (e.g. by using the Hilti Dynamic Set) or by other suitable means. The compliance with current standards (e.g. EC3) is the responsibility of the user An SLS-check is not performed for SOFA and has to be provided by the user! Attention! In case of compressive anchor forces a buckling check as well as the proof of the local load transfer into and within the base material (incl. punching) has to done separately. Bore hole cleaning must be performed according to instructions for use (blow twice with oil-free compressed air (min. 6 bar), brush twice, blow twice with oil-free compressed air (min. 6 bar)). Characteristic bond resistances depend on short- and long-term temperatures. Please contact Hilti to check feasibility of HIT-V rod supply. Checking the transfer of loads into the base material is required in accordance with EOTA TR 029, Section 7! The anchor plate is assumed to be sufficiently stiff in order to be not deformed when subjected to the actions!

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility! PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

www.hilti.co.uk Company: Specifier: Address: Phone I Fax: E-Mail: HLGS Page: Project: Sub-Project I Pos. No.: Date:

PROFIS Anchor 2.0.7


6 Dubai Pearl 3/6/2012

-|-

8. Installation data
Anchor plate, steel: S355(St52) Anchor type and diameter: HIT-HY 150 MAX + HIT-V (8.8), M20 Profile: Square hollow, 600 mm x 600 mm x 25 mm Installation torque: 0.150 kNm Hole diameter in the fixture: df = 22 mm Hole diameter in the base material: 24 mm Plate thickness (input): 30 mm Hole depth in the base material: 124 mm Recommended plate thickness: not calculated Minimum thickness of the base material: 172 mm Cleaning: Premium cleaning of the drilled hole is required Annular gap must be removed by e.g. filling the holes with mortar or welding the anchors to the anchor plate!

50.0 450.0

1 175.0 350.0

2 175.0 350.0

Coordinates Anchor [mm] Anchor x y 1 -175 -400 2 175 -400 3 -175 400

c -x 275 625 275

c +x 625 275 625

c -y 200 200 1000

c +y 1000 1000 200

Anchor 4 5 6

x 175 0 0

y 400 400 -400

50.0

450.0 c -x 625 450 450

c +x 275 450 450

c -y 1000 1000 200

c +y 200 200 1000

Input data and results must be checked for agreement with the existing conditions and for plausibility! PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

You might also like