SEE NOTE 14

SHORT CIRCUIT STRAP (SPACED MIDWAY BETWEEN SUPPORTS)

SEE NOTE 14
SHORT CIRCUIT STRAP (SPACED MIDWAY BETWEEN SUPPORTS)

500

500

4000

500

500

SEE NOTE 15 & 16

SHORT CIRCUIT STRAP (SPACED EVERY 1.3m)

SEE NOTE 15 & 16

SHORT CIRCUIT STRAP (SPACED EVERY 1.3m)

7800

TUNNEL CROSS SECTION 1 : 40

7800

MONORAIL (DETAILS TO BE CONFIRMED BY TUNNEL CONTRACTOR)


6063 ALUMINIUM OVERSTRAPS

=
POLYMERIC OVERSTRAP LINERS

365 315

= =

15

56

45

6
HITLI HSA-F M16 EXPANSION HD BOLTS 493

1300

= 493
145.0

= 250 = =

A4 STAINLESS STEEL CLOSURE FIXINGS

2380 2110 CABLE SUPPORT STRUCTURE SINGLE CABLE SADDLE


1386

6063 ALUMINIUM SPACER BARS POLYMERIC INSULATION WASHERS 500

TOP PLATE 1 : 10
415 315

500

= =

= =

50 ==

500

15

400kV CABLE 500 250 = =

504

ECC ONLY REQUIRED FOR NG CIRCUITS

500

500

100

== 50

ECC TRANSPOSED MID WAY THROUGH ROUTE.

BOTTOM PLATE 1 : 10

638

400kV CABLE SHORT CIRCUIT STRAP 1 : 10


500
ISSUE

A
SDP DS AH

REMARKS: FIRST ISSUE

NOTES: 1.
1500 TREFOIL CABLE SADDLE (132kV CABLES)

DRAWN CHKD APPD

ALL DIMENSIONS IN MILLIMETRES UNLESS NOTED OTHERWISE. ALL STEELWORK TO BE ERECTED TO COMPLY WITH NATIONAL GRID SPECIFICATIONS NGTS 3.10, NGTS 3.5.7 & DH 10. REFER TO DRAWING PN/CSED/6487 FOR DETAILS OF CABLE SUPPORT BRACKET. REFER TO ELLIS PATENTS DRAWING NUMBER 4006 FOR THE 400kV CABLE SADDLE CLEAT AND DRAWING NUMBER 4008 FOR SHORT CIRCUIT STRAP. REFER TO ELLIS PATENTS DRAWING NUMBER 4022 FOR 132kV CABLE SADDLE CLEAT AND DRAWING NUMBER TBC FOR SHORT CIRCUIT STRAP. TUNNEL SEGMENT DETAILS TAKEN FROM COSTAIN DRAWING NUMBERS 78-HAL-00034-20773-XXX-CIV REV D. SITE DRILLING OF STEELWORK IS FORBIDDEN. EACH BRACKET SHALL BE FIXED TO THE TUNNEL LINING WITH 4No HILTI M16 TYPE HSA-F HOT DIPPED GALVANISED ANCHORS. REQUIRED DRILL DEPTH FOR HD BOLTS SHALL BE 120mm.

2. 3. 4. 5. 6. TUNNEL SEGMENT SECTION 1 : 20


100 50

DATE

08/10/2012

Electricity Alliance
EDC Ref: AE/35

493

493

45

45

National Grid plc, Warwick Technology Park, Gallows Hill, Warwick, CV34 6DA

national gr d

DRAWING TITLE:

7. 8. 9.

4.0m DIA TUNNEL CROSS-SECTION 1 : 20


1
1 41

GA OF SINGLE SADDLE AND TREFOIL CABLE SUPPORT FOR 4.0 DIA TUNNELS
SITE:

10. NO HOLES FOR HD ANCHORS SHALL BE CLOSER THAN 150mm FROM THE EDGE OF THE TUNNEL SEGMENTS. 11. NO HOLES FOR HD ANCHORS SHALL BE CLOSER THAN 100mm FROM ANY CAST-IN POCKETS FORMING PART OF THE TUNNEL SEGMENTS.

45
Mi

600
M ax im

LONDON POWER TUNNELS


DRAWING No:

A1 CAD
Issue:

nim

um

Ca

Ca

ble

ble

6063 ALUMINIUM OVERSTRAP A4 STAINLESS STEEL CLOSURE FIXINGS

269

um

POLYMERIC OVERSTRAP LINER

111 A

12. ALL HILTI M16 ANCHORS TIGHTENING TORQUE TO BE 100Nm. 13. SUPPORT STEELWORK TO BE INSTALLED LEVEL (FRONT AND SIDE FACE).
306 100 299 120

PN/CSED/6517
NG DRAWING No:
Sheet No: No of Sheets:

150 Saddle Diameter 237 2xM12 FIXING HOLES ONTO STRUCTURE

14. SAGGING TOLERANCE IS 85mm - 210mm AS DEFINED BY SUDKABEL FOR THE 400kV CABLES. 15. SAGGING TOLERANCE IS 187mm - 375mm (WITH TARGET SAG AT 208mm) AS DEFINED BY SUDKABEL FOR THE 2000mm 132kV CABLES. 16. SAGGING TOLERANCE IS 140mm - 375mm (WITH TARGET SAG AT 287mm) AS DEFINED BY SUDKABEL FOR THE 800mm 132kV CABLES. 17. BRACKETS ON BOTH SIDES OF THE TUNNEL SHALL BE MOUNTED IMMEDIATELY OPPOSITE EACH OTHER.

77/EAA/0066

A
20773

SCALE: AS SHOWN NG CONTRACT No:

POLYMERIC INSULATION WASHERS BASE BRACKET AND M16 FIXINGS GALVANISED TO 65 MICRONS 146 130 260 SECTION A-A 130

6063 ALUMINIUM SADDLE

A 100

HOLES IN SADDLE WEB FOR ELLIS ROLLER SYSTEM

Engineering Department - Cabling Crossways Point 15, Victory Way, Dartford, Kent, DA2 6DT Tel: 01322 629900 Fax: 01322 629901
2012 BALFOUR BEATTY PLC The copyright in this drawing & the design right in the article(s) depicted belong to Balfour Beatty plc or its subsidiary. The drawing may not be copied by any means (including tracing) or stored as a microfilm, as a cad file, or CD-Rom or in any other electronic form, nor may articles be made from the drawing, either directly or indirectly, without the prior written consent of Balfour Beatty plc or its authorised representatives.

35

400kV CABLE SADDLE DETAIL 1:5

DIMENSIONED IN ACCORDANCE WITH SUDKABEL TECHNICAL DOCUMENT KSH-89237-F-01E

132kV CABLE SADDLE DETAIL 1 : 10

FOR CONSTRUCTION

=
TOP PLATE (SEE DETAIL 1)

365 315

= = 15

38

315

=
18 HOLES

25

250 419

80 x 80 x 6 SHS (SEE DETAIL 2)

350

43
195

25

DETAIL OF ELONGATION

DETAIL 1

18 HOLES FOR HITLI HSA-F M16 EXPANSION HD BOLTS

90 280 500 500 330 195

DRAIN / VENT HOLES CUT OUT OF TOP AND BOTTOM SIDES OF SHS

330 195 135

DRAIN / VENT HOLES CUT OUT OF TOP AND BOTTOM SIDES OF SHS

360
TOP: 18 HOLES BOTTOM: 40 HOLES

20

132

120

108

80 x 80 x 6 SHS (SEE DETAIL 2)

TOP: 14 HOLES BOTTOM: 30 HOLES

20

20
6mm (TYP)

20
BOTH ENDS 12 HOLES

90 280

80 = =

50

330

50 ==

18 12

BOTH ENDS 12 HOLES

80 = = 80 = =

14 12 30

500

500

80 = =

330 195

190

50 DETAIL 2

40

190

50 DETAIL 3 415 315

80 x 80 x 6 SHS (SEE DETAIL 2)

2740

2856

2603

=
120 x 120 x 6 SHS (CENTRALLY LOCATED ON BASEPLATE)

= =

18 HOLES FOR HITLI HSA-F M16 EXPANSION HD BOLTS

90 280

DRAIN / VENT HOLES CUT OUT OF ALL FOUR SIDES OF THE 120 x 120 x 6 SHS TOP AND BOTTOM

15
ISSUE DRAWN SDP DS MS

638

638

25 250 = =
18 HOLES

REMARKS:

CHKD APPD

NOTES REVISED
DATE 26/10/2012

310
80 x 80 x 6 SHS (SEE DETAIL 3)

25 20 20 DETAIL OF ELONGATION 20

120 DETAIL 4

18

ISSUE DRAWN CHKD APPD SDP DS MS

REMARKS:

FIRST ISSUE
DATE 08/10/2012

360 500 500 20 DRAIN HOLE DETAIL

NOTE:

Electricity Alliance
ALL DIMENSIONS IN MILLIMETRES UNLESS NOTED OTHERWISE. ALL STEELWORK TO BE TO BS EN 10025 - MINIMUM STEEL GRADE TO BE S275JR FOR BASE PLATES, OR BS EN 10219 - MINIMUM STEEL GRADE TO BE S275J2H FOR STRUCTURAL HOLLOW SECTIONS. ALL WELDED CONSTRUCTION WITH ALL WELDS CONTINUOUS TO BE MINIMUM 6MM FULL FILLET WELDS. ALL WELDING TO BE CARRIED OUT IN ACCORDANCE WITH BS 5135. ALL BURS, SHARP EDGES AND WELD SPLATTER TO BE REMOVED. ALL STRUCTURAL BOLTS AND NUTS TO BE GRADE 8.8 IN ACCORDANCE WITH BS 4190 HAVING A MINIMUM GALVANISED THICKNESS OF 43 MICRONS. ALL WASHERS TO BE GALVANISED AND IN ACCORDANCE WITH BS 4320. MEMBERS TO BE FREE FROM RUST AND GALVANISED TO BS EN 1461 WITH ZINC COATING THICKNESS NOT LESS THAN 85 MICRONS. ALL STRUCTURAL STEELWORK TO COMPLY WITH NATIONAL GRID TECHNICAL SPECIFICATIONS NGTS 3.10 (GENERIC TECHNICAL SPECIFICATION FOR CIVIL ENGINEERING WORKS). SUPPORT TYPE (I.E. TYPE 1A) TO BE HARD STAMPED ONTO STEELWORK BEFORE GALVANISING. APPROXIMATE WEIGHT OF COMPLETE STRUCTURE: 104kg REFER TO DRAWING PN/CSED/6517 FOR DETAILS ON INSTALLATION GENERAL ARRANGEMENTS. FOR ALL STRUCTURAL STEELWORK, AN INSPECTION CERTIFICATE TYPE 3.1 (EN10204) SHALL BE PROVIDED TO THE ENGINEER. THE TECHNICAL PART OF THE MATERIAL SUPPLIERS ORDER CONFIRMATION SHALL BE FORWARDED TO THE ENGINEER, PRIOR TO PLACEMENT OF MATERIAL ORDER.
Engineering Department - Cabling Crossways Point 15, Victory Way, Dartford, Kent, DA2 6DT Tel: 01322 629900 Fax: 01322 629901
2012 BALFOUR BEATTY PLC The copyright in this drawing & the design right in the article(s) depicted belong to Balfour Beatty plc or its subsidiary. The drawing may not be copied by any means (including tracing) or stored as a microfilm, as a cad file, or CD-Rom or in any other electronic form, nor may articles be made from the drawing, either directly or indirectly, without the prior written consent of Balfour Beatty plc or its authorised representatives.

1.

EDC Ref: AE/35

80 x 80 x 6 SHS (SEE DETAIL 3)

310
43

2. 3. 4. 5. 6.

120

National Grid plc, Warwick Technology Park, Gallows Hill, Warwick, CV34 6DA

nationalgr d

DRAWING TITLE:

BOTTOM PLATE (SEE DETAIL 4)

115

183

360
7. 8.

5 WAY CABLE SUPPORT BRACKET FOR 4.0m DIA TUNNEL


SITE:

LONDON POWER TUNNELS


DRAWING No:

A2 CAD
Issue:

315

9. 10.

PN/CSED/6487
NG DRAWING No:
Sheet No: No of Sheets:

77/EAA/0067
SCALE:

1
20773

FRONT VIEW

11.

ELEVATION VIEW

1:10

NG CONTRACT No:

12. 13. 14.

SUPPORT TYPE: TYPE 1A

FOR CONSTRUCTION