ETAP PowerStation
4.0.0C
Study Case: LF
Revision: Config.:
Generator 0
Load 2
Total 3
XFMR3 0
Reactor 0
Line/Cable 1
Impedance 0
Tie PD 0
Total 2
ETAP PowerStation
4.0.0C
Study Case: LF
Revision: Config.:
Bus
ID Bus1 Bus2 Bus5 Total Nunmber of Buses: 3 Type Swing Load Load kV 20.000 0.380 0.380
Initial Voltage
% Mag. 100.0 100.0 100.0 Ang. 0.0 0.0 0.0
Generator
MW Mvar
Motor Load
MW Mvar
Static Load
MW Mvar
Mvar Limits
Max. Min.
0.241
0.103
5.000
0.000
0.000
0.000
0.241
0.103
5.000
0.000
ETAP PowerStation
4.0.0C
Study Case: LF
Revision: Config.:
ETAP PowerStation
4.0.0C
Study Case: LF
Revision: Config.:
Transformer
ID T1 MVA 50.000 Prim. kV 20.000
Rating
Sec. kV 0.380 %Z 6.750 X/R 5.8 + 5% 0
Z Variation
- 5% 0 % Tol. 0
% Tap Setting
Prim. 0 Sec. 0
Adjusted
%Z 6.7500
Phase Shift
Type Std Pos. Seq. Angle 0.0
ETAP PowerStation
4.0.0C
Study Case: LF
Revision: Config.:
BRANCH CONNECTIONS
CKT/Branch
ID T1 Cable1 Type 2W XFMR Cable Bus1 Bus5 From Bus Bus5 Bus2
Connected Bus ID
To Bus
ETAP PowerStation
4.0.0C
Study Case: LF
Revision: Config.:
Equipment
ID Type Library Size
Heater
R (ohm)
ETAP PowerStation
4.0.0C
Study Case: LF
Revision: Config.:
Bus
ID * Bus1 Bus2 Bus5 kV 20.000 0.380 0.380
Voltage
%Mag. 100.000 20.534 99.907 Ang. 0.0 4.7 -0.2
Generation
MW 2.21 0 0 Mvar 0.32 0 0
Motor Load
MW 0 0.24 0 Mvar 0 0.10 0
Static Load
MW 0 0.21 0 Mvar 0 0.00 0 Bus5 Bus5 Bus2 Bus1 ID
Load Flow
MW 2.21 -0.45 2.21 -2.21 Mvar 0.32 -0.10 0.31 -0.31 Amp 64 3394 3394 3398 %PF 99.0 97.5 99.0 99.0
XFMR
% Tap
* Indicates a voltage regulated bus ( voltage controlled or swing type machine connected to it) # Indicates a bus with a load mismatch of more than 0.1 MVA
ETAP PowerStation
4.0.0C
Study Case: LF
Revision: Config.:
Bus
ID Bus1 Bus2 Bus5 kV 20.000 0.380 0.380 Rated Amp MW 2.214 0.447 2.210 Mvar 0.321 0.103 0.314
ETAP PowerStation
4.0.0C
Study Case: LF
Revision: Config.:
ETAP PowerStation
4.0.0C
Study Case: LF
Revision: Config.:
CKT / Branch
ID T1 Cable1
Losses
Kvar 6.7 210.8 217.5
% Bus Voltage
From 100.0 20.5 To 99.9 99.9
ETAP PowerStation
4.0.0C
Study Case: LF
Revision: Config.:
Equipment Cable
ID
Connected
Load Type kW
Losses
kvar
% Voltage
Bus Load
ETAP PowerStation
4.0.0C
Study Case: LF
Revision: Config.:
Marginal
Bus Voltage
OverVoltage UnderVoltage 105.0 95.0 102.0 98.0
Generator Excitation
OverExcited (Q Max.) UnderExcited (Q Min.)
Critical Report
ID Bus2 Device Type Bus Rating 0.380 Unit kV Calculated 0.078 %Mag. 20.5 Condition UnderVoltage
ETAP PowerStation
4.0.0C
Study Case: LF
Revision: Config.:
MW Swing Bus(es): Generators: Total Demand: Total Motor Load: Total Static Load: Apparent Losses: System Mismatch: 2.214 0.000 2.214 0.236 0.211 1.767 0.007
Number of Iterations: 4