You are on page 1of 10

Circuit No. R1 R2 R3 R4 R5 R6 R7 R8 Circuit No. Y1 Y2 Y3 Y4 Y5 Y6 Y7 Y8 Circuit No.

B1 B2 B3 B4 B5 B6 B7 B8

Description of Load Staff Room AC 1.0TR Councelling Room AC 0.8TR Pantry Power Point Lighting Circuit - Staff Room Lighting Circuit - Councelling Room Lighting - Ground Floor Toilet Lighting - Pantry Water Dispensers

Power Distribution for Ground Floor 5X10 Sqmm Copper 63A FP MCB Rating of MCB 40A DP MCB 16A SP MCB 16A SP MCB 16A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB 10A SP MCB 40A DP MCB 16A SP MCB 16A SP MCB 16A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB 10 A SP MCB 40A DP MCB 16A SP MCB 10A SP MCB 10A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB

Admission Area 0.8TR Principal's Cabin 0.8TR Photocopier Admission's Area Lighting Circuit - Admission Area Lighting Circuit - Principal's Cabin Lighting - General Area Circuit No.1 Lighting -General Area Circuit No.2 Raw Power Points General Area

Harishbhai's Cabin 0.8TR Inverter 1400 VA / 2000VA Pantry Power Point Lighting Circuit - Harishbhai's Cabin 1.5 HP Bore 1.0 HP Monobloc Pump Exterior Lighting Upper Floor Toilets

for Ground Floor

Details of Wiring 2 Nos. X 4.0 Sqmm + 1 No. X 2.5 Sqmm Copper Wires 2 Nos. X 2.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 2.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 2.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires Total R Phase 2 Nos. X 2.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 2.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 2.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 2.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires Total Y Phase 2 Nos. X 2.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 2.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 2.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires Total B Phase

Circuit No. R1 R2 R3 R4 R5 R6 Circuit No. Y1 Y2 Y3 Y4 Y5 Y6 Circuit No. B1 B2 B3 B4 B5 B6 B7 B8

Description of Load 1.5 TR AC Class Room -1 1.5 TR AC Class Room -1 16A Power Plug Class Room-1 Spare Spare Spare

Power Distribution for 1st Floor Art Gallery 5X6 Sqmm Copper 40A FP MCB Rating of MCB 40A DP MCB 16A SP MCB 16A SP MCB 16A SP MCB

1.5 TR AC Class Room -2 1.5 TR AC Class Room -2 16A Power Plug Class Room-2 Spare Spare Spare

40A DP MCB 16A SP MCB 16A SP MCB 16A SP MCB

Lighting Circuit # 1 Lighting Circuit # 2 Lighting Circuit # 3 Lighting Circuit # 4 Raw Power Plugs Circuit # 1 Raw Power Plugs Circuit # 2 CCTV Equipments Computer Wifi Switch / Router

40A DP MCB 6A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB

Distribution for 1st Floor Art Gallery

Details of Wiring 2 Nos. X 4.0 Sqmm + 1 No. X 2.5 Sqmm Copper Wires 2 Nos. X 4.0 Sqmm + 1 No. X 2.5 Sqmm Copper Wires 2 Nos. X 2.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires

Connected Load 1650 1650 1000

Total R Phase 2 Nos. X 4.0 Sqmm + 1 No. X 2.5 Sqmm Copper Wires 2 Nos. X 4.0 Sqmm + 1 No. X 2.5 Sqmm Copper Wires 2 Nos X 2.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires

4300 1650 1650 1000

Total Y Phase 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires Total B Phase Total Connected Load on Distribution Board

4300 400 400 400 400 300 300 250 250 2700 11300

Power Distribution for 2nd Floor Class Rooms ( Class Room- 1 and Class Room-2 ) 5X6 Sqmm Copper 40A FP MCB Circuit No. Description of Load Rating of MCB 40A DP MCB R1 1.5 TR AC Class Room -1 16A SP MCB R2 1.5 TR AC Class Room -1 16A SP MCB R3 16 A Plug Point in Alcove 16A SP MCB R4 Spare R5 Spare R6 Spare Circuit No. Y1 Y2 Y3 Y4 Y5 Y6 Circuit No. B1 B2 B3 B4 B5 B6 B7 B8 40A DP MCB 16A SP MCB 16A SP MCB 16A SP MCB

1.5 TR AC Class Room -2 1.5 TR AC Class Room -2 16 A Plug Point in Alcove Spare Spare Spare

Class Room - 1 Lighting Circuit # 1 Class Room - 1 Lighting Circuit # 2 Class Room - 2 Lighting Circuit # 3 Class Room - 2 Lighting Circuit # 4 Raw Power Plugs Circuit # 1 Class Room # 1 Raw Power Plugs Circuit # 2 Class Room # 1 Raw Power Plugs Circuit # 1 Class Room # 2 Raw Power Plugs Circuit # 2 Class Room # 1

40A DP MCB 6A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB

r Class Rooms ( Class Room- 1 and Class Room-2 )

Details of Wiring 2 Nos. X 4.0 Sqmm + 1 No. X 2.5 Sqmm Copper Wires 2 Nos. X 4.0 Sqmm + 1 No. X 2.5 Sqmm Copper Wires 2 Nos. X 2.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires

Connected Load 1650 1650 1000

Total R Phase 2 Nos. X 4.0 Sqmm + 1 No. X 2.5 Sqmm Copper Wires 2 Nos. X 4.0 Sqmm + 1 No. X 2.5 Sqmm Copper Wires 2 Nos. X 2.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires

4300 1650 1650 1000

Total Y Phase 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires Total B Phase Total Connected Load on Distribution Board

4300 350 350 350 350 400 400 400 400 3000 11600

Power Distribution for 3rd Floor Class Rooms ( Class Room- 1 and Class Room-2 ) 5X6 Sqmm Copper 40A FP MCB Circuit No. Description of Load Rating of MCB 40A DP MCB R1 1.5 TR AC Class Room -1 16A SP MCB R2 1.5 TR AC Class Room -1 16A SP MCB R3 16 A Plug Point in Alcove 16A SP MCB R4 Spare R5 Spare R6 Spare Circuit No. Y1 Y2 Y3 Y4 Y5 Y6 Circuit No. B1 B2 B3 B4 B5 B6 B7 B8 40A DP MCB 16A SP MCB 16A SP MCB 16A SP MCB

1.5 TR AC Class Room -2 1.5 TR AC Class Room -2 16 A Plug Point in Alcove Spare Spare Spare

Class Room - 1 Lighting Circuit # 1 Class Room - 1 Lighting Circuit # 2 Class Room - 2 Lighting Circuit # 3 Class Room - 2 Lighting Circuit # 4 Raw Power Plugs Circuit # 1 Class Room # 1 Raw Power Plugs Circuit # 2 Class Room # 1 Raw Power Plugs Circuit # 1 Class Room # 2 Raw Power Plugs Circuit # 2 Class Room # 1

40A DP MCB 6A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB

r Class Rooms ( Class Room- 1 and Class Room-2 )

Details of Wiring 2 Nos. X 4.0 Sqmm + 1 No. X 2.5 Sqmm Copper Wires 2 Nos. X 4.0 Sqmm + 1 No. X 2.5 Sqmm Copper Wires 2 Nos. X 2.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires

Connected Load 1650 1650 1000

Total R Phase 2 Nos. X 4.0 Sqmm + 1 No. X 2.5 Sqmm Copper Wires 2 Nos. X 4.0 Sqmm + 1 No. X 2.5 Sqmm Copper Wires 2 Nos. X 2.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires

4300 1650 1650 1000

Total Y Phase 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires Total B Phase Total Connected Load on Distribution Board

4300 350 350 350 350 400 400 400 400 3000 11600

Power Distribution for 4th Floor Class Rooms ( Class Room- 1 and Class Room-2 ) and Libr 5X6 Sqmm Copper 63A FP MCB Circuit No. Description of Load Rating of MCB 40A DP MCB R1 1.5 TR AC Class Room -1 16A SP MCB R2 1.5 TR AC Class Room -1 16A SP MCB R3 16 A Plug Point in Alcove 16A SP MCB R4 Class Room - 1 Lighting Circuit # 1 6A SP MCB R5 Class Room - 1 Lighting Circuit # 2 6A SP MCB R6 Raw Power Plugs Circuit # 1 Class Room # 1 6A SP MCB R7 Raw Power Plugs Circuit # 2 Class Room # 1 6A SP MCB R8 Spare Circuit No. Y1 Y2 Y3 Y4 Y5 Y6 Y7 Y8 Circuit No. B1 B2 B3 B4 B5 B6 B7 B8 40A DP MCB 16A SP MCB 16A SP MCB 16A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB

1.5 TR AC Class Room -2 1.5 TR AC Class Room -2 16 A Plug Point in Alcove Class Room - 2 Lighting Circuit # 3 Class Room - 2 Lighting Circuit # 4 Raw Power Plugs Circuit # 1 Class Room # 2 Raw Power Plugs Circuit # 2 Class Room # 1 Spare

1.5 TR AC Class Room -2 1.5 TR AC Class Room -2 16 A Plug Point in Pantry Library Lighting Circuit Store Room Lighting Circuit Pantry Lighting Circuit Exterior Lighting Circuit Spare

40A DP MCB 16A SP MCB 16A SP MCB 10A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB

Rooms ( Class Room- 1 and Class Room-2 ) and Library

Details of Wiring 2 Nos. X 4.0 Sqmm + 1 No. X 2.5 Sqmm Copper Wires 2 Nos. X 4.0 Sqmm + 1 No. X 2.5 Sqmm Copper Wires 2 Nos. X 2.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires Total R Phase 2 Nos. X 4.0 Sqmm + 1 No. X 2.5 Sqmm Copper Wires 2 Nos. X 4.0 Sqmm + 1 No. X 2.5 Sqmm Copper Wires 2 Nos. X 2.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires Total Y Phase 2 Nos. X 4.0 Sqmm + 1 No. X 2.5 Sqmm Copper Wires 2 Nos. X 4.0 Sqmm + 1 No. X 2.5 Sqmm Copper Wires 2 Nos. X 2.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires 2 Nos. X 1.5 Sqmm + 1 No. X 1.5 Sqmm Copper Wires

Connected Load 1650 1650 1000 350 350 400 400 5800 1650 1650 1000 350 350 400 400 5800 1650 1650 750 350 200 40 240

Total B Phase Total Connected Load on Distribution Board

4880 16480