You are on page 1of 7

Electronic timer CT-VBS.

17+18
OFF-delayed without auxiliary voltage, for DC contactors Data sheet
Characteristics
Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width 22.5 mm
2CDC 251 060 F0003

Approvals
1 2 A cULus E CCC

Marks
CT-VBS a Circuit diagram b Marker label a CE b C-Tick

Order data
Type CT-VBS.17 CT-VBS.18 Rated control supply voltage 100-127 V DC 200-240 V DC Order code 1SVR 430 261 R6000 1SVR 430 261 R5000

Order data (Accessories)


Type ADP.01 COV.01 MAR.01 Description Adapter for screw mounting Sealable transparent cover Marker label Width in mm 22.5 22.5 22.5 Order code 1SVR 430 029 R0100 1SVR 430 005 R0100 1SVR 366 017 R0100

Application
The CT-S range timers are designed for use in industrial applications. They operate over a universal range of supply voltages and a large time delay range, within compact dimensions. The easy-to-set front-face potentiometers, with direct reading scales, provide accurate time delay adjustment.

Operating mode
For the CT-VBS version with a 200-240 V AC supply voltage, the time delay is selected by connecting terminal 3 to 4. When jumpered, the time delay is from 0 to 2 s. If terminals 3-4 are not jumpered, the time delay is from 0 to 400 ms. The exact time delays can be seen in the delay time diagrams.

ABB

Electronic timer CT-VBS.17+18


OFF-delayed without auxiliary voltage, for DC contactors Data sheet
Function diagrams
B OFF-delay without auxiliary voltage (True delay on break) The DC contactor connected to the output is energized when control supply voltage is applied to terminals A1-A2. If control supply voltage is disconnected, the DC contactor remains energized for a short time delay. This delay time depends on the coil drop out voltage and on the wattage of the contactor coil.
2CDC 252 038 F0205
7W 9W 20 0 0 1 t [s] 2

A1-A2 1+/23-4
1) 1)

1+/2-

t1

t2

t1 = OFF-delay (without jumper between terminal 3 and 4) 1) t2 = OFF-delay (with jumper between terminal 3 and 4) 1) 1) only for version 200-240 V AC

Delay time diagrams


200 200

Contactor coil drop-out voltage [V]

160 140 120 100 80 60 40 20 0 0 100 200 t [ms] 300 400 9W 7W 3W

Contactor coil drop-out voltage [V]

180

180 160 140 120 100 80 60 40 3W

2CDC 252 127 F0205

Delay time guideline values 200-240 V AC version without jumper 3/4

Delay time guideline values 200-240 V AC version with jumper 3/4

120

Contactor coil drop-out voltage [V]

100

80

60

40 7W 9W 0 0

3W

20

1 t [s]

Delay time guideline values 110-127 V AC version

2CDC 252 129 F0205

ABB

2CDC 252 128 F0205

Electronic timer CT-VBS.17+18


OFF-delayed without auxiliary voltage, for DC contactors Data sheet
Connection diagrams
B CT-VBS.18
A1 A1 3 4 A2 1+ 22A2 3 4 1+ 2CDC 252 108 F0005 2CDC 252 107 F0005

1SVR 430 261 R5000 A1-A2 Supply: 200-240 V DC 1+ - 2- Contactor coil 3-4 Jumper for setting the time delay

B CT-VBS.17
A1 A1 1+

A2 1+ 2-

2A2

1SVR 430 261 R6000 A1-A2 Supply: 110-127 V DC 1+ - 2- Contactor coil

ABB

Electronic timer CT-VBS.17+18


OFF-delayed without auxiliary voltage, for DC contactors Data sheet
Technical Data
Input circuits Supply voltage A1-A2 A1-A2 Power consumption 100-127 V DC 200-240 V DC Supply voltage tolerance Supply voltage frequency AC/DC Version AC Version Duty time Timing circuit Time range Recovery time Repeat accuracy (constant parameters) Timing error within the supply voltage tolerance range Timing error within operating temperature range Output circuits 1+ - 2Contact material Related voltage acc. to VDE 0110, IEC 60947-1 Maximum switching voltage Rated switching current acc. to IEC 60947-5-1 AC-12 (resistive) 230 V AC-15 (inductive) 230 V DC-12 (resistive) 24 V DC-15 (inductive) 24 V Maximum lifetime mechanical electrical (AC-12, 230 V, 4 A) Short circuit proof, max. fuse rating n/c n/o General data Enclosure width length depth Wire size ne-strand with wire end ferrule ne-strand without wire end ferrule rigid Weight Mounting position Degree of protection enclosure / terminals Temperature range operating storage Mounting Standards Product standard EMC Directive Electromagnetic compatibility IEC/EN 61000-4-2 electrostatic discharge IEC/EN 61000-4-3 radiated, radio-frequency, electromagnetic eld IEC/EN 61000-4-4 electrical fast transient / burst Surge IEC/EN 61000-4-5 IEC/EN 61000-4-6 conducted disturbances, induced by radio-frequency elds Low Voltage Directive Operational reliability acc. to IEC 68-2-6 Mechanical resistance acc. to IEC 68-2-6 Isolation data Rated insulation voltage between supply circuit, acc. to VDE 0110, IEC 60947-1 control circuit and output circuit Rated impulse withstand voltage between all isolated circuits acc. to VDE 0110, IEC 664 Test voltage between all isolated circuits Pollution category acc. to VDE 0110, IEC 664, IEC 255-5 Overvoltage category acc. to VDE 0110, IEC 664, IEC 255-5 Environmental testing acc. to IEC 68-2-30 200-240 V DC 100-127 V DC max. 120 mA max. 70 mA -15...+10 % DC or 50/60 Hz 50/60 Hz 100 % see delay time diagrams < 50 ms 5% 10 % 0.2 % / C AgCdO see delay time diagrams 250 V AC, 250 V DC 4A 3A 4A 2A 30 x 106 switching cycles 0.1 x 106 switching cycles 10 A fast, operating class gL 10 A fast, operating class gL 22.5 mm 78.0 mm 100.0 mm 2 x 0.75 - 2.5 mm2 (18-14 AWG) 2 x 0.5 - 4 mm2 (20-12 AWG) approx. 150 g (5.3 oz) any IP50 / IP20 -20...+60 C -40...+85 C DIN rail (IEC/EN 60715) IEC 61812-1, EN 61812-1 2004/108/EC IEC 61000-6-2, EN 61000-6-4 level 3 6 kV / 8 kV level 3 10 V/m level 3 2 kV / 5 kHz level 4 2 kV L-L level 3 10 V 2006/95/EG 4g 6g supply up to 240 V: 300 V supply up to 440 V: 500 V 4 kV / 1.2-50 s 2.5 kV, 50 Hz, 1 min. III/C III/C 24 h cycle time, 55 C, 93 % rel., 96 h

ABB

Electronic timer CT-VBS.17+18


OFF-delayed without auxiliary voltage, for DC contactors Data sheet
Load limit curves
AC load (resistive)
2CDC 252 149 F0206 0.9 1.0 cos 2CDC 252 148 F0206 2CDC 252 124 F0206 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 250 V resistive load Switching current [A] 2CDC 252 150 F0206 AC voltage [V]

resistive load

AC current [A]

DC load (resistive)
DC voltage [V]

resistive load

DC current [A]

Derating factor F for inductive AC load


Derating factor F 1.0 0.9 0.8 0.7 0.6 0.5

Contact lifetime /switching cycles N


Switching cycles

220 V 50 Hz 1 AC 360 cycles/h

ABB

Electronic timer CT-VBS.17+18


OFF-delayed without auxiliary voltage, for DC contactors Data sheet
Dimensional drawings
Dimensions in mm
109,5 102 4.31 22,5 .886 4.02

100

3.94

Dimensional drawings (Accessories)


11.5 0.453

6.5 0.256

62.5 2.461 10 0.394 20 0.787 60 2.362 70 2.756

ADP.01 - Adapter for screw mounting on panel

22,5 .886

68,5 2.70

front-to-back size 107

COV.01 - Sealable transparent cover

3A11
20 .787

MAR.01 - Marker label

Further documentation
Document titel Electronic Products and Relays Document type Technical catalogue Document number 2CDC 110 004 C020x

You can nd the documentation on the internet at www.abb.com/lowvoltage R Control Products R Electronic Relays and Controls 6

2CDC 252 186 F0005

8 .315

2CDC 252 185 F0005

7 .275 3,5 .138

2CDC 252 188 F0005

78 3.07

ABB

Contact us

You can nd the address of your local sales organisation on the ABB home page http://www.abb.com/contacts -> Low Voltage Products and Systems

Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB AG. Copyright 2010 ABB All rights reserved

Document number 2CDC 111 002 D0204 (06/10)

ABB STOTZ-KONTAKT GmbH P. O. Box 10 16 80 69006 Heidelberg, Germany Phone: +49 (0) 6221 7 01-0 Fax: +49 (0) 6221 7 01-13 25 E-mail: info.desto@de.abb.com