MV SWITCHGEAR
No.
EQUIPMENT
DESCRIPTION
Load
FLA
Isc
BREAKER
Capacity
1
2
3
4
5
6
7
VCB
VCB
VCB
VCB
VCB
VCB
VCB
EVOLIS 1250
EVOLIS 1250
EVOLIS 630
EVOLIS 630
EVOLIS 630
EVOLIS 630
EVOLIS 630
Minimum Tripping
Time
Remarks
BREAKER
THERMAL
Remarks
RATING (In)
OVERLOAD RELAY
BREAKER
RELAY
RATING (In)
0.08
0.08
0.08
0.08
0.08
0.08
0.08
SEPAM S20
SEPAM S20
SEPAM T20
SEPAM T20
SEPAM T20
SEPAM T20
SEPAM T20
01-MCC-01
Rating
No.
EQUIPMENT NO
DESCRIPTION
BREAKER
FLA
Isc
Tstart
3000A
ACB,4P,NW32H1,3200A
Micrologic 2.0
0.27
18.5
18.5
15.0
15.0
def
def
def
def
3.0
3.0
3.0
3.0
MCCB,3P,NS80H-MA50
MCCB,3P,NS80H-MA50
MCCB,3P,NS100H-TM40D
MCCB,3P,NS100H-TM40D
0.005
0.005
0.02
0.02
8.0
36.0
20.0
8.0
24.0
12.0
8.0
8.0
8.0
12.0
MCCB,3P,NS100H-TM32D
MCCB,3P,NS160H-TM125D
MCCB,3P,NS100H-TM63D
MCCB,3P,NS100H-TM32D
MCCB,3P,NS100H-TM80D
MCCB,3P,NS100H-TM50D
MCCB,3P,NS100H-TM32D
MCCB,3P,NS100H-TM32D
MCCB,3P,NS100H-TM32D
MCCB,3P,NS100H-TM50D
0.02
0.02
0.02
0.02
0.02
0.02
0.02
0.02
0.02
0.02
(kW)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
INCOMING
INCOMING BREAKER
01-P-01A
01-P-01 B
01-P-02 A
01-P-02 B
01-LP-01
01-LP-02
01-WO-01
Welding Outlet
00-LP-01
00-LP-02
00-LP-03
00-LP-04
00-LP-05
00-LP-06
00-LP-07
Minimum
tripping
time
LRC
Attachment-1
Table protection setting
1 Of 5
LRD-3355
LRD-3355
2/6
02-MCC-01
No. EQUIPMENT NO
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
DESCRIPTION
RATING
P-2101 B
P-2102 A
P-2102 B
P-2103 A
P-2103 B
P-2104 A
P-2104 B
P-2105A
P-2105B
P-2106 A
P-2106 B
P-2107 A
P-2107 B
P-2108 A
P-2108 B
P-2109 A
P-2109 B
A-2101
A-2102
A-2103
P-2110 A
P-2110 B
P-2111 A
P-2111 B
P-2112 A
P-2112 B
P-2113 A
P-2113 B
P-2113 C
Isc
BREAKER
LRC
Tstart
ACB, 4P NW32H1
MCCB 4P, NS1000H
75.00
75.00
90.00
90.00
30.00
30.00
3.00
3.00
7.50
7.50
0.25
0.25
0.25
0.25
5.50
5.50
3.70
3.70
14.00
14.00
1.50
55.00
55.00
55.00
55.00
30.00
30.00
1.00
1.00
1.00
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
MCCB,3P,NS160H-MA150
MCCB,3P,NS160H-MA150
MCCB,3P,NS250H-MA220
MCCB,3P,NS250H-MA220
MCCB,3P,NS80H-MA80
MCCB,3P,NS80H-MA80
MCCB,3P,NS80H-MA12.5
MCCB,3P,NS80H-MA12.5
MCCB,3P,NS80H-MA25
MCCB,3P,NS80H-MA25
MCCB,3P,NS80H-MA1.5
MCCB,3P,NS80H-MA1.5
MCCB,3P,NS80H-MA1.5
MCCB,3P,NS80H-MA1.5
MCCB,3P,NS80H-MA12.5
MCCB,3P,NS80H-MA12.5
MCCB,3P,NS80H-MA12.5
MCCB,3P,NS80H-MA12.5
MCCB,3P,NS80H-MA50
MCCB,3P,NS80H-MA50
MCCB,3P,NS80H-MA6.3
MCCB,3P,NS160H-MA150
MCCB,3P,NS160H-MA150
MCCB,3P,NS160H-MA150
MCCB,3P,NS160H-MA150
MCCB,3P,NS80H-MA80
MCCB,3P,NS80H-MA80
MCCB,3P,NS80H-MA6.3
MCCB,3P,NS80H-MA6.3
MCCB,3P,NS80H-MA6.3
24.00
24.00
20.00
20.00
32.00
MCCB,3P,NS100H-TM80D
MCCB,3P,NS100H-TM80D
MCCB,3P,NS100H-TM63D
MCCB,3P,NS100H-TM63D
MCCB,3P,NS100H-TM100D
INCOMING 02-MCC-01
TIE BUS NORMAL DAN EMERGENCY
P-2101 A
FLA
(kW)
0
OTHERS
33
34
35
36
37
02-LP-01
02-LP-02
02-WO-01
Welding Outlet
02-WO-02
Welding Outlet
02-UPS-01
UPS A
Attachment-1
Table protection setting
2 Of 6
Minimum
tripping time
0.27
0.02
0.02
0.02
0.02
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.02
0.02
0.02
0.02
0.005
0.005
0.005
0.005
0.005
BREAKER
RATING
(In)
3000
THERMAL
OVERLOAD
RELAY
LR9-F5369
LR9-F5369
LR9-F5371
LR9-F5371
LRD-3359
LRD-3359
LRD-14
LRD-14
LRD-21
LRD-21
LRD-05
LRD-05
LRD-05
LRD-05
LRD-16
LRD-16
LRD-14
LRD-14
LRD-3353
LRD-3353
LRD-08
LR9-D5369
LR9-D5369
LR9-D5369
LR9-D5369
LRD-3359
LRD-3359
LRD-08
LRD-08
LRD-08
ADDITIONAL
RELAY
MICROLOGIC 2.0A
MICROLOGIC 2.0A
Remarks
3/6
02-MCC-02
No. EQUIPMENT NO
1
2
DESCRIPTION
Rating
(kW)
INCOMING 02-MCC-02
TIE BREAKER
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
P-2201 A
P-2201 B
P-2202 A
P-2202 B
P-2203 A
P-2203 B
P-2204 A
P-2204 B
P-2205 A
P-2205 B
P-2206 A
P-2206 B
P-2207 A
P-2207 B
P-2208 A
P-2208 B
P-2209 A
P-2209 B
P-2210 A
P-2210 B
23
24
25
26
02-LP-03
02-UPS-02
02-UPS-03
02-SH-1
FLA
0
30.00
30.00
22.00
22.00
1.50
1.50
1.50
1.50
75.00
75.00
15.00
15.00
1.50
1.50
3.70
3.70
2.20
2.20
2.20
2.20
32.00
32.00
32.00
20.00
Isc
BREAKER
Minimum
tripping time
0.27
LRC
Tstart
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
MCCB,3P,NS80H-MA80
MCCB,3P,NS80H-MA80
MCCB,3P,NS80H-MA50
MCCB,3P,NS80H-MA50
MCCB,3P,NS80H-MA6.3
MCCB,3P,NS80H-MA6.3
MCCB,3P,NS80H-MA6.3
MCCB,3P,NS80H-MA6.3
MCCB,3P,NS160H-MA150
MCCB,3P,NS160H-MA150
MCCB,3P,NS80H-MA50
MCCB,3P,NS80H-MA50
MCCB,3P,NS80H-MA6.3
MCCB,3P,NS80H-MA6.3
MCCB,3P,NS80H-MA12.5
MCCB,3P,NS80H-MA12.5
MCCB,3P,NS80H-MA6.3
MCCB,3P,NS80H-MA6.3
MCCB,3P,NS80H-MA6.3
MCCB,3P,NS80H-MA6.3
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
MCCB,3P,NS100H-TM100D
MCCB,3P,NS100H-TM100D
MCCB,3P,NS100H-TM100D
MCCB,3P,NS100H-TM63D
0.02
0.02
0.02
0.02
Attachment-1
Table protection setting
3 Of 6
BREAKER
RATING (In)
2000
THERMAL
OVERLOAD RELAY
LRD-3359
LRD-3359
LRD-3357
LRD-3357
LRD-08
LRD-08
LRD-08
LRD-08
LR9-F5369
LR9-F5369
LRD-3353
LRD-3353
LRD-08
LRD-08
LRD-14
LRD-14
LRD-10
LRD-10
LRD-10
LRD-10
ADDITIONAL
RELAY
MICROLOGIC 2.0A
MICROLOGIC 2.0A
Remarks
4/6
03-MCC-01
RATING
No.
EQUIPMENT NO
DESCRIPTION
FLA
LRC
Tstart
Isc
BREAKER
(Kw)
1
INCOMING
TIE BREAKER
ACB,4P,NW20H,2000A
Micrologic 2.0A
MCCB 4P, NS1000H
03-MCC-B
4
5
6
7
8
Minimum
BREAKER
tripping time
RATING (In)
THERMAL
OVERLOAD
RELAY
MICROLOGIC 2.0A
30.0
MCCB,3P,NS100H-TM100D
0.02
P-301 A
15.00
15.00
P-302 A
0.75
P-302 B
0.75
18.0
3.0
3.0
3.0
3.0
3.0
0.005
0.005
0.005
0.005
0.02
LRD-3353
def
def
def
def
def
MCCB,3P,NS80H-MA50
P-301 B
def
def
def
def
def
3.0
3.0
3.0
3.0
3.0
0.02
0.005
0.005
0.005
0.005
LR9-F5371
03-MCC-C
MCCB,3P,NS80H-MA2.5
MCCB,3P,NS80H-MA2.5
MCCB,3P,NS100H-TM50D
LRD-3353
LRD-07
LRD-07
ADDITIONAL
9
10
11
12
13
P-303 A
90.00
P-303 B
7.50
S/S 03 Pump 04
30.00
P-305 A
30.00
P-305 B
30.00
14
15
16
17
18
19
20
21
03-BC-01
Baterry charger
16.00
03-BC-02
55.00
03-BC-03
1.60
03-BC-04
1.60
03-CP-01
Cathodic Protection
4.00
03-LP-01
16.0
03-LP-02
03-WP-01
24.0
Welding Outlet
20.0
P-304
MCCB,3P,NS250H-MA220
MCCB,3P,NS80H-MA25
MCCB,3P,NS80H-MA80
MCCB,3P,NS80H-MA80
MCCB,3P,NS80H-MA80
Others
MCCB,3P,NS100H-TM50D
MCCB,3P,NS160H-TM160D
MCCB,3P,NS100H-TM16D
MCCB,3P,NS100H-TM16D
MCCB,3P,NS100H-TM25D
MCCB,3P,NS100H-TM50D
MCCB,3P,NS100H-TM80D
MCCB,3P,NS100H-TM63D
Attachment-1
Table protection setting
4 Of 6
Remarks
RELAY
0.27
MCCB,3P,NS80H-MA50
ADDITIONAL
0.02
0.02
0.02
0.02
0.02
0.02
0.02
0.02
LRD-21
LRD-3359
LRD-3359
LRD-3359
5/6
04-MCC-01
No. EQUIPMENT NO
1
2
DESCRIPTION
Rating
(kW)
Tstart
INCOMING 04-SWGR-01
TIE BREAKER
def
def
def
def
def
3.0
3.0
3.0
3.0
3.0
MCCB,3P,NS80H-MA80
MCCB,3P,NS80H-MA80
MCCB,3P,NS400H-MA320
MCCB,3P,NS400H-MA320
MCCB,3P,NS400H-MA320
0.005
0.005
0.02
0.02
0.02
MCCB,3P,NS100H-TM32D
MCCB,3P,NS100H-TM50D
MCCB,3P,NS100H-TM16D
MCCB,3P,NS100H-TM63D
0.02
0.02
0.02
0.02
04-MCC-A
4
5
6
7
8
P-401 A
P-401 B
P-411 A
P-411 B
P-411 C
9
10
11
12
04-LP-01
04-LP-02
04-CP-01
04-WO-01
Isc
Minimum
Tripping time
LRC
FLA
BREAKER
BREAKER
RATING (In)
THERMAL
OVERLOAD RELAY
0.27
0.02
MICROLOGIC 2.0A
150
30.00
30.00
160.00
160.00
160.00
8.0
16.0
4.00
20.0
Attachment-1
Table protection setting
5 Of 6
ADDITIONAL
RELAY
LRD-3359
LRD-3359
LR9-F7375
LR9-F7375
LR9-F7375
Remarks