MV SWITCHGEAR
No.

EQUIPMENT

DESCRIPTION

Load

FLA

Isc

BREAKER

Capacity
1
2
3
4
5
6
7

VCB
VCB
VCB
VCB
VCB
VCB
VCB

Incoming SWGR, from STG


Incoming SWGR, from DEG
FEEDER TO 01-TR-01
FEEDER TO 02-TR-01
FEEDER TO 02-TR-02
FEEDER TO 03-TR-01
FEEDER TO 04-TR-01

EVOLIS 1250
EVOLIS 1250
EVOLIS 630
EVOLIS 630
EVOLIS 630
EVOLIS 630
EVOLIS 630

Minimum Tripping
Time

Remarks

BREAKER

THERMAL

Remarks

RATING (In)

OVERLOAD RELAY

BREAKER

RELAY

RATING (In)
0.08
0.08
0.08
0.08
0.08
0.08
0.08

SEPAM S20
SEPAM S20
SEPAM T20
SEPAM T20
SEPAM T20
SEPAM T20
SEPAM T20

01-MCC-01
Rating
No.

EQUIPMENT NO

DESCRIPTION

BREAKER
FLA

Isc

Tstart

3000A

ACB,4P,NW32H1,3200A
Micrologic 2.0

0.27

18.5
18.5
15.0
15.0

def
def
def
def

3.0
3.0
3.0
3.0

MCCB,3P,NS80H-MA50
MCCB,3P,NS80H-MA50
MCCB,3P,NS100H-TM40D
MCCB,3P,NS100H-TM40D

0.005
0.005
0.02
0.02

8.0
36.0
20.0
8.0
24.0
12.0
8.0
8.0
8.0
12.0

MCCB,3P,NS100H-TM32D
MCCB,3P,NS160H-TM125D
MCCB,3P,NS100H-TM63D
MCCB,3P,NS100H-TM32D
MCCB,3P,NS100H-TM80D
MCCB,3P,NS100H-TM50D
MCCB,3P,NS100H-TM32D
MCCB,3P,NS100H-TM32D
MCCB,3P,NS100H-TM32D
MCCB,3P,NS100H-TM50D

0.02
0.02
0.02
0.02
0.02
0.02
0.02
0.02
0.02
0.02

(kW)

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

INCOMING

INCOMING BREAKER

01-P-01A

S/S 01 Pump 01A

01-P-01 B

S/S 01 Pump 01B

01-P-02 A

S/S 01 Pump 02A

01-P-02 B

S/S 01 Pump 02B

01-LP-01

Lighting Panel Area 01 A

01-LP-02

Lighting Panel Area 01 B

01-WO-01

Welding Outlet

00-LP-01

Lighting Panel Area 00 A

00-LP-02

Lighting Panel Area 00 B

00-LP-03

Lighting Panel Area 00 C

00-LP-04

Lighting Panel Area 00 D

00-LP-05

Lighting Panel Area 00 E

00-LP-06

Lighting Panel Area 00 F

00-LP-07

Lighting Panel Area 00 G

Minimum
tripping
time

LRC

Attachment-1
Table protection setting
1 Of 5

LRD-3355
LRD-3355

2/6

02-MCC-01
No. EQUIPMENT NO
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32

DESCRIPTION

RATING

S/S 02A Pump 01A

P-2101 B

S/S 02A Pump 01B

P-2102 A

S/S 02A Pump 02A

P-2102 B

S/S 02A Pump 02B

P-2103 A

S/S 02A Pump 03A

P-2103 B

S/S 02A Pump 03B

P-2104 A

S/S 02A Pump 04A

P-2104 B

S/S 02A Pump 04B

P-2105A

S/S 02A Pump 05A

P-2105B

S/S 02A Pump 05B

P-2106 A

S/S 02A Pump 06A

P-2106 B

S/S 02A Pump 06B

P-2107 A

S/S 02A Pump 07A

P-2107 B

S/S 02A Pump 07B

P-2108 A

S/S 02A Pump 08A

P-2108 B

S/S 02A Pump 08B

P-2109 A

S/S 02A Pump 09A

P-2109 B

S/S 02A Pump 09B

A-2101

S/S 02A Agitator motor 01

A-2102

S/S 02A Agitator motor 02

A-2103

S/S 02A Agitator motor 03

P-2110 A

S/S 02A Pump 10A

P-2110 B

S/S 02A Pump 10B

P-2111 A

S/S 02A Pump 11A

P-2111 B

S/S 02A Pump 11B

P-2112 A

S/S 02A Pump 12A

P-2112 B

S/S 02A Pump 12B

P-2113 A

S/S 02A Pump 13A

P-2113 B

S/S 02A Pump 13B

P-2113 C

S/S 02A Pump 13C

Isc

BREAKER

LRC

Tstart

ACB, 4P NW32H1
MCCB 4P, NS1000H

75.00
75.00
90.00
90.00
30.00
30.00
3.00
3.00
7.50
7.50
0.25
0.25
0.25
0.25
5.50
5.50
3.70
3.70
14.00
14.00
1.50
55.00
55.00
55.00
55.00
30.00
30.00
1.00
1.00
1.00

def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def

3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0

MCCB,3P,NS160H-MA150
MCCB,3P,NS160H-MA150
MCCB,3P,NS250H-MA220
MCCB,3P,NS250H-MA220
MCCB,3P,NS80H-MA80
MCCB,3P,NS80H-MA80
MCCB,3P,NS80H-MA12.5
MCCB,3P,NS80H-MA12.5
MCCB,3P,NS80H-MA25
MCCB,3P,NS80H-MA25
MCCB,3P,NS80H-MA1.5
MCCB,3P,NS80H-MA1.5
MCCB,3P,NS80H-MA1.5
MCCB,3P,NS80H-MA1.5
MCCB,3P,NS80H-MA12.5
MCCB,3P,NS80H-MA12.5
MCCB,3P,NS80H-MA12.5
MCCB,3P,NS80H-MA12.5
MCCB,3P,NS80H-MA50
MCCB,3P,NS80H-MA50
MCCB,3P,NS80H-MA6.3
MCCB,3P,NS160H-MA150
MCCB,3P,NS160H-MA150
MCCB,3P,NS160H-MA150
MCCB,3P,NS160H-MA150
MCCB,3P,NS80H-MA80
MCCB,3P,NS80H-MA80
MCCB,3P,NS80H-MA6.3
MCCB,3P,NS80H-MA6.3
MCCB,3P,NS80H-MA6.3

24.00
24.00
20.00
20.00
32.00

MCCB,3P,NS100H-TM80D
MCCB,3P,NS100H-TM80D
MCCB,3P,NS100H-TM63D
MCCB,3P,NS100H-TM63D
MCCB,3P,NS100H-TM100D

INCOMING 02-MCC-01
TIE BUS NORMAL DAN EMERGENCY
P-2101 A

FLA

(kW)
0

OTHERS

33
34
35
36
37

02-LP-01

Lighting Panel Area 02 A

02-LP-02

Lighting Panel Area 02 B

02-WO-01

Welding Outlet

02-WO-02

Welding Outlet

02-UPS-01

UPS A

Attachment-1
Table protection setting
2 Of 6

Minimum
tripping time
0.27

0.02
0.02
0.02
0.02
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.02
0.02
0.02
0.02
0.005
0.005
0.005
0.005
0.005

BREAKER
RATING
(In)
3000

THERMAL
OVERLOAD
RELAY

LR9-F5369
LR9-F5369
LR9-F5371
LR9-F5371
LRD-3359
LRD-3359
LRD-14
LRD-14
LRD-21
LRD-21
LRD-05
LRD-05
LRD-05
LRD-05
LRD-16
LRD-16
LRD-14
LRD-14
LRD-3353
LRD-3353
LRD-08
LR9-D5369
LR9-D5369
LR9-D5369
LR9-D5369
LRD-3359
LRD-3359
LRD-08
LRD-08
LRD-08

ADDITIONAL
RELAY
MICROLOGIC 2.0A
MICROLOGIC 2.0A

Remarks

3/6

02-MCC-02
No. EQUIPMENT NO
1
2

DESCRIPTION

Rating
(kW)

INCOMING 02-MCC-02
TIE BREAKER

3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22

P-2201 A
P-2201 B
P-2202 A
P-2202 B
P-2203 A
P-2203 B
P-2204 A
P-2204 B
P-2205 A
P-2205 B
P-2206 A
P-2206 B
P-2207 A
P-2207 B
P-2208 A
P-2208 B
P-2209 A
P-2209 B
P-2210 A
P-2210 B

23
24
25
26

02-LP-03
02-UPS-02
02-UPS-03
02-SH-1

S/S 02B Pump 01A


S/S 02B Pump 01B
S/S 02B Pump 02A
S/S 02B Pump 02B
S/S 02B Pump 03A
S/S 02B Pump 03B
S/S 02B Pump 04A
S/S 02B Pump 04B
S/S 02B Pump 05A
S/S 02B Pump 05B
S/S 02B Pump 06A
S/S 02B Pump 06B
S/S 02B Pump 07A
S/S 02B Pump 07B
S/S 02B Pump 08A
S/S 02B Pump 08B
S/S 02B Pump 09A
S/S 02B Pump 09B
S/S 02B Pump 10A
S/S 02B Pump 10B
OTHERS
Lighting Panel Area 02 C
UPS B
UPS C
Space Heater

FLA
0

30.00
30.00
22.00
22.00
1.50
1.50
1.50
1.50
75.00
75.00
15.00
15.00
1.50
1.50
3.70
3.70
2.20
2.20
2.20
2.20
32.00
32.00
32.00
20.00

Isc

BREAKER

Minimum
tripping time
0.27

LRC

Tstart

ACB 4P, NW20H1


NS1250H, 1250A

def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def
def

3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0

MCCB,3P,NS80H-MA80
MCCB,3P,NS80H-MA80
MCCB,3P,NS80H-MA50
MCCB,3P,NS80H-MA50
MCCB,3P,NS80H-MA6.3
MCCB,3P,NS80H-MA6.3
MCCB,3P,NS80H-MA6.3
MCCB,3P,NS80H-MA6.3
MCCB,3P,NS160H-MA150
MCCB,3P,NS160H-MA150
MCCB,3P,NS80H-MA50
MCCB,3P,NS80H-MA50
MCCB,3P,NS80H-MA6.3
MCCB,3P,NS80H-MA6.3
MCCB,3P,NS80H-MA12.5
MCCB,3P,NS80H-MA12.5
MCCB,3P,NS80H-MA6.3
MCCB,3P,NS80H-MA6.3
MCCB,3P,NS80H-MA6.3
MCCB,3P,NS80H-MA6.3

0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005
0.005

MCCB,3P,NS100H-TM100D
MCCB,3P,NS100H-TM100D
MCCB,3P,NS100H-TM100D
MCCB,3P,NS100H-TM63D

0.02
0.02
0.02
0.02

Attachment-1
Table protection setting
3 Of 6

BREAKER
RATING (In)
2000

THERMAL
OVERLOAD RELAY

LRD-3359
LRD-3359
LRD-3357
LRD-3357
LRD-08
LRD-08
LRD-08
LRD-08
LR9-F5369
LR9-F5369
LRD-3353
LRD-3353
LRD-08
LRD-08
LRD-14
LRD-14
LRD-10
LRD-10
LRD-10
LRD-10

ADDITIONAL
RELAY
MICROLOGIC 2.0A
MICROLOGIC 2.0A

Remarks

4/6

03-MCC-01
RATING
No.

EQUIPMENT NO

DESCRIPTION

FLA

LRC

Tstart

Isc

BREAKER

(Kw)
1

INCOMING

TIE BREAKER

ACB,4P,NW20H,2000A
Micrologic 2.0A
MCCB 4P, NS1000H

03-MCC-B

4
5
6
7
8

Minimum

BREAKER

tripping time

RATING (In)

THERMAL
OVERLOAD
RELAY

MICROLOGIC 2.0A

30.0

MCCB,3P,NS100H-TM100D

0.02

P-301 A

S/S 03 Pump 01A

15.00
15.00

P-302 A

S/S 03 Pump 02A

0.75

P-302 B

S/S 03 Pump 02B

0.75

Local Panel for Coal Handling System

18.0

3.0
3.0
3.0
3.0
3.0

0.005
0.005
0.005
0.005
0.02

LRD-3353

S/S 03 Pump 01B

def
def
def
def
def

MCCB,3P,NS80H-MA50

P-301 B

def
def
def
def
def

3.0
3.0
3.0
3.0
3.0

0.02
0.005
0.005
0.005
0.005

LR9-F5371

03-MCC-C

MCCB,3P,NS80H-MA2.5
MCCB,3P,NS80H-MA2.5
MCCB,3P,NS100H-TM50D

LRD-3353
LRD-07
LRD-07

ADDITIONAL

9
10
11
12
13

P-303 A

S/S 03 Pump 03A

90.00

P-303 B

S/S 03 Pump 03B

7.50

S/S 03 Pump 04

30.00

P-305 A

S/S 03 Pump 05A

30.00

P-305 B

S/S 03 Pump 05B

30.00

14
15
16
17
18
19
20
21

03-BC-01

Baterry charger

16.00

03-BC-02

Battery for STG

55.00

03-BC-03

Battery RCP STG

1.60

03-BC-04

Battery RCP DEG

1.60

03-CP-01

Cathodic Protection

4.00

03-LP-01

Lighting Panel Area 03 A

16.0

03-LP-02
03-WP-01

Lighting Panel Area 03B

24.0

Welding Outlet

20.0

P-304

MCCB,3P,NS250H-MA220
MCCB,3P,NS80H-MA25
MCCB,3P,NS80H-MA80
MCCB,3P,NS80H-MA80
MCCB,3P,NS80H-MA80

Others
MCCB,3P,NS100H-TM50D
MCCB,3P,NS160H-TM160D
MCCB,3P,NS100H-TM16D
MCCB,3P,NS100H-TM16D
MCCB,3P,NS100H-TM25D
MCCB,3P,NS100H-TM50D
MCCB,3P,NS100H-TM80D
MCCB,3P,NS100H-TM63D

Attachment-1
Table protection setting
4 Of 6

Remarks
RELAY

0.27

Local Panel for STG

MCCB,3P,NS80H-MA50

ADDITIONAL

0.02
0.02
0.02
0.02
0.02
0.02
0.02
0.02

LRD-21
LRD-3359
LRD-3359
LRD-3359

5/6

04-MCC-01
No. EQUIPMENT NO

1
2

DESCRIPTION

Rating
(kW)

Tstart

INCOMING 04-SWGR-01

TIE BREAKER

ACB 4P, NW20H1


Micrologic 2.0
MCCB 4P, NS1000H

def
def
def
def
def

3.0
3.0
3.0
3.0
3.0

MCCB,3P,NS80H-MA80
MCCB,3P,NS80H-MA80
MCCB,3P,NS400H-MA320
MCCB,3P,NS400H-MA320
MCCB,3P,NS400H-MA320

0.005
0.005
0.02
0.02
0.02

MCCB,3P,NS100H-TM32D
MCCB,3P,NS100H-TM50D
MCCB,3P,NS100H-TM16D
MCCB,3P,NS100H-TM63D

0.02
0.02
0.02
0.02

04-MCC-A

Local Panel Water Treatment

4
5
6
7
8

P-401 A
P-401 B
P-411 A
P-411 B
P-411 C

9
10
11
12

04-LP-01
04-LP-02
04-CP-01
04-WO-01

S/S 04 Pump 01A


S/S 04 Pump 01B
Cooling Water Pump 11 A
Cooling Water Pump 11 B
Cooling Water Pump 11 C
Others
Lighting Panel Area 05 A
Lighting Panel Area 05 B
Cathodic Protection
Welding Outlet

Isc

Minimum
Tripping time

LRC

FLA

BREAKER

BREAKER
RATING (In)

THERMAL
OVERLOAD RELAY

0.27
0.02

MICROLOGIC 2.0A

150
30.00
30.00
160.00
160.00
160.00
8.0
16.0
4.00
20.0

Attachment-1
Table protection setting
5 Of 6

ADDITIONAL
RELAY

LRD-3359
LRD-3359
LR9-F7375
LR9-F7375
LR9-F7375

Remarks