CENTELSA ENERWIND - CENTELSA AEOLIC USE CABLES / CENTELSA ENERWIND -CENTELSA AEOLIC USE CABLES

Step-Up
Transformer
Step-Up
Substaton
Juncton
Box Botom
Juncton
Box (Top)
C o n t r o l l e r
Generator
Collecton
Tower
Cables
Point
Collecton
Point
Collecton
System
Nearby Town
Cites
Collecton
System
Collecton
System
Cables
Cables
Cables
Transmission
Lines
EOLIC POWER:
In Greek Mithology, Aeolus was
the ruler or keeper of the winds






HARVESTING THE WIND
A new approach to energy ofers a clear path to
a more secure and prosperous future and a more
livable world. Increased use of wind, solar and
other renewable energy sources will spur
economic growth, protect consumers from price
spikes or supply shortages associated with
global fuel markets, and dramatically reduce the
pollution and global warming which harms our
planet.
CENTELSA is committed to improving en-
vironmental quality and ensuring compliance
with all environmental requirements. We
believe that a secure and reliable energy system
is essential for economic development and
protection of the environment.
CENTELSA collaborates with costumers to
develop a fexible delivery schedule that best
meets the clients project and construction
schedule. Additionally, CENTELSA provides
engineering support to assist clients in aligning
cable specifcations with industry standards to
ensure they are specifying the optimal products
for specifc application.
Some projects where CENTELSAs cables were
installed include Among other:
Cedar Creek - Colorado
Benton County - Indiana
Fowler - Indiana
Combine Hill - Oregon
Grand Ridge - Texas
Inandale - Texas
Papolote Creek - Texas
Pyron - Texas
Roscoe I & II - Texas
Sweetwater - Texas
Milford Corridor - Utah
WIND: A LEADING SOURCE
OF NEW ELECTRICITY
GENERATION
Wind energy has been historically used
directly to propel salling ships or converted
into mechanical energy for pumping water or
grinding grain, but the principal application
of wind power today is the generation of
electricity: Large scale wind farms are
typically connected to the local electric
power transmission network, with diferent
sizes turbines being used to provide
electricity to isolated locations and the
major cities worldwide. Wind energy as a
power source is favored by many
environmentalists as an alternative to fossil
fuels, as it is plentiful, renewable, widely
distributed, clean, and produces lower
greenhouse gas emissions.
Whether it is terrestrial or ofshore wind
farms requiring high-performance cables,
CENTELSA ofers a full array of cables needed
for wind turbines to generate, distribute and
transmit energy.
Wind Power, Renewable
Energy For the Future
CABLES FOR WIND ENERGY APPLICATIONS
Plants and Headquarters: Calle 10 No 38 - 43 Urb. Industrial Acopi, Yumbo PBX: 608 3400
www.centelsa.com.co / e-mail: sales@centelsa.com.co
MEDIUM VOLTAGE CABLES 5 kV - 69 kV
Applications: Power distribution in wind turbines for installation indoors or outdoors, wet or dry locations,
in any raceways, cable tray, messenger supported wiring, underground ducts and direct buried.
Compliance: AEIC CS8 - ICEA S-94-639 UL 1072
LOW VOLTAGE ALUMINUM ALLOY POWER CABLES 600 & 2000 Volts.
Applications: Power distribution in wind turbines, for generators and step-up transformers; indoors, in wet or
dry locations, and in any raceway.
Compliance: UL 44 UL VW-1 ICEA S 95-658/NEMA WC70 UL FT4
LOW VOLTAGE POWER & CONTROL CABLES 600 & 2000 Volts.
Applications: Power distribution in wind turbines, for controllers, high-speed shaft, and brakes; indoors or
outdoors, in wet or dry locations, and in any raceway.
Compliance: UL 44 UL 1277 - UL VW-1 ICEA S 95-658/NEMA WC70 UL FT4
LOW VOLTAGE INSTRUMENTATION CABLES 300 & 600 Volts.
Applications: Instrumentation circuits in wind turbines; for controllers, high speed shaft, and brakes; indoors or
outdoors, in any raceway or underground duct, cable tray, direct buried, open runs, or supported by a messen-
ger.
Compliance: UL 44 UL 2250 - UL VW-1 ICEA S 95-658/NEMA WC70 UL FT4
Product Line Insulation Jacket NED Code Types Voltage and Temperature Ratings
URD Underground distribution TR-XLPE OR EPR PE N/A 5 kV 69 kV, 90C & 105C
Product Line Insulation Jacket NED Code Types Voltage and Temperature Ratings
AEOLIC USE Premium (-40C, FT4) XLPE - UL TYPE RHW-2 600 V & 2000 V, 90C, -40C FT4
AEOLIC USE Standard (-25C, FT2) XLPE - UL TYPE RHW-2 600 V & 2000 V, 90C, -25C FT2

Product Line Insulation Jacket NED Code Types Voltage and Temperature Ratings
Power and Control
XLPE-FR CPE UL TYPE TC 600 V & 2000 V, 90C
EPR CPE UL TYPE TC 600 V & 2000 V, 90C

Product Line Insulation Jacket NED Code Types Voltage and Temperature Ratings
Instrumentation
UL TYPE -
-
-
-
PLTC & TC 300 V, 90C
UL TYPE PLTC & TC 300 V, 90C
BARE ALUMINUM TRANSMITION CABLES
Applications: Set up substation applications as well as open- air high voltage power transmission to the grid.
Compliances: Applicable ASTM

Product Line Construction Jacket NED Code Types Voltage and Temperature Ratings
Bare Aluminum Overhead ACAR, ACSR, AAAC N/A N/A According Power Transmition System
STANDARDS
OPTIONAL CONSTRUCTIONS
NOTE
AEIC CS8, Specifcation for Extruded Dielectric
Shielded Power Cables Rated 5 through 46 KV
ICEA S-94-649, Concentric Neutral Cables Rated
5 through 46 kV
UL 1072, Medium-Voltage Power Cables
Other concentric neutral confguration
available upon request
Copper grounding conductors available upon
request
No magnetic armour
Optional insulation in EPR or HEPR
Medium Voltage Cable
Electrical Distribution (XLPE - TR)
CENTELSA ENERWIND
COLLECTION SYSTEM CABLES
XLPE - TR
Insulation
APPLICATION
Medium voltage cables to connect individual
wind turbine generators pad mount transform-
ers to either the wind turbine generator or the
collection interconnection.
For indoor or outdoor installations, wet or dry
locations, in a raceway, cable tray, messenger
supported wiring, underground ducts and direct
buried.
FEATURES
CENTELSA Cables are manufactured and tested
in accordance with the latest revisions of the
following standards:
Optional constructions and other not indicated
available upon request.
IDENTIFICATION
TEMPERATURE RATING
CENTELSA ENERWIND MV cables meets or
exceeds ICEA S-94-649 Standard
XLPE-TR (Cross Linked Polyethylene - Tree
Retardand) insulation meeting the require-
ments of the referenced standards
Water blocking confguration
The jacket contains three longitudinally
extruded red stripes, and inkjet marking on the
cable Identifcation methods specifed upon
request.
90C
105C upon request
Halogen and heavy metals free, black
polyethylene extruded to fll jacket
whit 3 red extruded stripes
Semiconductive compound
insulation shield
Semiconductive compound
conductor shield
Concentric neutral. Soft
Copper metallic shield,
optional extruded to fll
jacket
Aluminum or
Copper conductor
blocked against moisture
W
e

C
o
n
n
e
c
t

T
o

T
h
e

F
u
t
u
r
e

W
i
t
h

C
l
e
a
n

E
n
e
r
g
y
W
e

C
o
n
n
e
c
t

T
o

T
h
e

F
u
t
u
r
e

W
i
t
h

C
l
e
a
n

E
n
e
r
g
y
B
u
i
l
d
i
n
g

a

N
e
w

E
n
e
r
g
y

F
u
t
u
r
e

P
r
o
t
e
c
t
i
n
g

t
h
e

E
n
v
i
r
o
n
m
e
n
t
B
u
i
l
d
i
n
g

a

N
e
w

E
n
e
r
g
y

F
u
t
u
r
e

P
r
o
t
e
c
t
i
n
g

t
h
e

E
n
v
i
r
o
n
m
e
n
t
Medium Voltage Cable
Electrical Distribution (XLPE - TR)
CENTELSA ENERWIND
COLLECTION SYSTEM CABLES
ENERWIND 35 kV Electrical Distribution Cables Installed in Wind Farms
345 mils (nominal) XLPE - TR Insulation
ENERWIND 46 kV Electrical Distribution Cables Installed in Wind Farms
445 mils (nominal) XLPE - TR Insulation
Conductor Neutral Cable
Jacket

Extruded
to Fill
Jacket
Extruded
to Fill

Approximated
Total
Cable Weight
Size Diameter
Wires Size
No. of Wires
Outside
Diameter
Outside
Diameter
Thickness
AWG/kcmil mils mm No.
Size
AWG
mils mm mils mm lbs/1000 ft Kg/km
1/0 362 9,2 19 FULL 16 14 1438 36,5 55 1,4 951 1415
1/0 362 9,2 19 1/2 8 14 1438 36,5 55 1,4 855 1272
1/0 362 9,2 19 1/3 6 14 1438 36,5 55 1,4 831 1237
1/0 362 9,2 19 2/3 11 14 1438 36,5 55 1,4 891 1326
3/0 456 11,6 19 FULL 16 12 1566 39,8 55 1,4 1228 1827
3/0 456 11,6 19 1/2 13 14 1532 38,9 55 1,4 1048 1559
3/0 456 11,6 19 1/3 9 14 1532 38,9 55 1,4 1000 1488
4/0 512 13,0 19 FULL 20 12 1681 42,7 85 2,2 1454 2164
4/0 512 13,0 19 1/2 16 14 1588 40,3 55 1,4 1169 1739
4/0 512 13,0 19 1/3 11 14 1588 40,3 55 1,4 1109 1650
350 661 16,8 37 1/3 18 14 1797 45,6 85 2,2 1512 2250
350 661 16,8 37 1/6 9 14 1797 45,6 85 2,2 1404 2089
500 789 20,1 37 1/3 16 12 1993 50,6 85 2,2 1940 2887
500 789 20,1 37 1/6 13 14 1959 49,8 85 2,2 1750 2604
750 968 24,6 61 1/6 19 14 2138 54,3 85 2,2 2223 3308
750 968 24,6 61 1/12 10 14 2138 54,3 85 2,2 2115 3147
1000 1118 28,4 61 1/6 16 12 2321 59,1 85 2,2 2725 4055
1000 1118 28,4 61 1/12 13 14 2288 58,1 85 2,2 2528 3762
1250 1250 31,8 61 1/6 20 12 2454 62,3 85 2,2 3058 4550
1250 1250 31,8 61 1/12 16 14 2420 61,5 85 2,2 2817 4192
Conductor Neutral Cable

Approximated
Cable Weight
Total

Size Diameter
Wires Size
No. of Wires

Thickness
AWG/kcmil mils mm No.
Size
AWG
mils mm mils mm lbs/1000 ft Kg/km
4/0 13,0 19 FULL 20 12 1877 47,7 85 2,2 1682 2503
4/0 512
512
13,0 19 1/2 16 14 1843 46,8 85 2,2 1454 2164
4/0 512 16,8 19 1/3 11 14 1843 46,8 85 2,2 1394 2074
350 661 16,8 19 1/3 18 14 2026 51,5 85 2,2 1800 2678
350 661 16,8 19 1/6 9 14 2026 51,5 85 2,2 1692 2518
500 789 20,1 37 1/3 16 12 2188 55,6 85 2,2 2207 3284
500 789 20,1 37 1/6 13 14 2155 54,7 85 2,2 2012 2994
750 968 24,6 61 1/6 19 14 2333 59,3 85 2,2 2508 3732
750 968 24,6 61 1/12 10 14 2333 59,3 85 2,2 2400 3571
1000 1118 28,4 61 1/6 16 12 2517 63,9 85 2,2 3033 4513
1000 1118 28,4 61 1/12 13 14 2483 63,1 85 2,2 2832 4214
1250 1250 31,8 61 1/6 20 12 2649 67,3 85 2,2 3382 5032
1250 1250 31,8 61 1/12 16 14 2616 66,4 85 2,2 3138 4669
W
i
n
d

P
o
w
e
r
,

R
e
n
e
w
a
b
l
e

E
n
e
r
g
y

F
o
r

T
h
e

F
u
t
u
r
e
W
i
n
d

P
o
w
e
r
,

R
e
n
e
w
a
b
l
e

E
n
e
r
g
y

F
o
r

T
h
e

F
u
t
u
r
e
AA-8000 Conductor
XLPE Insulaton
APPLICATION
2000 V thermosetting cross-linked polyethylene
insulated, UL listed E137698 cables used for power
distribution in wind turbines (tower and collection
system cables), for step-up transformers and
generators, in indoors and outdoors, in wet and dry
locations.
FEATURES
Meets FT4/UL fame test for Premium Grade
and FT2/UL fame test for Standard Grade
Rated at -40C/90C for Premium Grade
Rated at -25C/90C for Standard Grade
Oil, grease, water, and abrasion resistant
Smooth surface for reduced coefcient of
friction
Low power factor
IDENTIFICATION
Marking over insulation:
AEOLIC USE (PREMIUM) or (STANDARD) GRADE -
RHH/RHW-2 (AA-8000) 2000 V 90C XLPE (-40C) or
(-25C) (UL) E137698.
Additional information and optional markings upon
TEMPERATURE RATING
UL Type PREMIUM RHHW/RHW-2 Rated
at -40C/90C
UL Type STANDARD RHHW/RHW-2
Rated at -25C/90C
STANDARDS
Low voltage AEOLIC USE UL Type RHHW/RHW-2
AA-8000 cables are manufactured and tested in
accordance with the latest revisions of the
following standards:
ASTM B800 Standard Specifcation for 8000
Series Aluminum Alloy Wire for Electrical
Purposes-Annealed and Intermediate Tempers.
ASTM B801 Standard Specifcation for
Concentric-Lay-Stranded Conductors of 8000
Series Aluminum Alloy for Subsequent Covering
or Insulation.
UL 44 Thermoset-Insulated Wires and Cables.
UL 854 Service-Entrance Cables (for USE-2)
NFPA70: National Electrical Code.
OPTIONAL CONSTRUCTIONS
EPR Insulation
Material can be produced at specifc
lengths upon request
NOTE
Optional constructions and other not indicated
available upon request.
TOWER SYSTEM CABLES
Low Voltage Aluminum Alloy (AA - 8000) Power Cable
Premium & Standard Grade RHHW/RHW-2 2000 V
CENTELSA AEOLIC USE
request
F
r
o
m

N
a
t
u
r
e
,

C
l
e
a
n

E
n
e
r
g
y

T
o
d
a
y

F
o
r

O
u
r

F
u
t
u
r
e

G
e
n
e
r
a
t
i
o
n
s
F
r
o
m

N
a
t
u
r
e
,

C
l
e
a
n

E
n
e
r
g
y

T
o
d
a
y

F
o
r

O
u
r

F
u
t
u
r
e

G
e
n
e
r
a
t
i
o
n
s
STANDARD GRADE FT2, -25C
RHHW/RHW-2 8000 Series Aluminum Alloy 2000 V 90C XLPE

PREMIUM GRADE FT4, -40C
RHHW/RHW-2 8000 Series Aluminum Alloy 2000 V 90C XLPE

Low Voltage Aluminum Alloy Power Cable
Premium & Standard Grade (AA - 8000) RHHW/RHW-2 2000 V
CENTELSA AEOLIC USE
TOWER SYSTEM CABLES
Size

Diameter


Insulation
Thickness

Outside Diameter
Cable Weight
Total Approximated
AWG or
kcmil

mils mm mils mm mils mm lbs /1000 ft kg/km
2 268,1
6,81
70 1,8 414 10,5 96
1/0 335,4
8,52
90 2,3 524 13,3 152
2/0 376,8
9,57
90 2,3 566 14,4 183
3/0 423,2
10,75
90 2,3 612 15,5 221
4/0 475,2
12,07
90 2,3 664 16,8 267
250 521,7
13,25
105 2,7 742 18,8 329
300 571,7
14,52
105 2,7 792 20,1 383
400 659,8
16,76
105 2,7 88 1 22,4 490
500 737,8
18,74
105 2,7 958 24,3 595
750 909,4
23,1
120 3,0 1161 29,5 887
900 996,5
25,31
120 3,0 124 8 31,7 1044
1000 1050,4
26,68
120 3,0 1302 33,1 1148
143
226
272
329
397
490
570
729
885
1320
1553
1708
Size

Conductor

Diameter


Insulation
Thickness

Cable
Outside Diameter

Cable Weight
Total Approximated

AWG or
kcmil
mils mm mils mm mils mm lbs /1000 ft kg/km
2 268,1
6,81 70 1,8 414 10,5 108
1/0 335,4
8,52
90 2,3 524 13,3 172
2/0 376,8
9,57
90 2,3 566 14,4 205
3/0 423,2
10,75
90 2,3 612 15,5 245
4/0 475,2
12,07
90 2,3 664 16,8 294
250 521,7
13,25
105 2,7 742 18,8 363
300 571,7
14,52
105 2,7 792 20,1 420
400 659,8
16,76
105 2,7 88 1 22,4 531
500 737,8
18,74
105 2,7 958 24,3 640
750 909,4
23,1
120 3,0 1161 29,5 951
900 996,5
25,31
120 3,0 124 8 31,7 1113
1000 1050,4
26,68
120 3,0 1302 33,1 1220
161
256
305
365
437
540
625
790
952
1415
1656
1815
Conductor
Values here indicated are subject to normal manufacturing and/or standards tolerances.
Values here indicated are subject to normal manufacturing and/or standards tolerances.