You are on page 1of 18

GE Industrial Systems

Intelligent Energy
Management

- IEM

Product Management
GE Industrial Systems - UPS
High reliability based on Parallel-UPS creates high
operating cost

Why ?

Low UPS-efficiency in low-load conditions
Intelligent Energy Management
The Challenge

Reliability Efficiency
The GE Digital Energy solution:
Intelligent Energy Management
A
IEM
Intelligent Energy Management
UPS: Cost of Ownership
1. Purchasing Cost & Installation Cost
2. Direct Operating Cost
Efficiency = Energy Losses = Heat
3. Indirect Operating Cost
Heat = air conditioning / Ventilation
4. Maintenance Cost

40%
19%
22%
19%
Purchasing
cost
Direct
operating cost
Indirect
operating cost
Maintenance
cost
Cost of ownership mid-range UPS
Relative Cost
10%
38%
15%
37%
Purchasing
cost
Direct
operating cost
Indirect
operating cost
Maintenance
cost
Cost of ownership High-End UPS
Relative Cost
Typical Load Situation
Load
Time
100%
20%
20%
Example

70%
30%
Weekly Load situation
Full load : 5 x 10 = 50 hours
Partial load: 5 x 14 + 2 x 24 = 118 hours
LOAD 300 kVA
75 %
Time
Load
8.00 18.00
LOAD = 100 %
Load%
Efficiency
4 UPS
UPS 1 - 100 kVA
UPS 2 - 100 kVA
UPS 3 - 100 kVA
UPS 4 - 100 kVA
Full-Load Condition
75 %
75 %
75 %
LOAD 60 kVA
8.00
Time
18.00
LOAD = 20 %
Load
Load%
Efficiency
4 UPS
UPS 1 - 100 kVA
UPS 2 - 100 kVA
UPS 3 - 100 kVA
UPS 4 - 100 kVA
Partial-Load Condition
15 %
15 %
15 %
15 %
UPS 1 - 100 kVA
UPS 2 - 100 kVA
UPS 3 - 100 kVA
UPS 4 - 100 kVA
LOAD 60 kVA
Time 18.00 8.00
LOAD = 20 %
Load
Load%
Efficiency
2 UPS
30 %
30 %
Partial Critical Load Condition with IEM
(UPS Redundancy)
Partial-Load Condition
LOAD 60 kVA
Load
Time
18.00 8.00
LOAD = 20 %
Load%
UPS 1 - 100 kVA
UPS 2 - 100 kVA
UPS 3 - 100 kVA
UPS 4 - 100 kVA
Partial non-Critical Load Condition with IEM
(Utility Redundancy)
Efficiency
1 UPS
60 %
Partial-Load Condition
Parameters Used
Number of UPS : 4
Full load condition: 75%
Partial load condition:
10%
Losses : according to the efficiency curves of the UPS*
Cost per kW/h: 0.11 US$
Weekly hours at full load : 50 h
Weekly hours at partial load : 118 h
*: Load Efficiency
75% 94%
50% 93%
30% 87.5%
15% 79%
Yearly Cost Savings
10
15
20
30
40
60
80
100
120
160
200
250
330
400
500
0
5000
10000
15000
20000
25000
30000
35000
UPS POWER (kVA)
IEM Savings with Utility redundancy
IEM Savings with UPS redundancy
US$
IEM is available for:
UP TO 8 UNITS in Parallel
10-20-30-40 kVA
60-80-100-120 kVA
150-200-250-300 kVA


Cost of
ownwership
Application
and customer
needs
GE Digital Energys Mission
We accept your challenge
GEs
RPA
IEM
Technology for the Digital World

You might also like