Technical catalogue

Low-voltage moulded-case
circuit-breakers

604050/012 en

Contents

ABB SACE

Presentation

Main features

Ranges

Accessories

Characteristic curves and


technical information

Dimensions and circuit diagrams

Order codes

7
1/1

SACE Isomax S.
The greatest project for moulded-case circuit-breakers
A single series for all applications
SACE Isomax S is a project which evolves continually and is today the largest and
most complete family of low voltage moulded-case circuit-breakers on the market,
able to fulfil all installation requirements, from the small user up to large industrial
electrical power distribution

plants.

Innovation, Technology and Quality have always been the main guides for ABB
SACE in developing products and are at their peak in the SACE Isomax S series
the moulded-case circuit-breakers characterised by high quality, reliability, and

performance under all conditions, simplicity of installation and safety of operation.


The continual and constant evolution of the series has led to further extending the
range of products, thereby making the SACE Isomax S offer increasingly complete
over time.
The series, which is divided rationally into eight basic sizes from S1 to S8, does, in
fact, consist of different ranges destined to fulfil any installation need in a specific
and optimal way.

The completeness of the series can also


be noted in better rationalisation of use:
the overall dimensions, methods of
installation and possibility of applying
accessories are all the same, regardless
of the type of range the circuit-breaker is
placed in.
Great importance is also put on the
microprocessor-based electronic
releases (mounted on the circuitbreakers starting from 160A): SACE
PR211/P, PR212/P and SACE PR212/MP
(International ABB SACE Patent),
specifically designed to actuate dedicated functions for motor starting and
protection.
Thanks to innovative and state-of-the-art
protection functions, they ensure
reliability and precision and are unaffected by electromagnetic interference.
A basic characteristic of these types of
releases is their ability to communicate
and dialogue with the SACE SD-View 810
self-configuring software, thereby
allowing full integration of the circuitbreakers in the management logics
relative to electric network supervision
and control systems.

1/2

ABB SACE

The new series has


been studied
respecting the most
modern ergonomic
criteria. Witness to
this is the prize
awarded with the IF
seal to the circuitbreakers at the
Design Forum in
Hannover.

GSIS9071

ABB SACE

1/3

A world of solutions for installation design


engineering.
An answer to all requirements.
The SACE Isomax S family is divided into eight basic sizes, S1,
S2, S3, S4, S5, S6, S7 and S8 with rated uninterrupted currents
from 125 to 3200A.
The types of devices consist of: fixed, plug-in and withdrawThanks to its special construction char-

able circuit-breakers with seven ultimate rated breaking ca-

acteristics, this range of circuit-breakers combines normal Isomax safety

pacity levels - from 16 to 200kA (380-415V) - identified by the

characteristics with very high perform-

letters:

(double interruption per pole) and the


special shape of the breaking parts,
allow very high value short-circuit cur-

sidered

the

common

rents (200kA) to be tripped

GSIS9072

From this family, which is con-

extremely

rapidly, making these circuit-breakers


ideal wherever protection close to the

nu-

power supply source is needed.

cleus, a series of dedicated


ranges are configured, which
keep the same installation
characteristics and accessory application possibilities.
Alternating current

Within the series there are


therefore

circuit-breakers

available for alternating and


direct current distribution, current-limiting circuit-breakers,
circuit-breakers for motor protection, switch-disconnectors,
circuit-breakers for applications with voltages up to 1000V,

V
V~

V
V

Direct current

Circuit-breakers with thermomagnetic

Pole connection in series allows appli-

releases and circuit-breakers fitted with

cations in the most severe operating

microprocessor-based SACE PR211/P,

conditions and in any type of network

PR212/P releases are available for pro-

(insulated, with earthed polarity, and with

tection of alternating current networks.

median point of the power supply

These feature an application field from

earthed). The circuit-breakers for direct

10 to 3200A and a rated voltage of 690V.

current with thermomagnetic releases

Apart from the more generic applica-

are available for operating currents be-

tions, they are particularly suited to pro-

tween 10A and 800 A, with rated

tection of generators, capacitors, trans-

voltages up to 750 V, with 3 poles in

formers and machine tools.

series, and 250 and 500V, with two poles


in series.

and residual current circuitbreakers, as well as specific


ranges (for motor protection
and switch-disconnectors)

Centralised supervision

complying

and control

with

the

North

American UL489 and CSA


C22.2 Standards.
This means wider application
possibilities both in industrial

systems
The reliability,
efficiency

and

quality

of

LV

electrical power

The range for applications at 1000V in

distribution service

and civil sectors.

is considerably in-

They can therefore be mounted

creased by constant

alternating current and direct current


extends the use of the moulded-case
circuit-breakers even further and is a

supervision of users

in primary (Power Center) and

and all the parameters of the installa-

secondary (Panel Board) dis-

tion itself. The information regarding

tor protection and control (Motor Control Center), in genera-

tion of the SACE Isomax S series. They


are particularly suitable for installation

the installations is collected using mi-

in special ambients, such as mines,

croprocessor-based field components


which can be mounted directly on board
the apparatus, such as the SACE
PR212/P release, or using the devices

tors and for end users. Their

in the SACE SD family. Moreover, the

performances are, however, of

use of the SACE SD-View 810 software

GSIS9073

tribution switchboards, for mo-

good example of the continual evolu-

petrochemical plants and for electric


traction.

allows a simple personal computer to

particular interest where criti-

be converted into a work station for

cal situations arise (very high

supervising and controlling electrical

rated and fault currents), or

power distribution plants.


ABB SACE proposes various solutions,
which allow type 2 coordinations to be

where complex plant engi-

made for switching and protecting mo-

neering solutions are needed

tors, from 0.37kW to 355kW.


It is possible to select either circuit-

(special coordination require-

breakers suited just to protection

ments and plant automation).

against short-circuit, or circuit-break-

They also guarantee total selectivity of the protections up


to full breaking capacity of the
circuit-breaker installed on the

ers fitted with the new SACE PR212/MP

GSIS9074

ances. The breaking technique used

B, N, S, H, L, V, X.

electronic release, which is technologically advanced and has been specifically studied for motor protection. The
latter integrates protection functions on

load side.

1/4

ABB SACE

The switch-disconnectors are derived from


the corresponding circuit-breakers, keeping
the overall dimensions, versions and
accessories unchanged. They guarantee

SACE Isomax S
current-limiting
circuit-breakers

operation and isolation in maximum safety


and their release device can be activated

SACE Isomax S
switch-disconnectors

either by the undervoltage release or by


the shunt opening release. They can also

GSIS9091

be fitted with residual current releases,


thereby constructing pure residualcurrent circuit-breakers.

GSIS9093

GSIS9075

SACE Isomax S
Power distribution

SACE Isomax S
for applications
up to 1000V

SACE Isomax S
according to UL/CSA
Standards

Thanks to a specific range of SACE Isomax S circuit-breakers complying


with the UL489 and CSA22.2 Standards, there are also greater possibilities for those customers operating on markets subject to the specifications defined in the North American standards.

The range consists of

seven sizes with rated uninterrupted current from 100A to 2500A and
breaking capacities, at 480 V AC, which can reach 100kA.
board the circuit-breaker which are nor-

Within the basic series, there are circuit-breakers with magnetic only

mally carried out by other devices,

releases (MCP - Motor Control Protection) for motor protection, and

thereby ensuring numerous installation

switches (Moulded-Case Switch - MCS) for use as isolators or switching

and service advantages.

devices for lines, busbars or plant parts.

SACE Isomax S
for motor protection
classical and advanced

ABB SACE

1/5

A world of success

The SACE Isomax S offer has been constantly renewed according to market
requirements and often even anticipating these and is always to the fore from
the technological viewpoint. Meanwhile, the quality and reliability have always
remained at the maximum levels expected and the market has shown its appreciation of this.

Behind every reference lies a require-

ABB SACE apparatus is also responsi-

ment fulfilled. It is facts which speak for

ble for protection (sometimes also

SACE Isomax S. SACE Isomax S is a

integrated with control functions) of

highly successful product of recog-

plants of considerable economic and

nised quality, with many fields of

technological importance, constructed

application and it involves different

within the sphere of large infrastruc-

sectors all over the world,

ture projects. Orders are processed

with either

standard or highly personalised

which stand out both for their size

products. There is nowhere electrical

(such as the pumping stations of gas

power is used where SACE Isomax S is

pipelines thousands of kilometres

not to be found: manufacturing indus-

long) and for their advanced context

tries, steelworks, refineries and

(astronomical observatories and

chemical plants, drilling rigs, gas

international research centres).

pipelines, water pipelines, hospitals,

SACE Isomax S imposes itself on the

airports, trains, railway and under-

markets worldwide. For example,

ground railway stations, calculation

apparatus has been supplied to some

centres, offices, congress centres,

of the most important European and

theatres, and skyscrapers, as well as

Middle Eastern electricity boards as

the most prestigious buildings world-

well as to North American and Asian

wide.

electrified transport companies.

Protection and control


in installations for electric
traction

ABB SACE has, moreover, acquired


knowledge which is practically
unsurpassed in application areas
where the highest degree of safety is
required, and this has qualified it as

Particularly severe

the world leader in various sectors.

environmental conditions

Thousands of ships of all types

such as mines and steelworks

cruise ships, container ships, bulk


carriers, tankers, etc. and flying the
flags of all nations are equipped with
ABB SACE products, which are also
widely used in railway traction and are
the favourite product in the depths of
mines.

Refineries and chemical plants


as well as
gas pipelines, water pipelines

Installation on board ships

1/6

ABB SACE

Offices, theatres,
shopping malls and residential

GSIS9076

complexes

Underground railway
stations

Off-shore drilling rigs

Protection and control


of motors, generators

ABB SACE

1/7

Selection and design engineering tools,


management flexibility, services and consultancy:
an all-round offer
With the aim of guiding and facilitating selection of its products, ABB SACE
ensures 360 support, both before and after the sale. For this purpose, to design
and size electrical installations, it makes various work tools available, which
facilitate calculations, ensure compliance of the installation with the Standards
and reduce the risks of any errors.
These are basically divided into calculation, design and estimate software, and
manual tools.

1
D.O.C. (Design Optimization

The calculation methods and

& Computation) is a system

data indicated on the slide

which allows correct sizing of

rules are taken from the CEI,

industrial low voltage electri-

IEC and NFC Standards in

cal installations, able to pro-

force and from installa-

pose the most suitable design

tion practice.

selections regarding cables,

gineer to develop clear and

Guide to low
voltage installations is a brief

complete design documenta-

collection of le-

tion rapidly, based on the cal-

gal and techni-

culation models provided by

cal regulations

the most recent standards.

based

busbars and protection devices. It allows the design en-

C.A.T.

The

on

the

(Computer Aided

current stand-

Technical Selection) is both

ards, regarding

an electronic catalogue and

design, sizing

a technical aid tool for select-

and installation

ing and applying accessories

of

to each individual circuit-

plant.

breaker.

The guide takes into

By means of a guided path-

consideration the user

way, it is possible to select,

plant from the electric

configure and order the most

power delivery point (MV/LV

suitable apparatus for your

substation) in 1

own installation requirements.

systems.

Slide rules

an

electrical

st

category

colours, which make up the

Immediate ordering
and management flexibility

ABB Kits, allow rapid sizing

Rapid ordering procedures

calculations of the electrical

have been provided for cir-

installation. The following can

cuit-breakers in the SACE

be carried out:

Isomax S series, and the con-

Cable sizing and calcula-

figuration logic of the series

tion of the short-circuit cur-

enables efficient and flexible

rents (yellow slide rule)

warehouse management.

Checking the protections

An order file can be generated

against direct contact and

compatible with the EDIFACT

short-circuit of the cables

(Metel or ABB) standard, ready

(orange slide rule)

to be converted into EDI for-

Selective and back-up co-

mat and transmitted electroni-

ordination (green slide rule)

cally.

Four

of different

Sizing of motor lines and


transformer outgoing feeders (blue slide rule)

1/8

ABB SACE

1
Using EDI (Electronic Data In-

notes, under the guidance of

terchange) to send orders ra-

experts. Information and train-

tionalises the logistics chain,

ing have always been suc-

thereby reducing transit times

cess factors for professional

and the risk of errors. EDI

growth and development.

transmission allows the order

Professional refresher training

to be loaded automatically at

on both technical aspects and

ABB SACE so that the request

product developments, as well

is immediately sent to pro-

as on the standards and leg-

duction, together with the

islation, is essential, consid-

acknowledge-

ering that these have such im-

ment to the customer.

portant implications for the

The availability of

safety of people and plants.

standardised ac-

The primary aim is to meet the

order

for

information needs of profes-

g ro u p s o f c i r-

sionals, especially by convert-

cuit-breakers

ing the technical-standard

makes it pos-

and legislative concepts into

cessories

sible

to

duce

re-

practical terms which can be

the

applied directly to the various

number kept

products and installations.

in the warehouse

and

ABB SACE Service

short

Training courses are also pro-

procurement

vided for operators and main-

very

allow

tenance personnel who work

limited stocks

on ABB SACE apparatus and

to be kept as

systems. For this purpose and

times

be

to meet the need for evalua-

rapidly replen-

tion and maintenance of ex-

these

can

ished.

isting electrical installations,


the company has set up the
Service Division within its

ABB SACE

Training:
an indispensable tool
for professionals

own structure, which acts as

By means of its technical train-

the managers/users of the

ing courses, ABB SACE is

plants, to carry out mainte-

committed to putting its wealth

nance, repair and overhauling

of experience gained in over

activities at ABB SACE and on

more than 60 years of opera-

the users premises. The divi-

tion at disposal. The courses

sion also offers a spare parts,

are an opportunity for all op-

assembly and commissioning

erators in the sector to update

service for its own switch-

their knowledge and compare

boards.

a qualified interlocutor working in close collaboration with

1/9

Just one product for everyone

SACE Isomax S is a product which has been thought up and


constructed for all types of customers: the user, the design
engineer, the switchboard builder, the installer, the maintenance
technician and the wholesaler.

ABB SACE proposes technical solutions to the

user

which fulfil all requirements


and are always up to date
with technological innovations in the field of electrical
power distribution. It offers
high quality products,
reliability and precision,
which guarantee high
performances under any
conditions, safe products

ment of any faulty parts.

The

design engineer

has

simple installation inside the

products available which

switchboard. The whole

comply perfectly with the

range of products is divided

international technical

into eight sizes and con-

standards and which are

structed in only three depths,

able to do the job simply,

thereby allowing standardi-

safely and reliably at the

sation of the supporting

highest levels of perform-

structures and of the switch-

ance. SACE Isomax S circuit-

boards and installation in

breakers offer the design

prefabricated structures.

engineer solutions for sizing,

The dimensional uniformity

coordination and flexibility of

and the possibilities of

application which allow him

connection, thanks to the

to draw up a state-of-the-art

variety of terminal available,

project, selecting from

considerably facilitates

among well-known ranges

connections by means of

and circuit

busbars or cables.

diagrams to be

integrated in a complete

GSIS9079

necessary, simple replace-

GSIS9090

during service and, when


GSIS9092

system, and satisfying all

ABB SACE provides the

SACE Isomax S circuit-

to a current-limiting circuit-

installation requirements and

installer

breakers allow easy and safe

breaker).

performances according to

any type of plant, which are

maintenance to be carried

Standardisation of Isomax S

the standards.

practical to install, simple to

out, enabling the accessories

circuit-breakers and their

use, assemble and connect

to be inserted conveniently

accessories means simple

The requirements of a

and easy to check, thanks

on the front of the circuit-

and economical manage-

switchboard builder are fully

also to the quality of the

breaker.

ment of the spare parts

satisfied thanks to careful

accessories supplied with

Construction rationality as

warehouse for the

design of the product. The

the apparatus and the

well as modularity of the

saler.

limited volumes of the pieces

technical support documen-

structure, allow the

tation provided.

maintenance technician to carry out

Furthermore, the clarity of

of apparatus allow the


switchboard dimensions to

replacements without the

helps product ordering,

be kept to a minimum and

need for any special adapta-

reduces procurement times

the modularity and compact-

tion, even when changing

and allows limited stocks to

ness the ranges of products

from one type of circuit-

be kept in the warehouse

are conceived with allow

breaker to another (for

since the products can be

example from an automatic

replenished rapidly.

1/10

with products for

whole-

product coding considerably

ABB SACE

Main characteristics

Index
Panorama of the SACE Isomax S family
A single series for all applications ...................................................................................... 2/2

Construction characteristics
Distinctive features of the series ........................................................................................ 2/4
Conditions of use ................................................................................................................ 2/8
Modularity of the series SACE Isomax S ........................................................................... 2/10

Compliance with the Standards


Standards, Approvals, Certifications and company quality system ................................. 2/12

ABB SACE

2/1

Panorama of the SACE Isomax S family


A single series for all applications

CIRCUIT-BREAKERS FOR AC / DC DISTRIBUTION


Poles
Iu
Ue (AC)
Icu (380/415V AC)

[nr.]
[A]
[V~]
[kA]
B
N
S
H
L
V

Ue (DC)

CURRENT-LIMITING CIRCUIT-BREAKERS
Poles
Iu
Ue
Icu (380/415V)
Icu (690V)
CIRCUIT-BREAKERS FOR MOTOR PROTECTION
Poles
Iu
In
Ue
Magnetic only release IEC 60947-2
Electronic release PR211/P (I), IEC 60947-2
Electronic release PR212/MP, IEC 60947-4-1

[V]

S1
3-4
125
500

S2
3-4
160
690

16
25

16
35
50

250

500
S2X 100
3
100
690
70
10

[nr.]
[A]
[A]
[V~]

S2X 80
3
80
180
690
-

[nr.]
[A]
[kA]

CIRCUIT-BREAKERS FOR APPLICATIONS AT 1000 V AC


Poles
Iu
Icu (1000V DC), 4 poles in series

[nr.]
[A]
[kA]

SWITCH-DISCONNECTORS according to IEC 60947-3 Standard


Poles
Ith
Ue
Icm
Icw

[nr.]
[A]
[V~]
[kA]
[kA]

2/2

SACE Isomax S2

[nr.]
[A]
[V~]
[kA]
[kA]

CIRCUIT-BREAKERS FOR APPLICATIONS AT 1000 V AC


Poles
Iu
Icu (1000V AC)

Circuit-breakers according to UL 489 and CSA 22.2 Standards


Poles
Maximum continuous current (40 C)
Maximum Ampere Breaking Capacity (480 V)
Thermal-magnetic trip unit
Microprocessor based trip unit
MCP
MCS

SACE Isomax S1

[no.]
[A]
[kA]

S2D
3-4
125 - 160
690
3,1
2,2
S1N
3
100
20
-

ABB SACE

SACE Isomax S3

SACE Isomax S4

SACE Isomax S5

SACE Isomax S6

SACE Isomax S7

SACE Isomax S8

S3
3-4
160-250
690

S4
3-4
160-250
690

S5
3-4
400-630
690

S6
3-4
630-800
690

S7
3-4
1250-1600
690

S8
3-4
2000-2500-3200
690

35

35

35

65
85

65
100

65
100

35
50
65
100

50
65
100

85

750

750

750

S3X
3-4
125-200
690
200
75

S4X
3-4
250
690
200
75

S3 / S3X
3
160-250 / 125-200
25200
690

S4 / S4X
3
160-250 / 250
100250
690
-

S5
3
400-630
320630
690
-

S6 / S6X
3
630-800 / 400-630
320..800
690
-

S4L / S4X
3
160-250 / 250
8 / 30

S5L
3
400
8

S6L / S6X
3
630-800 / 630
12 / 30

S5L
4
400
40

S6L
4
630 / 800
40 / 50

120
-

S6X
3-4
400-630
690
200
75

2
S7
3
1250-1600
10001600
690
-

S3L / S3X
3
160 / 125
6 / 30

S3L
4
160-250
40

S3D
3-4
100 - 160 - 250 - 320
690
10
6,5
S3 B/N/H/L
2-3
150 - 225
85
S3L
S3 H-D 150/225

ABB SACE

S6D
3-4
400 - 630 - 800
690
30
15

S7D
3-4
1000 - 1250 - 1600
690
52,5
25

S8D
3-4
2000-2500-3200
690
85
40

S4 N/H/L
2-3
250
100
-

S5 N/H/L
2-3
400
100

S6 N/H/L
2-3
800
100

S7H
2-3
1200
65
-

S8V
3
1600-2000-2500
100
-

S4 N/H/L
S4 H-D

S5 N/H/L
S5 H-D

S6 N/H/L
S6 H-D

S7H
S7 H-D

S8V
S8 V-D

2/3

Construction characteristics
Distinctive features of the series

Terminals

Fixed
contacts

Identification
nameplate

Arcing
chamber

Moving
contacts

Operating lever

Microprocessor-based
electronic release

2/4

GSIS9069

ABB SACE

GSIS9051

GSIS9048

Double insulation

Positive operation

The double insulation technique consists of total separation

The operating lever always indicates the exact position of the

between the power circuits and the auxiliary circuits and is a

circuit-breaker moving contacts, thereby guaranteeing safe and

characteristic of all SACE Isomax S apparatus from size S3 up.

reliable indications (I = Closed; O = Open; yellow-green line =

The housing of each electrical accessory is completely segre-

Open due to release trip). The circuit-breaker operating mecha-

gated from the power circuit, thus avoiding all risk of contact

nism has free release, regardless of the pressure on the lever

with live parts, thereby increasing operator safety conditions

or the speed of operation. Release tripping automatically opens

during management and inspection of the installations.

the moving contacts: to close them again, it is necessary to

Moreover, the circuit-breaker has redundant insulation be-

reset the operating mechanism by pushing the operating lever

tween the internal live parts, both regarding thickness of mate-

from the intermediate position to the lower limit of the open

rials and the distances, which are greater than those required

position.

by the IEC Standards and are in accordance with American

For plug-in or withdrawable circuit-breakers, the moving part

usage.

can only be detached from the fixed part with the circuit-breaker

open (moving contacts separate from the relative fixed con-

GSIS9050

GSIS0074

tacts).

Selectivity

Possibility of inspection

The complete range of releases means that the protection func-

With the circuit-breaker out of service, it is possible to check

tions of the apparatus can be coordinated according to cur-

the state of the internal parts and live components of the cir-

rent-type, time-type, energy-type or residual-current selectivity

cuit-breaker directly. The arcing chambers and the fixed and

chains. It is therefore possible to isolate only the areas affected

moving contacts are accessible simply by removing the cir-

by the fault, ensuring maximum service continuity. Circuit-break-

cuit-breaker cover. The operation, facilitated by the limited

ers in category B are available from 400 A up.

number of components, reduces maintenance times and ensures a higher degree of safety.

ABB SACE

2/5

Construction characteristics

Isolation behaviour

Racking-out with the door closed

In the open position, the circuit-breaker guarantees isolation of

This system, starting from 160 A, allows the circuit-breaker to

the circuit in compliance with the IEC 60947-2 Standard. For

be racked in and out with the compartment door closed, in-

plug-in or withdrawable version circuit-breakers, in the racked-

creasing operator safety and allowing construction of internal

out or withdrawn position, the power and auxiliary circuits are

arc proof low voltage switchboards. Racking out can only take

isolated, ensuring that no parts are live. Under these condi-

place with the circuit-breaker open, using a special racking-

tions and by means of special connectors, it is possible to

out crank handle supplied with the withdrawable version cir-

carry out blank tests, operating the circuit-breaker in complete

cuit-breaker.

safety. The redundant insulation distances guarantee the absence of leakage currents and dielectric strength in the event

GSIS9129

of any overvoltages between the input and output.

GSIS9127

GSIS9126

GSIS9125

Distinctive features of the series

Electromagnetic compatibility

Tropicalisation

By using SACE PR211/P, PR212/P, PR212/MP microprocessor-

The SACE Isomax S series of circuit-breakers and accessories

based overcurrent releases and SACE RC210, RC211, RC212

comply with the strictest regulations for use in hot-humid-sa-

electronic residual-current releases, the absence of unwar-

line climates (in compliance with climatograph 8 of the IEC

ranted trips is guaranteed even in the presence of interference

721-2-1 Standards), thanks to:

caused by electronic equipment, atmospheric disturbance or

insulating cases made of fibreglass-reinforced synthetic res-

discharges of electrical type. Furthermore, the apparatus does


not generate interference with other electronic equipment in
the vicinity of the installation. This is in compliance with the IEC

ins;
anti-corrosion treatment on all main metal parts (C UNI 356465 environment);

60947-2 Appendix F, IEC 1000-4, EN 61000-4, EN 50081-1, EN

Fe/Zn 12 galvanisation (UNI ISO 2081), protected by a con-

50081-2, EN 50082-1, EN 50082-2 European Directive No. 89/

version layer consisting mainly of chromates (UNI ISO 4520).

336 specifications regarding electromagnetic compatibility


EMC.

2/6

ABB SACE

GSIS9062

GSIS9128

Installation positions

Mounting on DIN rail up to 630 A

The circuit-breaker can be installed in any position without any

The brackets for fixing onto standardised DIN EN 50022 rails

effect on its rated characteristics. In compliance with the IEC

for S1, S2 and DIN EN 50023 rails for S3, S4, S5 simplify assem-

60947-2 Standards, SACE Isomax S circuit-breakers can be

bly of the circuit-breakers up to 630 A in standard switchboards.

supplied through either top or bottom terminals, without jeop-

This allows standardised supporting structures to be used and

ardising operation of the apparatus.

facilitates the stage for designing and constructing the switch-

They can be installed in switchboards, mounted directly on the

board metalwork structure.

GSIS9130

GSIS9131

base plate or on Din rails up to size S5.

Resistance to vibration

Degrees of protection

The circuit-breakers are unaffected by vibrations generated

Different measures have been taken in SACE Isomax S circuit-

mechanically or due to electromagnetic effects, in compliance

breakers to achieve IP20 degree of protection for the fixed,

with the IEC 68-2-6 Standards and the strictest regulations of

plug-in and withdrawable version circuit-breaker, excluding

the major classification organisations:

the terminals, and IP30 for the front parts of the circuit-breakers

RINA

installed in switchboards.

DET Norske Veritas

The fixed parts are always provided with IP20 degree of protec-

Lloyds Register of Shipping

tion. It is possible to achieve IP54 degree of protection in ac-

Germanischer Lloyd

cordance with the IEC 60529 Standard with the circuit-breaker

Bureau Veritas.

installed in a switchboard fitted with rotary handle operating


mechanism transmission on the compartment door and the
special insulation gaskets which can be ordered separately.

ABB SACE

2/7

Construction characteristics
Conditions of use
Degrees of protection (according to CEI EN 60529 Standard file 519)
Circuit-breaker

Circuit-breaker in switchboard

IP20

IP30

Direct operating mechanism

GSIS9082

GSIS9081

GSIS9080

IP30

Front for lever operating mechanism


without terminal covers

IP40 (1)

IP30

GSIS9085

Direct rotary handle

GSIS9084

GSIS9083

IP50

Rotary handle transmission


with terminal covers

IP54

IP40

with terminal covers


and direct rotary handle

Motor operator

(1) IP30 for withdrawable circuit-breakers

2/8

GSIS9088

Special IP54 protection

GSIS9087

GSIS9086

IP30 (2)

(2) IP40 for S1-S2 and S6-S7 circuit-breakers

ABB SACE

Operating temperature
SACE Isomax S circuit-breakers can be used in ambient con-

temperature but, in the case of temperatures higher than 40

ditions where the temperature in the surrounding atmosphere

C, the maximum setting of the protection against overloads

varies between -25 C and +70 C and stored in ambients with

(function L) must be reduced to take into consideration inertial

temperatures between -40 C and +70 C.

phenomena that occur in the copper parts of the circuit-

The circuit-breakers fitted with thermomagnetic overcurrent

breaker through which the phase current passes (moving and

release have their thermal element set for a reference tem-

fixed contacts, and connection terminals) which cause a de-

perature

crease in the rated uninterrupted current as indicated in the

of +40 C.

5/34.

For temperatures between +40 C and +70 C, with the same

table on page

setting, there is lowering of the thermal trip threshold due to

The performances of the circuit-breaker cannot be guaran-

the temperature-related behaviour of the bimetallic strip of the

teed for temperatures above +70 C.

release itself.

To ensure service continuity of the installations, careful thought

For temperatures lower than +40 C, on the other hand, there

must be given as to how to keep the temperature within ac-

is an increase in the thermal trip threshold as indicated in the

ceptable levels for operation of all the various devices and not

table on page

5/39.

only the circuit-breakers. For example, forced ventilation in

The electronic microprocessor-based overcurrent releases

the switchboards and in the areas where they are installed

do not undergo any variations in performance with changes in

may be necessary.

Altitude
Up to an altitude of 2000 m SACE Isomax S circuit-breaker

the rated uninterrupted current.

rated performances are unaffected.


As the altitude increases, the atmospheric properties change
in terms of composition, dielectric strength, cooling capacity
and pressure.
The circuit-breakers therefore undergo derating, which can

Altitude

[m]

2000

3000

4000

Rated service voltage, Ue

[V~]

690

600

500

Rated uninterrupted current, Iu

%Iu

100%

95%

90%

basically be measured through the change in significant parameters such as the rated maximum operating voltage and

ABB SACE

2/9

Construction characteristics
Modularity of the series SACE Isomax S

Starting from the fixed version circuit-breaker and by means of

the bracket for rear fixing onto DIN EN 50022 rail for S1-S2

mounting the conversion kit, all the other versions which are

circuit-breakers, DIN EN 50023 rail for S3-S4-S5 circuit-break-

used for the various requirements are obtained.


The following are available:
kit for conversion from fixed circuit-breaker to moving part of
a plug-in or withdrawable circuit-breaker
conversion kit for the connection terminals which make it

ers
direct action motor operator, with stored energy and with
solenoid.
rotary handle operating mechanisms directly on the circuitbreaker and with transmission on the compartment door

possible to obtain front and rear terminals for Copper or

residual-current releases

Aluminium cables, and front and rear terminals for flat bar

accessories for microprocessor-based overcurrent releases

terminals.
Various accessories are also available:
shunt opening releases

such as the signalling, dialogue and actuation unit and external CTs.
the fixed parts for plug-in or withdrawable circuit-breakers

undervoltage releases

with front terminals for cables or for flat bars and rear termi-

auxiliary contacts

nals for flat bars.

position contacts

2/10

ABB SACE

GSIS0159

ABB SACE

2/11

Compliance with the Standards


Standards, Approvals, Certifications and company quality
system
SACE Isomax S circuit-breakers and their

The attention paid to protecting the en-

accessories comply with the IEC 60947-

vironment is another important priority

2, EN 60947-2 (unified in 17 countries

for ABB SACE, and as confirmation of

of CENELEC), CEI EN 60947 and IEC

this, the environmental management

61000 international Standards and con-

system has been certified by RINA.

form with the EC directive:


Low Voltage Directives (LVD)
no. 73/23 EEC
Electromagnetic Compatibility Directive (EMC) no. 89/336 EEC.

GSIS9119

Certification of compliance with the


above-mentioned product Standards, is
carried out, in respect of the European
EN 45011 Standard, by the

GSIS9132

Italian certification organisation, ACAE (Association for


Certification of Electrical Apparatus),- member of the European organisation LOVAG
(Low

Vo l t a g e

A g re e m e n t

ABB SACE was the first industrial com-

Group).

pany in the electro-mechanical sector


in Italy to obtain this recognition, and,
thanks to a revision of its production
process with an eye to ecology, has
managed to reduce consumption of raw
materials, processing waste and the risk
of accidents by 20%.

ISO 9001

The attention paid to protecting the environment and to the safety of workers is

GSIS9119

a priority commitment of ABB SACE and


as confirmation of this, the company developed the Environmental Management
System in compliance with the InternaThe ABB SACE Quality System complies

tional ISO 14001 Standard, certified in

with the International ISO 9001 Stand-

1997, integrating this in 1999 with the

ard (model for assuring quality in design,

Health and Safety in the Workplace Man-

development, construction, installation

agement System in accordance with BS

and assistance) and to the equivalent

8800 (British Standards).

European EN ISO 9001 and Italian UNI


EN ISO 9001 Standards.

The prizes obtained by ABB SACE at the

The certification Organisation is RINA-

Forum Design in Hannover and at

QUACER.

Electro in Paris bear witness to the consideration given to man and the respect

ABB SACE obtained its first certification

for ergonomic criteria.

in 1990.
The ABB SACE Test Room is accredited
by SINAL. The apparatus complies with
the prescriptions for on-board installations and is approved by major Shipping
Registers, such as: LLOYDS REGISTER
OF SHIPPING, GERMANlSCHER LLOYD,
BUREAU VERITAS, RINA, DET NORSKE

GSIS9118

VERITAS, POLSKI REIESTR STATKOW

2/12

Please contact ABB SACE for information


regarding the types of circuit-breakers ap-

and the AMERICAN BUREAU OF SHIP-

proved, the performances approved and

PING.

their relative validity.

ABB SACE

The ranges

Index
SACE Isomax S circuit-breakers for power distribution ........................................... 3/3
Electrical characteristics IEC 60947-2 .............................................................................. 3/4
General characteristics ..................................................................................................... 3/6
Thermomagnetic releases ................................................................................................. 3/8
Electronic releases ............................................................................................................ 3/10

SACE Isomax S current-limiting circuit-breakers ...................................................... 3/15


Electrical characteristics IEC 60947-2 .............................................................................. 3/16
General characteristics ..................................................................................................... 3/18

SACE Isomax S circuit-breakers for motor protection


(protection against short-circuit) .................................................................................. 3/23
Electrical characteristics IEC 60947-4 .............................................................................. 3/24
General characteristics ..................................................................................................... 3/26

SACE Isomax S circuit-breakers for motor protection


(integrated protection) .................................................................................................... 3/28
Electrical characteristics IEC 60947-2 and IEC 60947-4 ................................................. 3/28
General characteristics ..................................................................................................... 3/30

SACE Isomax S circuit-breakers for applications up to 1000V ................................ 3/35


Electrical and general characteristics IEC 60947-2 ......................................................... 3/36

SACE Isomax S switch-disconnectors ........................................................................ 3/39


Electrical and general characteristics IEC 60947-3 ......................................................... 3/40

SACE Isomax S circuit-breakers in accordance with UL489 and CSA C22.2


Standards .......................................................................................................................... 3/43
Electrical and general characteristics ............................................................................... 3/44

ABB SACE

3/1

Circuit-breakers for power


distribution

Eight sizes to optimise use for all plant and


installation requirements
690V 125-3200 A 16-120 kA (380/415 V)

GSIS9063

3/3

SACE Isomax S circuit-breakers


for power distribution

SACE Isomax S2

SACE Isomax S3

[A]
Nr.

125
3-4

160
3-4

160 - 250
3-4

[V]
[V]

500
250

690
500

690
750

[kV]
[V]

6
500

6
690

8
800

(AC) 50-60Hz
(DC)

Rated impulse withstand voltage, Uimp


Rated insulation voltage, Ui
Test voltage at industrial frequency for 1 min.
Rated ultimate short-circuit breaking capacity, Icu

GSIS9135

SACE Isomax S1
Rated uninterrupted current, Iu
Poles
Rated service voltage, Ue

GSIS9134

GSIS9133

Electrical characteristics IEC 60947-2

[V]
B

3000
N

3000
N

3000
H

(AC) 50-60 Hz 220/230 V


(AC) 50-60 Hz 380/415 V[kA]

[kA]

25
16

40
25

25
16

50
35 (1)

65
50

65
35 (1)

100
65

170
85

(AC) 50-60 Hz 440 V


(AC) 50-60 Hz 500 V

[kA]
[kA]

10
8

16
12

10
8

20
12

25
15

30
25

50
40

65
50

(AC) 50-60 Hz 690 V


(DC) 250 V - 2 poles in series

[kA]
[kA]

16

25

6
16

8
35

10
50

14
35

18
65

20 (5)
85

(DC) 500 V - 2 poles in series


(DC) 500 V - 3 poles in series

[kA]
[kA]

16

35

50

35
-

50
-

65
-

50%

50%

100%

75%

75%

20
100%

35
75%

50
75%

32
8

52,5
6

32
8

74
7

105
6

74
8

143
7

187
6

(DC) 750 V - 3 poles in series


Rated short-circuit service breaking capacity, Ics (2)

[kA]
[%Icu]

Rated short-circuit making capacity (415 V)


Opening time (415V at Icu)

[kA]
[ms]

Rated short-time withstand current for 1 s, Icw


Utilisation category (EN 60947-2)

[kA]
A

fixed

F-P
FC-R

F-P
EF - FC - FC CuAl - R

F-P-W
F- EF - ES - FC

plug-in

FC-R

FC - R

FC CuAl - RC - R
EF - FC - R

EF - FC - R

Isolation behaviour
IEC 60947-2, EN 60947-2
Releases: thermomagnetic

T fixed, M fixed 5 Ith


T fixed, M fixed 10 Ith
T adjustable, M fixed 3 Ith
T adjustable, M fixed 5 Ith
T adjustable, M fixed 10 Ith
T adjustable, M adjustable

magnetic only
with microprocessor

M fixed
PR211/P (I-LI)
PR212/P (LSI-LSIG)

Interchangeability
Versions
Terminals

withdrawable (3)
Fixing on DIN rail
Mechanical life

[No. operations / hourly operations]

DIN EN 50022
25000/240

DIN EN 50022
25000/240

DIN EN 50023
25000/120

Electrical life (at 415 V)


Basic dimensions, fixed

[No. operations / hourly operations]


3/4 poles
L [mm]

8000/120
78/103

8000/120
90/120

10000(160A)-8000(250A)/120
105/140

70
120

70
120

103,5
170

[kg]
[kg]

0,9 /1,2
1 / 1,4

1,1/1,5
1,3/1,7

2,6 / 3,5
3,1 / 4,1

[kg]

3,5 / 4,5

D [mm]
H [mm]
Weights fixed
plug-in
withdrawable

3/4 poles
3/4 poles
3/4 poles

(1)

All the versions with Icu=35kA are certified at 36kA

(2)

For S3 N/H/L, S4 N/H/L, S5 N/H, and S6 N/S/H circuit-

with the front flange for the lever operating mechanism or

breakers the performance percentage of Ics at 690V is

with its alternative accessories, such as the rotary handle

reduced by 25%.

or the motor operator

3/4

(3)

The withdrawable version circuit-breakers must be fitted

(4)

For the S5 circuit-breaker, the plug-in version is only

(5)

The SACE S3 circuit-breaker with breaking capacity L at

available for the version with 400 A rated current

690 V can only be supplied from above

ABB SACE

SACE Isomax S6

SACE Isomax S7

SACE Isomax S8

160 - 250
3-4

400 - 630
3-4

630 - 800
3-4

1250 - 1600
3-4

2000 - 2500 - 3200


3-4

690
-

690
750

690
750

690
-

690
-

8
800

8
800

8
800

8
800

8
690

3000

GSIS9136

GSIS9098

SACE Isomax S5

GSIS9096

GSIS9097

GSIS9095

SACE Isomax S4

3000
H

3000
H

3000
H

65
35 (1)

100
65

200
100

65
35 (1)

100
65

200
100

65
35 (1)

85
50

100
65

200
100

85
50

100
65

200
100

85
85

120
120

30
25

50
40

80
65

30
25

50
40

80
65

30
25

45
35

50
40

80
65

40
35

55
45

80
70

70
50

100
70

18
-

22
-

30
-

20
35

25
65

30
100

20
35

22
50

25
65

30
100

20
-

25
-

35
-

40
-

50
-

35
-

50
-

65
-

20
-

35
-

50
-

65
-

100%

100%

75%

20
100%

35
100%

50
75%

100%

75%

50%

50%

50%

74
8

143
7

220
6

74
8

143
7

220
6

105
22

143
22

220
22

187
20

264
20

16
20
35
50
100% 100% 100% 75%
74
10

105
9

143
8

220
7

2500

5 (400A)
B (400A) - A (630A)

7,6 (630A) - 10 (800A)


B

15 (1250A) - 20 (1600A)
B

35
B

F-P-W
F - EF - ES - FC

F - P (400) - W
F - EF(400A) - ES - FC

F-W
F - EF - ES - FC CuAl

F-W
F - EF - ES - FC CuAl (1250A)

F
F (2000-2500A) - VR

FC CuAl - RC - R
EF - FC - R

FC CuAl (400A)-RC (400A)-R


EF - FC - R

RC - R
-

HR - VR
-

EF - FC - R

EF(400A) - ES - FC (400A)
R - VR (630A)

EF - HR - VR

EF - HR - VR

DIN EN 50023
20000/120

DIN EN 50023
20000/120

20000/120

10000/120

10000/20

10000(160A)-8000(250A)/120
105/140

7000(400A)-5000(630A)/60
140/184

7000(630A)-5000(800A)/60
210/280

7000(1250A)-5000(1600A)/20
210/280

2500(2500A)/20-1500(3200A)/10
406/556

103,5
254

103,5
254

103,5
268

138,5
406

242
400

4 / 5,3
4,5 / 5,9

5/7
6,1 / 8,4

9,5 / 12
-

17 / 22
-

57/76
-

6,4 / 8,7

12,1 / 15,1

21,8 / 29,2

4,9 / 6,3
KEY TO VERSIONS
F = Fixed
P = Plug-in
W = Withdrawable

ABB SACE

KEY TO TERMINALS
F = Front
EF = Extended front
ES = Extended spreaded front

FC = Front for copper cables

RC = Rear for copper or aluminium cables

FC CuAl = Front for copper or aluminium cables

HR = Rear horizontal flat bar

R = Rear threaded

VR = Rear vertical flat bar

3/5

SACE Isomax S circuit-breakers


for power distribution
General characteristics
The SACE Isomax S series of moulded-case circuit-breakers conforming to the IEC
60947-2 Standard, is divided into eight basic sizes, with rated uninterrupted currents
from 125 to 3200 A and breaking capacities from 16 to 120 kA (380/415 V).
Selection of the size allows the basic electrical characteristics to be identified simply and immediately, whereas selection of the overcurrent release depends on the
type of application required.

Range of application of the alternating current circuit-breakers

GSIS0078

For protection of alternating current networks, SACE S1, S2, and S3 circuit-breakers fitted with thermomagnetic releases

KEY
TM = Thermomagnetic
M = Magnetic only
PR211-PR212 = Electronic releases

and SACE S4, S5, S6, S7, and S8 circuitbreakers fitted with SACE PR211/P or
PR212/P electronic releases are available. These are characterised by an application range from 10 to 3200 A and by
a rated voltage of 690 V.

3/6

ABB SACE

Range of application of the direct current circuit-breakers

GSIS0079

SACE S1, S2, S3, S5, and S6 circuit-

capacities up to 100 kA (250 V DC) and

breakers fitted with thermomagnetic re-

65 kA (500 V DC); whereas the SACE

leases are used in protection of direct

S3, S5, and S6 circuit-breakers with 3

current networks, with an application

poles in series can reach 750 V and

range from 10 to 800 A and a minimum

breaking capacities up to 50 kA.

operating voltage of 24 V DC.

The various possible wiring diagrams

With 2 poles in series, SACE Isomax S

and the trip threshold correction factors

circuit-breakers can be used with rated

are indicated on page 5/47.

KEY
TM = Thermomagnetic
M = Magnetic only

voltage of 250 and 500 V and breaking

ABB SACE

3/7

SACE Isomax S circuit-breakers


for power distribution
Thermomagnetic releases
SACE Isomax S1, S2, S3, S5, and S6 circuit-breakers can be
fitted with thermomagnetic releases and are used for protection of alternating current networks with the S1, S2, and S3
circuit-breakers (for applications from 10A to 250A) and in
direct current with the S1, S2, S3, S5, and S6 circuit-breakers
(from 10A to 800A). They allow protection against overloads
using a thermal device (with fixed threshold for S1 and adjustable threshold for S2, S3, S5, and S6) carried out using the

GSIS9058

bimetallic strip technique, and protection against short-circuit


using a magnetic device (with fixed threshold for S1, S2, and
S3 and adjustable threshold for S5 and S6).
The four-pole circuit-breakers are always fitted with the neutral protected by the release.

3
Thermomagnetic releases
L1 - L2 - L3

R10

R12,5

R16

R20

R25

R32

R32

R40

R50

R50

R63

R80

R100

R125

R125

neutral

R10

R12.5

R16

R20

R25

R32

R32

R40

R50

R50

R63

R80

R100

R125

R80

S1 125
S2 160
S3 160
S3 250
S5 400
S5 630
S6 630
S6 800
10 x Ith L1-L2-L3

5 x Ith
3 x Ith

500

500

500

500

500

500

500

500

500

500

630

800

1000

1250

1250

neutral

500

500

500

500

500

500

500

500

500

500

630

800

1000

1250

800

L1-L2-L3

160

160

160

200

200

200

300

200

250

300

320

400

500

630

630

neutral

160

160

160

200

200

200

300

200

250

300

320

400

500

630

400

L1-L2-L3

300

375

neutral

300

240

TM adjustable
L1-L2-L3
neutral

3/8

ABB SACE

Magnetic only releases


L1 - L2 - L3

R16

R40

R50

R50

R63

R80

R100

R125

R125

R125

R160

R200

R250

neutral

R16

R40

R50

R50

R63

R80

R100

R125

R80

R80

R100

R125

R160

L1-L2-L3

500

500

630

800

1000

1250

1250

1250

1600

2000

2500

neutral

500

500

630

800

1000

1250

800

800

1000

1250

1600

S1 125
S2 160
S3 160
S3 250
10 x Ith

5 x Ith

L1-L2-L3

160

200

250

300

320

400

630

neutral

160

200

250

300

320

400

400

The magnetic only releases which equip the SACE


S1, S2, and S3 circuit-breakers have a fixed trip
threshold as indicated in the table. For S1, the magnetic only release is available in the version with
breaking capacity N = 25 kA; for S2, breaking capacities N = 36 kA and S = 50 kA are available. The

GSIS0068

latter version is only available in the 10 x Ith version.

R160

R200

R250

R320

R400

R500

R630

R800

R100

R125

R160

R200

R250

R320

R400

R500

The letter R identifies the setting current for phase (L1-L2-L3) and neutral protection
(second line). The ones indicated are the combinations provided as standard.
On request, circuit-breakers with neutral at 100% of the phase setting can be supplied.

The thermomagnetic releases which equip the SACE


S2 and S3 circuit-breakers have the thermal element
with threshold adjustable from 0.7 1 x In. The regulated current value which is obtained by using the
appropriate selector must be intended as the rated

threshold, with trip values which vary according to


the phase setting.
The S2 circuit-breaker with breaking capacity S = 50 kA

GSIS0069

value at 40 C. The magnetic element has fixed trip

is only available in the 10 x Ith version.

The thermomagnetic releases which equip SACE S5


and S6 circuit-breakers have the thermal element with
threshold adjustable from 0.7 1 x In. The regulated
current value which is obtained by using the appropriate selector must be intended as the rated value at

5 10 x In. The table gives the maximum magnetic


trip values (10 x In) for protection of the phases (L1
- L2 - L3) and of the neutral.

1600

2000

2500

1000

1250

1600

800

1000

1250

500

625

800

480

600

750

300

375

480

GSIS0070

40 C. The magnetic element can be adjusted from

The trip thresholds of the magnetic protection are a function of the setting used both
for protection of the phases (L1 - L2 - L3) and of the neutral. The releases denominated
10 x Ith are indicated for all distribution applications, whereas the releases denominated 5 x Ith and 3 x Ith are used where a low magnetic trip threshold is required. With

ABB SACE

regard to this, the 3 x Ith are particularly suitable for protection of generators.

3200

4000

5000

6300

8000

2000

2500

3200

4000

5000

3/9

SACE Isomax S circuit-breakers for power


distribution
Electronic releases
The SACE Isomax S4, S5, S6, S7 and S8 circuit-breakers for protection in alternating
current can be fitted with SACE PR211/P or SACE PR212/P overcurrent releases,
constructed using electronic microprocessor-based technology. This allows protection functions to be obtained which guarantee a high level of reliability and tripping precision and which are unaffected by the external ambient. The power supply
needed for correct operation is supplied directly by the release current transformers,
in the presence of a phase current higher than or equal to 18% of their rated current,
GSIS9060

even with a single phase supplied with voltage. There is only one adjustment for all
the phases and the neutral and the release is simultaneous for all the circuit-breaker
poles, with trip characteristics which are unaffected by the external ambient. The
functions and settings of the release protections can be verified by means of the
SACE TT1 and SACE PR010/T Test units.

SACE PR211/P

SACE PR212/P

The SACE PR211/P release (available

The SACE PR212/P release (available

PR212/T actuator unit which is always

from S4 to S7) provides protection func-

from S4 to S8) provides protection func-

supplied when the dialogue unit is re-

tions against overload L and instanta-

tions against overload L, delayed short-

quired.

neous short-circuit I, and is available in

circuit S and instantaneous short-circuit

It is particularly suitable in applications

the versions with functions I and LI.

I, and against earth fault G. It is available

with selective coordination require-

The wide range of adjustments make this

in the

versions PR212/P with functions

ments, for earthing protection against the

release particularly suitable in all distri-

LSI and LSIG; both allow use of the

risk of fire and evolutionary faults, and

bution where tripping reliability and pre-

PR010/K signalling unit, the PR212/D

for remote control and parametrisation,

cision is required and where magnetic

dialogue unit and the PR212/T actuator

network supervision and centralised

only protection is needed (from 1.5 to

unit, which can be used either simulta-

load management.

12 x In), using the SACE PR211/P ver-

neously or individually, except for the

sion I release.

In

100 A

160 A

250 A

320 A

40100

64160

100250

128320

1001000

1601600

2502500

3203200

1501200

2401920

3753000

4803840

20100

32160

50250

64320

neutral (50%)

2050

3280

50125

64160

neutral (100%)

40100

64160

100250

128320

S4 160
S4 250
S5 400
S5 630
S6 630
S6 800
S7 1250
S7 1600
S8 2000
S8 2500
S8 3200

3/10

ABB SACE

For four-pole circuit-breakers fitted with

The protection release consists of cur-

coincides with circuit-breaker opening.

SACE PR212/P release (LSI-LSIG), pro-

rent transformers (three or four accord-

All the protection functions with relative

tection of the neutral can be set to 50%

ing to the circuit-breaker polarity), the

trip times can be verified and tested us-

or 100% of the phase protection setting

SACE PR211/P or SACE PR212/P pro-

ing the SACE PR010/T accessory unit

(by means of dip-switches on the front

tection unit and an OS demagnetising

(only for PR212/P).

of the release).

opening solenoid which acts directly on

In the versions with SACE PR212/P - LSI/

For those with SACE PR211/P release (I-

the circuit-breaker operating mecha-

LSIG release, it is possible to set the

LI), protection of the neutral at 100% can

nism group.

adjustment parameters of the protection

be ordered by means of an additional

The current transformers are housed

functions directly from the front (dip-

code 1SDA037505R1.

inside the release box and supply the

switch positioned on MAN), or to set the

With three-pole and distributed neutral

energy needed for correct operation of

parameters remotely (dip-switch posi-

circuit-breakers, external toroids can be

the protection and the signal required to

tioned on ELT) thanks to the use of the

used by connecting these directly either

determine the current. They are avail-

SACE PR212/D dialogue units.

to the SACE PR211/P release, or to the

able with primary rated current as indi-

In case of any anomalies in remote

SACE PR212/P release. On request, it is

cated in the table below.

parametrisation, the protection auto-

possible to obtain full protection of the

When the protection intervenes, the cir-

matically uses the set of parameters set

neutral with setting equal to 100% of the

cuit-breaker opens by means of the

manually on the front of the circuit-

protection.

opening solenoid (OS), which changes

breaker.

The SACE PR211/P and SACE PR212/P

over a contact for signalling release

The PR010/K signalling or PR212/D dia-

microprocessor-based releases are

tripped. Resetting the signal is of me-

logue units supply the PR212/P (24 VDC

self-supplied and ensure correct opera-

chanical type and takes place with re-

20%) protection release continuously

tion of the protection functions, even with

setting of the circuit-breaker operating

and this allows the adjustment param-

only a single phase supplied with volt-

lever.

eters to be set even with the circuit-

age, in the presence of a current higher

It is possible to test the opening sole-

breaker open.

than or equal to 18% of the rated phase

noid (OS) by means of the SACE TT1

value.

test device. A positive result of the test

400 A

630 A

800 A

1000 A

1250 A

1600 A

2000 A

2500 A

3200 A

160400

252630

320800

4001000

5001250

6401600

8002000

10002500

12803200

4004000

6306300

8008000

100010000

125012500

160016000

200020000

250025000

322032000

6004800

9457560

12009600

150012000

187515000

240019200

300024000

375030000

480038400

80400

126630

160800

2001000

2501250

3201600

4002000

5002500

6403200

80200

126315

160400

200500

250625

320800

4001000

5001250

6401600

160400

252630

320800

4001000

5001250

6401600

ABB SACE

3/11

SACE Isomax S circuit-breakers


for power distribution
Electronic releases
Protection functions and parametrisation of the SACE PR211/P, PR212/P releases
Protection function

Trip threshold
I1 = 0,4 - 0,5 - 0,6 - 0,7 - 0,8 - 0,95 - 1 x In PR211/P (I - LI)

Against overload with inverse long time


delay and trip characteristic according to
a time dependent curve (I2t = constant)

I1 = 0,4 - 0,5 - 0,55 - 0,6 - 0,65 - 0,7 - 0,75 - 0,8 - 0,85 - 0,875 0,9 - 0,925 - 0,95 - 0,975 - 1 x In PR212/P (LSI - LSIG)

CANNOT
BE EXCLUDED

Release between 1,05 ... 1,30 x I1 (IEC 60947-2)


I2t=cost
ON

Against short-circuit with inverse short


time delay and trip characteristic with
dependent time (I2t = constant) or
independent time
CAN
BE EXCLUDED

I2 = 1 - 2 - 3 - 4 - 6 - 8 - 10 x In
Tolerance + 10%

I2t=cost
OFF

I2 = 1 - 2 - 3 - 4 - 6 - 8 - 10 x In
Tolerance + 10%

I3 = 1,5 - 2 - 4 - 6 - 8 - 10 - 12 x In (*)
Against short-circuit with adjustable
instantaneous trip
CAN
BE EXCLUDED

3
CAN
BE EXCLUDED

Against earth fault with short inverse


time delay and trip characteristic
according to a dependent time curve
(I2t = constant)

Tolerance + 20%
(*) For S5 630, I3 max = 8 x In

I4 = 0,2 - 0,3 -0,4 - 0,6 - 0,8 - 0,9 - 1xIn


Tolerance + 20%

SACE PR211/P electronic release, functions I or LI


Protection I

Against overload

Against short-circuit with


instantaneous trip

Socket for Test


SACE TT1 Test unit

GSIS9054

Protection L

3/12

ABB SACE

Characteristics of SACE PR211/P,


SACE PR212/P electronic releases
Trip curves
A

Operating temperature

25 C +70 C

at 6 x I1
t1 = 3s

at 6 x I1
t1 = 6s

at 6 x I1
t1 = 12s

at 6 x I1
t1 = 18s

Relative humidity

90%

Service frequency

45 ... 66 Hz
able to measure
harmonics
up to 550 Hz

(tolerance: + 10% up to 2 x In; + 20% above 2 x In)

at 8 x In

at 8 x In

at 8 x In

at 8 x In

t2 = 0,05s

t2 = 0,1s

t2 = 0,25s

t2 = 0,5s

(tolerance: + 20% )
t2 = 0,05s

t2 = 0,1s

t2 = 0,25s

t2 = 0,5s

(tolerance: + 20% )

Electromagnetic compatibility (LF and HF) IEC 60947-2 Annex F


Electrostatic discharges

IEC 61000-4-2

Radiated electromagnetic field

IEC 61000-4-3

Short-time transients

IEC 61000-4-4

Mean time between failure (MTBF)

15 years (at 45 C)

Characteristics of the signalling contact


Maximum interrupted current

0,5 A

Maximum interrupted voltage

24 VDC/AC

up to 3,25 x I4

up to 2,25 x I4

up to 1,6 x I4

up to 1,25 x I4

Breaking capacity

3 W/VA

t4 = 100ms

t4 = 200ms

t4 = 400ms

t4 = 800ms

Contact/contact insulation

500 VAC

Contact/coil insulation

1000 VAC

(tolerance: + 20% )

SACE PR212/P electronic release, functions LSI or LSIG


Protection L

Protection S

Protection I

Protection G

Against overload

Against short-circuit
with delayed trip

Against short-circuit

Against earth fault

ABB SACE

selection for electronic


or manual setting

dip-switch for
setting the neutral

GSIS9056

Socket for Test


SACE TT1 Test unit

with instantaneous trip

Socket for connection of


SACE PR010/T Test unit

3/13

SACE Isomax S current-limiting


circuit-breakers

To interrupt and limit even


the worst faults
690V 100-630A 70-200kA (380/415 V)

GSIS9064

3/15

SACE Isomax S current-limiting


circuit-breakers

GSIS9137

Electrical characteristics IEC 60947-2

SACE Isomax S2X 100


Rated uninterrupted current, Iu
Poles

[A]
No.

100
3

Rated service voltage, Ue (AC) 50-60Hz


Rated impulse withstand voltage, Uimp

[V]
[kV]

690
6

[V]

690
3000

Rated insulation voltage, Ui


Test voltage at industrial frequency for 1 min.

[kA]

X
100

(AC) 50-60 Hz 380/415 V


(AC) 50-60 Hz 440 V

[kA]
[kA]

70
70

(AC) 50-60 Hz 500 V


(AC) 50-60 Hz 690 V

[kA]
[kA]

50
10

Rated ultimate short-circuit breaking capacity, Icu


(AC) 50-60 Hz 220/230 V

Rated service short-circuit breaking capacity, Ics (1)


Rated short-circuit making capacity (415 V)
Opening time (415V at Icu)
Utilisation category (EN 60947-2)

[%Icu]
[kA]

75%
154

[ms]

3,5
A

Isolation behaviour
IEC 60947-2, EN 60947-2
Releases:

thermomagnetic - T adjustable, M fixed 10 Ith


with microprocessor PR211/P (I-LI)

with microprocessor PR212/P (LSI-LSIG)


Interchangeability
Versions
Terminals

F-P
EF - FC - FC CuAl - R

fixed

FC-R
-

plug-in
withdrawable

DIN EN 50022
25000/240

Fixing on DIN rail


Mechanical life
Electrical life (at 415 V)
Basic dimensions, fixed

Weights, 3/4 poles

[No. operations / hourly operations]


[No. operations / hourly operations]
L (3/4 poles)
D

[mm]
[mm]

H
fixed

[mm]
[kg]

plug-in
withdrawable

70
120
1,1/1,5
1,3/1,7

[kg]
[kg]

(1) The value of Ics at 500V and 690V for S3X, S4X and S6X is reduced by 25%

KEY TO VERSIONS

(2) For S3X with R32 setting:

Icu (690V) = 50 kA and Ics = 100% Icu

F = Fixed

Icu (500V) = 75 kA and Ics = 100% Icu

P = Plug-in

(3)

3/16

8000/120
90/120

S3X at 690V can only be supplied from above

W = Withdrawable

ABB SACE

GSIS9100

GSIS9099

GSIS9138

SACE Isomax S3X

SACE Isomax S4X

SACE Isomax S6X

125-200
3-4

250
3-4

400-630
3-4

690
8

690
8

690
8

800
3000

800
3000

800
3000

X
300

X
300

X
300

200
180

200
180

200
180

150
75 (2)(3)

150
75

150
75

100%
440

100%
440

100%
440

3,5
A

3,5
A

3,5
A

F-P-W
F - EF - ES - FC - FC CuAl - RC - R

F-P-W
F - EF - ES - FC - FC CuAl - RC - R

F-W
F - EF - ES - FC CuAl - RC - R

EF - R
EF - R

EF - R
EF - R

EF - HR - VR

DIN EN 50023
25000/120

DIN EN 50023
20000/120

20000/120

10000(125A)-8000(200A) / 120
105/140

800 / 120
105/140

7000(630A)-5000(800A)/60
210/280

103,5
255

103,5
339

103,5
268

3,6 / 4,8
6,3 / 8,7

5/7
8,2 / 10,7

9,5 / 12
-

7,1 / 9,5

9 / 11,5

12,1 / 15,1

KEY TO TERMINALS

FC = Front for copper cables

RC = Rear for copper or aluminium cables

F = Front

FC CuAl = Front for copper or aluminium

HR = Rear horizontal flat bar

EF = Extended front

cables

VR = Rear vertical flat bar

ES = Extended spreaded front

R = Rear threaded

ABB SACE

3/17

SACE Isomax S current-limiting


circuit-breakers
General characteristics
SACE Isomax S2X 100 - S3X - S4X - S6X current-limiting
circuit-breakers
These pieces of apparatus are characterised by a rated voltage Ue of 690 V AC, by
rated uninterrupted currents from 100 A to 630 A, by service currents from 1 to 630 A
and by an ultimate short-circuit breaking capacity up to 200 kA at 380/415 V AC and
75 kA at 690 V AC.
The circuit-breakers, which comply with IEC 60947-2 Standards, are available in the
three- and four-pole type (only three-pole for S2X 100) in the fixed, plug-in and
withdrawable versions.
The function carried out by the current-limiting circuit-breakers is to limit the specific let-through energy to a maximum in the case of short-circuit, safeguarding the
integrity of the circuits and of the apparatus located on the load side.
The breaking system used, which foresees double interruption per pole, allows very
GSIS9028

high value short-circuits to be interrupted extremely rapidly.


Moreover, the special shape of the interruptive parts allows the peak values of fault
currents to be limited to figures considerably lower than those of the short-circuit
current present at the point of installation.
For the circuit-breakers on the load side, the rapidity of opening notably reduces
exposure to the electrodynamic stresses which occur in the case of a fault.

Integration with the SACE Isomax S family


The range of current-limiting circuit-

application flexibility which allows all

For S3X, S4X and S6X, conversion from

breakers has been conceived as a prod-

low voltage application requirements to

the fixed circuit-breaker into the mov-

uct aimed at particularly severe require-

be covered.

ing part of plug-in or withdrawable cir-

ments, but comes within the sphere of

In the SACE Isomax S series, the cur-

cuit-breaker is carried out by means of

the general SACE Isomax S project in

rent-limiting circuit-breakers offer the

special kits listed under the chapter en-

any case.

same benefits of modular construction.

titled Ordering codes (for S2X 100, the

The user gains considerable advan-

All the other versions can be made from

kit is the same as the corresponding

tages because it means being able to

the basic version of the current-limit-

S2 B/N/S one).

optimise stocks, standardise support

ing circuit-breaker by means of special

The fixed parts of current-limiting plug-

and installation structures and rational-

conversion kits.

in or withdrawable version circuit-breakers can, on the other hand, be used ei-

ise circuit-breaker selection thanks to

ther for the current-limiting circuit-breakers themselves or for the corresponding


SACE S2 - S3 - S4 and S6 automatic circuit-breakers.

With regard to accessories, too, the S2X


100, S3X, S4X and S6X current-limiting

GSIS9029

circuit-breakers use the same accessoGSIS9114

ries provided for the corresponding automatic circuit-breakers and also keep
the same electrical characteristics.

SACE Limitor

SACE Isomax S

LN A 32-63-100

S2X 100

LN 100 / LN 125

S3X 125

LN 160 / LN 200

S3X 200

LN 320 (setting 250 A)

S4X 250

LN 320

S6X 400

LN 500 / LN 630

S6X 630

The electrical characteristics of


the SACE Isomax S currentlimiting circuit-breakers allow a
comparison with the circuitbreakers in the previous SACE
Limitor series to be established,
to determine any replacements in

3/18

the case of installation upgrading.

ABB SACE

Applications

Only the following are an exception:


the mechanical interlocking plate for
two superimposed circuit-breakers

S3X and S4X)

civil, industrial and service sector


plants, as well as in electrical installa-

The wiring diagrams are those of the


corresponding SACE S2, S3, S4 and S6
circuit-breakers.

to the corresponding S2 B/N/S, of the


circuit-breakers, the S3X, S4X and S6X
current-limiting circuit-breakers keep
the standardised depth of 103.5 mm,
standardised widths of 105 mm (S3XS4X) / 210mm (S6X) for the three-pole
140

tions on board ships, in mines, on offshore oil rigs and, generally, wherever
very high short-circuit currents can oc-

Apart from S2X 100 which are identical

and

The current-limiting circuit-breakers are


suitable for installation in all types of

the bracket for fixing onto DIN rail (for

versions

They can also be inserted in plants

mm

(S3X-S4X)

280mm (S6X) for the four-pole versions,


identical drilled fixing holes for the plug-

cur due to the high powers of the generators and transformers up to 200 kA
at 380/415 V AC, 180 kA at 440 V AC

where back-up protection is foreseen,


which allows use on the load side of circuit-breakers with breaking capacity
lower than the prospective short-circuit
current at the point of installation.
The breaking capacities of the SACE
Isomax S current-limiting circuit-breakers have exceeded the best performances achieved by other apparatus of
this type.

and 75kA at 690 V AC.


The circuit-breakers can be placed
near the power supply source both for
general protection (plants, user groups
and electrical lines) and for protection
of electric machines (motors, generators, transformers, capacitor banks).

in and withdrawable versions and identical drilled holes for the compartment
door in all the versions and for all the
accessories.

Limited
let-through current

Prospective
short-circuit
current
The increased contact opening
speed, the dynamic blast action
produced by the magnetic field
and the structure of the arcing
chamber contribute to extinguishing the arc in the shortest
GSIS0084

possible time, limiting the specific

ABB SACE

let-through energy value I t and


the peak current.

3/19

SACE Isomax S current-limiting


circuit-breakers
General characteristics
Thermomagnetic overcurrent releases
The table below summarises the size values for the different types of releases:

Ith
Im
In

rated current of the thermomagnetic release, referred to an ambient temperature of 40 C

magnetic trip current

rated current of the electronic release

Thermomagnetic overcurrent releases


Circuit-breaker
S2X 100

L1 - L2 - L3 phases
S3X 200

Neutral

Setting

Thermal adjustment [A]

Magnetic trip [A]

Setting

[A]

0.7 ... 1 x Ith

Im = 10 x Ith

[A]

R1

0.7 ... 1

10

R 1,6

1.1 ... 1.6

16

R 2.5

1.75 ... 2.5

25

R4

2.8 ... 4

40

R 6.3

4.4 ... 6.3

63

R 10

7 ... 10

100

R 12.5

8.7 ... 12.5

125

R 16

11 ... 16

160

R 20

14 ... 20

200

R 25

17.5 ... 25

250

R 32

22.5 ... 32

320 (S2X 100) - 500 (S3X)

R 32 (S3X)

R 40

28 ... 40

400

R 50

35 ... 50

500

R 100 (S3X)

R 63

44 ... 63

630

R 80

56 ... 80

800

R 80 (S3X)

R 100

70 ... 100

1000

R 100 (S3X)

R 125

87.5 ... 125

1250

R 80

R 160

112 ... 160

1600

R 100

R 200

140 ... 200

2000

R 125

GSIS9057

S3X 125

SACE S2X 100 and S3X circuit-breakers, with


thermomagnetic overcurrent releases
3/20

ABB SACE

Electronic overcurrent releases


SACE PR211/P - PR212/P electronic overcurrent releases
Circuit-breaker
S4X 250

L
S
I
G
(1)

S6X 400

Release
S6X 630

L1 - L2 - L3 phases

Neutral (1)

Neutral

current

In [A]

I1 [A]

I2 [A]

I3 [A]

I4 [A]

[A]

[A]

100

40 ... 100

100 ... 1000 150 ... 1200

20 ... 100

20 ... 50

40 ... 100

160

64 ... 160

160 ... 1600 240 ... 1920

32 ... 160

32 ... 80

64 ... 160

250

100 ... 250

250 ... 2500 375 ... 3000

50 ... 250

50 ... 125

100 ... 250

320

128 ... 320

320 ... 3200 480 ... 3840

64 ... 320

64 ... 160

128 ... 320

400

160 ... 400

400 ... 4000 600 ... 4800

80 ... 400

80 ... 200

160 ... 400

630

252 ... 630

630 ... 6300 945 ... 7560

126 ... 630

126 ... 315 252 ... 630

Protection function against overload

Protection function against short-circuit with delayed trip

Protection function against short-circuit with instantaneous trip

Protection function against earth fault with delayed trip

(50% Ith) (100% Ith)

Only for PR212/P. Available on request for PR211/P, with additional ordering code 1SDA037505R1.

N.B. For more detailed information about the protection functions, please see page

3/12.

GSIS9115

SACE S4X, S6X circuit-breakers, with microprocessorbased overcurrent releases

ABB SACE

3/21

3/22

ABB SACE

SACE Isomax S circuit-breakers


for motor protection

Protection against short-circuit


Magnetic only and electronic circuit-breakers for
classical switching coordinations and
motor protection of any power
690V 80-1600 A 70-200 kA (380/415 V)

3
Integrated protection
The evolution of motor protection:
intelligence on board the circuit-breaker to design
protection around the motor, optimising space and time

GSIS9065

690V 160-1250 A 35-200 kA (380/415 V)

3/23

SACE Isomax S circuit-breakers for


motor protection (protection against short-circuit)

S2X 80

S3X

S3

Rated uninterrupted current, Iu

[A]

80

160 / 250

125 / 200

Rated service current, In


Poles

[A]
Nr.

180
3

3160 / 160200
3

3 125 / 125200
3

[V]
[kV]

690
6

690
8

690
8

[V]
[V]

690
3000

800
3000

800
3000

[kA]

X
100

N
65

H
100

L
170

X
300

(AC) 50-60 Hz 380/415 V


(AC) 50-60 Hz 440 V

[kA]
[kA]

70
70

35 (1)
30

65
50

85
65

200
180

(AC) 50-60 Hz 500 V


(AC) 50-60 Hz 690 V

[kA]
[kA]

50
10

25
14

40
18

50
20

150
75 (3)

[%Icu]
[kA]

75%
154

100%
74

75%
143

75%
187

100%
440

[ms]

3,5
A

7
A

Rated service voltage, Ue (AC) 50-60Hz


Rated impulse withstand voltage, Uimp
Rated insulation voltage, Ui
Test voltage at industrial frequency for 1 min.
Rated ultimate short-circuit breaking capacity, Icu
(AC) 50-60 Hz 220/230 V

GSIS9138

GSIS9135

GSIS9139

Electrical characteristics IEC 60947-2 and IEC 60947-4-1

Rated service short-circuit breaking capacity, Ics (2)


Rated short-circuit making capacity (415 V)
Opening time (415V at Icu)
Utilisation category (EN 60947-2)

3,5
A

Isolation behaviour
IEC 60947-2, EN 60947-2
Releases:

F-P
EF - FC

F-P-W
F - EF - ES - FC

F-P-W
F - EF - ES - FC

FC CuAl - R
FC - R

FC CuAl - RC - R
EF - FC - R

FC CuAl - R - RC
EF - R

DIN EN 50022

EF - FC - R
DIN EN 50023

EF - R
DIN EN 50023

25000/240
90

25000/120
105

25000/120
105

D [mm]
H [mm]

70
120

103,5
170

103,5
255

fixed, 3 poles
plug-in, 3 poles

[kg]
[kg]

1,1
1,3

2,6
3,1

3,6
6,3

withdrawable, 3 poles

[kg]

3,5

7,1

magnetic only, fixed 13xIn


magnetic only, adjustable 412xIn

microprocessor-based, PR211/P (I)


Interchangeability
Versions
Terminals

fixed
plug-in
withdrawable

Fixing on DIN rail


Mechanical life
Basic dimensions fixed, 3 poles

Weights

[No. operations / hourly operations]


L [mm]

(1) All the versions with Icu=35kA are certified at 36kA

KEY TO VERSIONS

(2) For S3N/H/L, S4N/H/L, S5N/H, and S6N/H circuit-breakers, the percentage performance of Ics at 690V is reduced by 25%

F = Fixed

(3) S3X at 690V can only be supplied from above

P = Plug-in
W = Withdrawable

3/24

ABB SACE

S4X

S5

S6

GSIS9106

GSIS9105

GSIS9104

GSIS9103

GSIS9102

GSIS9101

S4

S6X

S7

160 / 250

250

400 / 630

630 / 800

400 / 630

1250 / 1600

100, 160 / 250


3

100, 160, 250


3

320, 400 / 630


3

630 / 800
3

320, 400 / 630


3

1000, 1250 / 1600


3

690
8

690
8

690
8

690
8

690
8

690
8

800
3000

800
3000

800
3000

800
3000

800
3000

800
3000

N
65

H
100

L
200

X
300

N
65

H
100

L
200

N
65

S
85

H
100

L
200

X
300

S
85

H
100

L
200

35 (1)
30

65
50

100
80

200
180

35 (1)
30

65
50

100
80

35 (1)
30

50
45

65
50

100
80

200
180

50
40

65
55

100
80

25
18

40
22

65
30

150
75

25
20

40
25

65
30

25
20

35
22

40
25

65
30

150
75

35
20

45
25

70
35

100%
74

100%
143

75%
220

100%
440

100%
74

100%
143

75%
220

100%
74

100%
105

100%
143

75%
220

100%
440

100%
105

75%
143

50%
220

7
A

3,5
A

8
7
6
B(400A) / A(630A)

10

3,5
A

22

22
B

22

F-P-W
F - EF - ES - FC

F -P - W
F - EF - ES - FC

F - P(400A) - W
F - EF - ES - FC

F-W
F - EF - ES

F-W
F - EF - ES

F-W
F - EF - ES -

FC CuAl - R - RC
EF - FC - R

FC CuAl - R - RC
EF - R

FC CuAl - R - RC(400A)
EF - FC - R

FC CuAl - R - RC
-

FC CuAl - R - RC
-

FC CuAl (1250A) - HR - VR
-

EF - FC - R
DIN EN 50023

EF - R
DIN EN 50023

EF - FC - R - VR (630A)
DIN EN 50023

EF - HR - VR
-

EF - VR - HR
-

EF - VR - HR
-

20000/120
105

20000/120
105

20000/120
140

20000/120
210

20000/120
210

10000/120
210

103,5
254

103,5
339

103,5
254

103,5
268

103,5
406

138,5
406

4
4,5

5
8,2

5
6,1

9,5
-

15
-

17
-

4,9

6,4

12,1

25,4

21,8

KEY TO TERMINALS

FC = Front for copper cables

RC = Rear for copper or aluminium cables

F = Front

FC CuAl = Front for copper or aluminium cables

HR = Rear horizontal flat bar

EF = Extended front

R = Rear threaded

VR = Rear vertical flat bar

ES = Extended spreaded front

ABB SACE

3/25

SACE Isomax S circuit-breakers for


motor protection (protection against short-circuit)
General characteristics IEC 60947-2 and IEC 60947-4-1
Magnetic and electronic overcurrent releases
Three-phase asynchronous motor starting, switching and pro-

The new SACE S2X 80, with fixed magnetic protection at 13

tection are essential operations for its correct use. The tradi-

times the rated service current, is an extremely compact cir-

tional system used for this purpose has three different devices:

cuit-breaker, which stands out for its exceptional performances

a circuit-breaker for protection against short-circuit, a thermal

in terms of breaking capacity and limitation of the specific let-

relay for protection against overload and lack of or unbal-

through energy.

anced phase, and a counter for the motor operations. Every-

Extremely simple and rapid to install, it has the same possibility

thing must necessarily take into account the problems which

of mounting accessories and personalisation as the S2B/N/S

arise on start-up.

circuit-breakers. It can be used in a vast range of start-ups,

In particular, different factors must be taken into account when

from 0.37kW to 37kW and from 400V-50kA up to 690V-50kA.

selecting these devices, such as:

SACE S3 N/H/L 160/250 circuit-breakers and the S3X 125/200

the motor power

current-limiting circuit-breaker are fitted with a magnetic only

the starting diagram

release adjustable from 4 to 12 times the rated service cur-

the type of motor: with cage rotor or with wound rotor

rent. They cover coordinations from 37 to 132kW and allow

the fault current at the point of motor installation in the net-

optimal motor protection thanks to their great flexibility due to

work.

the wide setting range of the magnetic threshold.

ABB SACE proposes a wide range of circuit-breakers, which

Finally, SACE S4 160/250, S5 400/630, S6 630/800, and S7

by implementing the protection against short-circuit exclusively,

1250/1600, with different N-S-H-L breaking capacity levels,

are suitable for use inside protected starters of traditional type.

like the current-limiting S4X and S6X, can be fitted with the

3
Magnetic only fixed overcurrent releases
SACE Isomax S2X 80
Phases L1 - L2 - L3
Setting
[A]

Magnetic trip
Im = 13 x In [A]

R1

13

R1.6

21

R2

26

R2.5

32

R3.2

42

R4

52

R5

65

R6.5

84

R8.8

110

R11

145

R12.5

163

R16

210

R20

260

R25

325

R32

415

R42

545

R52

680

R63

820

R80

1040

Circuit-breaker
with magnetic

3/26

release

Contactor

Thermal relay

GSIS9116

Motor

ABB SACE

PR211/P (I) electronic microprocessor-based release. Above


all, they are used for protection of high power motors and, thanks
to adjustment of the protection against short-circuit from 1.5 to
12 times, allow the optimum trip value to be selected for any

GSIS9141

type of motor.

Magnetic only adjustable overcurrent releases


Circuit-breaker
S3N 160

S3H 160
S3L 160

Phases L1 - L2 - L3

S3N 250
S3H 250
S3L 250

S3X 125

S3X 200

(*)

Setting

Magnetic adjustment [A]

[A]

Im = 4 ... 12 x Ith

R3

12 ... 36

R5

20 ... 60

R 10

40 ... 120

R 25

100 ... 300

R 50

200 ... 600

R 100

400 ... 1200

R 125

500 ... 1500

R 160

640 ... 1600 (10 x Ith)

R 160

640 ... 1920

R 200

800 ... 2400

(*) Only to be used in coordination with contactors

SACE PR211/P (I) electronic microprocessor-based overcurrent releases for motor protection
Circuit-breaker
S4N 160
S4H 160
S4L 160

S4N 250
S4H 250
S4L 250

S5N 400
S5H 400
S5L 400

S6N 630
S6H 630
S6L 630

S6N 800
S6H 800
S6L 800

S7S 1250 S7S 1600


S7H 1250 S7H 1600
S7L 1250 S7L 1600

Phases L1 - L2 - L3
S4X 250

S6X 400

S6X 630

Rated current
of release
In [A]

I3 [A]

100

150 ... 1200

160

240 ... 1920

250

375 ... 3000

320

480 ... 3840

400

600 ... 4800

630

945 ... 7560

800

1200 ... 9600

1000

1500 ... 12000

1250

1875 ... 15000

1600

2400 ... 19200

I (*)

(*) I = Protection function against short-circuit

ABB SACE

3/27

SACE Isomax S circuit-breakers for motor


protection (integrated protection)

GSIS9107

Electrical characteristics IEC 60947-2 and IEC 60947-4

S4
Rated uninterrupted current, Iu

[A]

160 / 250

Rated service current, In


Poles

[A]
Nr.

100, 160 / 200


3

[V]
[kV]

690
8

[V]
[V]

800
3000

Rated service voltage, Ue (AC) 50-60Hz


Rated impulse withstand voltage, Uimp
Rated insulation voltage, Ui
Test voltage at industrial frequency for 1 min.

[kA]

N
65

H
100

L
200

(AC) 50-60 Hz 380/415 V


(AC) 50-60 Hz 440 V

[kA]
[kA]

35 (1)
30

65
50

100
80

(AC) 50-60 Hz 500 V


(AC) 50-60 Hz 690 V

[kA]
[kA]

25
18

40
22

65
30

100%
74

100%
143

75%
220

7
A

Rated ultimate short-circuit breaking capacity, Icu


(AC) 50-60 Hz 220/230 V

Rated service short-circuit breaking capacity, Ics (2)


Rated short-circuit making capacity (415 V)

[%Icu]
[kA]

Opening time (415V at Icu)


Utilisation category (EN 60947-2)

[ms]

Isolation behaviour
IEC 60947-2, EN 60947-2, IEC 60947-4-1, EN 60947-4-1
PR212/MP (LRIU) microprocessor-based releases
Interchangeability
Versions
Terminals

fixed

F-P-W
F - EF - ES - FC

plug-in

FC CuAl - R - RC
EF - FC - R
EF - FC - R

withdrawable
Fixing on DIN rail DIN EN 50023
Mechanical life
Basic dimensions, fixed 3 poles

[No. operations / hourly operations]


L [mm]
D [mm]
H [mm]

Weights

20000/120
105
103,5
254

fixed, 3 poles
plug-in, 3 poles

[kg]
[kg]

4
4,5

withdrawable, 3 poles

[kg]

4,9

(1) All the versions with Icu=35kA are certified at 36kA

KEY TO VERSIONS

(2) For S4N/H/L, S5N/H, and S6N/H circuit-breakers the percentage performance of

F = Fixed

Ics at 500V and 690V is reduced by 25%

P = Plug-in
W = Withdrawable

3/28

ABB SACE

S5

S6

250
100, 160, 200

400
320
3

3
690
8
800
3000
X
300
200
180
150
75
100%
440
3,5
A

F-P-W
F - EF - ES - FC FC CuAl - R RC
EF - R
EF - R
20000/120
105
103,5
339
5
8,2
9

GSIS9112

GSIS9111

GSIS9110

GSIS9109

GSIS9108

S4X

S6X

S7

630

400 / 630

1250

630
3

320, 400 / 630


3

1000
3

690
8

690
8

690
8

690
8

800
3000

800
3000

800
3000

800
3000

N
65

H
100

L
200

N
65

H
100

L
200

X
300

S
85

H
100

35(1)
30

65
50

100
80

35(1)
30

65
50

100
80

200
180

50
40

65
55

25
20

40
25

65
30

25
20

40
25

65
30

150
75

35
20

45
25

100%
74

100%
143

75%
220

100%
74

100%
143

75%
220

100%
440

100%
105

75%
143

7
B

8
B

3,5
A

22

22
B

F-P-W
F - EF - ES - FC

F-W
F - EF - ES

F-W
F - EF

F-W
F - EF - ES

FC CuAl - R - RC
EF - FC - R

FC CuAl - R - RC
-

FC CuAl - R - RC
-

FC CuAl - HR - V
-

EF - FC - R

EF - HR - VR
-

EF - VR - HR
-

EF - VR - HR
-

20000/120
140

20000/120
210

20000/120
210

10000/120
210

103,5
254

103,5
268

103,5
406

138,5
406

5
6,1

9,5
-

15
-

17
-

6,4

12,1

25,4

21,8

KEY TO TERMINALS

FC = Front for copper cables

RC = Rear for copper or aluminium cables

F = Front

FC CuAl = Front for copper or aluminium cables

HR = Rear horizontal flat bar

EF = Extended front

R = Rear threaded

VR = Rear vertical flat bar

ES = Extended spreaded front

ABB SACE

3/29

SACE Isomax S circuit-breakers for motor


protection (integrated protection)
General characteristics
SACE PR212/MP electronic microprocessor-based releases
SACE Isomax S4N-H-L 160/250, S5N-H-L 400, S6N-H-L 800,
S7S-H 1250 and S4X 250, S6X 400/630 circuit-breakers are

Circuit-breaker with

fitted with SACE PR212/MP electronic releases constructed

SACE PR212/MP

using microprocessor-based electronic technology. This al-

electronic

lows functions to be obtained which guarantee high trip preci-

microprocessor-based

sion, utmost reliability and insensitivity to variations in the ex-

release

ternal temperature. The SACE PR212/MP electronic release


guarantees complete motor protection as is fully integrated on
board the circuit-breaker; moreover, it is able to control contactor opening in the case of a fault (except for short-circuit),

Contactor

by means of the SACE PR212/CI contactor accessory operating mechanism unit. Furthermore, the PR010/T unit for testing
the release and checking the protection functions, the PR010/K
signalling unit and the PR212/D dialogue unit are available.
The electronic microprocessor-based releases are self-supplied and consist of three current transformers, the SACE
PR212/MP protection unit and an opening solenoid which acts
directly on the circuit-breaker operating mechanism unit. The
Motor

current transformers housed inside the release box, supply


the energy and the signal required for correct operation of the

The release is temperature-compensated and sensitive to lack


of phase according to Table IV of the 60947-4-1 7.2.1.5.2 Standard.

SACE PR212/MP electronic microprocessor-based releases for motor protection


Circuit-breaker
S4N 250
S4H 250
S4L 250

S5N 400
S5H 400
S5L 400

S6N 800
S6H 800
S6L 800

S7S 1250
S7H 1250

S4X 250

S6X 400

S6X 630

Release rated
current
In [A]

I1 [A]

I5 [A]

I3 [A]

Iu [A]

100

40 ... 100

600 ... 1300

160

64 ... 160

960 ... 2080

200

80 ... 200

1200 ... 2600

320

128 ... 320

400

160 ... 400

630

252 ... 630

3780 ... 8190

1000

400 ... 1000

6000 ... 13000

Protection function against rotor block with relative setting current and time (I5 = 3-4-5-6-7-8-10 x I1 - t5 = 1-4-7-10 s)

Protection function against short-circuit with relative setting current (I3 = 6-7-8-9-10-11-12-13 x In)

Protection function against lack of or unbalance of

3/30

1920 ... 4160

0,4 x I1

S4N 160
S4H 160
S4L 160

Phases L1 - L2 - L3

3 ... 10 x I1

protection.

2400 ... 5200

Protection function against overload with relative setting current (I1 = 0.4 ... 1 x In, with 0.01 steps - Class = 10A, 10, 20, 30)

phase with relative setting current and time (Iu = 0.4 x I1 - t = 4 s)

ABB SACE

The SACE Isomax S range of moulded-

thereby saving space, assembly mate-

case circuit-breakers for motor protec-

rial, installation time and relative cabling

tion is perfectly coordinated with the new

operations.

ABB line of contactors. The latter, de-

The circuit-breaker-contactor group en-

fined as A-Line, together with the line of

hances this characteristic even further

overload thermal relays and SACE

with the SACE PR212/MP electronic

Isomax S moulded-case circuit-break-

overcurrent release, which allows con-

ers, is the basis for the new generation

struction of an extremely compact pro-

of apparatus specially designed to guar-

tected starter, implementing protection

antee a system of products which can

against overload in accordance with the

be integrated according to the applica-

IEC 60947-4-1 Standard.

tions required. All this is done with the


aim of not only continuously improving
the products, but above all to provide
designers, installers and end users with
the best solutions in terms of performance and reliability, combined with simplicity of the system.
In particular, SACE Isomax S circuitbreakers and the A series of contac-

SACE Isomax S moulded-case circuit-breakers and the new A series contactors share the same
width and depth and have been
designed to construct a single

tors are an extraordinary solution in terms

compact unit

of compactness, since they share the


same width and design characteristics,

GSIS9061

Typical operating characteristic of an asynchronous motor


l1

trip current function L

l3

trip current function I

I5

trip current function R

t5

trip time function R

I6

trip current function U

t6

trip time function U

le

rated service current of the motor

la

starting current of the motor

Ip

peak value of the subtransient starting


current

ta

motor starting time

tp

duration of the starting subtransient phase

typical motor starting curve

example of trip curve of a motor


protection circuit-breaker with electronic
release

The different curves of the functions, with numerous threshold and time settings, allow an overall

GSIS0082

trip curve to be drawn which is really close to the

ABB SACE

motor starting curve, thereby optimising its protection

3/31

SACE Isomax S circuit-breakers


for motor protection (integrated protection)
General characteristics
Protection functions and parametrisation of the SACE PR212/MP release
Function L
Protection against overload

Parametrisation of protection L
l1 = 0,4 ... 1 x In with 0.01 x In steps

Function L protects the motor against undesired overloads according


to the indications and classes defined in the IEC 60947-4-1 Standards.
Protection is based on a pre-established thermal model (ABB SACE
International Patent) which, by simulating the copper and iron
overtemperatures inside the motor, allows precise safeguarding of
the

machine.

The

protection

intervenes

when

the

preset

overtemperature is reached. The trip time is fixed by selecting the trip


class defined in the above-mentioned Standards.
The function is temperature-compensated and sensitive to phase

where l1 is the rated service current of the circuit-breaker, which


must be the same or higher than that of the motor to be protected (I1
> Ie), and In is the rated current of the current transformers.
t1 = 4 - 8 - 16 - 24 s
where t1 is the trip at 7.2 x I1 cold,
depending on the class selected
Class 10A - 10 - 20 - 30
are the motor starting classes which determine the trip times for
overload according to the IEC 60947-4-1 4.7.3 Table II Standards.

missing/unbalance in accordance with the IEC 60947-4-1 Standard.


In the case of auxiliary power supply, the thermal memory function is
guaranteed, which allows the release to continue calculating the motor
temperature even after an opening operation.

Release of the contactor: in normal operating mode


Tolerances: in accordance with the IEC 60947-4-1 Standard.

Function R
Protection against rotor block

Parametrisation of protection R

Function R protects the motor against any rotor block during operation.

where l5 is the current at which the rotor is considered to be blocked


and l1 is the rated service current of the circuit-breaker selected for
function L.

This protection is automatically disabled for the whole of the motor


starting phase and is then re-activated.
The protection already provides its function from low current increases

l5 = OFF - 3 - 4 - 5 - 6 - 7- 8 - 10 x l1

t5 = 1 - 4 - 7 - 10 s

(from 3 times the l1 service current of the circuit-breaker) and can


also be disabled.

where t5 is the preset time threshold above which the release trips.

Both the current level to be tripped and the trip time delay can be
selected.
The protection intervenes when at least one of the phase currents
exceeds the preset value and remains above that threshold for the

Release of the contactor: in normal operating mode


Tolerances:

10%
20%

of the trip thresholds


of the trip times

set t5 time.

Function I
Protection against short-circuit
This protection function intervenes in the case of a short-circuit between phases. It is sufficient for a single phase to exceed the set
threshold to cause immediate opening of the circuit-breaker (the protection cannot be excluded).
The trip current can be adjusted up to 13 times the rated current of the
release, whereas the time is fixed.
To prevent unwarranted trips during starting, the protection recognises whether the motor to be protected is in the starting phase or
whether there is a short-circuit. This is to allow starting under com-

Parametrisation of protection I
l3 = 6 - 7 - 8 - 9 - 10 - 11 - 12 - 13 x In
where I3 is the instantaneous trip current for short-circuit and In is
the rated current of the current transformers.
To prevent unwarranted trips during the inrush phase of the motor,
instantaneous tripping of protection I takes place at 1.5 x I3 (for I3 <
9 x In), whereas for higher values (I3 > 9 x In) tripping takes place
at 13.5 x In.
Tolerances: 20% of the trip thresholds
20% of the trip times

pletely safe conditions.

Function U
Protection against lack of and/or unbalance of a
phase
Function U can be used in those cases where particularly precise
control is needed regarding lack of and/or unbalance of phase currents. This function can be excluded and intervenes if the effective

Parametrisation of protection U
On, (with I6 = 0.4 x l1 and t6 = 4 s).
Off, in the Off position, the release remains sensitive to the lack of
phase according to the IEC 60947-4-1 Standard, modifying the trip
curves for protection L.
Release of the contactor: in normal operating mode

value of one or two currents drops below the level of 0.4 of the l1
current set with function L and remains there for more than 4 seconds.

3/32

Tolerances: 20% of the trip thresholds


20% of the trip times

ABB SACE

Parametrisation of the release

Operating methods

Back-up protection

By means of the microswitch located on the


front, the release can be fitted for
parametrisation:
Man. (manual), thresholds and times are adjusted by using the microswitches on the front
of the relay
Elt. (electronic), thresholds and times are adjusted remotely by means of the SACE
PR212/D dialogue unit.

Normal mode: in the case of a fault detected


by functions L-R-U, contactor opening can be
controlled by means of the accessory SACE
PR212/CI module or directly, without the need
for external modules, with an ABB contactor
fitted with an electronic interface with the circuit-breaker.
Heavy duty mode: the circuit-breaker opens
for any type of L-R-I-U fault.

The electronic release verifies whether the


circuit-breaker or the contactor is effectively
in the open or relay tripped position following
an opening command. If this is not so, after a
delay set to long or short time, the command
for circuit-breaker opening is given again.

Protection L
against motor
overload

luminous signalling of
overload:
fixed for I > 0.9 x I1;
flashing for I > 1.05 x I1

Protection R

Protection I

Protection U

Man. / Elt.

against blocked
rotor

against
instantaneous
short-circuit

against the lack


and/or unbalance
of a phase

release
parametrisation
methods

socket for connection


of SACE PR010/T Test
unit

GSIS9053

Class
class of
motor starting
according to the IEC
60947-4-1 Standards

socket for selection between:


SACE TT1 - PTC (*) temperature
Test unit sensor input
- 0/1 generic input

setting the
back-up time

setting the Reset


following a trip:
- manual
- automatic

setting
the work
methods

(*) A special input is available to connect a PTC temperature probe, inserted in the motor to be protected

Characteristics of the SACE PR212/MP electronic microprocessor-based release


Overloading capacity

2 x In continuously, 7.2 x In for 35 s at 45 C

Operating temperature

25 C ... + 70 C

Maximum relative humidity percentage

90% without condensation

Rated service frequency

45 - 66 Hz, able to measure harmonics up to 550 Hz

Current measurement methods

r.m.s. up to 3 x In (functions L, R, U)
peak value for values over 3 x In (functions L, R, U)
peak value for function I

Electromagnetic compatibility

According to: IEC 60947-2 Standard Annex F

Electrostatic discharges

According to: IEC 61000-4-2 Standard

Radiated electromagnetic field

According to: IEC 61000-4-3 Standard

Short-time transients

According to: IEC 61000-4-4 Standard

Mean time between failure (MTBF)

15 years (at 45 C)

ABB SACE

3/33

3/34

ABB SACE

SACE Isomax S circuit-breakers


for applications up to 1000V

Taking the SACE Isomax S limits higher and higher


1000 V 160-800 A 6-50 kA

GSIS9066

3/35

SACE Isomax S circuit-breakers


for applications up to 1000V
Electrical and general characteristics IEC 60947-2
Within the panorama of Isomax proposals, there is also the range of circuitbreakers and switch-disconnectors for
direct current and alternating current
applications up to 1000V.
The typical application sectors are installations in mines, road or railway tunnels, traction and industrial applications
in general.
The circuit-breakers for direct current
(connection diagrams on page 5/47) are
available in the four-pole version,
whereas those for alternating current are
available in the three-pole version, with
adjustable or electronic thermomagnetic
releases and have the same dimensions
as the standard versions.
They can also be combined with all the
accessories available for the Isomax
series.

~
V
V~

Range at 1000 V in a.c.

S3

Rated uninterrupted current, Iu


Poles
Rated service voltage, Ue (AC) 50-60Hz
Rated impulse withstand voltage, Uimp

[A]
Nr.

160
3

[V]
[kV]

1000
8

[V]

1000
3000

Rated insulation voltage, Ui


Test voltage at industrial frequency for 1 min.
Rated ultimate short-circuit breaking capacity,
Icu (AC) 50-60 Hz 1000 V

[kA]

L
6

Rated short-circuit making capacity


Opening time

[kA]
[ms]

9,2
20

Rated short-time withstand current for 1 s, Icw


Utilisation category (EN 60947-2)

[kA]
A

Isolation behaviour
IEC 60947-2, EN 60947-2
Thermomagnetic releases T adjustable, M fixed 10 Ith
PR211/P (LI only) microprocessor-based releases
PR212/P (LSI-LSIG) microprocessor-based releases
Versions

Terminals
Fixing on DIN rail

F
DIN EN 50023

Mechanical life
Dimensions

[No. operations / hourly operations]


L [mm]
D [mm]
H [mm]

Weights

Range at 1000 V in d.c.

[kg]

V
V

Rated uninterrupted current, Iu


Poles

Rated insulation voltage, Ui


Test voltage at industrial frequency for 1 min.

103,5
170
2,6

S3

S5

S6

S6

160-250
4

400
4

630
4

800
4

[V ]
[kV]

1000
8

1000
8

1000
8

1000
8

[V]

1000
3000

1000
3000

1000
3000

1000
3000

[A]
Nr.

Rated service voltage, Ue


Rated impulse withstand voltage, Uimp

25000/120
105

Ultimate rated short-circuit breaking capacity, Icu


(4 poles in series)

[kA]

L
40

L
40

L
40

L
50

Rated short-circuit making capacity


Opening time

[kA]
[ms]

40
25

40
35

40
45

50
50

Rated short-time withstand current for 1 s, Icw


Utilisation category (EN 60947-2)

[kA]

5
B

7,6
B

10
B

Isolation behaviour
IEC 60947-2, EN 60947-2
Thermomagnetic releases, T adjustable - M fixed 10 Ith
Thermomagnetic releases, T adjustable - M adjustable

Versions
Terminals

F
F

F
F

F
F

F
F

DIN EN 50023
25000/120

DIN EN 50023
20000/120

20000/120

20000/120

L [mm]
D [mm]

140
103,5

184
103,5

280
103,5

280
103,5

H [mm]
[kg]

170
3,5

254
7

268
12

268
12

Fixing on DIN rail


Mechanical life
Basic dimensions, fixed

Weights, fixed

3/36

[No. operations / hourly operations]

ABB SACE

S3X

S4

S4X

S5

S6

S6X

125
3

160-250
3

250
3

400
3

630-800
3

630
3

1000
8

1000
8

1000
8

1000
8

1000
8

1000
8

1000
3000

1000
3000

1000
3000

1000
3000

1000
3000

1000
3000

X
30

L
8

X
30

L
8

L
12

X
30

63
10

13,6
30

63
20

13,6
30

24
30

63
25

5
B

7,6 (630A)-10 (800A)


B

F
DIN EN 50023

F
DIN EN 50023

F
DIN EN 50023

F
DIN EN 50023

25000/120
105

20000/120
105

20000/120
105

20000/120
140

20000/120
210

20000/120
210

103,5
255

103,5
254

103,5
254

103,5
254

103,5
268

103,5
406

3,6

9,5

15

Circuit-breakers with electronic release for alternating current


In100
S4L 160

In400

In630

In800

1501200

3753000

600 ... 4800

9457560

S4L 250
S4X 250
S5L 400
S6L 630
S6X 630
S6L 800
Im = 1,5 12 x In [A]

In250

12009600

Circuit-breakers with thermomagnetic release for alternating current


(thermal threshold adjustable from 0.7 to 1 x In; fixed magnetic threshold)
R32

R50

R80

R100

R125

R160

R200

R250

S3L 160
S3X 125
Im AC (10xIn) [A]

500

500

800

1000

1250

1600

2000

2500

Circuit-breakers with thermomagnetic release for direct current


R32 (1)

R50 (1)

R80 (1)

R100 (1)

R125 (1)

R160 (1)

R200 (1)

R250 (1)

R400 (2)

R630 (2)

R800 (2)

S3L 250

S5L 400

500

500

800

1000

1250

1600

2000

2500

S3L 160

S6L 630
S6L 800
Im DC (10xIn) [A]
Im DC (5-10xIn) [A]

2000-4000 3150-6300 4000-8000

(1) Thermal threshold adjustable from 0.7 and 1 x In; fixed magnetic threshold
(2) Thermal threshold adjustable from 0.7 and 1 x In; magnetic threshold adjustable between 5 and 10 x In.

ABB SACE

3/37

3/38

ABB SACE

SACE Isomax S
switch-disconnectors

Close, carry and isolate.


The certainty of operating in complete safety.
690 V 125-3200 A 3,1-85 KA (Icm) 2,2-40 kA (Icw)

GSIS9067

3/39

SACE Isomax S switch-disconnectors

GSIS9142

GSIS9143

Electrical and general characteristics IEC 60947-3

Conventional thermal current at 60 C, Ith


Number of poles
Rated service voltage, Ue

(AC) 50-60Hz
(DC)

Rated current, Iu
Rated impulse withstand voltage, Uimp
Rated insulation voltage, Ui
Test voltage at industrial frequency for 1 min.
Rated short-circuit making capacity (415 V~), Icm
Rated short-time withstand current for 1 s, Icw

S2D

S3D

[A]
Nr.

125 / 160
3/4

100 / 160 / 250 / 320


3/4

[V~]
[V]

690
500

690
750

[A]
[kV]

125-160
6

100-160-250-320
8

[V]
[V]

690
3000

800
3000

[kA]
[kA]

3,1
2,2

10
6,5

F-P
EF - FC - FC CuAl

F-P-W
F - EF - FC

R - RC
FC - R

FC CuAl - R - RC
F - FC - R

25000/240

F - FC - R
25000/120

Isolation behaviour
IEC 60947-3

Versions
Terminals

fixed
plug-in

Mechanical life

withdrawable
[No. of operations / hourly operations]

Basic dimensions, fixed

Weights, fixed

L (3/4 poles)
D

[mm]
[mm]

90/120
70

105/140
103,5

H
3/4 poles

[mm]
[kg]

120
1,1/1,5

170
2,6/3,5

Coordination with the circuit-breakers (kA at 380-415 V AC)


LOAD SIDE

SUPPLY SIDE

S2D 125

S2D 160

S3D 100

S3D 160

S1B

16

16

S1N

25

25

S2B

16

16

16

16

S2N

35

35

35

35

S2S

50

50

S3D 250

S3D 320

50

50

S3N

35

35

35

35

S3H

65

65

65

65

S6D 400

S6D 630

S6D 800

S5N

35

35

35

S5H

35

35

35

S6N

35

35

35

S6S

50

50

50

S6H

65

65

65

S7D 1000

S7S

50

S7H

65

S8H
S8V

3/40

ABB SACE

GSIS9146

GSIS9145

GSIS9144

S6D

S7D

S8D

400 / 630 / 800


3/4

1000 / 1250 / 1600


3/4

2000 / 2500 / 3200


3/4

690
750

690
750

690
750

400-630-800
8

1000-1250-1600
8

2000-2500-3200
8

800
3000

800
3000

800
3000

30
15

52,5
25

85
40

F-W
F - EF - FC CuAl

F-W
F - EF - FC CuAl (1250A)

F
EF (2500A)-R

R - RC
-

HR - VR
-

F - HR - VR
20000/120

F - HR - VR
10000/120

10000/20

210/280
103,5

210/280
138,5

406/556
242

268
9,5/12

406
17/22

400
57/76

S7D 1250

S7D 1600

S8D 2000

S8D 2500

The switch-disconnectors derive from the corresponding circuit-breakers, of which they keep the same overall dimensions,
versions, fixing systems and possibility of mounting accessories.
They are characterised by a rated voltage of 690 V in alternating current and 750 V in direct current.

Applications

S8D 3200

They can be used as general circuit-breakers in sub-switchboards, as switching and isolating parts for lines, busbars or
groups of apparatus, or as bus-ties. They can be part of general isolation devices of groups of machines or units for motor
switching and protection.

Isolation
The main function carried out by these circuit-breakers consists of isolating the circuit they are inserted in.
Once open, the contacts are at a sufficient distance to prevent
an arc striking, in accordance with the standard prescriptions
relative to isolation behaviour. The position of the operating
lever corresponds with certainty to that of the contacts (positive operation).

Protection
Each switch-disconnector must be protected on the supply
side by a coordinated device which safeguards it against shortcircuits. The coordination table at the side shows the SACE
Isomax S circuit-breaker which can carry out the protection
function for each switch-disconnector. These are always pieces
of apparatus of a size corresponding to or lower than that of
the switch-disconnector.

Making capacity
The making capacity, Icm, is of considerable importance, since
a switch-disconnector must be able to withstand the dynamic,
thermal and current stresses that can occur during closing
without being destroyed, up to and including closing under
short-circuit conditions.
50

50

65

65

ABB SACE

Endurance in the closed position


85

85

85

120

120

120

This identifies the capacity for maintaining the closed position


for short-time overcurrents. It is an important parameter which
qualifies the performances of these pieces of apparatus.
3/41

3/42

ABB SACE

SACE Isomax S circuit-breakers


according to UL489 and
CSA C22.2 Standards

SACE Isomax S quality to conquer New worlds


480/600 V 100-2500 A 25-100 kA (480V)

GSIS9068

3/43

SACE Isomax S circuit-breakers according to


UL489 and CSA C22.2 Standards
Electrical and general characteristics
Circuit-breaker type

S1

Maximum frame continuous current 40 C

[A]

100

150

Number of poles
Rated operational voltage (AC) 50-60 Hz

Nr.
[V]

3
277/480

2-3
600

(DC)
Test voltage (1min.) 50-60 Hz

[V]
[V]

3000

600
3000

UL/CSA short-circuit interrupting capacity


240 V AC

S3 225
225
2-3
240 (B); 480 (N/H/L)
500
3000

[kA rms]
[kA rms]

N
50

N
65

H
100

L
150

B
150

N
65

H
100

L
150

[kA rms]

14 (R15)
20 (R20-R100)

25

50

65 (R15, R30)
85

25

50

65

600 V AC
[kA rms]
500 V DC (2 poles in series)[kA rms]

14
35

14
50

25
65

50

20

35

50

600 V DC (3 poles in series) [kA rms]


Overcurrent trip relays

20

35

50

480 V AC

Thermal-magnetic
Microprocessor based

[in/mm]

4,72 / 120

6,70 / 170

6,70 / 170

W
D

[in/mm]
[in/mm]

3,07 / 78
2,75 / 70

4,13 / 105
4,07 / 103,5

4,13 / 105
4,07 / 103,5

Mechanical duration
Weights (fixed - 3P)

[op./ frequency]
[lbs.]

25000 / 240
2,42

25000 / 120
6,75

25000 /120
6,75

Interchangeability
Dimensions
H
fixed version

S3 150

In the field of moulded-case circuit-breakers, complying with


the UL489 and CSA22.2 standards, the SACE Isomax S offer is
enriched by the following ranges:
circuit-breakers for power distribution (fitted with
thermomagnetic or electronic releases)
circuit-breakers with magnetic only releases for motor protection (Motor Control Protection MCP)
switch-disconnectors for use as isolators or switching devices for lines, busbars or parts of a plant circuit-breakers
(Moulded Case Switch MCS).
The SACE Isomax S offer in compliance with UL/CSA Standards is completed with the introduction of three new sizes. There
are therefore increasing possibilities for those customers who
also operate on markets subject to the standards defined in the
UL/CSA Standards, with a whole range of moulded-case circuit-breakers available, with rated currents which go from 100A
to 2500A and breaking capacities, at 480 V AC, which can
reach 100kA.
Apart from lowering the range of rated currents, introduction of

3/44

the S1 size allows all those applications typical of power subdistribution where a circuit-breaker characterised by limited
dimensions, but guaranteeing great versatility of application of
accessories and installation, is particularly convenient.
They further increase the possibility of selection, thanks to the
introduction of the new rating for S3, Iu=225A, with three levels
of breaking capacity (N/H/L), up to service voltage values of
Ue=480V AC and 500 V DC.
Finally, the S8 circuit-breaker according to the UL/CSA Standard also allows completion towards higher rated currents.
Isomax S8V 1600, 2000 and 2500 are suited to installation
immediately to the load side of power supply sources of low
voltage systems and can operate safely under the most severe
service conditions required by modern installations. Their high
performances, great flexibility in mounting accessories, simple
coordination with the devices on the load side and the possibility of limiting the depth of the switchboards thanks to their compact overall dimensions, make Isomax S8 a particularly advantageous choice.

ABB SACE

S4

S5

S6

S7

S8

250

400

800

1200

1600-2000-2500

2-3
600

2-3
600

2-3
600

2-3
600

3
600

3000

600
3000

600
3000

3000

3000

N
65

H
150

L
200

N
65

H
150

L
200

N
65

H
150

L
200

H
100

V
120

25

65

100

35

65

100

50

65

100

65

100

18
-

22
-

35
-

22
35

22
50

35
65

25
35

35
50

42
65

50
-

85
-

20

35

50

20

35

50

10,00 / 254

10,00 / 254 (300A); 13,62 / 346 (400A)

14,25 / 268

16 / 406

15,75 / 400

4,13 / 105
4,07 / 103,5

5,51 / 140
4,07 / 103,5

8,27 / 210
4,07 / 103,5

8,27 / 210
5,45 / 138.5

15,98 / 406
9,25 / 235

20000 / 120
8,8

20000 / 120
11

20000 / 120
22

10000 / 120
37,5

10000 / 20
135

Motor Control protection - MCP


Type
Poles
Trip Unit

S3L

S4 N/H/L

S5 N/H/L

S6 N/H/L

S7H

S8V

Adjustable magnetic only


(4...12xIn)
PR211/P - I
Rating

325

50150

400

400

400

1000-1200

1600-2000-2500

Interrupting capacity
240 V AC

[A]

L
50

L
150

N
65

H
150

L
200

N
65

H
150

L
200

N
65

H
150

L
200

H
100

V
120

480 V AC
600 V AC

25
10

85
25

25
18

65
22

100
35

35
22

65
22

100
35

50
25

65
35

100
42

65
50

100
85

65
50

500 V DC
600 V DC
(1)

65
50

(1)
(1)

100-250

600-800 600-800 600-800

Performance available only for the 25 A rating version

Moulded Case Switches - MCS


Type

S3 H-D 150

S3 H-D 225

S4 H-D

S5 H-D

S6 H-D

S7 H-D

S8 V-D

Rating
Poles

[A]

150
3

225
3

250
3

400
3

800
3

1200
3

2500
3

Magnetic trip
Rated voltage

[A]

1500

2250

3000

5000

10000

20000

35000

(AC) 50-60 Hz
[V~]
(DC) 3 poles in series [V]

600
600

480
500

600
600

600
600

600
600

600
600

600
600

ABB SACE

3/45

3/46

ABB SACE

Accessories

Index
Versions ............................................................................................................................. 4/3
Connection terminals ..................................................................................................... 4/6
Service releases ............................................................................................................... 4/10
Electric signals ................................................................................................................. 4/14
Remote controls .............................................................................................................. 4/17
Operating mechanisms and locks ................................................................................ 4/22
Residual current releases ............................................................................................... 4/26
Accessories for electronic releases .............................................................................. 4/30
Installation accessories and spare parts ..................................................................... 4/35

ABB SACE

4/1

GSIS9070

4/2

ABB SACE

Accessories
Versions

GSIS9120

GSIS9122

GSIS9121

SACE Isomax S circuit-breakers are available in the FIXED, PLUG-IN or WITHDRAWABLE, three-pole or four-pole versions.

FIXED

PLUG-IN

WITHDRAWABLE

The FIXED version circuit-breaker with

The PLUG-IN version circuit-breaker con-

The WITHDRAWABLE version circuit-

three or four-poles has:

sists of:

breaker is made up of:

the same upper and lower terminals

fixed part to be installed directly on the

fixed part, to be installed directly on

lever operating mechanism

base plate of the cubicle

the base plate of the cubicle with the

thermomagnetic or electronic release

moving part obtained from the fixed

side group mounted on the fixed part

flange for the front door of the switch-

circuit-breaker with the addition of the

to allow the racking-out/racking-in

board

isolating contacts in correspondence

possibility of assembly on base plate


or on DIN rail (up to 630A)
circuit-breakers featuring only four

movement

with the connection terminals, of the

moving part obtained from the fixed

rear frame for fixing to the fixed part

circuit-breaker with the addition of the

and of the terminal covers.

isolating contacts in correspondence

depths (70mm for S1-S2, 103.5 for

Circuit-breaker racking out is carried out

with the connection terminals, of the

S3...S6, 138.5 for S7 and 242 for S8)

by unscrewing the top and bottom fixing

rear frame (which is coupled with the

standardised front for groups of circuit-

screws. A special lock prevents the cir-

side piece provided on the fixed part

breakers (45mm for S1...S5, 105mm for

cuit-breaker from being racked in and out

for sliding) for fixing to the fixed part,

S3...S7).

with the contacts in the closed position.

and of the terminal covers.


accessory to be applied on the front of
the circuit-breaker with selection between front for lever operating mechanism, motor operator and rotary han-

Fixed

Plug-in

Withdrawable

dle operating mechanism; application


of one of these accessories allows the

S1 125

circuit-breaker lock to be made in the


withdrawn position.
Racking-in/out of the moving part is car-

S2 160

S3 160

ried out by means of the special operating lever supplied with the circuit-breaker
in the moving part for withdrawable ver-

S3 250

sion or with the conversion kit of the fixed

S4 160

circuit-breaker into moving part of with-

S4 250

drawable circuit-breaker. The special


mechanism allows the circuit-breaker to

S5 400

be put into the isolated position (with

S5 630

power and auxiliar y circuits discon-

S6 630

nected) with the compar tment door

S6 800

S7 1250

S7 1600

S8 2000

S8 2500

S8 3200

closed, providing increased operator


safety. The lever can only be inserted with
the circuit-breaker open.
Once racked out or withdrawn, the circuit-breaker can be operated in the open/
closed position and, by means of the
special connection extensions, blank
operating tests of the auxiliary control
circuits can be carried out.

ABB SACE

4/3

Accessories
Versions

Starting from the fixed version with front terminals, SACE Isomax S circuit-breakers can be converted into the various versions
using the Conversion kits. This makes management of the product, its versions and stocks as a whole highly flexible. It is, in

any

case, always possible to ask for the circuit-breaker in the required version fully prepared in the factory.

Conversion kit into moving part for plug-in circuit-breaker


This allows the fixed circuit-breaker with
front terminals to be converted into the

S1-S2

S3-S4

moving part of a plug-in circuit-breaker.


The kit consists of:
tulip isolating contacts
frame
assembly screws and nuts.
The fixed part is needed to complete the

GSIS0102

GSIS9036

GSIS0101

circuit-breaker.

4
Fixed part
The fixed part allows the circuit-breaker
to be constructed in the plug-in or
withdrawable version. It can also be
provided in the switchboard as a reserve
power supply to be completed with a
circuit-breaker at the appropriate time.
For plug-in or withdrawable version
circuit-breakers, different circuit-breaker
positions are possible:

Withdrawable: racked-in racked-out


- withdrawn.

GSIS9123

Plug-in: racked-in racked-out

The fixed part for withdrawable version


circuit-breaker is fitted with a guide for
supporting the moving part during the
isolation or withdrawal operations of the

breakers, there are two guides.

4/4

GSIS9124

moving part. For SACE S6-S7 circuit-

ABB SACE

Conversion kit into moving part for withdrawable circuit-breaker


This allows the fixed circuit-breaker with
front terminals to be converted into the
moving part of a withdrawable circuitbreaker. The kit consists of isolating contacts, frame, assembly screws and nuts.
The circuit-breakers in the withdrawable
version must always be completed, alternatively, with one of the following accessories:
front for lever operating mechanism
rotary handle operating mechanism
motor operator,
in order to make the racking-out lock if
necessary.
The fixed part is needed to complete the

GSIS9037

circuit-breaker.

Conversion kit for fixed part of plug-in into fixed part of withdrawable
A guide for converting the fixed part of a
plug-in version circuit-breaker into the
fixed part of a withdrawable version circuit-breaker is available for SACE S3-S4-

GSIS9047

S5 circuit-breakers.

Racking-out handle
This allows racking-out and racking-in
even with the door closed of the circuit-breaker in the fixed part.
The handle is the same for the whole

as standard with the Conversion kit or


with the circuit-breakers supplied in the

GSIS9012

range of circuit-breakers and is supplied

withdrawable version.

ABB SACE

4/5

Accessories
Connection terminals

The basic version of the circuit-breaker is supplied with:

The information needed to make the connections is summa-

front terminals for SACE S3, S4, S5, S6, S7, and S8 circuit-

rised for each type of terminal on pages

4/8-9.

Flat bars of

different dimensions and composition are recommended for

breakers

connection with busbars. Furthermore, the minimum depth

front terminals for copper cables for SACE S1, and S2 cir-

the flat bar to be connected must have is also indicated, if it is

cuit-breakers.
Different types of terminals are available, which can be com-

of a different composition to the one recommended. The mini-

bined in different ways (upper of one type, lower of another

mum and maximum cross-section of the cables which can be

type), allows the circuit-breaker to be connected to the plant

tightened in the terminals and the diameter of the terminal are

in the most suitable way for installation requirements.

indicated for connection with bare cables

The following distinctions can be made between:

The torque values to be applied to the tightening screws of the

front terminals which allow connection of cables or busbars

terminals for cable and to the screws used for connecting the

by acting directly from the front of the circuit-breaker.

busbars to the flat bar terminals are given.

rear terminals

which allow installation of the circuit-break-

ers in switchboards with rear access to both cable and

The circuit-breakers can be ordered complete with the termi-

busbar connections.

nals required, mounted directly in the factory, or the terminals

Terminals for connection of busbars or cables terminated with

can be ordered individually in packs of 3 - 4 - 6 - 8 pieces.

cable terminals and terminals for direct connection of bare

Codes for ordering circuit-breakers directly in the configura-

cable are available.

tion

with upper / lower terminals of the same type are avail-

able.

EF

ES

FC Cu

GSIS0089

GSIS0088

GSIS0087

GSIS0086

4
Front
terminals

Front extended
terminals

Front extended
spreaded terminals

Front terminals
for copper cables

S1 125

F-P

S2 160

F-P

S2X 80, S2X 100

F-P

S3 160 / 250

F-P-W

F-P-W

S3X 125 / 200

F-P-W

F-P-W

S4 160 / 250

F-P-W

F-P-W

S4X 250

F-P-W

F-P-W

S5 400 / 630

F(400A)-P(400A)-W(400A)

F - W(630A)

F - P(400A) - W(400A)

S6 630 / 800

F-W

S6X 400 / 630

F - W (only at the bottom)

S7 1250 / 1600

F-W

F (2000A / 2500A)

S8 2000 / 2500 / 3200

F = Fixed
4/6

P = Plug-in

W = Withdrawable
ABB SACE

Insulating terminal covers


The terminal covers are applied to the terminals of the circuitbreaker to prevent accidental contacts with live parts and
thereby guarantee protection against indirect contacts. The
following are available:
which guarantee IP40 degree of
GSIS9052

lower terminal covers,

protection for fixed circuit-breakers with rear terminals and


for moving parts of plug-in or withdrawable circuit-breakers.

upper terminal covers

for fixed circuit-breakers with front

terminals, front terminals for cables and rear terminals, which


guarantee IP40 degree of protection.

terminal covers for fixed parts

Screws for sealing the terminal covers

of plug-in or withdrawable

circuit-breakers, guarantee IP40 degree of protection on the

These are applied to the terminal covers of fixed circuit-break-

front with moving part connected. They are available in a

ers or to the moving parts of plug-in or withdrawable circuit-

single version.

breakers. They prevent removal of the upper or lower terminal

The degrees of protection indicated are valid for circuit-break-

covers, and can be locked with wire and a lead seal.

ers installed in switchboards.

FC CuAl

RC

HR

VR

GSIS0194

GSIS0193

GSIS0192

GSIS0191

GSIS0190

4
Front terminals
for Cu/Al cables

Rear threaded
terminals

Rear terminals
for Cu/Al cables

Rear terminals
in horizontal flat bar

Rear terminals
in vertical flat bar

F-P

F-P

F-P

F-P-W

F-P-W

F-P-W

F-P-W

F(400A)

F - P(400A) - W

F(400A)

W(630A)

F(1250A)

F-W

F-W

ABB SACE

4/7

Accessories
Connection terminals

S3-S4-S5

Front terminals

S6

These allow busbars or cables terminated with a cable terminal to be connected

Type
S3 160, S3X 125
S3 250, S3X 200
S4 160
S4 250, S4X 250
S5 400
S5 630
S6 630,
S6X 400-630
S6 800
S7 1250
S7 1600
S8 2000
S8 2500

S7

S2

S3-S4-S5

S6 630

version pieces
F
F
F
F
F
F

1
1
1
1
2
2

L
20
20
20
20
25
25

F
F
F
F
F
F

2
2
2
2
3
4

40
50
50
50
100
100

busbars [mm]
H
P
10
4
10
6
10
4
10
6
12
5
12
8
12
12
20
20

5
5
8
10
5
5

hole
9
9
9
9
11
11

tightening
B [Nm]
9
9
9
9
18
18

2x7
2x7
2 x 11
2 x 11
4 x 15
4 x 15

9
9
18
18
70 (2)
70 (2)

terminal covers
upper
lower fixed part
R
R
R
R
R
R
R
R
R
R
R
R
R
R

R
R
R
R
R

Front extended terminals


These allow busbars or cables terminated with a cable terminal to be connected

S6 800

Type

S7

S2 160
S3 160, S3X 125
S3 250, S3X 200
S4 160
S4 250, S4X 250
S5 400
S6 630,
S6X 400-630
S6 800
S7 1250
S7 1600

PF S3-S4-S5
PF S6

version

pieces

F
F-P-W
F-P-W
F-P-W
F-P-W
F-P-W

1
1
1
1
1
2

busbars [mm]
L
P
hole
20
4
8
20
4
8.5
20
6
8.5
20
4
8.5
20
6
8.5
25
5
11

F-W
F-W
F-W
F-W

2
2
2
2

40
50
50
50

11
14
4x11(4)
4x11(4)

40
50

tightening [Nm]
A
B
5
9
9
9
9
9
9
9
9
9
18
18

11
14

9
9
45
45

terminal covers
upper lower fixed p.
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

18
30
18
18

R
R
R
R

Front extended spreaded terminals

PF S7

These allow busbars or cables terminated with a cable terminal to be connected

Type

version

pieces
L

S3-S4-S5

5
5
8
10

cable term. [mm ]


L
hole
20
8
20
8.5
20
8.5
20
8.5
20
8.5
25
11

PF S5 630

busbars [mm]
P
hole

cable term. [mm]


L
hole

tightening [Nm]
A
B

terminal covers
upper lower fixed p.

S3

30

8.5

30

8.5

S4

30

8.5

30

8.5

S5 400

40

11

40

11

18

18

S5 630

F-W

40

11

40

11

18

18

S6

50

3 x 13

4 x 45

13

30

S7 1600

50

10

3 x 13

4 x 45

13

45

20

Front terminals for copper cables


These allow bare copper cables to be connected directly to the circuit-breaker. They are not
suitable for tube cable terminals

Type
S6

S1
S2
S3
S3
S4
S4
S5
S5
S3-S4-S5

4/8

pieces

125
160
160, S3X 125
250, S3X 200
160
250, S4X 250
400
630

F-P
F-P
F-P-W
F-P-W
F-P-W
F-P-W
F-P-W
F-W

1
1
1
1
1
1
1
2

cable

[mm2 ]

1.5...50
1.5...70
6...185
6...185
6...185
6...185
16...240
50...185

busbars cable term. tightening


L [mm]
L [mm]
B [Nm]
max.10
max.10
2.5-5 (1)
max.12
max.12
2.5-5 (1)
16
16
16
16
25
31

clamps
[mm]

11
12.5
18
18
18
18
24
20

terminal covers
upper lower fixed p.
R
R
R
R
R
R
S
R
R
S
R
R
S
R
R
S
R
R
S
S

Key

GSIS0095

S1-S2

version

S7

(1) Tightening torque of 2.5 Nm for < 10 mm2


cable cross-section
(2) M12 class 8.8 screws
(3) M16 class 8.8 screws
(4) Only use two holes diagonally

A = Tightening of the terminal onto the circuit-breaker


B = Tightening the cable/busbar or cable terminal onto
the terminal
R = On request
S = Standard

ABB SACE

Front terminals for copper or aluminium cables

S2-S3-S4-S5

S5

These allow copper or aluminium cables to be connected directly to the circuit-breaker (it is not possible to
use solid aluminium cables). For the SACE S2 circuit-breaker, these terminals must be connected to the
front extended terminals, which are supplied if the circuit-breaker is ordered fitted directly in the factory,
whereas the front extended terminal kit must be specified if they are ordered as loose parts..

Type
S2 160
S3 160 (R100A)
S3 160, S3X 125
S3 250, S3X 200
S4 160
S4 250, S4X 250
S5 400
S6 630, S6X400-630
S6 800
S7 1250

version
F
F
F
F
F
F
F
F
F
F
F
F

pieces
1
1
1
1
1
1
1
2
1
2
3
4

cable

[mm2]

tightening
A [Nm]
B [Nm]

2.5...50
35...95
2.5...50
35...95
25...150
35...95
25...150
95...120
120...240
120...240
70...185
95...240

9
9
9
9
9
9
9
18
18
5
9
37

clamps
[mm]

5.6
13.5
5.6
13.5
31
13.5
31
31
43
31
43
43

9.5
13.5
10
14.2
17
14.2
17
15.5
21.5
21.5
19
21.5

terminal covers
upper lower fixed p.

S6 630

S
S
R
R
R
R
R
S
R
R
S
S

S6 800

S7

S3-S4-S5

S6 630

Rear terminals for copper or aluminium cables


These allow copper or aluminium cables to be connected directly to the circuit-breaker.

Type
S3 160, S3X 125
S3 250, S3X 200
S4 160
S4 250, S4X 250
S5 400
S6 630, S6X400-630
S6 800

version
F
F
F
F
F
F
F

pieces
1
1
1
1
1
2
3

tightening
A [Nm]
9
9
9
9
18
9
9

clamps
B [Nm]
31
31
31
31
43
43
31

[mm]

16
16
16
16
21
21
17.5

terminal covers
upper lower fixed p.
S
S
S
S
S
S
S

Rear threaded terminals

S6 800

S1-S2

S3-S4-S5-S6

These allow rear connection of busbars.

Type
S1 125
S2 160
S3 160, S3X 125
S3 250, S3X 200
S4 160
S4 250, S4X 250
S5 400
S5 630
S6 630, S6X 400-630
S6 800

version

pieces

F
P
F
P
F
P-W
F
P-W
F
P-W
F
P-W
F
P-W
F
P-W
F
F

1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2

busbars [mm]
L
P
hole
16
3
16
3
18
4
18
4
20
4
12.5
20
4
12.5
20
6
12.5
20
6
12.5
20
4
12.5
20
4
12.5
20
6
12.5
20
6
12.5
25
5
16.5
25
5
16.5
40
5
25
40
5
25
40
5
25
50
5
25

cable term. [mm] tightening


terminal covers
L
hole
A
B upper lower fixed p.
5
8
S
8
5
8
S
8
20
12.5 10
20
S
20
12.5 10
20
20
12.5 10
20
S
20
12.5 10
20
20
12.5 10
20
S
20
12.5 10
20
20
12.5 10
20
S
20
12.5 10
20
25
16.5 18
40
S
25
16.5 18
40
40
25
18
100
S
40
25
18
100
40
25
18
100
S
50
25
18
100
S

4
PF S3-S4-S5-S5 630

S7

PF S6 630

Rear terminals in horizontal and vertical flat bar


These allow rear connection of busbars.

S5 630
S6 630, S6X 400-630
S6 800
S7 1250
S7 1600
S8 2000
S8 2500
S8 3200

ABB SACE

version

pieces

W
W
W
F-W
F-W
F
F
F

2
2
2
2
2
3
4
6

busbars [mm]
L
P
hole
40
5
11
40
5
14
50
5
14
50
8 4x11 (4)
50
10 4x11 (4)
100
5
4x15
100
5
4x15
100
5
4x18

PF S6
cable term. [mm] tightening
L
hole
B [Nm]
40
11
20
40
14
30
50
14
30
20
20
70 (2)
70 (2)
100 (3)

terminal covers
upper lower fixed p.

PF S7
S
S
GSIS0096

Type

4/9

Accessories
Service releases

The service releases, shunt opening and undervoltage releases, housed and fixed in a slot in the left part of the circuit-break er
are always alternative to each other. The power supply is made by means of special connectors for sizes S3 to S7, whereas for
S1-S2, it is made by means of free wires 0.6 m long or with plug-socket connectors which can be supplied on request.
Assembly is carried out by pressure into the appropriate housing in the left part of the circuit-breaker.

Shunt opening release


This allows circuit-breaker opening by

S1-S2

means of an electric command. Release

S3-S4-S5

operation is guaranteed for a voltage


between 70% and 110% of the rated
power supply voltage Un, both in AC and
in DC. It is always fitted with an auxiliary

GSIS0108

GSIS0107

limit contact.

(*)

S8

GSIS0110

GSIS0109

GSIS9001

S6-S7

(*) For the SACE S1-S2 circuit-breakers , the service releases are fixed to the circuit-breaker cover

Power supply voltages


S1 - S2

S3 -S4 - S5

S6 - S7

S8

50-60 Hz

DC

50-60 Hz

DC

50-60 Hz

DC

50-60 Hz

DC

[V~]

[V]

[V~]

[V]

[V~]

[V]

[V~]

[V]

60

24

24

24

24

24

30

48

48

48

48

48

48
100 ... 27

24 30

12

48
100 130

12

24

220 250

60

60 ... 72

60

60

380 440

110 120

110 125

110 120

110 125

100 ... 127

60

24

220 240

220 250

220 240

220 250

127 ... 150

48

380 400

380 400

150 ... 180

160

110

480

480

200 ... 255

200 ... 250

220

380 ... 500

250

Powers absorbed
on inrush
S1...S5

Circuit-breaker
opening times

S6...S7

S8

S3

Number of
operations

S4...S7

S8

S3-S4

S5

S6-S7

AC

DC

AC

DC

AC

DC

[ms]

[ms]

[ms]

[nr.]

[nr.]

[nr.]

[VA]

[W]

[VA]

[W]

[VA]

[W]

< 15

< 15

< 20

10000

7500

2500

100

120

150

150

200

150

4/10

ABB SACE

Undervoltage release
This opens the circuit-breaker due to a

S1-S2

power supply failure to the release, or

S3-S4-S5

voltage drops to minimum values of 0.7


x Un with a trip range from 0.7 to 0.35 x
Un.
After tripping, the circuit-breaker can be

GSIS0111

closed again, starting with a voltage

voltage release de-energised, neither

GSIS0108

higher than 0.85 x Un. With the under(*)

circuit-breaker nor main contact closure


is possible.

S8

Power supply voltages

GSIS0112

GSIS0109

GSIS9002

S6-S7

(*) For the SACE S1-S2 circuit-breakers , the service releases are fixed to the cover of the circuit-breaker

S1 - S2

S3 -S4 - S5

S6 - S7

S8

50 Hz

60 Hz

DC

50-60 Hz

DC

50-60 Hz

DC

50 Hz

60 Hz

DC

[V~]

[V~]

[V]

[V~]

[V]

[V~]

[V]

[V~]

[V~]

[V]

24
48

24

24

48

48

60

60

110 127

110 127

220 250

220 250

380 440

380 440

480

480

48

110
110
220
380

380 440

24
24

30
30
48
48
60

24

24

24

48

48

48

100

110...115

110...115

125 .. 127

60

60

60

110

110 125

110 125

60

110...125
120

220

220 250

220 250

127...130
208...220
220...250
220
230...240

277
240
310
380

380...400

440

415...440

480

500

Powers absorbed
during continuous service
S1...S5

S6 - S7

Circuit-breaker
opening times
S1...S2

S8

S3

Number
of operations
S4...S7

S8

S3-S4

S5

S6-S7

AC

DC

AC

DC

AC

DC

[ms]

[ms]

[ms]

[ms]

[nr.]

[nr.]

[nr.]

[VA]

[W]

[VA]

[W]

[VA]

[W]

< 15

< 18

< 25

< 25

10000

7500

2500

10

30

15

ABB SACE

4/11

Accessories
Service releases
Time-delayed undervoltage release
The undervoltage release can be combined with an external electronic power
supply time-delay device, which allows
circuit-breaker opening to be delayed in
the case of a power cut

to the release

itself, according to fixed time-delays of


GSIS9042

0.5-1-2-3 [s], so as to avoid unwarranted


trips caused by temporary malfunctions.
It is available for the SACE S3, S4, S5,
S6, and S7 circuit-breakers with power
supply voltages at 110-220 V (50-60 Hz)
only coupled with an undervoltage release at 310 V DC. Different power supply voltages are possible for S8.

Shunt closing release


This allows circuit-breaker closure by
means of an electric command. Opera-

Power supply voltages

S8

S8

tion of the release is guaranteed for a

50 Hz

60 Hz

DC

voltage between 80% and 110% of the

[V~]

[V~]

[V]

rated power supply voltage Un, both in

24

AC and in DC.

24
24

GSIS0112

30

30
48
48
60
60
100

110...115

110...115

125...127

GSIS9003

110...125
120
127...130
220
208...220
220...250
230...240

277
240
310

380...400

440
380

415 ... 440

480

500

Powers absorbed
on inrush

Circuit-breaker
closing times
S8

S8

4/12

AC

DC

[ms]

[VA]

[W]

< 55

200

220

ABB SACE

Connectors for service releases


These allow the shunt opening release
or the undervoltage release to be con-

S1 - S2

nected to the power supply circuit. They


are available in the following versions:

GSIS0113

(free cables always supplied)

GSIS0114

plug-socket for S1-S2 circuit-breakers

for fixed S3 ... S7 circuit-breakers


for plug-in/withdrawable S3 ... S7
circuit-breakers.
Assembly is by means of pressure into
special slots in the left side of the circuit-

S3 ... S7

breaker.

GSIS9013

GSIS0115

GSIS0116

Cables of different lengths are available.

4
Extension for testing service releases
Available for SACE S3, S4, S5, S6, and
S7 circuit-breakers, this allows supply to
the service releases with the circuitbreaker in the racked-out position. It is

erating tests of the circuit-breaker with


the circuit-breaker in safe conditions, i.e.

GSIS9017

therefore possible to carry out blank op-

isolated in relation to the power circuits.

ABB SACE

4/13

Accessories
Electric signals

These allow information relative to the circuit-breaker state of operation to be taken outside the circuit-breaker.
Installation of these accessories is carried out directly from the front of the circuit-breaker in special slots, completely se gregated
from the live parts, with increased operator safety.

Auxiliary contacts
These carry out electrical signalling of the
operating state of the circuit-breaker:

S1-S2

S3-S4-S5

Open/closed: indicates the position of


the circuit-breaker contacts.
Release trip: signals circuit-breaker
opening because the overcurrent release has tripped (for an overload or

shunt opening or undervoltage release


has tripped, or the emergency open-

GSIS0118

GSIS0117

shor t-circuit), the residual current,

(*)

ing pushbutton of the motor operator


or

the

test

pushbutton

has

been

pressed. Signalling is reset when the

S6-S7

circuit-breaker is reset (recovery).


For SACE S3, S4, S5, S6, and S7 circuitbreakers the auxiliary contacts of the circuit-breaker are also available in the
gold-plated version for digital signals,
also suitable for use with voltages Un <
24 V with the same type of signalling and

GSIS0119

versions.
The signals indicated in the table are
available:

(*) For SACE S1-S2 circuit-breakers the auxiliary contacts are fixed to the cover of the circuit-breaker

GSIS9004

Signals

S1...S2

4/14

In [A]

S8

1 contact during open/closed changeover +


1 contact during release tripped changeover

1 circuit-breaker open signal + 1 circuit-breaker


closed signal + 1 release tripped signal

3 NO or NC contacts

release tripped signal

microswitch for signalling closing springs


charged

S3-S4-S5-S6-S7
ohmic load
inductive In [A]

S4...S7

2 contacts during open/closed changeover

S1-S2
Rated voltage Un
V ~ (50-60 Hz) V

S3

Rated voltage Un
V ~ (50-60 Hz)
V

S8
ohmic load
In [A]

Rated voltage Un
V ~ (50-60 Hz)
V
220

ohmic load
In [A]

30

125

0,3

127

2A (cosj = 0,3)

250

0,15

380

1
6

220

2A (cosj = 0,3)

250

500

400

ABB SACE

Connectors for auxiliary contacts


These allow the auxiliary contacts to be
connected to the relative power supply

S1 - S2

circuit. For S1, S2 circuit-breakers, the

wires or with mobile plug-socket connecGSIS0113

tors. For SACE S3, S4, S5, S6, and S7


circuit-breakers, the auxiliary contacts

GSIS0114

power supply is made by means of free

(fitted with plug connector) can only be


supplied by means of the specific connection connectors to be ordered specifying the size and version of the circuit-

S3 ... S7

breaker (fixed or plug-in/withdrawable).


Assembly is carried out by pressure into
special slots in the right side of the cir-

GSIS0120

GSIS0121

cuit-breaker.

GSIS9015

(*)

(*) Connectors for auxiliary contacts, for fixed, plug-in or withdrawable circuit-breakers

Extension for testing auxiliary contacts


Available for SACE S3, S4, S5, S6, and
S7 circuit-breakers, this allows the auxiliary contacts to be connected to the relative power supply circuit with the circuit-

the circuit-breaker in safe conditions, i.e.


isolated in relation to the power circuits,

GSIS9089

breaker in the racked-out position. With

blank tests of circuit-breaker operation


can be carried out.

ABB SACE

4/15

Accessories
Electric signals
Early auxiliary contact for undervoltage release
The early auxiliary contact for the undervoltage release, interlocked with the ro-

S3 ... S7

tary handle operating mechanism, keeps


the release de-energised with the circuit-

GSIS0122

breaker open.
It is supplied complete with socket connector of the type with double slide for
simultaneous connection of the under-

GSIS9038

GSIS0123

voltage release and the accept contact.

Circuit-breaker position contacts


For the fixed part of the SACE S2, S3, S4,
S5, S6, and S7 circuit-breakers, these

S3 ... S7

carry out electrical position signalling of

part: racked-in, racked-out. They can


only be connected by means of free wires
and are available in the following ver-

GSIS9006

sions:
Contacts for signalling circuit-breaker
racked in

GSIS0160

the circuit-breaker in relation to the fixed

Contacts for signalling circuit-breaker


racked out.
A maximum of three contacts for S2, two
contacts for S3, three contacts for S4-S5
and five contacts for S6-S7 can be installed on the fixed part, in any combination.
The circuit-breaker position contacts are
also available in the gold-plated version
for digital signals also suitable for use
with voltages Un < 24 V with the same
type of signals and combinations.

4/16

S2
Rated voltage Un
V ~ (50-60 Hz) V

S3-S4-S5-S6-S7

ohmic load
In [A]
inductive In [A]

Rated voltage Un
V ~ (50-60 Hz)
V

ohmic load
In [A]

30

125

0,3

127

2A (cosj = 0,3)

250

0,15

220

2A (cosj = 0,3)

250

400

ABB SACE

Accessories
Remote controls

These allow remote control of circuit-breaker opening and closing and are particularly suitable for use in electrical network
supervision and control systems. They are complete with manual operating lever and emergency opening pushbutton (starting
from S3). A selector allows changeover from automatic to manual operation. They are always fitted with a padlock and, on
request, can be fitted with a key lock in the open position.

Solenoid operating mechanism for SACE S1-S2


circuit-breakers
S1-S2
This operates both opening and closing

of the circuit-breaker, acting directly on


its lever.
There are two versions available, one
placed beside the circuit-breaker (for
installation on a panel or DIN EN 50022
GSIS0124

rail), the other on the front, suitable for


being installed directly on the front of the
circuit-breaker.
Both versions can be used either for S1

GSIS0125

or for S2 and in the three- and four-pole


version.

Rated voltage, Un

AC

48

[V]

110

60

[V]

220 ... 230

110

[V]

220

Operating voltage

85 ... 110% Un

85 ... 110% Un

Inrush power absorption, Ps

2300-2500 [VA]

GSIS9022

Duration
Mechanical life

GSIS9023

Minimum duration of the opening


and closing command impulse

700-900 [W]

opening [s]

< 0.1

closing [s]

< 0.1

[no. operations]

25000

Degree of protection, on the front

ABB SACE

DC

[V]

IP 30
[ms]

> 100

4/17

Accessories
Remote controls

Direct action motor operator for SACE S3-S4 and S5 circuit-breakers


Both the opening and closing command
is controlled by the motor, which acts di-

S3-S4-S5

rectly on the circuit-breaker lever. The


table shows the power supply voltage

GSIS0126

GSIS9021

GSIS0127

values Un [V].

Rated voltage, Un

AC

24

[V]

48-60

[V]

110-127

110-125

[V]

220-240

220-250

[V]

380

[V]

440

85 ... 110% Un

85 ... 110% Un

Inrush power absorption, Ps

500 [VA]

500 [W]

Service power absorption, Pc

350 [VA]

Operating voltage

Operating frequency

[Hz]

Time constant
Duration

[ms]

18
0.1

[no. operations]

Degree of protection, on the front


Minimum duration of the opening
and closing command impulse

350 [W]
50-60

opening [s]
closing [s]

Mechanical life

4/18

DC

[V]

0.1
15000 (S3-S4) / 10000 (S5)
IP 30

[ms]

> 150

ABB SACE

Stored energy motor operator for SACE S6-S7 circuit-breakers


With the stored energy operating mechanism, during circuit-breaker opening the

S6-S7

release mechanism automatically precharges a system of springs: the stored


energy is exploited for closing the circuitbreaker. It is supplied complete with
shunt closing release (Ps=100VA~/

GSIS0128

door. The table shows the power supply

GSIS0129

100W) and flange for the compartment

voltage values Un [V].


In the case of interlocked circuit-breakers, the key lock against manual operation is necessary.

GSIS9020

Rated voltage, Un

AC

DC

[V]

24

[V]

48

[V]

60

[V]

110

110

[V]

120-127

120-127

[V]

220-250

220-250

[V]

380

[V]

85 ... 110% Un

85 ... 110% Un

Inrush power absorption, Ps

660 [VA]

600 [W]

Service power absorption, Pc

180 [VA]

Operating voltage

Operating frequency

[Hz]

Time constant

[ms]

Duration

0.09

opening

1.2

[no. operations]

Degree of protection, on the front


Minimum duration of the opening
and closing command impulse

ABB SACE

22

closing
resetting

Mechanical life

180 [W]
50-60

2
10000 (S6) / 5000 (S7)
IP 30

[ms]

> 100

4/19

Accessories
Remote controls
Geared motor for SACE S8 circuit-breaker
This allows the springs of the circuitb re a k e r

closing

mechanism

to

Rated voltage, Un

AC

DC

24-30

be

[V]

charged automatically, immediately fol-

[V]

48-60

lowing an closing operation. It includes

[V]

100-130

100-130

[V]

a limit microswitch for electrical signal-

Inrush power absorption, Ps

ling of closing springs charged.

Service power absorption, Pc

220-250
1000 [W]

230 [VA]

Charging time

[s]
[no. operations]

230 [W]
7 ... 10
5000

GSIS9007

Mechanical life

220-250
1000 [VA]

Connectors for motor operators


The motor operators, from S3 to S7, can
only be supplied by means of the spe-

S3 ... S7

cific connection connectors. They are of


the slide type and allow simultaneous
connection of both the motor operator
and the auxiliary contacts to the relative
power supply circuit. They are an alternative to the corresponding connectors

GSIS0130

are housed in the same seat. They must


be ordered specifying the size and version of the circuit-breaker (fixed or plugin/withdrawable).

Extension for testing motor operators


For the SACE S3, S4, S5, S6, and S7 cirS3 ... S7
cuit-breakers, this allows both motor operators and the auxiliary contacts to be
connected to the relative power supply
circuit with the circuit-breaker in the
racked-out position. With the circuitbreaker in safe conditions, i.e. isolated
in relation to the power circuits, blank
operating tests of the circuit-breaker can
be carried out. It must be ordered speci-

GSIS9016

GSIS9014

for the auxiliary contacts only since they

fying the size and version of the circuitbreaker (fixed or plug-in/withdrawable)


and automatically excludes the corresponding extension for testing the auxiliary contacts

4/20

ABB SACE

Rotary handle operating mechanism


The rotary handle operating mechanism
facilitates operation thanks to its ergo-

S1-S2

nomic handle. It is always fitted with a


padlock in the open position, which prevents the circuit-breaker being closed.
The lock slot can take up to 3 padlocks
stem 6 mm (not supplied). On request
it can be fitted with a compartment door
lock or a key lock in the open position.
For SACE S2, S3, S4, S5, S6, and S7 circuit-breakers, application of the rotary
handle operating mechanism is an alterGSIS0131

native to the front flange for the lever operating mechanism and for the motor
operator. Different types of rotary handle

S6-S7

operating mechanism are available.


The position of the rotary handle indicates
with certainty the position of the contacts:
open, closed, relay tripped. The release

S3-S4-S5

settings and the nameplate data remain


accessible to the user. For the SACE S6,
S7 circuit-breakers, the direct rotary handle operating mechanism on the circuitbreaker is always supplied complete with

GSIS0123

flange for the compartment door.


The rotary handle operating mechanism

GSIS0132

in the emergency version, complete with


red-yellow handle and yellow plate, suitable for machine tool control, is also available for all the circuit-breakers.

S1-S2
GSIS9025

F/P
Direct
Direct emergency

119,5 mm

Transmitted with fixed emergency distance

119,5 mm

Transmitted with adjustable emergency distance


GSIS9024

F/P

S6-S7

Transmitted with fixed distance


Transmitted with adjustable distance

ABB SACE

S3-S4-S5

Extension for transmitted handle

300 mm 300 mm

500 mm 500 mm

300 mm

500 mm

180/500 mm

500 mm

4/21

Accessories
Operating mechanisms and locks
Front flange for lever operating mechanism
This can be installed on SACE S3, S4,
S5, S6, and S7 fixed, plug-in or withdraw-

S6-S7

S3-S4-S5

able circuit-breakers. In the case of withdrawable circuit-breakers installed in


compartments, it allows the IP40 degree
of protection to be kept for the whole isolation run of the circuit-breaker. It is always fitted with a padlock in the open
position (stem 6 mm - up to three pad-

GSIS0133

locks - not supplied) which prevents closing of the circuit-breaker. On request, it


can be fitted with a key lock in the open

GSIS0134

position for one or more circuit-breakers


and with the compartment door lock.
It is available in the following versions:
for fixed or plug-in circuit-breaker.
for withdrawable circuit-breaker.
For the SACE S6, S7 circuit-breakers, it
is always supplied complete with flange
for the compartment door, whereas for
the SACE S3, S4, and S5 circuit-breakers the flange supplied with the circuit-

GSIS9026

breaker can be used.

4
Key lock in open position
This allows the mechanical closing operation of the circuit-breaker to be locked.

S3 ... S7

The following versions are available:


lock with different key for each circuitbreaker
lock with the same key for groups of
circuit-breakers.
Different locks are supplied for direct

front flange for lever operating mecha-

GSIS0136

motor operator, and for rotary handle or

GSIS0135

action motor operator, for stored energy

nism. The circuit-breaker lock in the open


position ensures circuit isolation in com-

GSIS9008

pliance with the IEC 947-2 Standard.

4/22

ABB SACE

Compartment door lock


This prevents the compartment door being opened with the circuit-breaker

S3...S7

closed. It can be used with the SACE S3,


S4, S5, S6, and S7 circuit-breakers in the
fixed, plug-in or withdrawable version
and fitted with rotary handle operating
mechanism or front flange for lever operating mechanism. It consists of two eleGSIS9010

ments: one applied to the rotary handle


operating mechanism or to the front
flange for the lever operating mechanism,
the other, consisting of a metal striker, to
be applied onto the compartment door.
GSIS0137

For the SACE S1-S2 circuit-breakers it is


an integral part of the rotary handle operating mechanism.

Lock for fixed part of withdrawable circuit-breaker


Key locks or padlocks are available to
be applied to the guide of the fixed part

S3...S7

of a withdrawable circuit-breaker to prevent the moving part from being rackedin. The following different versions are
available:
Padlock, which can take up to three
padlocks with stem 6 mm (not sup-

GSIS0138

ferent key for each circuit-breaker

GSIS0139

plied).
Key lock in the open position with dif-

Key lock in the open position between


two or more circuit-breakers with the
same key for groups of circuit-breakers

GSIS9009

GSIS0140

Key lock of Ronis type (without key).

ABB SACE

4/23

Accessories
Operating mechanisms and locks
Padlock for operating lever
This is applied on the cover of the SACE
S1-S2 circuit-breakers

S1-S2

to prevent the

operating lever movement. If activated,


the circuit-breaker remains locked in the
open position, guaranteeing circuit isolation in compliance with the IEC 947-2

GSIS9035

GSIS0141

Standard.

Anti-tampering lock
S2-S3

S2, S3 circuit-breakers in correspondence with the regulator of the thermal element of the thermomagnetic release

GSIS0142

GSIS0143

and prevents it being tampered with.

GSIS0144

GSIS9049

This is applied on the cover of the SACE

4/24

ABB SACE

Mechanical interlock between two circuit-breakers


This allows installation of two circuitbreakers on a single support and, by

S3 ... S7

means of special lever mechanism,


makes them mechanically inter-dependent. It prevents operation in parallel of two
power supply sources (e.g.: normal emergency). It consists of a kit with levers and assembly accessories and a
metallic support.
The circuit-breakers and any operating
mechanism accessories must be ordered
separately. The mechanical interlock is
available for SACE S3, S4, S5, S6, and
S7 circuit-breakers in side by side and
superimposed versions.
To be able to take the circuit-breakers
mounted directly on the interlocking
plate, the code 1SDA050093R1 must
be specified as an accessory of the sec-

N.B. for the S3X, S4X , S6X circuit-breakers,

GSIS0145

is to be interlocked.

GSIS0146

ond circuit-breaker (or fixed part) which

only the version side by side can be used.

ABB SACE

4/25

Accessories
Residual current releases

All the circuit-breakers in the SACE Isomax S series are preset for combined assembly with residual current releases. In partic ular,
the SACE S1, S2, and S3 circuit-breakers can be combined with residual current releases in the SACE RC210, RC211 or RC212
series, in the version side by side or underneath the circuit-breaker.
Apart from the protection against overloads and short-circuits typical of circuit-breakers, the residual current circuit-breake rs
which are derived from them also guarantee protection against earth fault currents, thereby ensuring protection against the ris

of fire. The residual current releases can also be mounted on the SACE S2D and S3D switch-disconnectors. In that case, the
derived apparatus is a pure residual-current circuit-breaker, which

therefore guarantees only residual current protection an d

not the protections typical of circuit-breakers. The pure residual-current circuit-breakers are only sensitive to the earth f ault
current and are generally applied as main isolators in small distribution switchboards towards end users.
The use of pure and non-pure residual-current circuit-breakers allows continuous monitoring of the state of insulation of t he
installation, ensuring effective protection against the risk of fire and explosion and, in the case of devices with I

Dn

30mA, they

guarantee protection of people against indirect and direct contacts to integrate the compulsory measures foreseen by the
standards and by the accident prevention regulations.
The residual-current releases are constructed in compliance with the following standards:
IEC 947-2 appendix B
IEC 255-3 and IEC 1000: for protection against unwarranted trips.

SACE RC210 polarised residual-current release


The SACE RC210/1 polarised residualcurrent release is available for four-pole

S1

SACE Isomax S1 circuit-breakers for assembly side by side on DIN 50022 rail.
The release is constructed using polarised type technology and acts directly
on the release operating mechanism of

piston which passes through a pre-cut

GSIS9027

GSIS0147

the circuit-breaker, by means of a small

window on the side of the circuit-breaker.


It is fitted with a test button for periodically checking the circuit-breaker.

SACE RC211, RC212 electronic residual current releases


The SACE

RC211 and RC212 residual

current releases can be installed both


on the SACE S1, S2 and S3 circuit-breakers and on the SACE S2D and S3D

SACE RC211/2, RC212/2 for S2 circuitbreakers


SACE RC211/3, RC212/3 for S3 circuitbreakers.

presence of one-direction pulsating currents with continuous components.


The operating conditions of the apparatus can be controlled constantly by

switch-disconnectors, in the fixed four-

They are constructed using analogue

means of the test pushbutton of the elec-

pole version, and can be supplied in two

technology and act directly on the cir-

tronic circuit and the residual current trip

versions as follows:

cuit-breaker by means of an opening

magnetic indicator.

for assembly in position beside the

solenoid, supplied with the release, to

The circuit-breaker complete with re-

be housed in the special slot made in

sidual current release can be fitted with

the area of the third pole.

the electrical accessories normally avail-

They do not require an auxiliary power

able for the circuit-breaker. The opening

supply since they are supplied directly

and undervoltage releases are housed

The following releases are available:

from the network and their operation is

in the special slot made in the fourth pole.

SACE RC211/1, RC212/1 for S1 circuit-

guaranteed even with only a single

circuit-breaker
for assembly in position under the circuit-breaker.

breakers

4/26

phase supplied with voltage and in the

ABB SACE

Residual current release beside the four-pole version circuit-breaker


This is supplied complete with:
power cables for connection to the

S1-S2-S3

lower terminals of the circuit-breaker


(respecting correspondence with the
neutral and phases)
an opening solenoid to be housed in

GSIS0148

the area of the third pole, complete with


plug-socket connector for connection
to the residual current release
2 brackets for fixing on DIN rail (one
for the circuit-breaker and one for the
residual current release)
plug connector to make the connection of the remote opening pushbutton

beside

(to be provided by the customer).


For SACE S1-S2 circuit-breakers the residual current release is fitted with front
terminals for cables.
For the SACE S3 circuit-breaker, the residual current release is fitted with front

On request, the front terminals for ca-

terminals and is also supplied with a front

bles can be mounted, using the stand-

flange H= 45 mm for the circuit-breaker.

ard circuit-breaker kit.

Residual current release under the four-pole version circuit-breaker


This is supplied complete with:
an opening solenoid to be housed in

S1-S2-S3

the area of the third pole, complete with


plug-socket connector for connection
to the residual current release
plug connector to make the connection of the remote opening pushbutton
(to be provided by the customer) with
the SACE RC212 residual current release
flange for compartment door (one for
SACE S1, S2; two for SACE S3)
protection for assembly in the area
GSIS0149

between the circuit-breaker and residual current release.


For SACE S1, S2 circuit-breakers, the residual current release is supplied with
front terminals for cables On request, the
rear threaded terminals can be mounted,

under

using standard kit of the circuit-breaker.


For SACE S3 circuit-breakers, the residual current release is supplied with

nals for cables can be mounted or the

front terminals (together with a front flange

rear terminals using the kit with 4 pieces

H= 45mm for circuit-breaker). On re-

for the circuit-breaker can be mounted

quest, using the standard kit of the cir-

(code 1SDA023365R1) and the kit for

cuit-breaker, front terminals for cables,

residual

extended front terminals, or rear termi-

1SDA025543R1).

ABB SACE

current

release

(code

4/27

Accessories
Residual current releases
Technical characteristics
Residual current releases
Technology
Action
Primary operating voltage

SACE RC210

SACE RC211

polarised type

electronic

SACE RC212
electronic

direct

with solenoid

with solenoid

[V]

up to 500

220 ... 500

50 ... 500

[Hz]

50 60 Hz 10%

50 60 Hz 10%

50 60 Hz 10%

Range of test operation

[V]

230 ... 500

220 ... 500

50 ... 500

Rated service current

[A]

up to 125

up to 250

up to 250

Trip thresholds IDn

[A]

0,3 - 0,5

0,03 - 0,1 - 0,3

0,03 - 0,1 - 0,3 - 0,5 - 3

Tolerance for IDn

[%]

+0, -25

+0, -20

instantaneous

instantaneous

0 - 0,1 - 0,25 - 0,5 - 1 - 1,5

Operation frequency

Trip times
Tolerance over trip times

[s]
[%]

20

Trip signalling
Self-supply
Input for remote opening
Indication of pre-alarm at 50%
AC type only for alternating current
Type A for alternating current, pushbutton
Low sensitivity
High sensitivity
Mounting under the circuit-breaker
Mounting beside the circuit-breaker
Dimensions (L x H x P)

[mm]

103 x 120 x 70

120 x 120 x 70

140 x 170 x 108

Connection to the residual current circuit-breaker network

4
Network connection diagrams for which the protection

Network connection diagrams for which the protection


is active with at least two phases supplied with voltage

GSIS0077

is active even with only one phase supplied with voltage

(1) Terminal to be connected to the neutral or to the earthing conductor.

4/28

ABB SACE

SACE RCQ switchboard residual-current relays


The SACE Isomax S4, S5, S6, and S7 circuit-breakers can be combined with the
SACE RCQ switchboard residual-current
relay with separate toroid (to be installed
externally on the line conductors) and
satisfies requirements with trip thresholds
up to 30 A and times up to 5 s or where
the installation conditions are particuGSIS9046

larly restrictive, such as circuit-breakers


already installed, limited space in the circuit-breaker compartment.
Thanks to its wide setting range, the
SACE RCQ switchboard residual-current
relay is suitable for applications where a
coordinated residual current protection
system is to be constructed at the various distribution levels, from the main
switchboard to the end user. It is particularly suitable where low sensitivity residual current protection is required, for
example in partial (current-type) or total
(time-type) selective chains, and for high
sensitivity applications (with physiologi-

Residual-current relay
Power supply voltage

SACE RCQ
AC [V]
DC [V]

Operation frequency

80 ... 500
48 ... 125

[Hz]

50 60 Hz 10%

- 1a range of adjustments

[A]

0,03 - 0,05 - 0,1 - 0,3 - 0,5

- 2a range of adjustments

[A]

1 - 3 - 5 - 10 - 30

[s]

0 - 0,1 - 0,2 - 0,3 - 0,5 - 0,7 - 1 - 2 - 3 - 5

Trip threshold adjustment IDn

cal sensitivity) to realise protection of

Trip time adjustment

people against direct contacts

Pre-alarm threshold adjustment

On a drop in the auxiliary power supply

Range of use of the closed transformers

[%] x IDn

25 ... 75% x IDn

IDn

voltage, the opening command inter-

- Toroidal transformer 60 [mm]

[A]

0,03 ... 30

venes after a minimum time of 100 ms

- Toroidal transformer 110 [mm]

[A]

0,03 ... 30

and after the time set plus 100 ms.

- Toroidal transformer 185 [mm]

[A]

0,1 ... 30

The SACE RCQ relay is suitable for use


in the presence of earth currents of alternating type only (AC Type), for alternating current and/or pushbutton with continuous components (Type A) and is suit-

Range of use of the transformers which can be opened


[A]

0,3 ... 30

- Toroidal transformer 180 [mm]

[A]

0,3 ... 30

- Toroidal transformer 230 [mm]

[A]

Alarm pre-threshold signalling

1 N.O. changeover contact


6 A - 250 V AC 50/60 Hz
Residual-current relay trip signalling

Yellow flashing LED

The SACE RCQ relay is of the type with

2 changeover contacts (N.O. N.C.; N.O.)

indirect action and acts on the release


mechanism of the circuit-breaker by

6 A - 250 VAC 50/60 Hz


Remote opening command

N.O. Contact

means of the circuit-breaker shunt opening release (to be ordered by the user)

Trip time 15 ms
Connection to the toroidal transformer

By means of 4 twisted conductors


Maximum length 5 m

to be housed in the special slot made on


the third pole of the circuit-breaker.

ABB SACE

1 ... 30
Yellow flashing LED

able for carrying out residual current selectivity .

Dn

- Toroidal transformer 110 [mm]

Dimensions L x H x D

[mm]

96 x 96 x 131,5

Drilling for assembly on door

[mm]

92 x 92

4/29

Accessories
Accessories for electronic releases
SACE PR212/D-M Modbus and SACE PR212/D-L Lon dialogue unit
The dialogue unit is a device which al-

in any case, in accordance with what

lows two-way communication from the

has been set manually. The SACE PR212/

circuit-breaker to the outside and vice

D-M and SACE PR212/D-L dialogue units

versa. ABB SACE has built two distinct

are always fitted in combination with the

dialogue units able to support two differ-

SACE PR212/T actuator unit, which al-

ent standard market protocols: SACE

lows remote closing or opening opera-

PR212/D-M (Modbus RTU protocol) and

tion of the circuit-breaker (Remote Con-

SACE PR212/D-L (LonTalk protocol by

trol) by means of two digital outputs which

Echelon). Both units are housed in exter-

can be disabled thanks to the dip-switch

nal modules, which can be installed on

(LOC/REM) positioned on LOC.

DIN rails, and can be used with the S4,


S5, S6, and S7 circuit-breakers fitted with

Information available

SACE PR212/P electronic release, both

State of the circuit-breaker: open;

in the LSI and LSIG versions, or SACE


PR212/MP release. They must be sup-

closed; tripped
Installation alarms: pre-alarm L; tripped

plied with a stabilised voltage of 24 VDC


(20% with maximum ripple 5%) and

L-S-I-G-R-V-PTC
Measurements: currents; N opera-

be earthed. Communication towards the


outside is generally addressed to a su-

tions; N trips
Reading and writing curves and trip

pervision and control unit, which has the

t h re s h o l d s :

task of collecting and storing the infor-

(MAN), electronic reading and writing

mation regarding the part of the plant


controlled.

only

manual

re a d i n g

(ELT)
Circuit-breaker commands: opening;

In the case of an error in the serial com-

closing; reset.

munication due to a fault in the dialogue


unit or lack of auxiliary power supply, the
SACE PR212/P protection unit works according to the last parameters set and,

4
PR212/DM

PR212/D-M

Protocol

Modbus RTU

LonTalk

EIA RS485

TP (Twisted Pair)

9600 19200 bit/s

78Kbit/s

bus

bus

Physical means of transmission


Speed
Architecture

4/30

PR212/D-L

ABB SACE

The SACE PR212/T actuator unit allows

The PR212/D dialogue unit sends the

circuit-breaker opening and closing by

digital opening and closing commands,

means of the motor operator mounted on

received from the supervision and con-

the circuit-breaker. It is always supplied

trol system, to the inputs of the SACE

in combination with the SACE PR212/D

PR212/T actuator unit, which carries out

dialogue unit. An auxiliary power supply

circuit-breaker closing and opening by

with a stabilised voltage of 24 VDC

means of a power relay. The motor op-

(20%, with maximum ripple - 5%) and

erator of the circuit-breaker (use the

earthed is required for operation of the

versions with power supply voltage at

unit.

110 V AC/DC or 220 V AC) must be

GSIS9043

SACE PR212/T actuator unit

connected to these relays.

This allows control of tripping of the SACE

input bushings located on the front of the

PR211/P, SACE PR212/P, and SACE

SACE PR211/P, SACE PR212/P, or SACE

PR212/MP electronic releases and the

PR212/MP releases.

trip test of the opening solenoid OS. The

The limited dimensions of the accessory

device is supplied by means of a 12 V

make it practically pocket-type. The trip

replaceable battery and is fitted with a

test device can be used on the SACE

two-pole polarised connector-tracer point

Isomax S4, S5, S6, S7, and S8 circuit-

housed on the bottom of the box, which

breakers.

GSIS9031

SACE TT1 Test unit

allows connection of the device to the test

4
The SACE PR212/K signalling unit, only

garding the state of activation of the pro-

available for S8, is able to convert the

tection functions passes, on the basis of

digital signals supplied by the SACE

which the relative power contacts are

PR212/P - (LSIG) protection unit into elec-

closed to signal:

tric signals by means of normally open

pre-alarm for protection function L

electrical contacts. An auxiliary power

(I>0.9 x I1)

supply is needed to operate the unit. It is

protection function L, S, I, G trip

connected to the internal bus of the pro-

release trip

tection unit by means of a dedicated se-

communication error with protection

rial line over which the information re-

GSIS9041

SACE PR212/K signalling unit

unit.

PR212/K
Auxiliary power supply

24 V DC 20%
maximum ripple 5%

Maximum current interrupted

5A

Maximum voltage interrupted

250 V AC / 130 V DC

Breaking capacity resistive load

50 W / 800 VA (48 V DC and 220 V AC)

Breaking capacity - inductive load

25 W / 500 VA (48 V DC and 220 V AC)

Contact/contact insulation

1000 Veff

Contact/coil insulation

2000 Veff

ABB SACE

4/31

Accessories
Accessories for electronic releases

The SACE PR010/K signalling unit can

Alarm signalling remains active for the

convert the signals received via the bus

whole duration of the overload up to any

from the SACE PR212/P (LSI or LSIG) and

release trip.

SACE PR212/MP (LRIU) protection units

The protection trip signals remain ac-

into electric signals by means of normally

tive during the timing phase and remain

open electrical power contacts.

that way even after release trip.

An auxiliary power supply with a voltage

A Reset pushbutton on the front of the

stabilised at 24V DC (20% with maxi-

unit allows the state of all signals to be

mum ripple - 5%) and ear thed is

reset.

needed to operate the unit.

There are also two LEDs available on the

It is connected to the Internal Bus of the

unit for visually signalling the following

protection unit by means of a dedicated

information:

serial line over which the information re-

Power ON: auxiliary power supply

garding the state of activation of the pro-

present

tection functions passes, on the basis of

TX (Int Bus): flashing synchronised

which the relative power contacts are

with the communication activity with

closed.

GSIS9147

SACE PR010/K signalling unit

the Internal Bus

In particular, the following signals are

The table below shows the characteris-

available:

tics of the signalling relays available in


the SACE PR010/K unit.

K51

PR212/P (LSI-LSIG)

PR010/K

Protection L alarm

Auxiliary power supply

Protection S alarm

Maximum current interrupted

5A

Protection I alarm

Maximum voltage interrupted

250 V AC / 130 V DC

Protection G alarm

Bus K.O.

Release trip

Protection L pre-alarm

K51

PR212/MP (LRIU)

Protection L alarm

Protection R alarm

Protection I alarm

Protection U alarm
Welded contactor alarm contacts

Bus K.O.

PTC alarm
(temperature sensor on motor) (*)
Generic input 0/1

Release trip

Protection L pre-alarm
Back-up protection alarm

24 V DC 20%
maximum ripple 5%

Breaking capacity resistive load

50 W / 800 VA (48 V DC and 220 V AC)

Breaking capacity inductive load

25 W / 500 VA (48 V DC and 220 V AC)

Contact/contact insulation

1000 Veff

Contact/coil insulation

2000 Veff

(*) alternatively by means of dip-switch

4/32

ABB SACE

SACE PR010/T Test and Configuration Unit


The SACE PR010/T unit is an instrument

possible to upgrade the SW of the SACE

able to carry out the Test, programming

PR010/T unit to allow adaptation of the

and parameter readout functions for the

Test unit to evolution of new products.

protection units which equip the SACE

The results of most importance regard-

Isomax S moulded-case circuit-breakers

ing the test can also be stored in the unit

and the SACE Emax air circuit-breakers.

itself and sent to the Personal Computer

In particular, for circuit-breakers fitted

on explicit request for issue of report.

with SACE PR212/P or SACE PR212/MP

Both in automatic and manual mode, the

releases, the test, programming and

SACE PR010/T unit is able to test the fol-

readout parameter functions are avail-

lowing:

able.

protection functions L, S, I, G;

All the functions mentioned can be car-

protection functions LRIU for SACE

SACE PR010/T unit to the multipin front


flange connector on the protection unit;

PR212/MP;
monitoring of correct operation of the
microprocessor.

connection is guaranteed by means of

The SACE PR010/T unit is of the portable

special interfacing cables supplied as

type and operates with rechargeable bat-

standard with the unit.

teries and/or with an external power supply.

The man-machine interface is guaran-

In its standard supply, the unit includes:

teed by using a membrane keyboard and

SACE PR010/T Test unit complete with

a multi-line alphanumerical display.

the PC (serial RS232)

instruction manual and diskette with

SACE TT1 Test unit

signal the following respectively:

100...240 V AC /12 V DC external

application SW

power supply

situation of the battery charging state.

connection cables between the unit

Two different types of Test are provided:

and the multipin connector present on

automatic and manual.

the ranges of releases which equip the

By means of connection to the PC (with

SACE Isomax S and the SACE Emax

software provided by ABB SACE), it is

series

connection cable between the unit and

power supply cable

rechargeable batteries

There are also two LEDs on the unit which

POWER-ON and STAND BY situation

GSIS9045

ried out ON BOARD by connection of the

plastic container.

SACE PR212/CI contactor control unit


The SACE PR212/CI accessory unit can
be associated with all the circuit-breakers fitted with SACE PR212/MP electronic
release for motor protection. When the
appropriate dip-switch on the front of the
release is positioned on the Normal

opened in the case of fault for overload


L, blocked rotor R or phase missing/

GSIS9040

mode, it allows the contactor to be

unbalance U.
The SACE PR212/CI unit can always be
installed both on a DIN rail and on the
rear of the door.

ABB SACE

4/33

Accessories
Accessories for electronic releases
CT for external neutral
This is applied to the neutral conductor

S4

S5

S6

S7

S8

and allows protection against earth faults

[A]
100
160
250

[A]
320
400
630

[A]
630
800

[A]
1000
1250
1600

[A]
1600
2000
2500
3200

with three-pole circuit-breakers to be realised. The circuit-breaker must be fitted


with SACE PR212/P LSIG release. The
transformer must be connected to the

GSIS9005

release by means of the specific X3-X4


connectors, selected according to the
version of the circuit-breaker and the type
of protection release used.

Connectors
These allow connection of the microprocessor-based release to units or components of external plants. They are, in fact,

available outside and to connect the protection transformer of the neutral conductor outside the circuit-breaker or to the
actuator, dialogue and signalling units, if

GSIS0150

Connector X3 for circuit-breaker fixed

GSIS0151

these are provided.

fitted with releases SACE PR211/P


Connector X3 for plug-in/withdrawable
circuit-breaker (to be applied in the
fixed part) fitted with SACE PR211/P
release
Connectors X3-X4 for fixed circuit-

Connectors X3

Connectors X4

breaker fitted with SACE PR212/P release


Connectors X3-X4 for plug-in/withdrawable circuit-breaker fitted with
SACE PR212/P release

GSIS9030

used to make the relay tripped signal

4/34

ABB SACE

Accessories
Installation accessories and spare parts
Bracket for fixing on DIN rail
This is applied to the fixed circuit-breaker
and allows installation on standardised

S3-S4-S5

S1-S2

DIN rails. It simplifies assembly of circuitbreakers up to 630 A in standard switchboards.


Bracket for fixing on DIN EN 50022 rail
for

SACE S1-S2 circuit-breakers.

for SACE S3-S4-S5 circuit-breakers.


The fixing bracket kit for SACE S3-S4-S5

GSIS0153

GSIS0152

Bracket for fixing on DIN EN 50023 rail

circuit-breakers also includes the front

GSIS9011

flange H = 45mm.

Flange for compartment door


This is always supplied with the circuitbreaker and can also be used with the

S3 ... S7 fixed

S1-S2

rotary handle operating mechanism for


the SACE S3, S4, S5, S6, and S7 circuitbreakers, the front flange for lever operating mechanism and the motor operator. In case of use of these accessories
with SACE S6, S7 circuit-breakers, a

It is not supplied for SACE S1, S2, and

GSIS0155

the one supplied with the circuit-breaker.

GSIS0154

flange is supplied to be used instead of

S3 circuit-breakers which are complete


with SACE RC210, RC211, RC212 re-

ABB SACE

S3 ... S7 withdrawable

S8

GSIS0157

GSIS9018

beside the circuit-breaker.

GSIS0156

sidual current releases in the version

4/35

Accessories
Installation accessories and spare parts
IP54 protection for rotary handle
This allows IP54 degree of protection to
be attained. It is available in the follow-

S1-S2

ing versions:
for rotary handle operating mechanism
on compartment door with fixed dis-

GSIS9034

tance for SACE S1-S2 circuit-breakers


for rotary handle operating mechanism
GSIS0158

on compartment door with adjustable


distance for circuit-breakers SACE S3S4-S5-S6 and S7 circuit-breakers.

Spare parts
The following spare parts are available:

kit with washers, screws and dowels

operating lever

for assembly of the connection termi-

cover group

nals.

arcing chambers
isolating contacts
opening

solenoid

For further details, please ask the Servfor

the

SACE

RC211and RC212 residual current re-

ice Division of ABB SACE for the spare


parts catalogue.

leases

4/36

ABB SACE

Characteristic curves and


technical information

Index
Characteristic curves
Trip curves for distribution
Circuit-breakers with thermomagnetic releases ................................................................ 5/2
Circuit-breakers with SACE PR211/P, SACE PR212/P electronic releases ..................... 5/7
Trip curves for motor protection
Circuit-breakers with magnetic only releases ................................................................... 5/9
Use of the trip curves of circuit-breakers with SACE PR212/MP electronic release ...... 5/10
Circuit-breakers with electronic release SACE PR212/MP ............................................... 5/12
Limitation curves
230 V .................................................................................................................................... 5/14
400-440 V ............................................................................................................................ 5/17
500 V .................................................................................................................................... 5/20
690 V .................................................................................................................................... 5/21
Specific let-through energy curves
230 V .................................................................................................................................... 5/24
400-440 V ............................................................................................................................ 5/27
500 V .................................................................................................................................... 5/30
690 V .................................................................................................................................... 5/31

Technical information
Temperature performance
Circuit-breakers with electronic releases .......................................................................... 5/34
Circuit-breakers with thermomagnetic releases ................................................................ 5/39
Power loss values ............................................................................................................. 5/40
Operation and protection of the low-voltage side of three-phase transformers .. 5/42
Operation and protection of three-phase AC capacitors .......................................... 5/44
Protection of three-phase AC generators .................................................................... 5/46
Applications in direct current ......................................................................................... 5/47
Backup protection (backup table) ................................................................................. 5/50
ABB SACE

5/1

Trip curves for distribution


Circuit-breakers with thermomagnetic releases
SACE
S1 125 - S2 160

t [s]

Magnetic tripping threshold


Im = 10 x Ith

104

103

102

10

10-1

S1

R50125

S2

R50160

R32
R40

R20
R25

R12,5
R16

R10

SACE
S1 125 - S2 160
Magnetic tripping threshold
Im = 5 x Ith

t [s]

1,05

10

102
x Ith

GSIS0201

10-1

102
x Ith

GSIS0202

10-2

104

103

102

5
10

10-1

S1

R40125

S2

R40160

R25
R32

R12,5
R16
R20

R10

10-2

10-1

5/2

1,05

10

ABB SACE

SACE S2X 100

104

t [s]

Magnetic tripping threshold


Im = 10 x Ith

103

102

10

10-1

10-1

SACE S3 160

1,05

102
x Ith

10

GSIS0203

10-2

Y
=
=

70

70

650
70

120

70

70

Y
70

=
46

284

273

375

350

101

30

13.5

Magnetic tripping threshold


Im = 10 x Ith

101

331
=

525

10.5

4
2

65

103.5
288

27.5

Y
51.5 70

70

70

48.5

293
=

20

26

273

280

109
129 =
109

101

525

175

820
=

273

779

109

129 =
109

26

310

ABB SACE

4
65

288

27.5

GSIS0204

17
=

GSIS0024

5/3

Trip curves for distribution


Circuit-breakers with thermomagnetic releases
SACE
S3 160 - S3 250

t [s]

Magnetic tripping threshold


Im = 10 x Ith

104

103

102

10

S3 160 R80R160
S3 250 R200, R250

10-1

10-1

SACE S3 160
Magnetic tripping threshold
Im = 5 x Ith

t [s]

1,05

102
x Ith

10

GSIS0205

10-2

104

103

102

10

10-1
R50

R32

10-1

5/4

1,05

10

102
x Ith

GSIS0206

10-2

ABB SACE

SACE
S3 160 - S3 250

t [s]

Magnetic tripping threshold


Im = 3 x Ith
Magnetic tripping threshold
Im = 5 x Ith

104

103

102

10

S3 160 R80R160
S3 250 R200, R250

10-1

10-1

SACE S5 400
(R320-400)
SACE S5 630
(R500)
Thermal tripping threshold
In = 0,71 x Ith
Magnetic tripping threshold
Im = 510 x Ith

t [s]

1,05

10

102
x Ith

GSIS0207

10-2

104

103

102

10

10-1

10-1

ABB SACE

1,05

10

102
x Ith

GSIS0208

10-2

5/5

Trip curves for distribution


Circuit-breakers with thermomagnetic releases
SACE S6 630 (R630)

t [s]

Thermal tripping threshold


In = 0,71 x Ith
Magnetic tripping threshold
Im = 510 x Ith

104

103

102

10

10-1

10-1

SACE S6 800 (R800)


Thermal tripping threshold
In = 0,71 x Ith
Magnetic tripping threshold
Im = 510 x Ith

t [s]

1,05

10

102
x Ith

GSIS0209

10-2

104

103

102

10

10-1

10-1

5/6

1,05

10

102
x Ith

GSIS0210

10-2

ABB SACE

Trip curves for distribution


Circuit-breakers with electronic releases
SACE S4-S5-S6-S7

t [s]

104

SACE PR211/P
Functions LI - I

0,5
0,4

103

0,7 0,95
0,6 0,8 1
0,9
1,5

N.B. For S5 630


The maximum threshold that
can be set for the I function is
8 x In

D
C

102

6
8

D
C

10

10
12

B
A

10-1

10-1

SACE
S4-S5-S6-S7-S8
SACE PR212/P
Function LSI,
S inverse short delay
(I2t = constant ON)

t [s]

1,05

102
x In

10

GSIS0211

10-2

104
0,4-0,5-0,55-0,6-0,65-0,7-0,75-0,80,85-0,875-0,9-0,925-0,95-0,975-1
0,4

103
1,5
2

D
C

102

N.B. For S5 630


The maximum threshold that
can be set for the I function is
8 x In

B
1

6
8

10

D
C

2
3

B
A

10
12

A
6
8
10

I2t ON

10-1

10-1

ABB SACE

1,05

10

102
x In

GSIS0212

10-2

5/7

Trip curves for distribution


Circuit-breakers with electronic releases
SACE
S4-S5-S6-S7-S8

t [s]

104
0,4-0,5-0,55-0,6-0,65-0,7-0,75-0,80,85-0,875-0,9-0,925-0,95-0,975-1

0,4

SACE PR212/P
Function LSI,
S definite short delay
(I2t = constant OFF)

103
1,5

102

N.B. For S5 630


The maximum threshold that
can be set for the I function is
8 x In

D
C
B

10

D
C

10
12

8 10

D
C

10-1

I2t OFF

B
A

SACE
S4-S5-S6-S7-S8

t [s]

104

0,2

0,3 0,4

0,6

1,05

10

102
x In

GSIS0213

10-1

10

102
x In

GSIS0214

10-2

0,8
0,9
1

SACE PR212/P
Function G

103

102

10

D
C
B

10-1

10-2

10-1

5/8

1,05

ABB SACE

Trip curves for motor protection


Circuit-breakers with magnetic only releases
SACE S2X 80

t [s]

104
13

Fixed magnetic tripping


threshold
Im = 13 x Ith

SACE S3
Adjustable magnetic
tripping threshold
Im = 412 x Ith

12

S3

S3

103

S2X80

102

10

10-1

10-1

1,05

10

102
x In

GSIS0215

10-2

ABB SACE

5/9

Trip curves for motor protection


Use of the trip curves of circuit-breakers with
SACE PR212/MP electronic release
For correct parameter setting of the SACE PR212/MP electronic release, it may be useful to compare the overall circuit-breaker
curve with the motor starting curve.
For this purpose, with the protection function graphics shown on the following pages, it is possible to draw the overall curve
required for the circuit-breaker fitted with SACE PR212/MP release simply and immediately.

N.B. For function L, as for all the other functions, make sure you place a glossy tracing sheet over the curve so that the time

s on

the axis of the co-ordinates coincide.

Function L (cannot be excluded) Protection against overload


To protect the motor against any overloads, as a first step it
is necessary to adjust function L to a current
or equal to the rated current of the motor Ie:

I1 higher than
I1 > Ie.

Function I (cannot be excluded) Protection against short-circuit


This protection function against short-circuit recognises
whether the motor is in the starting phase, thereby avoiding
unwarranted trips; the trip threshold can be set from 6 x In to

For example, if Ie = 135 A, an S4H160 circuit-breaker can

13 x In.

be selected with In = 160 A and the following adjustment

To trace the curve correctly on the glossy sheet, simply

carried out: I1 = 0.85 x In = 136 A.

place the glossy sheet over the graph of function I so that

The second step is to select the trip class according to the

I/In = 1 (on the glossy sheet) corresponds to I/In = 1 (on the

motor starting time

ta.

For a motor with a start-up overload

graph) and draw the desired curve.

of 6 seconds, class 10 can be selected, with a trip time of 8s


at 7.2 x I1.
To trace the curve correctly on the glossy sheet, according
to

I/In,

simply place the glossy sheet over the graph of

function L so that I/In = 0.85 (on the glossy sheet) corresponds to I/I1 = 1 (on the graph) and draw the curve relative

Function U (can be excluded) Protection against loss and/or unbalance


of a phase
Protection against loss or unbalance of a phase, if set to
ON, intervenes when one or two phases have a current

to class 10.

lower than 0.4xI1 (0.4 x 0.85 x In = 0.4 x 0.85 x 160 A =


54.4A in this case).

Function R (can be excluded) Protection against rotor blockage


Protection against rotor blockage can be set both with re-

I5 = 3 ... 10xI1 (in this case I5 = 3 ...


10 x 0.85 x 160), and with regard to the trip time t5.
gard to the trip current

To trace the curve correctly on the glossy sheet, simply


place the glossy sheet over the graph of function U so that
I/In = I1/In (on the glossy sheet) corresponds to I/I1 = 1 (on
the graph). In this case I/In = I1/In = 0.85,

and draw the

desired curve.

To trace the curve correctly on the glossy sheet, simply


place the glossy sheet over the graph of function R so that
I/In = I1/In (on the glossy sheet) corresponds to I/I1 = 1 (on
the graph). In this case I/In = I1/In = 0.85,

and draw the

desired curve.

5/10

ABB SACE

Typical operating characteristic of an asynchronous motor


l1

function L trip current

l3

function I trip current

I5

function R trip current

t5

function R trip time

I6

function U trip current

t6

function U trip time

le

rated service current of the motor

la

motor starting current

Ip

peak value of the sub-transient starting


current

ta

motor starting time

tp

duration of the sub-transient starting phase

typical motor starting curve

example of trip curve of a motor protection


circuit-breaker with electronic release

GSIS0082

ABB SACE

5/11

Trip curves for motor protection


Circuit-breakers with electronic releases SACE PR212/MP
SACE S4-S5-S6-S7

t [s]

SACE PR212/MP
Function L (hot and cold
trip)

105

hot
cold

104

103

102

10
30
20
10
10A

30
20
10
10A

10-1

SACE S4-S5-S6-S7
SACE PR212/MP
Function L (hot trip with 1
or 2 phases supplied)

t [s]

1,05

102
I / I1

10

GSIS0216

10-1

105

hot

104

103

5
102

10

30

20
10
10A

10-1

5/12

1,05

10

102
I / I1

GSIS0217

10-1

ABB SACE

SACE S4-S5-S6-S7

t [s]

SACE PR212/MP
Function R - U

105

Function U
Function R

104

103

102

4
5
6
7
8
10
10

10

7
4

10-1

SACE S4-S5-S6-S7

t [s]

1,05

102
I / I1

10

GSIS0218

10-1

103
13

SACE PR212/MP
Function I

12
11

102

10
9
8

10

10-1

10-2

10-1

ABB SACE

1,05

10

102
x In

GSIS0219

10-3

5/13

Limitation curves
230 V
SACE S1

Ip [kA] 100

50

20
125
100
80

10

63
50

40
32

25
20
16
12,5
10

SACE S2

10

20

50

100

200

500

1000
Is [kA]

GSIS0220

Ip [kA] 100

50

20
160
125
100
80

10

63
50
40
32

25
20
16
12,5

5/14

10

20

50

100

200

500

1000
Is [kA]

GSIS0221

ABB SACE

SACE S3 160,
S3 250

Ip [kA] 100

50
250
200
160
125

20

100
80
50
32

10

SACE S4 160,
S4 250, S5, S6 630,
S6 800, S7, S8

10

20

50

100

200

500

1000
Is [kA]

GSIS0222

Ip [kA] 300
S7

200

S8

100
S6 800

S6 630
S5

50

S4 250
S4 160

20

10

ABB SACE

10

20

50

100

200

500

1000
Is [kA]

GSIS0223

5/15

Limitation curves
230 V
SACE S2X 80,
S2X 100

Ip [kA] 100

42-52-6380-100

10

25-32
20
16
12,5
11

8,5
6,5
5
4
3,2
2,5
2

0,1

1,6

0,01
0,01

SACE S3X 125,


S3X 200, S4X, S6X

0,1

10

100

1000
Is [kA]

GSIS0224

Ip [kA] 100

50
S6X

S4X

20

S3X 200
In200
S3X 200
In160
S3X 200
In125

10

S3X 125
In125
S3X 125
In100
S3X 125
In80

S3X 125
In50
S3X 125
In32

5/16

10

20

50

100

200

500

1000
Is [kA]

GSIS0225

ABB SACE

Limitation curves
400-440 V
SACE S1

Ip [kA] 100

50

20
125
100
80

10

63
50
40
32

25
20
16
12,5
10

SACE S2

10

20

50

100

200

500

1000
Is [kA]

GSIS0226

Ip [kA] 100

50

160

20

125
100
80
63

10

50
40
32
25

20
16
12,5

ABB SACE

10

20

50

100

200

500

1000
Is [kA]

GSIS0227

5/17

Limitation curves
400-440 V
SACE S3 160,
S3 250

Ip [kA] 100

50
250
200

160

20

125
100
80
50

10

32

SACE
S4 160, S4 250,
S5, S6 630, S6 800,
S7, S8

10

20

50

100

200

500

1000
Is [kA]

GSIS0228

500

1000
Is [kA]

GSIS0229

Ip [kA] 300
200

S8
S7

100
S6 800

S6 630
S5

50

S4 250
S4 160

20

10

3
1

5/18

10

20

50

100

200

ABB SACE

SACE S2X 80,


S2X 100

Ip [kA] 100

42-52-6380-100

10

25-32
20
16
12,5
11
8,5
6,5

5
4
3,2
2,5
2
1,6

0,1

0,1

0,01

SACE S3X 125,


S3X 200, S4X, S6X

1000
Is [kA]

100

10

GSIS0230

0,01

Ip [kA] 100
S6X

50
S4X
S3X 200
In 200
S3X 200
In 160
S3X 200
In 125

20

S3X 125
In 125
S3X 125
In 100

10

S3X 125
In 80
S3X 125
In 50
S3X 125
In 32

ABB SACE

10

20

50

100

200

500

1000
Is [kA]

GSIS0231

5/19

Limitation curves
500 V
SACE S1

Ip [kA] 100

50

20

125
100

10

80
63
50
40

32
25
20
16
12,5

10

10

20

50

100

200

500

1000
Is [kA]

GSIS0232

5/20

ABB SACE

Limitation curves
690 V
SACE S2

Ip [kA] 100

50

20

10

160
125
100
80

63
50
40
32
25

20
16
12,5

SACE S3 160,
S3 250

10

20

50

100

200

500

1000
Is [kA]

GSIS0233

Ip [kA] 100

50

250

20

200
160
125
100

10

80
50
32

ABB SACE

10

20

50

100

200

500

1000
Is [kA]

GSIS0234

5/21

Limitation curves
690 V
SACE
S4 160, S4 250, S5,
S6 630, S6 800, S7,
S8

Ip [kA] 300
200

100

S8

S7

50
S6 800
S6 630
S5
S4 250

20

S4 160

10

SACE S2X 80,


S2X 100

10

20

50

100

200

500

1000
Is [kA]

GSIS0235

Ip [kA] 100

42-52-6380-100

10

25-32

20
16
12,5
11
8,5

6,5
5
4
3,2

2,5

0,1

2
1,6

0,01
0,01

5/22

0,1

10

100

1000
Is [kA]

GSIS0236

ABB SACE

SACE S3X 125,


S3X 200, S4X, S6X

Ip [kA] 100

S6X

50
S4X
S3X 200
In 200
S3X 200
In 160

20

S3X 200
In 125
S3X 125
In 125
S3X 125
In 100

10

S3X 125
In 80
S3X 125
In 50
S3X 125
In 32

10

20

50

100

200

500

1000
Is [kA]

GSIS0237

ABB SACE

5/23

Specific let-through energy curves


230 V
SACE S1

I2t [A2s] 108

107

125

106

100
80
63
50
40
32

105

25
20
16
12,5
10

SACE S2

10

20

50

100

200

500

1000
Is [kA]

GSIS0238

104

I2t [A2s] 108

107

5
160

106

125
100
80
63
50
40
32

105

25
20
16
12,5

5/24

10

20

50

100

200

500

1000
Is [kA]

GSIS0239

104

ABB SACE

SACE S3 160,
S3 250

I2t [A2s] 108

107

250
200

106

160
125
100
80
50
32

105

SACE S4 160,
S4 250, S5, S6 630,
S6 800, S7, S8

10

20

50

100

200

500

1000
Is [kA]

GSIS0240

104

I2t [A2s] 109

S8

S7

108

5
S6 800

107
S6 630
S5
S4 250
S4 160

106

ABB SACE

10

20

50

100

200

500

1000
Is [kA]

GSIS0241

105

5/25

Specific let-through energy curves


230 V
SACE S2X 80,
S2X 100

I2t [A2s] 106

42-52-6380-100

105

25-32
20
16
12,5

104

11
8,5
6,5
5
4

103

3,2
2,5

2
1,6

102

0,01

SACE S3X 125,


S3X 200, S4X, S6X

0,1

10

100

1000
Is [kA]

GSIS0242

10

I2t [A2s] 108

107
S6X

5
S4X

106

S3X 200
In 200
S3X 200
In 160
S3X 200
In 125
S3X 125
In 125
S3X 125
In 100

105

S3X 125
In 80
S3X 125
In 50
S3X 125
In 32

5/26

10

20

50

100

200

500

1000
Is [kA]

GSIS0243

104

ABB SACE

Specific let-through energy curves


400-440 V
SACE S1

I2t [A2s] 108

107

125
100
80
63

106

50
40
32

25

105

20
16
12,5
10

SACE S2

10

20

50

100

200

500

1000
Is [kA]

GSIS0244

104

I2t [A2s] 108

107

160
125
100
80

106

63
50
40
32

25

105

20
16
12,5

ABB SACE

10

20

50

100

200

500

1000
Is [kA]

GSIS0245

104

5/27

Specific let-through energy curves


400-440 V

SACE S3 160,
S3 250

I2t [A2s] 108

107

250
200
160
125
100

106

80
50
32

105

SACE S4 160,
S4 250, S5, S6 630,
S6 800, S7, S8

10

20

50

100

200

500

1000
Is [kA]

GSIS0246

1000
Is [kA]

GSIS0247

104

I2t [A2s] 109

S8

S7

108

5
S6 800
S6 630

107

S5
S4 250
S4 160

106

105

5/28

10

20

50

100

200

500

ABB SACE

SACE S2X 80,


S2X 100

I2t [A2s] 106


42-52-6380-100
25-32

105

20
16
12,5
11
8,5
6,5

104

5
4
3,2
2,5

103
2
1,6

102
1

0,01

SACE S3X 125,


S3X 200, S4X, S6X

0,1

10

100

1000
Is [kA]

GSIS0248

10

I2t [A2s] 108

S6X

107

S4X
S3X 200
In 200
S3X 200
In 160

106

S3X 200
In 125
S3X 125
In 125
S3X 125
In 100
S3X 125
In 80

105

S3X 125
In 50
S3X 125
In 32

ABB SACE

10

20

50

100

200

500

1000
Is [kA]

GSIS0249

104

5/29

Specific let-through energy curves


500 V
SACE S1

I2t [A2s] 108

107

106

125
100
80
63
50
40
32

105

25
20
16
12,5
10

10

20

50

100

200

500

1000
Is [kA]

GSIS0250

104

5/30

ABB SACE

Specific let-through energy curves


690 V
SACE S2

I2t [A2s] 108

107

160

106

125
100
80
63
50
40

105

32
25
20
16
12,5

SACE S3 160,
S3 250

10

20

50

100

200

500

1000
Is [kA]

GSIS0251

104

I2t [A2s] 108

107

250
200
160
125

106

100
80
50
32

105

ABB SACE

10

20

50

100

200

500

1000
Is [kA]

GSIS0252

104

5/31

Specific let-through energy curves


690 V
SACE S4 160,
S4 250, S5, S6 630,
S6 800, S7, S8

I2t [A2s] 109

108
S8

S7
S6 800
S6 630

107

S5
S4 250
S4 160

106

SACE S2X 80,


S2X 100

10

20

50

100

200

500

1000
Is [kA]

GSIS0253

105

I2t [A2s] 106

42-52-6380-100
25-32

105

20
16
12,5

11
8,5

104

6,5
5
4
3,2
2,5

103

2
1,6
1

102

0,01

5/32

0,1

10

100
Is [kA]

GSIS0254

10

ABB SACE

SACE S3X 125,


S3X 200, S4X, S6X

I2t [A2s] 108

S6X

107

S4X
S3X 200
In 200
S3X 200
In 160

106

S3X 200
In 125
S3X 125
In 125
S3X 125
In 100
S3X 125
In 80
S3X 125
In 50

105

S3X 125
In 32

10

20

50

100

200

500

1000
Is [kA]

GSIS0255

104

ABB SACE

5/33

Temperature performance
Circuit-breakers with electronic releases

SACE S4 160
Fixed
Front flat bar
Front for cables
Rear for cables
Rear threaded

Plug-in - Withdrawable
up to 40 C
50 C
Imax [A]
I1 Imax [A]
160
1 160
160
1 160
160
1 160
160
1 160

I1
1
1
1
1

60 C
Imax [A]
160
160
160
160

I1
1
1
1
1

70 C
Imax [A]
I1
160
1
160
1
152
0.95
152
0.95

Front flat bar


Front for cables
Rear for cables
Rear threaded

up to 40 C
50 C
Imax [A]
I 1 Imax [A]
160
1 160
160
1 160
160
1 160
160
1 160

Front flat bar


Front for cables

60 C
I 1 Imax [A]
1 160
1 160
1 160
1 160

70 C
I1 Imax [A]
I1
1 152
0.95
1 152
0.95
1 144
0.9
1 144
0.9

Front flat bar


Front for cables

Rear for cables


Rear threaded

GSIS0256

Rear for cables


Rear threaded

SACE S4 250
Fixed
Front flat bar
Front for cables
Rear for cables
Rear threaded

Plug-in - Withdrawable
up to 40 C
50 C
Imax [A]
I1 Imax [A]
250
1 250
250
1 250
250
1 250
250
1 250

I1
1
1
1
1

60 C
Imax [A]
250
250
250
250

I1
1
1
1
1

70 C
Imax [A]
I1
237.5
0.95
237.5
0.95
225
0.9
225
0.9

Front flat bar


Front for cables
Rear for cables
Rear threaded

up to 40 C
50 C
Imax [A]
I 1 Imax [A]
250
1 250
250
1 250
250
1 250
250
1 250

60 C
I 1 Imax [A]
1 250
1 250
1 250
1 250

70 C
I1 Imax [A]
I1
1 225
0.9
1 225
0.9
1 200
0.8
1 200
0.8

5
Front flat bar
Front for cables

Rear for cables


Rear threaded

GSIS0257

Rear for cables


Rear threaded

Front flat bar


Front for cables

5/34

ABB SACE

SACE S5 400
Fixed
Front flat bar
Front for cables
Rear for cables
Rear threaded

Plug-in - Withdrawable
up to 40 C
50 C
Imax [A]
I 1 Imax [A]
400
1 400
400
1 400
400
1 400
400
1 400

I1
1
1
1
1

60 C
Imax [A]
400
400
400
400

I1
1
1
1
1

70 C
Imax [A]
I1
380
0.95
380
0.9
360
0.9
320
0.8

Front flat bar


Front for cables
Rear for cables
Rear threaded

up to 40 C
50 C
60 C
70 C
Imax [A]
I 1 Imax [A]
I 1 Imax [A]
I 1 Imax [A]
I1
400
1 400
1 400
1 380
0.95
400
1 400
1 380
0.95 360
0.9
400
1 400
1 380
0.95 360
0.9
400
1 380
0.95 360
0.9 320
0.8

Front flat bar

Front flat bar

Front for cables


Rear for cables

Front for cables


Rear for cables

Rear threaded

GSIS0258

Rear threaded

SACE S5 630
Fixed
Front flat bar
Front for cables
Rear threaded

Withdrawable
up to 40 C
50 C
60 C
70 C
Imax [A]
I 1 Imax [A]
I1 Imax [A]
I1 Imax [A]
I1
630
1 598.5
0.95 567
0.9 504
0.8
630
1 567
0.9 504
0.8 441
0.7
630
1 504
0.8 441
0.7 378
0.6

Front flat bar


Rear flat bar
Rear threaded

up to 40 C
50 C
60 C
70 C
Imax [A]
I 1 Imax [A]
I 1 Imax [A]
I 1 Imax [A]
I1
630
1 504
0.8 441
0.7 378
0.6
630
1 567
0.9 504
0.8 441
0.7
630
1 441
0.7 378
0.6 315
0.5

5
Front flat bar
Rear flat bar

Front for cables

Rear threaded

Front flat bar

GSIS0259

Rear threaded

ABB SACE

5/35

Temperature performance
Circuit-breakers with electronic releases

SACE S6 630
Fixed
Front flat bar
Front for cables
Rear for cables
Rear threaded

Withdrawable
up to 40 C
50 C
Imax [A]
I1 Imax [A]
630
1 630
630
1 630
630
1 630
630
1 630

I1
1
1
1
1

60 C
70 C
Imax [A]
I1 Imax [A]
I1
630
1 598.5
0.95
598.5
0.95 567
0.9
598.5
0.95 567
0.9
567
0.9 504
0.8

Front flat bar


Rear vertical flat bar
Rear horizontal flat bar

up to 40 C
50 C
60 C
70 C
Imax [A]
I 1 Imax [A]
I 1 Imax [A]
I1 Imax [A]
I1
630
1 630
1 598.5
0.95 567
0.9
630
1 630
1 598.5
0.95 567
0.9
630
1 598.5
0.95 567
0.9 504
0.8

Front flat bar


Rear vertical flat bar

Front flat bar

Rear horizontal flat bar


Front for cables

GSIS0260

Rear threaded

SACE S6 800
Fixed
Front flat bar
Front for cables
Rear for cables
Rear threaded

Plug-in - Withdrawable
up to 40 C
50 C
Imax [A]
I1 Imax [A]
800
1 800
800
1 800
800
1 800
800
1 800

I1
1
1
1
1

60 C
70 C
Imax [A]
I1 Imax [A]
I1
800
1 760
0.95
760
0.95 720
0.9
760
0.95 720
0.9
720
0.9 640
0.8

Front flat bar


Rear vertical flat bar
Rear horizontal flat bar

up to 40 C
50 C
60 C
70 C
Imax [A]
I 1 Imax [A]
I 1 Imax [A]
I1 Imax [A]
I1
800
1 800
1 760
0.95 720
0.9
800
1 800
1 760
0.95 720
0.9
800
1 760
0.95 720
0.9 640
0.8

Front flat bar


Rear vertical flat bar

Front flat bar

Rear horizontal flat bar

Front for cables


Rear for cables

GSIS0261

Rear threaded

5/36

ABB SACE

SACE S7 1250
Fixed
Front flat bar
Rear vertical flat bar
Front for cables
Rear horizontal flat bar

Withdrawable
up to 40 C
Imax [A]
I1
1250
1
1250
1
1250
1
1250
1

50 C
Imax [A]
1250
1250
1250
1250

I1
1
1
1
1

60 C
70 C
Imax [A]
I1 Imax [A]
I1
1250
1 1187.5
0.95
1250
1 1187.5
0.95
1187.5
0.95 1125
0.9
1250
1 1125
0.9

Front flat bar


Rear vertical flat bar
Rear horizontal flat bar

up to 40 C
Imax [A]
I1
1250
1
1250
1
1250
1

50 C
Imax [A]
1250
1250
1250

60 C
70 C
I 1 Imax [A]
I 1 Imax [A]
I1
1 1187.5
0.95 1125
0.9
1 1187.5
0.95 1125
0.9
1 1125
0.9 1000
0.8

Front flat bar


Rear vertical flat bar

Front flat bar


Rear vertical flat bar

Rear horizontal flat bar

Front for cables

GSIS0262

Rear horizontal
flat bar

SACE S7 1600
Fixed
Front flat bar
Rear vertical flat bar
Rear horizontal flat bar

Withdrawable
up to 40 C
Imax [A]
I1
1600
1
1600
1
1600
1

50 C
60 C
Imax [A]
I1 Imax [A]
I1
1520
0.95 1440
0.9
1520
0.95 1440
0.9
1440
0.9 1280
0.8

70 C
Imax [A]
I1
1280
0.8
1280
0.8
1120
0.7

Front flat bar


Rear vertical flat bar
Rear horizontal flat bar

up to 40 C
Imax [A]
I1
1600
1
1600
1
1600
1

Front flat bar


Rear vertical flat bar

60 C
70 C
Imax [A]
I 1 Imax [A]
I1
1280
0.8 1120
0.7
1280
0.8 1120
0.7
1120
0.7 906
0.6

Front flat bar


Rear vertical flat bar

Rear horizontal
flat bar

GSIS0263

Rear horizontal
flat bar

50 C
Imax [A]
I1
1440
0.9
1440
0.9
1280
0.8

ABB SACE

5/37

Temperature performance
Circuit-breakers with electronic releases

SACE S8 2000

SACE S8 2500

Fixed

Fixed
up to 40 C
Imax [A]
I1
2000
1
2000
1

Front flat bar


Rear vertical flat bar

50 C
Imax [A] I1
2000
1
2000
1

60 C
70 C
Imax [A]
I1 Imax [A]
I1
1900 0,95 1715
0,85
2000
1
1785
0,9

up to 40 C
50 C
Imax [A]
I1 Imax [A]
I1
2500
1
2500
1
2500
1
2500
1

Front flat bar


Rear vertical flat bar

60 C
70 C
Imax [A]
I1 Imax [A]
I1
2270
0,9 2040
0,8
2375 0,95 2130
0,85

2550

2050

Rear vertical flat bar

Rear vertical flat bar

2500
2000
2450
1950
2400
2350

1900

2300
1850
2250
Front flat bar

1800

2200

Front flat bar

2150

1750

2100
1700
2050
2000

1650
35

40

45

50

55

60

65

30

70

35

40

45

50

55

60

65

70
GSIS0264

30

SACE S8 3200
Fixed
up to 45 C
50 C
60 C
70 C
Imax [A]
I1 Imax [A]
I1 Imax [A] I1 Imax [A]
I1
3200
1
3060 0,95 2780 0,85 2510
0,8

Rear vertical flat bar

3300

3200

3100

3000

2900

2800

Rear vertical flat bar


2700

2600

2500
30

5/38

35

40

45

50

55

60

65

70

GSIS0265

ABB SACE

Temperature performance
Circuit-breakers with thermomagnetic releases
SACE S1
10 C

20 C

30 C

40 C

50 C

60 C

70 C

R 10

13

12

11

10

R 12,5

13

12

11

10

R 16

20

18,5

17

16

15

14

13

R 20

24

22,5

21

20

19

18

17

R 25

30

28

26,5

25

23

21

19

R 32

38

36

34

32

30

28

26

R 40

49

45

43

40

37

35

34

R 50

60

56

53

50

47

44

41

R 63

75

71

67

63

59

55

51

R 80

96

91

86

80

74

68

62

R 100

120

114

108

100

94

88

82

R 125

145

138

132

125

120

112

104

11...15,5

10...14,5

9,5...13

9...12,5

8...11,5

7,5...10,5

6,5...9,5

SACE S2
R 12,5
R 16

14...19

13...18

11,5...17

11...16

10,5...15

9,5...14

8,5...13

R 20

18...24,5

16,5...23

15...21,5

14...20

13...18

12...17

11...16

R 25

21...30

19,5...28

18,5...26,5

17,5...25

16,5...23

15...21

13...19

R 32

28...38

25,5...36

24...34

22,5...32

20,5...29

19...27

17...25

R 40

33...47

32...45

30...42

28...40

26...37

24...34

21...31

R 50

44...58

39...56

38...53

35...50

33...47

30...43

27...40

R 63

53...74

50...70

47...66

44...63

42...60

38...56

34...52

R 80

66...94

63...90

59...85

56...80

52...75

49...70

44...65

R 100

84...118

80...112

76...106

70...100

65...94

59...85

49...75

R 125

102...145

100...140

93...133

88...125

81...116

75...108

58...101

R 160

130...184

125...176

120...168

112...160

106...150

100...140

90...130

SACE S3
R 32

26...43

24...39

22...36

19...32

16...27

14...24

11...21

R 50

37...62

35...58

33...54

30...50

27...46

25...42

22...39

R 80

59...98

55...92

52...86

48...80

44...74

40...66

32...58

R 100

83...118

80...113

74...106

70...100

66...95

59...85

49...75

R 125

103...145

100...140

94...134

88...125

80...115

73...105

63...95

R 160

130...185

124...176

118...168

112...160

106...150

100...104

90...130

R 200

162...230

155...220

147...210

140...200

133...190

122...175

107...160

R 250

200...285

193...275

183...262

175...250

168...240

160...230

150...220

SACE S5 400/630
R 320

260...368

245...350

234...335

224...320

212...305

200...285

182...263

R 400

325...465

310...442

295...420

280...400

265...380

250...355

230...325

R 500

435...620

405...580

380...540

350...500

315...450

280...400

240...345

SACE S6 630/800

ABB SACE

R 630

520...740

493...705

462...660

441...630

405...580

380...540

350...500

R 800

685...965

640...905

605...855

560...800

520...740

470...670

420...610

5/39

Power loss values

Power [W]

S1

S2

Setting

Iu [A]

R 10

10

4,5

R 12,5

12,5

R 16

16

R 20

20

R 25

S3

S4

P-W

6,5

6,5

8,5

7,5

8,5

8,5

25

9,5

10

11

R 32

32

13

14

14

15

12

13

R 40

40

11

12

10

11

R 50

50

13

14

13

14

16

18

R 63

63

15

16

16

17

R 80

80

19

20

21

23

18

21

R 100

100

16

17

18

20

21

25

R 125

125

20

22

24

26

20

26

R 160

160

30

35

30

40

R 200

200

36

46

R 250

250

50

65

R 320

S5

P-W

S6

P-W

320

60

90

R 400

400

65

96

R 500

500

R 630
R 800

S7

630

92

117

800

93

119

90

115

96

125

In= 100

100

In= 160

160

15

22

In= 250

250

40

55

In= 320

320

In= 400

400

60

90

In= 630

630

170

200

45

S8

65

In= 800

800

In= 1000

1000

102

140

In= 1250

1250

160

220

In= 1600

1600

260

360

In= 2000

2000

200

In= 2500

2500

315

In= 3200

3200

500

The values indicated in the table refer to balanced loads, with a current flow equal to the Iu and to both three-pole and fourpole fixed version
apparatus. For the latter, the current of the neutral is nil by definition.

5/40

ABB SACE

Power [W]

S2X 80

S2X 100

Setting

Iu [A]

R1

R 1,6

1,6

8,2

8,2

8,2

8,2

R 2,5

2,5

R 4,3

4,3

11

11,2

11

11,2

11

11,2

11

R 6,3

11,2

6,3

11

11,2

11

11,2

R 10

10

16

16,3

16

16,3

R 12,5

12,5

20

20,3

20

20,3

R 16

16

10

10,6

10

10,6

R 20

20

13

13,6

13

13,6

R 25

25

13

13,7

13

13,7

R 32

32

26

26,6

26

26,6

R 40

40

26

26,9

26

26,9

R 50

50

22

23,3

22

23,3

R 63

63

22

24,1

22

24,1

R 80

80

26

29,1

26

29,1

R 100

100

30

34,4

R 125

S3X

S4X

P-W

125

30,8

37,8

R 200

200

48

58

In= 250

250

In= 400
In= 630

S6X

P-W

400

60

75
80,4

101

630

126,6

151,6

The values indicated in the table refer to balanced loads, with a current flow equal to the Iu and to both three-pole and fourpole fixed version
apparatus. For the latter, the current of the neutral is nil by definition.

Shock resistance
Tests according to IEC 60068-2-27

Shock value [g]


S1 **

12

S2 **

12

S3-S3X *

12

S4X-S4X *

12

S5 *

12

S6-S6X *

12

S7 *

12

* for fixed/plug-in/withdrawable circuitbrakekers with motor operator, undervoltage


release and auxiliary contacts
** for fixed/plug-in circuit-brakekers

with

undervoltage release and auxiliary contacts

ABB SACE

5/41

Operation and protection of the low-voltage side


of three-phase transformers

In order to choose the SACE Isomax S circuit-breakers to install

of use. The table has been drawn up considering infinite power

both on the transformer risers and on the lines branching

upstream and the most unfavourable case has been assumed,

downstream of them, reference can be made to the following

that is, that the short circuit occurs on the transformer clamps.

table dealing with transformers with no-load voltage on the

As regards users, the short circuit is considered downstream

secondary equal to 400 V which is the most common condition

of the user circuit-breaker clamps.

Power supply transformers


P

Ucc

Ib riser

Ib total

Icc riser

[kVA]

[A]

[A]

[kA]

type

type

settings

1 x 63

91

91

2,2

S1B125

R100

0,95

91

182

2,2

S1B125

R100

0,95

144

144

3,6

S2B160

R160

0,95

144

288

3,6

S2B160

R160

0,95

180

180

4,5

S3N/S4N250

R200/In = 250 A

0,95/0,8

180

360

4,5

S3N/S4N250

R200/In = 250 A

0,95/0,8

231

231

5,8

S3N/S4N250

R250/In = 250 A

0,95/0,95

231

462

5,8

S3N/S4N250

R250/In = 250 A

0,95/0,95

289

289

7,2

S5N400

In = 320 A

0,95

289

578

7,2

S5N400

In = 320 A

0,95

361

361

S5N400

In = 400 A

0,95

361

722

S5N400

In = 400 A

0,95

455

455

11,3

S6N630

In = 630 A

0,8

455

910

11,3

S6N630

In = 630 A

0,8

577

577

14,4

S6N630/S6N800

In = 630/800 A

0,95/0,8

577

1154

14,4

S6N630/S6N800

In = 630/800 A

0,95/0,8

722

722

18

S6N800/S7S1250

In = 800/1000 A

0,95/0,8

722

1444

18

S6N800/S7S1250

In = 800/1000 A

0,95/0,8

909

909

23

S7S1250

In = 1000 A

0,95

2 x 630

909

1818

23

S7S1250

In = 1000 A

0,95

3 x 630

909

2727

46

S7S1250

In = 1000 A

0,95

1155

1155

23

S7S1250/S7S1600

In = 1250/1600 A

0,95/0,8

1155

2310

23

S7S1250/S7S1600

In = 1250/1600 A

0,95/0,8

2 x 63
1 x 100

2 x 100
1 x 125

2 x 125
1 x 160

2 x 160
1 x 200

2 x 200
1 x 250

2 x 250
1 x 315

2 x 315
1 x 400

2 x 400
1 x 500

2 x 500
1 x 630

Circuit-breaker "A"(secondary of transformer)

1 x 800

2 x 800
3 x 800

SACE Isomax S

Release TM / PR211-212

1155

3465

46

S7S1250/S7S1600

In = 1250/1600 A

0,95/0,8

1443

1443

29

S7S1600

In = 1600 A

0,95

2 x 1000

1443

2886

29

S7S1600

In = 1600 A

0,95

3 x 1000

1443

4329

58

S7H1600

In = 1600 A

0,95

1 x 1000

1 x 1250

1804

1804

36

S8H2000

In = 2000 A

0,95

2 x 1250

1804

3608

36

S8H2000

In = 2000 A

0,95

3 x 1250

1804

5412

72

S8H2000

In = 2000 A

0,95

2309

2309

37

S8H2500

In = 2500 A

0,95

2 x 1600

2309

4618

37

S8H2500

In = 2500 A

0,95

3 x 1600

2309

6927

74

S8H2500

In = 2500 A

0,95

2887

2887

46

S8H3200

In = 3200 A

0,95

2 x 2000

2887

5774

46

S8H3200

In = 3200 A

0,95

3 x 2000

2887

8661

92

S8V3200

In = 3200 A

0,95

1 x 1600

1 x 2000

5/42

6,25

6,25

ABB SACE

GSIS0272

Circuit-breaker "B" (user outgoing)


Icu user

User rated current and type of circuit-breaker

[kA]

32 A

63 A

2,2

S250

S250

125 A

4,4

S250

S250

S1B125

3,6

S250

S250

S1B125

160 A

250 A

400 A

7,2

S250

S250

S1B125

4,5

S250

S250

S1B125

S2B160

S250

S250

S1B125

S2B160

5,8

S250

S250

S1B125

S2B160

11,6

S1B125

S1B125

S1B125

S2B160

S3N250

7,2

S250

S250

S1B125

S2B160

S3N250

14,4

S1B125

S1B125

S1B125

S2B160

S3N250

S5N400

S250

S250

S1B125

S2B160

S3N250

630 A

18

S1N125

S1N125

S1N125

S2N160

S3N250

S5N400

11,3

S1B125

S1B125

S1B125

S2B160

S3N250

S5N400

22,6

S1N125

S1N125

S1N125

S2N160

S3N250

S5N400

S5N / S6N630

14,4

S1B125

S1B125

S1B125

S2B160

S3N250

S5N400

800 A

1250 A

28,8

S2N160

S2N160

S2N160

S2N160

S3N250

S5N400

S5N / S6N630

18

S1N125

S1N125

S1N125

S2N160

S3N250

S5N400

S5N / S6N630

36

S2N160

S2N160

S2N160

S2N160

S3N250

S5N400

S5N / S6N630

S6N800

23

S1N125

S1N125

S1N125

S2N160

S3N250

S5N400

S5N / S6N630

S6N800

46

S2S160

S2S160

S2S160

S2S160

S3H250

S5H400

S5H / S6S630

S6S800

S7S1250

69

S2X100

S2X100

S3L160

S3L160

S3L250

S5L400

S5L / S6L630

S6L800

S7L1250

23

S1N125

S1N125

S1N125

S2N160

S3N250

S5N400

S5N / S6N630

S6N800

46

S2S160

S2S160

S2S160

S2S160

S3H250

S5H400

S5H / S6S630

S6S800

S7S1250

1600 A

69

S2X100

S2X100

S3L160

S3L160

S3L250

S5L400

S5L / S6L630

S6L800

S7L1250

29

S2N160

S2N160

S2N160

S2N160

S3N250

S5N400

S5N / S6N630

S6N800

S7S1250

58

S2X100

S2X100

S3H160

S3H160

S3H250

S5H400

S5H / S6H630

S6H800

S7H1250

S7H1250

87

S4L160

S4L160

S4L160

S4L160

S4L250

S5L400

S5L/S6L630

S6L800

S7L1250

S7L1250

36

S2N160

S2N160

S2N160

S2N160

S3N250

S5N400

S5N/S6N630

S6N800

S7S1250

S7S1600

72

S3L160

S4L160

S3L160

S3L160

S3L250

S5L400

S5L/S6L630

S6L800

S7L1250

S7L1250

108

S3X125

S3X125(R80)

S3X125

S3X200

S4X250

S6X400

S6X630

S8V2000

S8V2000

S8V2000

37

S2S160

S2S160

S2S160

S2S160

S3H250

S5H400

S5H/S6S630

S6S800

S7S1250

S7S1600

74

S3L160

S3L160(R80)

S3L160

S3L160

S3L250

S5L400

S5L/S6L630

S6L800

S7L1250

S7L1600

111

S3X125

S3X125(R80)

S3X125

S3X200

S4X250

S6X400

S6X630

S8V2000

S8V2000

S8V2000

46

S2S160

S2S160

S2S160

S2S160

S3H250

S5H400

S5H/S6S630

S6S800

S7S1250

S7S1600

92

S4L160

S4L160

S4L160

S4L160

S4L250

S5L400

S5L/S6L630

S6L800

S7L1250

S7L1600

138

S3X125

S3X125(R80)

S3X125

S3X200

S4X250

S6X400

S6X630

ABB SACE

5/43

Operation and protection of three-phase


AC capacitors

Table for choosing SACE Isomax S circuit-breakers in relation


to the rated current of the bank and the power of the transformer
installed.

Circuit-breaker

Rated
current of
release

Rated
current of
capacitor

Max
electronic/
magnetic
release setting

400

440

500

690

[kA]

[A]

[A]

PR... / TM

[V]

[V]

[V]

[V]

man

man/h

man

man/h

16 / 25

125

83

- / Im=10 In

58

64

72

100

25000

240

8000

120

S2 B/N/S 160

16 / 35 / 50

160

107

- / Im=10 In

74

81

92

127

25000

240

8000

120

S3 N/H/L 160

35 / 65 / 85

160

107

- / Im=10 In

74

81

92

127

25000

120

10000

120

S3 N/H/L 250

35 / 65 / 85

250

167

- / Im=10 In

115

127

144

199

25000

120

8000

120

S4 N/H/L 160

35 / 65 / 100

160

107

I3=OFF / -

74

81

92

127

20000

120

10000

120

S4 N/H/L 250

35 / 65 / 100

250

167

I3=OFF / -

115

127

144

199

20000

120

8000

120

S5 N/H/L 400

35 / 65 / 100

400

267

I3=OFF / Im=10 In

185

203

231

319

20000

120

7000

60

S5 N/H/L 630

35 / 65 / 100

500/630

333

I3=OFF / Im=10 In

231

254

288

398

20000

120

5000

60

S6 N/S/H/L 630

35/50/65/100

630

420

I3=OFF / Im=10 In

291

320

364

502

20000

120

7000

60

S6 N/S/H/L 800

35/50/65/100

800

533

I3=OFF / Im=10 In

369

406

462

637

20000

120

5000

60

S7 S/H/L 1250

50 / 65 / 100

1250

833

I3=OFF / -

577

635

722

996

10000

120

7000

20

S7 S/H/L 1600

50 / 65 / 100

1600

1067

I3=OFF / -

739

813

924

1275

10000

120

5000

20

S8 H/V 2000

85 / 120

2000

1333

I3=OFF / -

924

1016

1155

1593

10000

120

3000

20

S8 H/V 2500

85 / 120

2500

1667

I3=OFF / -

1155

1270

1443

1992

10000

120

2500

20

S8 H/V 3200

85 / 120

3200

2133

I3=OFF / -

1478

1626

1847

2550

10000

120

1500

10

Type
S1 B/N 125

Icu
380/415 V

Maximum rating
of capacitor bank
in kVAR-50 Hz

Mechanical
endurance

Electrical
endurance

5/44

ABB SACE

Coefficient for calculating capacitor bank power in kVAR/kW


to increase the cos

value.

Cosj to be obtained
Initial Cosj

0,81

0,85

0,9

0,91

0,92

0,93

0,94

0,95

0,96

0,97

0,98

0,99

0,60

0,584

0,714

0,849

0,878

0,905

0,939

0,971

1,005

1,043

1,083

1,131

1,192

1,334

0,61

0,549

0,679

0,815

0,843

0,870

0,904

0,936

0,970

1,008

1,048

1,096

1,157

1,299

0,62

0,515

0,645

0,781

0,809

0,836

0,870

0,902

09,36

0,974

1,014

1,062

1,123

1,265

0,63

0,483

0,613

0,749

0,777

0,804

0,838

0,870

0,904

0,942

0,982

1,030

1,091

10233

0,64

0,450

0,580

0,716

0,744

0,771

0,805

0,837

0,871

0,909

0,949

0,997

1,058

1,200

0,65

0,419

0,549

0,685

0,713

0,740

0,774

0,806

0,840

0,878

0,918

0,966

1,007

1,169

0,66

0,388

0,518

0,654

0,682

0,709

0,743

0,775

0,809

0,847

0,887

0,935

0,996

1,138

0,67

0,358

0,488

0,624

0,652

0,679

0,713

0,745

0,779

0,817

0,857

0,905

0,966

1,108

0,68

0,329

0,459

0,595

0,623

0,650

0,984

0,716

0,750

0,788

0,828

0,876

0,937

1,079

0,69

0,299

0,429

0,565

0,593

0,620

0,654

0,686

0,720

0,758

0,798

0,840

0,907

1,049

0,70

0,270

0,400

0,536

0,564

0,591

0,625

0,657

0,691

0,729

0,769

0,811

0,878

1,020

0,71

0,242

0,372

0,508

0,536

0,563

0,597

0,629

0,663

0,701

0,741

0,783

0,850

0,992

0,72

0,213

0,343

0,479

0,507

0,534

0,568

0,600

0,634

0,672

0,712

0,754

0,821

0,963

0,73

0,186

0,316

0,452

0,400

0,507

0,541

0,573

0,607

0,645

0,685

0,727

0,794

0,936

0,74

0,159

0,289

0,425

0,453

0,480

0,514

0,546

0,580

0,618

0,658

0,700

0,767

0,909

0,75

0,132

0,262

0,398

0,426

0,453

0,487

0,519

0,553

0,591

0,631

0,673

0,740

0,882

0,76

0,105

0,235

0,371

0,399

0,426

0,460

0,492

0,526

0,564

0,604

0,652

0,713

0,855

0,77

0,079

0,209

0,345

0,373

0,400

0,434

0,466

0,500

0,538

0,578

0,620

0,687

0,829

0,78

0,053

0,182

0,319

0,347

0,374

0,408

0,440

0,474

0,512

0,552

0,594

0,661

0,803

0,79

0,026

0,156

0,292

0,320

0,347

0,381

0,413

0,447

0,485

0,525

0,567

0,634

0,776

0,80

0,130

0,266

0,294

0,321

0,355

0,387

0,421

0,459

0,499

0,541

0,608

0,750

0,81

0,104

0,240

0,268

0,295

0,329

0,361

0,395

0,433

0,473

0,515

0,582

0,724

0,82

0,078

0,214

0,242

0,269

0,303

0,335

0,369

0,407

0,447

0,489

0,556

0,698

0,83

0,052

0,188

0,216

0,243

0,277

0,309

0,343

0,381

0,421

0,462

0,530

0,672

0,84

0,026

0,162

0,190

0,217

0,251

0,283

0,317

0355

0,395

0,437

0,504

0,645

0,85

0,136

0,164

0,191

0,225

0,257

0,291

0,329

0,369

0,417

0,478

0,620

0,86

0,109

0,140

0,167

0,198

0,230

0,264

0,301

0,343

0,390

0,450

0,593

0,87

0,083

0,114

0,141

0,172

0,204

0,238

0,275

0,317

0,364

0,424

0,567

0,88

0,054

0,085

0,112

0,143

0,175

0,209

0,246

0,288

0,335

0,395

0,538

0,89

0,028

0,059

0,086

0,117

0,149

0,183

0,230

0262

0,309

0,369

0,512

0,031

0,058

0,089

0,121

0,155

0,192

0,234

0,281

0,341

0,484

0,90

ABB SACE

5/45

Protection of three-phase AC generators


(Ue = 400 V)

Power

In

generator

[kVA]

[A]

S1

S2

S3

S3

S4

S4

S5

S5

S6

S6

S7

S7

S8

S8

S8

125

160

160

250

160

250

400

630

630

800

1250

1600

2000

2500

3200

In [A]

In [A]

In [A]

In [A]

In [A]

In [A]

In [A]

In [A]

In [A]

In [A]

In [A]

250

320

250

320

40

100

50

100

63

91

100

100

100

160

160

100

100

144,5

160

231,2

200

289

320

630

630

250

361

400

630

630

800

315

455

630

630

800

1000

400

578

630

630

800

1000

500

723

800

1000

1600

630

910

1000

1600

800

1156

1250

1600

1000

1445

1600

1120

1617

1600

1250

1804

1400

2021

2500

1600

2309

2500

2000

2887

200
250

160

2000

3200

5/46

ABB SACE

Applications in direct current


Connection diagrams

Suitable connection arrangements must be adopted to obtain

breaking capacity required at the various operating voltages.

the number of poles in series necessary to guarantee the

Circuit protection and isolation with three-pole circuit-breakers


Diagram A: breaking

with 1 pole per polarity

Diagram B:breaking

with 2 poles in series

per polarity and

Diagram C: breaking

1 pole for the

with 3 poles in series

per polarity

other polarity

Load

Load

Load

Poles in parallel
Diagram D:breaking

with 2 poles in parallel

Diagram E: breaking

per polarity

with series of 2 poles in

parallel per polarity

Load

Load

Use at 1000 V DC with four-pole circuit-breakers


Diagram F: breaking

with 4 poles in series

Diagram G:3+1

Diagram H:2+2

poles in series

poles in series

for one polarity

Load

Load

GSIS0271

Load

The following table shows which connection arrangement to

to obtain the required breaking capacity for the type of

adopt according to the number of poles to connected in series

distribution network.

Rated
voltage
< 250
< 500
< 750
< 1000

Protection

Function
Isolation

Distribution network
isolated
from earth

with one
polarity* to earth

with median
point to earth

A, D

A, D

A, D

A, D

A, D

C, E

earth being sufficient for the fault

the circuit breaking poles is

G, H

than 750V the 1000 VDC range

3) Diagram D and diagram E

* The negative pole is assumed


to be earthed.

Notes
1) The risk of a double fault to

current to affect only one side of

considered negligible.
2) For rated voltages greater

is required.

only for S6.

ABB SACE

5/47

Applications in direct current


Connection diagrams

Example of tripping threshold adjustment in DC - diagram A


Setting

S1 125
Ith

Im=5Ith

Ith

Im=10Ith

S3 160
Im=5Ith

S3 250
Ith

Im=10Ith

Im=5Ith

R 200

140200

2600

1300

R 250

175250

3250

1625

R 10

Im=10Ith

S2 160
Ith

Im=10Ith

Im=5Ith

1932

650

390

3050

650

390

10

208

12,5

208

912,5

208

R 16

16

208

11,216

208

R 20

20

650

260

1420

650

260

R 25

25

650

260

17,525

650

260

R 32

32

650

260

22,532

650

260

R 40

40

650

260

2840

650

260

R 50

50

650

325

3550

650

325

R 63

63

819

416

4463

819

416

R 80

80

1040

520

5680

1040

520

4880

1040

520

R 100

100

1300

650

70100

1300

650

70100

1300

650

R 125

125

1625

819

87,5125

1625

819

87,5125

1625

819

112160

2080

1040

112160

2080

1040

R 12.5

R 160

N.B. For the lower settings R10, R12.5, R16 only the version I = 5
m

Ith

can be used

The correction value to adopt for the protection thresholds of


each circuit-breaker is shown in the following table.

Circuit-breaker

Diagram A

Diagram B

Diagram C

Diagram F

Diagram G

Diagram H

S1

km= 1

km= 1

km= 1

S2

km= 1

km= 1

km= 1

S3

km= 1

km= 1,15

km= 1,15

km= 1

km= 1

km= 1

S5

km= 1,1

km= 1

km= 1

km= 1,1

km= 1,1

km= 1,1

S6

km= 1,1

km= 1

km= 1

km= 0,9

km= 0,9

km= 0,9

5/48

ABB SACE

Setting

S5 400

S5 630

Ith=0,71xIn

Im=510xIn

R 320

225320

17603520

R 400

280400

22004400

S6 630

Ith=0,71xI n

Im=510xIn

350500

27505500

R 500
R 630

S6 800

Ith=0,71xI n

Im=510xIn

440630

30656930

R 800

Ith=0,71xIn

Im= 510xIn

560800

44008800

Using these the correction factors means that the tripping cur-

therefore in this specific case, having chosen circuit-breaker

rent values will be higher for the same tripping threshold, or,

S6 R630 (ln = 630 A), the magnetic threshold setting value will

vice versa, that having identified the tripping value one needs

be:

to set the tripping threshold following the reclassified scale


range.

set =
Example

5000
1,1 x 630

Operating current: Ib = 600 A


Magnetic protection required: Im = 5000 A
Magnetic protection required
to set:

set =

Im
km x In

ABB SACE

5/49

Backup protection
(backup table with Ue = 400 V~)

The table below shows the backup protection available, with

circuit-breakers (SACE Isomax S, SACE Limitor LNA and SACE

the related breaking capacities for the rated voltage

Emax) and pro

system modular circuit-breakers.

Ue=400V~, between ABB moulded-case and air low voltage

CIRCUIT-BREAKER UPSTREAM
S270 S280/20 S280/20 S290 S500
In [A] <
Icu [kA]

15

20

25

15

50

S1B
125

S2B
160

S1N
125

S2N
160

S3N
250

S4N
250

S5N
630

S6N
800

S2S
160

S6S
800

S7S
1600

16

16

25

35

35

35

35

35

50

50

50

S240

S240

S240

S240

S250

S250
S250

S250

S270
S280/20
S280/25
S1B

S270

CIRCUIT-BREAKER DOWNSTREAM
10
15

S240
S250

16
20

25

30

S240

S240
S250
S240
S250
S270
S240
S250
S270
S240

S250

S1B
S2B

S1B
S2B

S270
S280/20
S280/20
S1B
S2B

S1B
S1N
S2B

S1N

S250

S1B
S2B

S270

S280/20 S280/25 S280/25


S280/25
S1B
S1N
S2B

35

S250
S270

S280/20
S1N

S1N

S280/25

S250

S1N

40

50

S270
S280/20
S280/25
S1B
S1N

S1B
S1N
S2B
S2N

S3N
S4N
S5N
S6N

S2N
S3N
S4N
S5N

65

85

100

130
150
170

200

5/50

ABB SACE

In the interest of facilitating clear representation, the latter must


be read using the follow key:

S250:
S270:

S250, S260, S270K


S270 (B-C-D), S280 (In = 3 ... 8 A),
S280 (In = 50 ... 63 A), S290

S280/20: S280
S280/25: S280

(In = 32 ... 40 A)
(In = 10... 25 A)

S3H
250

S4H
250

S5H
630

S6H
800

S7H
1600

S2X
100

S3L
250

S4L
250

S5L
630

S6L
800

S7L
1600

S3X
125

S3X
200

S4X
250

S6X
630

E2L
1600

E3L
2500

65

65

65

65

65

70

85

100

100

100

100

200

200

200

200

130

130

S250

S250

S1B
S2B

S5N

S6N

S240

S250

S250
S270

S250
S1B
S2B

S1B
S2B

S240

S250
S270

S1B
S2B

S1B
S2B

S250

S270
S280/20
S280/20

S250

S270
S280/20
S280/20

S270

S280/25 S280/25
S1B
S2B

S240

S280/25 S280/25

S280/20

S1B
S2B

S1N

S1N

S3N
S4N
S5N
S6N

S270

S280/20
S280/25
S1B
S1N
S2N
S2S
S3N

S280/25

S280/25 S280/25

S1N

S1N
S2N
S2S
S3N

S270
S270
S280/20 S280/20

S2N
S2S
S3N
S4N

S1B
S2B

S1N

S1N

S2B
S1B

S6N

S2N
S2S
S3N
S4N
S5N

S2N
S3N
S4N

S1N
S2N
S2S
S3N
S3H

S3N
S4N
S5N

S1N

S2N
S2S
S3N
S3H
S3L

S2N
S3N
S4N

S5N

S2S
S3H
S3L
S4H

S1N

S6N

S1B
S2B

S5H
S6S
S6H

S6S

S1B

S2S
S3H
S3L
S4H
S5H

S2B

S1B
S2B

S2N
S3N
S4N

S1N

S2S

S5H
S6S
S6H
S7S
S7H
S5L
S6L
S7L

S6H
S7S
S7H

S6L
S7L

S1N
S1N
S500
LNA
S2N
S2S

ABB SACE

S500
LNA
S2N
S2S
S3N
S3H
S3L

LNA
S2N
S2S
S3N
S3H
S3L

S5N
S3H
S3L
S4H
S4L
S5H
S5L
S6S
S6H
S6L

5/51

5/52

ABB SACE

Overall dimensions and


circuit diagrams

Index
Overall dimensions
SACE Isomax S1-S2
Fixed circuit-breaker ............................................................................................................
Plug-in circuit-breaker ..........................................................................................................
Circuit-breaker with SACE RC210-RC211-RC212 residual current releases .....................
Accessories ..........................................................................................................................

6/2
6/3
6/4
6/5

SACE Isomax S3-S4-S5-S3X-S4X


Fixed circuit-breaker ............................................................................................................
Mounting parts for fixed circuit-breaker ...............................................................................
Plug-in circuit-breaker - withdrawable circuit-breaker .........................................................
Mounting parts for plug-in circuit-breaker - withdrawable circuit-breaker ...........................
SACE S3 circuit-breaker with SACE RC211/3 - RC212/3 residual current releases .........
Accessories ..........................................................................................................................

6/7
6/9
6/10
6/11
6/12
6/14

SACE Isomax S6-S6X


Fixed circuit-breaker ............................................................................................................
Mounting parts for fixed circuit-breaker ...............................................................................
Withdrawable circuit-breaker ...............................................................................................
Mounting parts for withdrawable circuit-breaker .................................................................
Accessories ..........................................................................................................................

6/18
6/20
6/22
6/23
6/24

SACE Isomax S7
Fixed circuit-breaker ............................................................................................................
Mounting parts for fixed circuit-breaker ...............................................................................
Withdrawable circuit-breaker ...............................................................................................
Mounting parts for withdrawable circuit-breaker .................................................................
Accessories ..........................................................................................................................

6/28
6/29
6/30
6/31
6/32

SACE Isomax S8
Fixed circuit-breaker ............................................................................................................ 6/36
Mounting parts for fixed circuit-breaker ............................................................................... 6/37
Distances to be respected ..............................................................................................
Minimum distance between centres .............................................................................

6/38
6/39

Circuit diagrams
Index ................................................................................................................................... 6/41

ABB SACE

6/1

Overall dimensions
SACE S1-S2
Fixed circuit-breaker
Mounting on
sheet metal

Mounting on
DIN EN 50022 channel

Terminal covers
(to order when not included in supply)

(*) 75 with sealable screws

Y
B

(4 POL)

A
E

(3 POL)

71

1.52

71(*)
40

1
120

96

X 45 X

X 45

Low

High

48

2
C

(3 POL)

75

(4 POL)

Terminals
Front for Cu cables or flat
bars

Front for Cu cables or


flat bars

(with separator plates between the


phases)

(with high or low terminal


covers)

Extended front for S2

Threaded rear

(*) high terminal covers included in


supply

(**) low terminal covers included in supply (protection class IP20)

23.5

View A

17.5

8.5

(*)

24.5

42

15

(**)
I

27.5

M8

11

E
102

39
M
75

Template for drilling sheet metal support


Template for drilling compartment door and fitting flange

(minimum thickness of sheet metal: 3 mm)


For front terminals

(thickness of sheet metal: 1.5 - 2 mm)

For threaded rear terminals


Y
4 POL

Y
=

Key

3 POL

(3-4 POL)
E

18

Flange for compartment door

Bracket for fitting circuit-breaker


on DIN channel (to order)

Separator plate

Sealable screws

O
Q
62 63

62
100

102 100

64

53

4
P

M4/4.5

M4/4.5

= =
E

GSIS0001

R 1.5

3 POL 4 POL

3 POL 4 POL

S1

78

103

39

91

25

116

91

25.5

10.5 x 11

29

62

83.5 108.5

86

S2

90

120

45

103

30

133

93

27.5

12.5 x 12.5

27

60

95.5 125.5

98

6/2

...

...

...

111

42

43

...

...

...

128

48

49

...

...

...

ABB SACE

Plug-in circuit-breaker
Fixed parts mounted on sheet metal or channel
(terminal covers for mobile part with IP20 always included in supply)

B
=

A
E

(4 POL)

123 (*)

2.5
10

(3 POL)

=
E

(*)127 mm with sealable screws

1.52 mm

Key
2

1
SAC

=
45
=

96 163

off

70

124

50

75

Flange for compartment door

Sealable screws

Fixed part

Moving part complete with terminal


covers

42

(3 POL)

52

(4 POL)

Terminals
Front

Threaded rear
2.5

View A

10

2.5

76
40
26
M8

102

39

65.5

Drilling template for support (5) or channel (6)


Template for drilling
compartment door and fitting
flange

(minimum thickness of sheet metal: 2.5 mm)


For threaded rear terminals
Y
Y
L
M

(thickness of sheet metal: 1.5 - 2 mm)

L
M

(4 POL)
(3 POL)

(4 POL)
(3 POL)

Y
O

84

144

60
MAX

5.5

35

144

60
102 MAX

5.5

35

63

64

53

R 1.5

R 13

M4 4.5

84

M4 4.5
R

R
E (3 POL)
M (4 POL)

(3 POL)

(4 POL)

3 POL 4 POL

3 POL 4 POL

S1

78

103

39

91

25

116

91

28

10.5 x 11

75

50

83.5 108.5

86

S2

90

120

45

103

30

133

93

28

12.5 x 12.5

90

60

95.5 125.5

98

ABB SACE

GSIS0002

For front terminals

...

...

111

42

43

12.5

...

...

128

48

49

15

...

...

6/3

Overall dimensions
SACE S1-S2
Circuit-breaker with SACE RC210-RC211-RC212 residual current release
Vertical installation RC211-RC212
(*) Without terminal covers
(**) With low terminal covers
(***) With high terminal covers

(mounting on sheet metal)

Front terminals for Cu


cables or flat bars

Threaded rear terminals


(low terminal covers included in supply)

Version with high terminal covers:


front or rear output cables

(high terminal covers to order)

Y
C
A

71

71()

24.5

71()

1.52 mm

1.52 mm

SAC

X1

45

=
=

off

96

245

249 325
(**) (***)

80

(*)

X1
245

249 227

325

SAC

X2

45
48

X2

96

75

75

() 75 with sealable screws

Template for drilling sheet metal support


(minimum thickness of sheet metal: 3 mm)

75

4 POL
3 POL
= =
D

Template for drilling compartment door and fitting


flange (thickness of sheet metal: 1.5 - 2 mm)

20
G
H

18

96.5
63 62

X1

M4 - 4,5

100

X1

38

25

293

Holes for rear


terminals only

Holes for cables


with rear outlet only

X1 53 64

125
100

X2

39

125

X2

38

71.5

G
R1.5

18

X2 53 64

20
= =
D

Horizontal installation SACE RC210-RC211-RC212


=

=
D

I
D

Key

70

24.5

2
120

=
=

45

Bracket for mounting on DIN EN 50022 channel

Flange for compartment door

Separator plate

GSIS0003

75

25

206

S1 - RC211/RC212

103

39

116

25

43

41.7

111

108.5

206

S2 - RC211/RC212

120

45

133

30

49

47.7

128

125.5

240

6/4

Note
See the various different versions for the dimensions
of the terminals

~70

S1 - RC210

Front terminals for cables and flat bars

48

ABB SACE

Accessories
Solenoid operator at the side of the circuit-breaker
B

24.5

Key

92
70.2

6.7

1
Y
E

120

SACE S

=
45
=

X
48

124
100 +0.15
X
X

=
X

66 0.15

62

52
80 +0.15

2
C

Plate for fixing circuitbreaker onto DIN EN 50022


rail (a richiesta)

Separator plates between


the phases

Spacer
(for SACE S1 only)

50

3
D

A 3 POL B 3 POL C 4 POL D 4 POL

S1

78

162

64

187

25 0.15

38.5 0.2

S2

90

168

75

198

30 0.1

36 0.2

Drilling for fixing the circuitbreaker and solenoid


operator assembly onto
sheet

Key

Solenoid operator on the front of the circuit-breaker


B
A

78
24.5

150
147

1.5-2

1
3
=

SACE S

=
X 96

83.5
X 45

64 +0.15 X

R1.5

Separator plates between


the phases
A 3 POL B 4 POL

X 53

85

140.5

GSIS0004

Y
91

Template for drilling


compartment door and
fitting flange

124

=
50

+0.15

Flange for compartment


door

23

S1

78

103

S2

90

120

Interlock across two horizontally-installed circuit-breakers


Y

Y1

120 (S2S2)
117.5 (S1S2)
115 (S1S1)

30

62
100

90

30
X

X
S2S2

4.5-M4
25
SACE

90

30

Key

X
S1S2

25

90

Y1

Note
See the various different versions for the dimensions of the circuit-breakers

ABB SACE

Template for drilling sheet


metal support

Tightening torque 1,1 Nm


Remove the screws for
stirruping the cover and
replace them with the ones
in the KIT.

X
S1S1

Interlock device

30

GSIS0005

6/5

Overall dimensions
SACE S1-S2
Accessories
Compartment door-mounted rotary handle operating mechanism for fixed or plug-in circuit-breakers
Fixed depth

Adjustable depth (max 300 mm)


23 max

119.5
18
20 (*)

68

Shaft lenght= A+B-137.5


B = 18 (20*)

45

45

X
=

47

137.5

51.5
49.5 (*)

68

23 max

A =168 min. 300 max (298*)

47

7
5

2.5

2.5

2
1

(*) If protection class IP54 required

(*) If protection class IP54 required A = 298


B = 20

Adjustable depth (max 621,5 mm)

C = 340 min. 621.5 max (619.5*)

23 max
47

137.5
68

Shaft lenght= C+B-137.5

65

X
=

B = 18 (20*)

6.8

45
=

42

2.5

45

2.5

(*) If protection class IP54 required C max = 619.5


B = 20

GSIS0006

R min. 200

2
1

6.8
X
33

53
Y

Note
See the various different versions for the circuitbreaker mounting holes
6/6

Key
X

Padlock device for open position (max 3 padlocks with 6 to be


provided by customer)

Transmission assembly

Rotary handle assembly

Minimum radius of rotation for fulcrum of compartment door

Circuit-breaker operating lever

Drilling of compartment door

Joint

Shaft

Support
ABB SACE

Overall dimensions
SACE S3-S4-S5-S3X-S4X
Fixed circuit-breaker

Mounting on sheet metal

Mounting on DIN EN
50023 channel

Terminal covers
(to order when not included in supply)

Y
117

(4 POL)

(3 POL)

3
25

135
101.5

108

46

4.5

2.5

D
10.25

=
o

X
C

161

105

22.5

X1

off

45
O

off

Low

off

High

4
E

103.5
107

105

57 (S5 630)
53.8 (S5 400)

Terminals
Front for flat bars
10 (S3-S3X)
15 (S4-S5)

3 (*)

31.8

Front for cables


L

31.2

15.5 (S5 400)


20 (S5 630)

21

M8 (S3/S3X-S4/S4X)
M10 (S5)

(**)

(**) high terminal covers


included in the supply
I

I
20

1 x 240 mm2 (S5 400)

(*) 3 mm = minimum admissible


thickness for S5 400

For SACE S3 - S4
S5 400 - S3X - S4X only

GSIS0007

2 x 120 mm2

For SACE S5 400 - S5 630 only

Key

S3

105

140

S4

105

140

S5 400

140

S5 630

140

S3X
S4X
ABB SACE

170

87.25

35

143

10

254

125.25

35

218

11

183.75

254

125.25

43.75

10

218

12

183.75

254

125.25

43.75

10

218

12

100

140

255

175.25

35

228

10

105

140

359

210.25

35

307.5

11

73.75

18x18

24

17.5

107.25 18x18

24

17.5

107.25 24x24

31

19.5

107.25

31

19.5

158.75 18x18

24

17.5

196.75 18x18

24

17.5

Flange for compartment door

Bracket for mounting on DIN EN 50023


channel

45 mm front flange

Tightening torque 2 Nm

6/7

Overall dimensions
SACE S3-S4-S5-S3X-S4X
Fixed circuit-breaker
Terminals
For rear Cu/Al cables

Extended front
25

13.5 (S3/S3X-S4/S4X)
16.5 (S5)

(**)
L

(***)

6
12.5

P
46

33.5

N
D

I
o

O
(**) high terminal covers included in supply

off

(***) Separator plates between the phases to order

Extended front spreaded


A1
C1
F1

G1

B1
C1

D1

E1

F1

G1

H1

101

D1

D1

I1

E1

H1

2.5

L1

60

2.5

I
O

off

3 POL

off

4 POL

Threaded rear
View A

25

(**)

S
U

GSIS0008

X
T

(**) low terminal covers included in supply

A1

B1

C1

D1

E1

F1

G1

H1

I1

L1

S3

87.25

73.75

16

20

8.5

100

81.5

36.5

55

100

M 12

130

165

50

45

30

155

...

8.5

12.5

45

S4

125.25 107.25

16

20

8.5

100

81.5

36.5

55

100

M 12

130

165

50

45

30

155

...

8.5

12.5

45

S5 400

125.25 107.25

21

25

11

100

86.5

39.5

62

108

M 16

...

...

...

...

...

...

...

...

...

...

S5 630

125.25 107.25

106

41

70

135

M 24

158

202

59

54

40

...

11

15

49

S3X

175.25 158.75

16

20

8.5

100

81.5

36.5

55

100

M 12

130

165

50

45

30

155

...

8.5

12.5

45

S4X

210.25 196.75

16

20

8.5

100

81.5

36.5

55

100

M 12

130

165

50

45

30

155

...

8.5

12.5

45

6/8

189

max

ABB SACE

Mounting parts for fixed circuit-breaker


Template for drilling sheet metal support
(minimum thickness of sheet metal: 3 mm)
For terminals:
Front for flat bars
Extended front
Front for cables

For terminals for rear


Cu/Al cables

For threaded rear terminals

Y
Y
A

(3 POL)

(4 POL)

(3 POL)

(4 POL)

M5/5.5

D
C

X
E

A
M5/5.5

M5/5.5

(3 POL)

(3 POL)

(4 POL)

For threaded rear


terminals
Y

Template for drilling compartment door


and fitting flange

Y
43.75 43.75 43.75

32

For SACE S3 - S4 - S5 400 -S3X - S4X only

43.75 43.75

(4 POL)

32

(thickness of sheet metal: 2 mm)


M5/5.5

Y
112
=
=

105.25

107.25

105.25

=
80

87.5
=

218 X

X 214

112 142

214

43.75

22
8

8
7

GSIS0009

Y
M5/5.5

(3 POL)

(4 POL)

For SACE S5 630 only

S3

35

70

S4

35

70

S5

43.75

S3X

35

S4X

35

70

ABB SACE

139

71.75

214

105.25

87.5

214

70

224

17.5

94.75

185

R15

17.5

128.25

260

R15

105

73.75

24

143

105

107.25

24

218

105.25

22

134.25

272

R20

156.75

17.5

179.75

270

R15

131.25 107.25
105

158.5

30

218

24

228

303.5 194.75

17.5

218

350

R15

105

196.75

24

307.5

6/9

Overall dimensions
SACE S3-S4-S5-S3X-S4X
Plug-in circuit-breaker - withdrawable circuit-breaker
Plug-in SACE S3-S4-S5 400-S3X-S4X

Witdrawable SACE S3-S4-S5 400-S3X-S4X

Y
27.5

117
B
A

(3 POL)

=
I

o
off

(3 POL)

(4 POL)

1
3

X C

(4 POL)

isolating travel

161

105

X 105

G
5.5

161

1.75

5
E

153

105
H
96

Witdrawable SACE S5 630

Fixed part

Moving part complete with IP20 protection class terminal


covers

27.5 isolating travel

(4 POL)

(3 POL)

Flange for compartment door (included in supply)

3
133.25

Lock for compartment door (to order)

Tightening torque 1,1 Nm (S3-S4-S3X-S4X) - 2 Nm (S5)

X 105

The withdrawable circuit-breaker must be completed with


one of the following accessories:
front flange for operating lever mechanism
rotary handle operating mechanism
motor operator

161 G 270

5.5 1.75

Note

E
F

74

Key

195.5

184.5

105

167
190

156.5
F

167
190

E
F
H
96

195.5
78,5

Terminals
Front for flat bars (up to 400 A and S5 630-400A)
I

Front for cables (up to 400 A)

17,5
(S3X-S4X)

Threaded rear

P
L
L
N

Front spreaded for SACE S5 630


158

View A
U

Vertical flat bar rear terminals for SACE S5 630

31 (S3-S4-S3X-S4X)
34 (S5 400)
54,5 (S5 630)

201,7

5,5

184
15 11

59

59.5

54

35

59,5

5,5

83 (S3-S4-S3X-S4X)
84 (S5 400)
118 (S5 630)

108

43.75
40

40

GSIS0010

11

S3

105

140

175

89.75

35

52.5

143

84

10

33.5

8.2

20

37.5

79.5

36

18x18

73.75

48

M12

100

S4

105

140

259

127.75

35

52.5

218

84

10

33.5

8.2

20

37.5

79.5

36

18x18 107.25

48

M12

100

S5 400

140

183.75

259

127.75 43.75

70

218

101.5

14

43.5

10.2

25

47.5

91.5

37

24x24 107.25

58

M16

108

S5 630

140

183.75

259

127.75 43.75

70

218

101.5

14

49

10.2

25

55.75

91.5

37

24x24 109.25

80

M24x2

143

S3X

105

140

260

174.5

35

52.5

143

84

10

33.5

8.2

20

73.75

48

M12

100

S4X

105

140

344

212.75

35

52.5

218

84

10

33.5

8.2

20

107.25

48

M12

100

6/10

ABB SACE

Mounting parts for plug-in circuit-breaker - withdrawable circuit-breaker


Template for drilling sheet metal support
(minimum thickness of sheet metal: 3 mm)

SACE S3-S4-S5 400-S3X-S4X

SACE S5 630

For terminals
Threaded rear

For terminals:
Front for flat bars
Front for cables

Y
(3 POL)

(4 POL)

(3 POL)
115 (3 POL)
160 (4 POL)

(4 POL)

For terminals:
Front
Front for Cu cables
Front spreaded

For terminals:
Vertical flat bar rear terminals
Threaded rear

115 (3 POL)
160 (4 POL)

52

6 (M5)

65

6 (M5)

G
D

83.25

65.75

83.25

65.75

135

135
86.75

57.5

57.5

86.75

52

72

R4

65

(3 POL)

(4 POL)

132,5 (3 POL)
177,5 (4 POL)

144 (3 POL)
188 (4 POL)

Template for drilling compartment door and fitting flange


(thickness of sheet metal: 2 mm)
4
80

112

135

80

63

45

72.5

112 142

94

126

27.5

16

142 X
=

81
125
R min. 200

For plug in circuit-breaker

S3 - S3X

Nr. 3 8

For withdrawable circuit-breaker

70

105

100

52.25

25

M4-5 73.75

143

35

70

105

R14

S4 - S4X

82

117

135

65.75

41

M4-5 107.25

218

35

70

105

R14

S5

115

160

135

65.75

58

M5-6 107.25

218

43.75

87.5

131.25

R18

ABB SACE

GSIS0011

6/11

Overall dimensions
SACE S3-S4-S5-S3X-S4X
SACE S3 circuit-braker with SACE RC211/3 - RC212/3 residual current release
Vertical installation

(mounting on sheet metal)

(*) Without terminal covers


(**) with low terminal covers
(***) with high terminal covers

Front terminals for cables

Rear terminals

(terminal covers to order)

(low terminal covers included in supply)

1.52

109

153
140

109

25

1.52
81,5

36,5

97.5

X1

45

=
=

45

X1

310 397
(**) (***)

305
(*) 90.5

X2

X1

96

X1
305

X1

X1

279

280

35

12

35

310

35

=
=

X2

96

X2

X2

X2

X2
55
100

52.5

50

Version with extended front


terminals

Terminals for rear Cu/Al cables


(high terminal covers included in supply)

Y
153
140
35 35 35

1.52

109

31

45

=
=

X1

96

X1

X2

45

=
=

8.5

X1
346 305

90.5

X2

96

Key

X1

X2

Tightening torque 2 Nm

Flange for compartment door

397

X2

X2

Note
See the various different versions
for the dimensions of the terminals

6
3

X1
305 279

279

X2

1.52

97.5

X1

109

12.5

45

Template for drilling sheet metal support

Template for drilling compartment door


and fitting flange

(minimum thickness of sheet metal: 3 mm)

(thickness of sheet metal: 1.5 - 2 mm)


Y
70
0.1

Y
17.5

145.5
0.1

R1

55.25
4

105.5
82

84

X1

X1
321

274
0.15

279

Holes for threaded Holes for rear


rear terminals only terminals for
cables only

X1

64
0.1 53

X1
135.5

5.5 - M5
64
0.1 53

X2

56.5

35 35 35
148

6/12

GSIS0012

X2
24

ABB SACE

SACE S3 circuit-braker with SACE RC211/3 - RC212/3 residual current release

Horizontal installation
140

140
25

Y
35

35

35

2
97.5
=

SACE S3

off

X1
TEST

=
45
=

X1
=

50

3.5

108

X1

GSIS0013

170

X1

Key
1

Front terminals for cables

Bracket for mounting on DIN EN 50023


channel

ABB SACE

6/13

Overall dimensions
SACE S3-S4-S5-S3X-S4X
Accessories
Motor operator for fixed circuit-breaker
Key

Y
(4 POL)

A
2

220

(3 POL)

=
C

=
=

112
80

Drilling of compartment door

S3-S4
S3X-S4X

Y
=

117

Dimensions with connectors

See the various different versions for


the circuit-breaker mounting holes

112 142 X

225.5

Note

161

105

Flange for compartment door


(included in supply)

1
Y

S5

140

105

58

183.75

140

75.5

Key

Motor operator for plug in circuit-breakers


Y

269.5

=
C

(3 POL)

112

=
=

=
80

105

Dimensions with connectors

Drilling of compartment door

See the various different versions for


the circuit-breaker mounting holes

112 142

161

Note

2
=

Flange for compartment door


(included in supply)

(4 POL)

isolating travel

27.5

140

105

58

183.75

140

75.5

S3-S4
S3X-S4X
7
=

S5

=
117

Key

Motor operator for withdrawable circuit-breaker


Y
78.5
2

A
269.5

(4 POL)
B

6
=

63

5.5

126
16

2
167

Nr. 3 8

94

161

X 105

Drilling of compartment door

See the various different versions for


the circuit-breaker mounting holes

135
7

1.75

Note

Flange for compartment


door (included in supply)

(3 POL)

7
81
125
R min. 200

=
27.25

142 X
=

GSIS0014

isolating travel

27.5

1
96

S3-S4
S3X-S4X
S5

6/14

140

105

58

183.75

140

101.5

ABB SACE

Accessories
Interlock across two horizontally-installed circuit-breakers
Y
=
B

B B

Key

Y
=

A
C
= =

B B

M
P

=
E

F
G

I
O

(S5)

1 (S3-S4)

Template for drilling


mounting holes in sheet
metal

Drilling template for all


versions with rear terminals

Dimensions with four-pole


withdrawable version
mounted on right

Tightening torque 3,7 Nm

Interlock device

105

1
N

65
103.5

Y
275

Note
See the various different versions
for the dimensions of the circuitbreakers

Y
27.5

S3

350

35

66

265

134.5

87.2

170

12

227.5

116

324

155

R15

16

68

75

S4

350

35

66

350

173.5

125.3

254

12

315

156

324

155

R15

16

143

75

S5

500

43.75

119

350

173.3

125.3

254

16

315

156

472

202

R15

48

114

117

S3X

350

35

66

265

135

172

255

12

227.5

116

324

155

R15

16

68*, 153**

75

S4X

350

35

66

350

173.3

210

339

12

315

156

324

155

R15

16

143*, 232.5**

75

* Per interruttore estraibile


con terminals posteriori
** Per interruttore fisso con
terminals posteriori (uscita posteriore)

Interlock across two vertically-installed circuit-breakers (S3-S4-S5)


Y
103.5

Key

Y
=

65
=

H
N

Interlock device

Drilling template for


mounting circuit-breakers on
sheet metal

Drilling template for all


versions with rear terminals

Dimensions with four-pole


withdrawable version

Tightening torque 3,7 Nm

F
=
105
=

=
G

N
M

11.5
27.5

isolating travel

Note

B B B

275

Nr. 8 7

GSIS0015

105

See the various different versions


for the dimensions of the circuitbreakers

S3

180

35

152.5

157.5

578

87.5

170

157.5

350

155

75

68

92

14

77.5

R15

S4

180

35

198.5

195.5

750

125.3

254

157.5

490

155

75

143

101

23.5

77.5

R15

S5

220

43.75

198.5

195.5

750

125.3

254

201

490

202

107

114

66

98.5

R15

ABB SACE

6/15

Overall dimensions
SACE S3-S4-S5-S3X-S4X
Accessories
Rotary handle operating mechanism on fixed or plug in circuit-breaker
Key

Y
=

105

80

Rotary handle operating


mechanism

Lock for compartment door


(to order)

Drilling of compartment door

Dimensions for connector


for early contact for
undervoltage release

Flange for compartment


door (included in supply)

45
==
=

X 105

161

117

80
= =
112
= =

3
R min 200

72.5

= =
142 112
= =

Note
See the various different versions
for the circuit-breaker mounting
holes

S3-S4
S3X-S4X

III

58

S3-S4
S3X-S4X

IV

93

S5

III

75.5

S5

IV

119.25

Compartment door-mounted rotary handle operating mechanism with adjustable depth for fixed or
plug in circuit-breaker
7
9

105

1
2
11.5

105

90

52.5

4
R min 200

Y
5

11.5

=
33

Key

See the various different versions for


the circuit-breaker mounting holes

27
R min 200

Note

46

5
54

6/16

59

46.5
26

10

GSIS0016

26

Transmission assembly

Rotary handle assembly with


door lock device

Padlock device for open


position (maximum 3
padlocks with max 6mm to
be provided by customer)

Minimum radius of rotation


for fulcrum of door

Drilling of door

6 Support for depths of up to


500 mm
7 66 ... 300 mm
(with IP54 protection min. 90)
8 Distance 7 + 2 mm
(shaft length)
9 301...500 mm
(with IP54 protection min.325)
10 Distance 9 + 2 mm
(Shaft length)
ABB SACE

Accessories
Rotary handle operating mechanism on withdrawable circuit-breaker
Key

Y
2

170
105

38.5 22

80

Rotary handle
operating mechanism

Lock for compartment


door (to order)

Y
135
63
45

X 105

72.5 =
126
X
=

161

Nr. 5 7
27.25 =
142 X
=

94
16

R min. 200

Padlock device for


open position
(maximum 3 padlocks
max. 6 mm to be
provided by user)

Note
See the various different
versions for the circuitbreaker mounting holes

Y
35

81
125

3
1

35

37
42.5

Front flange for operating lever mechanism


Y
105

37

Key

80

Y
45
==

Front flange for lever


operating mechanism

Lock for compartment


door (to order)

Drilling of compartment
door

Flange for
compartment door
(included in supply)

161 X

X 105

72.5

=
112

142

=
7

80
= =
112
= =

117

Note
See the various different
versions for the circuitbreaker mounting holes

42.5

External neutral for SACE S4-S5 circuit-breakers


76.5

50
25

36.25

=
=
In

120

66 40

6 Line

100
160
200
250

Load

95

320
400

=
=

ABB SACE

X3

GSIS0017

11

1 4 5 6

6/17

Overall dimensions
SACE S6 - S6X
Fixed circuit-breaker (S6)

Terminal covers
104.75

107

(4 POL)

279.5
210
140 =

(3 POL)

(to order when not included in the supply)

12

low

101.5

125.25

high

111.75

47

=
161

X 268

241

105

2.5

16.5

152

14

Key

9
103.5

Mounting on sheet metal

159

Flange for compartment door


(included in supply)

Tightening torque 2 Nm

Terminals
Front extended
70

70

Front
70

40

41.5
5

11

40
15

23 5 min.

22.5 0.1
6.5

48.5

62

47
12

S6 630

S6 630 - S6 800
Threaded rear

41.5
14

50

53.5

8
67

20

47

(low terminal covers included in supply)


70

70

70

73
44

2.5

M24x2

S6 800

S6 630 - S6 800

Y
45

116
90

116

116

22.5
23

22.5

45
13

49.5

Front for Cu/Al cables

For rear Cu/Al cables

(IP20 high terminal covers included in


the supply for S6 800)

(IP20 high terminal covers included in


the supply)

21.5
47
32

8 20

21
19.5

12

116.5

S6 630

S6 630
59

S6 630 - S6 800

20
42
25

17.5
16.75

12

S6 800
S6 800

6/18

GSIS0018

Front extended spreaded

ABB SACE

Fixed circuit-breaker (S6X)

Terminal covers

(to order when not included in the supply)

105

1
=

280
210
140

(4 POL)

107
-3

(3 POL)
=

101.5

2
12

249.75

low

263.25

high

47

=
161

X 406

379

105

2.5

16.5

Key
14
=

103.5
115

152

Mounting on sheet
metal

159

Flange for compartment door (included in


supply)

Tightening torque 2 Nm

Terminals
Extended front
70

70

Front for Cu/Al cables


70

40

21.5
47
32

41.5

48.5

15

11
62

47

For rear Cu/Al cables

Front

(IP54 high terminal covers included in the supply)

40
23 5 min.

22.5 0.1
6.5
21
19.5

12
12

14

Threaded rear

(low terminal covers included in supply)

70

70

2.5

73
44

M24x2
23

ABB SACE

GSIS0019

70

6/19

Overall dimensions
SACE S6 - S6X
Mounting parts for fixed circuit-breaker
(S6)
Template for drilling sheet metal support
(minimum thickness of sheet metal: 3 mm)

For terminals:
Front for flat bars
Front extended
Front for cables

For terminals for rear Cu/Al cables

SACE S6 630

SACE S6 800

Y
Y

70

70

140

140

(3 POL)

70

(3 POL)
(4 POL)

237

(4 POL)

35

141.75

109.75

(3 POL)

140

35

(4 POL)

109.75

237

141.75

109.75
301

237

M5/5.5
M5/5.5

M5/5.5

R18

R21.5

84

35

168

238

301

85.75
(3 POL)
(4 POL)

171.5

(3 POL)

241.5

(4 POL)

Template for drilling


compartment door and
fitting flange
For terminals threaded rear

(thickness of sheet metal: 2 mm)


Y

=
70

109.75

237

111.75

70
70

70

241

109.75

147

70

105

70

35

=
115

111.75

237

241

M5/5.5

35

M5/5.5

6/20

35
7

112 142

GSIS0021

3 POL

4 POL

ABB SACE

Mounting parts for fixed circuit-breaker (S6X)


Template for drilling sheet metal support
(minimum thickness of sheet metal: 3 mm)

For terminals:
Front for flat bars
Front extended
Front for cables

For terminals for rear Cu/Al cables

Y
Y

70

70

140

140

(3 POL)

(3 POL)
(4 POL)

35

(4 POL)

247.75

279.75

247.75

109.75

109.75

375

439

375

M5/5.5

M5/5.5

R18

84

35

168

238

(3 POL)
(4 POL)

Template for drilling


compartment door and
fitting flange

For terminals threaded rear


3 POL

(thickness of sheet metal: 2 mm)

4 POL

70

70

70

Y
105

35

147
=

249.75

247.75

249.75

109.75 379

70

247.75

375

109.75

379

375

=
115

112 142

=
70

70

M5/5.5

35

M5/5.5

35

=
GSIS0020

Y
Y

ABB SACE

6/21

Overall dimensions
SACE S6 - S6X
Withdrawable circuit-breaker

Key

Y
27.5 isolating travel

(4 POL)

280

210

70

70

(3 POL)
70

133
89.5

=
140

Fixed part

Moving part

Flange for compartment


door (included in supply)

Lock for compartment door


(to order)

Tightening torque 9 Nm

58

5.5

14.5

208

145

196 X
A

295

5
152

A
167
2

96

190

131
136.5

123.5

195.5

S6

273

S6X

411

193.5

Terminals
Front for SACE S6 630, S6 800
31

70

14

10

70

70
40

20

158

Horizontal or vertical rear flat bar for SACE S6 630, S6 800


3

80.5
20

14
40

10

6/22

GSIS0022

ABB SACE

Mounting parts for withdrawable circuit-breaker


Template for drilling sheet metal support
(minimum thickness of sheet metal: 3 mm)
Y
140

(3 POL)

210

(4 POL
70

(4 POL)

77.5
R2
57.5

45.5

120

8.5 (M8)

86.5

77.5

107

(4 POL)

214

(3 POL)

284

(4 POL)

Template for drilling compartment door and fitting flange


(thickness of sheet metal: 2 mm)

4
80

Y
170
80.5
45
==

Nr. 5 8

90

9
161
39

19.75
16
101
162.5
121
R min 200

ABB SACE

=
177

GSIS0023

6/23

Overall dimensions
SACE S6 - S6X
Accessories
Interlock across two horizontally-installed circuit-breakers

Y
=
=

70

70

Key
=

650
70

120

70

70

Y
70

=
46

284

273

375

350

101 =

2
30

13.5

101

331

Drilling template for all


versions with rear terminals

Dimensions with
withdrawable version
mounted on right

Tightening torque 9 Nm

4
2

65

Note
See the various different
versions for the dimensions of
the circuit-breakers

103.5
288

isolating travel

Drilling template for


mounting circuit-breaker on
sheet metal

525

10.5

Interlock device

27.5

A mm

S6

129 (fixed, withdrawable)

S6X

267 (fixed)
129 (withdrawable)

Interlock across two vertically-installed circuit-breakers (for S6 only)


Y
51.5 70

70

Key

70 48.5

293
=

R
20

26

273

280

109

=
9

129 =

6/24

4
65

288

27.5

isolating travel

Tightening torque 9 Nm

GSIS0024

310

Note
See the various different versions
for the dimensions of the circuitbreakers

3
Y

Dimensions with
withdrawable version
mounted underneath

109

26

2
17

109

273

Drilling template for all


versions with rear terminals

109
101 779

525

175

820

Drilling template for


mounting circuit-breaker on
sheet metal

3
129 =

Interlock device

ABB SACE

Accessories
Motor operator for fixed circuit-breaker

222.5

198.5

23.5

91.5

Y
81.250.1

81.250.1
19.75

8 (7 fori)

192.25
338

125.25

270

304

319

R8

72.25

22.75

111.75
174
1220.1
R. min.200

67
140 =
215.5
285.5

X
159.5

102.25 94.75

96.5

Key

Note
See the various different
versions for the circuit-breaker
mounting holes

Flange for compartment


door (included in supply)

Template for drilling


compartment door

Dimensions with connectors

Motor operator for withdrawable circuit-breakers


Y
27.5

222.5

isolating travel

91.5

Y
81.250.1

81.250.1
19.75

8 (7 fori)

186.5
338

270

304

X
A

319
72.25

159.5
22.75

117.5
174
1220.1
R. min.200
23.5
2

247.5

140

Y
GSIS0025

Key

S6
S6X
ABB SACE

108

100.5

102.25 94.75

Note
See the various different
versions for the circuit-breaker
mounting holes

Flange for compartment door


(included in supply)

Template for drilling


compartment door
6/25

Overall dimensions
SACE S6 - S6X
Accessories
Rotary handle operating mechanism on fixed circuit-breaker
Key

Y
2

104.75
152
140

103.5

44.5 22

37

45

Lock for compartment door


(to order)

Drilling of compartment door

Flange for compartment


door (included in supply)

Tightening torque 2 Nm

2.75
= =
177 147
= =

196

140

Rotary handle operating


mechanism on circuitbreaker

80

=
=

=
=

90

=
=

115
147

R min 200

42.5

Drilling only required for version with rear terminals

3 POL

Y
70

4 POL
106 (S6)
244 (S6X)

70
237 (S6)
375 (S6X) 104

70

133

241 (S6)
379 (S6X)

70

237 (S6)
375 (S6X) 104
133

8
M5/5.5

70

105

Note
See the various different versions
for the circuit-breaker mounting
holes

70

106 (S6)
244 (S6X)

35

241 (S6)
379 (S6X)

M5/5.5

35

=
=

35

Compartment door-mounted rotary handle mechanism with adjustable depth for fixed circuit-breaker
Y
105
41.5

Key

22

63

103.5

31

23

Y
41.5
5

19

Transmission assembly

Rotary handle assembly


with door lock device

Padlock device (maximum 3


padlocks max 6 mm to be
provided by customer only
for circuit-breaker open
position)

Minimum radius of rotation


for fulcrum of door

=
46
28

28

105

33

36

3
2

27

54
R min 200

168

Drilling template for


mounting circuit-breaker on
sheet metal

R min 200

Drilling only required for version with rear terminals

106 (S6)
244 (S6X)

70
237 (S6)
375 (S6X) 104

70

133

241 (S6)
379 (S6X)

70

M5/5.5

35

237 (S6)
375 (S6X) 104
133

6/26

70

4 POL

70

72...506 mm (with IP54


protection min. 96)

Distance 6 -4 mm
(shaft length)

105

70

35

106 (S6)
244 (S6X)
241 (S6)
379 (S6X)

M5/5.5

35

X
GSIS0026

3 POL

6
Y

Note
See the various different versions
for the circuit-breaker mounting
holes
ABB SACE

Accessories
Rotary handle operating mechanism on withdrawable circuit-breaker
Key
Y

80

210

2 44.5

22

Rotary handle on
circuit-breaker

Lock for compartment


door (to order)

Y
170
80.5
45
==

Nr. 5 8

196

3
90

177

161

39

3
151

16
19.75
101
162.5
121
R min 200

1
37
222.5
91.5
123.5

Note
See the various different versions
for the circuit-breaker mounting
holes

42.5

Padlock device for


open position
(maximum 3 padlocks
max. 6 mm to be
provided by user)

131
136.5

Front flange for operating lever mechanism


Y
104.75
152
140

103.5

37

Key

80

Front flange for operating


lever mechanism

Lock for compartment door


(to order)

Drilling of compartment door

Flange for compartment


door (included in supply)

Tightening torque 2 Nm

Y
45
=
=

=
=
177 147
=
=

196

140
=
=

2.75

=
=

115
147

42.5

3 POL

Note
See the various different versions
for the circuit-breaker mounting
holes

Drilling only required for


version with rear terminals
106 (S6)
244 (S6X)

237 (S6)
375 (S6X) 104
70

133
8

External neutral

241 (S6)
379 (S6X)

70

115

75

70

40

52.5

10

25

35

M5/5.5

4 POL

90

Y
70

70

70

=
5

Line
In

115

100 A
160 A

185 77 49

200 A
250 A

106 (S6)
244 (S6X)
237 (S6)
375 (S6X)

104

105

35

320 A
400 A

Load

241 (S6)
379 (S6X)

X
5

25

=
M5/5.5

35

ABB SACE

11

GSIS0027

133

6/27

Overall dimensions
SACE S7
Fixed circuit-breaker
Y
210
152

=
70

70

Terminal covers

(4 POL)
(3 POL)

280
=

low

70

7
7
30.5

37

217

177
=

406

161

105

326

37

Key

7
140

Terminals

138.5
140.5
146.5
214.5

Front

Flange for compartment door


(included in supply)

Tightening torque 2 Nm

Front extended

Y
10 10 10
33.5

140
50
22

70

70

39 15

70

22

50

11

11

22
107
71

22

22

Front for Cu/Al cables for S7 1250

Y
70

70

21.4

97
78
57
38

70

Horizontal or vertical flat bar rear terminals

30.5

37

Y
70

70

85

70

16

A
171.5

Front extended spreaded


Y
45

116
90

315

116

116

22.5

22.5

23

45

X
50

15

13

B
107

50

22
GSIS0028

11
14

22

A = horizontal installation
B = vertical installation
6/28

ABB SACE

Mounting parts for fixed circuit-breaker


Template for drilling sheet metal support
(Minimum thickness of sheet metal:3 mm)

For terminals:
Front
Front extended
Front for Cu/Al cables

For flat bar rear terminals

Y
70

3 POL

4 POL

(3 POL)

140

(4 POL)

220
203

378

3.6 H12

290

50 80
203

3.6 H12

378

171.5

315
R40

70
= =
70

70

50 80
203
378

171.5

140

315
R40

70

70

70

M5/5.5
35
5.5 - M5
35

5.5 - M5

Template for drilling compartment door


and fitting flange
(thickness of sheet metal: 2 mm)
Y
147
=

=
115

112 142

GSIS0029

ABB SACE

6/29

Overall dimensions
SACE S7
Withdrawable circuit-breaker

Key

Y
241.5

280
210
140

(4 POL)
(3 POL)

Fixed part

Moving part

Flange for compartment


door (included in supply)

Lock for compartment door


(to order)

Tightening torque 9 Nm

4
211.25
143.25
=

160
max

8.25

140

270

196

406

5
96

131

123.5

136.5

5.5
218.5
247

193.5

27.5 isolating travel

Terminals
Front

Y
31

70

16

70

70
50
22

11

14

67
22

Horizontal or vertical flat bar rear terminals


108
3

11
22 50

143.25
22

14

70

6/30

70

70

GSIS0030

16

ABB SACE

Mounting parts for withdrawable circuit-breaker


Template for drilling sheet metal support or channel
(Minimum thickness of sheet metal: 3 mm)
Y
140

(3 POL)

210

(4 POL)
70

120.5

92.5

68.25

120

8.5 (M8)
76

120.5

107
214

(3 POL)

284

(4 POL)

Template for drilling compartment door and fitting flange


(thickness of sheet metal: 2 mm)

4
80

Y
170
7

80.5
45
==

Nr. 5 8

90

9
161

=
177

39

7
19.75

16

101

121
R min 200

ABB SACE

GSIS0031

162.5

6/31

Overall dimensions
SACE S7
Accessories
Interlock across two horizontally-installed circuit-breakers
Y

Key

660
=

70

70

70

120

70

70

70

30

300

300

406 450
=

420

117 407

115

40

5.5

Drilling template for


mounting circuit-breaker on
sheet metal

Drilling template for all


versions with rear terminals

Dimensions with
withdrawable version
mounted on right

Tightening torque 9 Nm

6.5

Interlock device

115 =

20

6.5

550

40

65

140.5
336

isolating travel

Note
See the various different versions
for the dimensions of the circuitbreakers

27.5

Interlock across two vertically-installed circuit-breakers

Key

Interlock device

Drilling template for


mounting circuit-breaker on
sheet metal

Drilling template for all


versions with rear terminals

Tightening torque 9 Nm

315
=

406

115

=
=
7

290

875

166

1100
=

408
R30

994

=
=

406
=

70

70

70

6/32

=
65

340

336

27.5

isolating travel

GSIS0032

Note
See the various different versions
for the dimensions of the circuitbreakers
ABB SACE

Accessories
Motor operator for fixed circuit-breaker
Y
222.5
91.5
140
=
=

Y
23.5

231.5

81.250.1

81.250.1
19.75

7
Nr. 7 8

217

195.75
338

304

319

R8

270

72.25

159.5
98.75

108.25

91.25
22.75
174
1220.1
R. min.200

91

215.5

285.5

Key
Y

Note
See the various different
versions for the circuit-breaker
mounting holes

Flange for compartment


door (included in supply)

Template for drilling


compartment door

Dimensions with connectors

Motor operator for withdrawable circuit-breaker


Y

27.5 isolating travel

222.5
91.5
140
=
=

81.250.1

81.250.1
19.75

Nr. 7 8

211.25

190
338

304

R8

319
72.25
159.5

104.5
114

22.75
174
1220.1
R. min.200

23.5
2

97

295.5

GSIS0033

270

Key
Note
See the various different
versions for the circuit-breaker
mounting holes
ABB SACE

Flange for compartment door


(included in supply)

Template for drilling


compartment door
6/33

Overall dimensions
SACE S7
Accessories
Rotary handle operating mechanism on fixed circuit-breaker
Y

140

44.5

105

140.5

22

Key

37

1
80

45

211.25

=
X

406

196 140

2.75

90

177147
= =

=
=

115
147

4 POL

378

315

70

50

378

70

Drilling template for


mounting circuit-breaker on
sheet metal

Flange for compartment


door (included in supply)

Tightening torque 2 Nm

197.25 165.75

70

Drilling of compartment door

50
197.25 165.75

Drilling only required for version with rear terminals


Y

Lock for compartment door


(to order)

=
R min 200

42.5

3 POL

152

Rotary handle operating


mechanism on circuitbreaker

Note
See the various different versions
for the dimensions of the circuitbreakers

35

315

70

70
140

70

5.5- M5

5.5- M5

R 40

R 40

Compartment door-mounted rotary handle operating mechanism for fixed circuit-breaker


Y

105

Key

105
41.5

63

31

22

19

41.5
5
=

Rotary handle assembly


with door lock device

46

28

406

105 28
36

Transmission assembly

23

211.25

1
Y

33

90

3
27

Minimum radius of rotation


for fulcrum of door

Template for drilling


compartment door

Drilling template for


mounting circuit-breaker on
sheet metal

72 ... 506 mm (with IP54


protection min. 96)

Distance
lenght)

54
R min 200

8
205

4
R min 200

Drilling only required for version with rear terminals


Y

4 POL

50
197.25 165.75

378

315

70
70

378

70
5.5- M5

R 40
220

6/34

50
197.25 165.75

3.6 H12

315

35

7 - 4 mm (shaft

X
70

70
140

70
5.5- M5

80
R 40
290

3.6 H12

80
GSIS0034

3 POL

Padlock device (maximum 3


padlocks max 6 mm to be
provided by customer only
for circuit-breaker open
position)

Note
See the various different versions
for the dimensions of the circuitbreakers
ABB SACE

Accessories
Rotary handle operating mechanism on withdrawable circuit-breaker
Y
210

80

2 44.5

Key

22

Rotary handle operating


mechanism on circuitbreaker

Lock for compartment door


(to order)

170
80.5
45
==

211.25

90

196

Nr. 7 7

177

161
39

406
=

16
19.75
101
162.5
121
R min 200

1
222.5
131
136.5

91.5
123.5

X 3

37

Padlock device for open


position (maximum 3
padlocks max. 6 mm to be
provided by user)

Note
See the various different versions
for the circuit-breaker mounting
holes

42,5

Front flange for operating lever mechanism


Y

140

Key

105
=

140.5

37
80

Front flange for lever


operating mechanism

Lock for compartment door


(to order)

Drilling of compartment door

45

211.25
=
=
X

406

196 140

2.75

90

177 147
=

X
=

=
=

115
147

=
=

3 POL

Drilling only required for


version with rear terminals

Y
50
197.25 165.75

378

Flange for compartment


door (included in supply)

Tightening torque 2 Nm

70

Note
See the various different versions
for the circuit-breaker mounting
holes

External neutral

70

315

42.5

152

Drilling template for


mounting circuit-breaker on
sheet metal

70

115

75
40

5.5- M5

52.5

10

=
R 40

25

4 POL

=
5

Line
In

115

100 A

185 77 49

50
197.25 165.75

320 A
400 A

Load

35
70

70
140

70

X
=

25

5.5- M5

315

200 A
250 A

X 378

160 A

ABB SACE

11

GSIS0035

=
R 40

6/35

Overall dimensions
SACE S8
Fixed circuit-breaker
380

242

556

2.5

3
20

20

400
313

X 280

280 400

20
120

15

20
150

120

120

120
236,5

203
406

286,5

530

3 POL

4 POL

Terminals
Front (S8 2000-2500)

Rear (S8 2000-2500)


Y

Y
65

324
80
20

40

15

20

120
115

324
20

80

40

20

20

85

65

80 40
40

= 15
40

40

20

15
150

120

120

150

120

20

120
Y
20

Rear (S8 3200)


100
95
50

324
85

17,5

20

100

40
20
40

20

580

520

25
50
15
65

65

25
18

15
=
150

40

120

80

120

20

Key
1

Flange for compartment door

Circuit-breaker mounting holes

Internal side of compartment door

6/36

GSIS0036

15

20

ABB SACE

Mounting parts for fixed circuit-breaker


Template for drilling sheet metal support

Template for drilling compartment door


and fitting flange

(Minimum thickness of sheet metal: 3mm)

(Minimum thickness of sheet metal: < 2,5mm)

N. 8 9

N. 8 9

3 POL

4 POL

Key
1

Hole for rear terminals only

Minimum radius of rotation of compartment door

Accessories
External neutral

ABB SACE

6/37

Overall dimensions
Distances to be respected
Insulation distances for installation in metal compartment with wall
to chassis ground or wall to chassis ground protected with insulating plate

Wall to chassis ground [mm]

A(*)

(Ub 415V)

(Ub 440V)

S1

25

50

20

20

S2

25

50

20

20

S3

35

100

25

20

S4

35

100

25

20

S5

35

100

25

20

S6

35

100

25

20

S7

50

100

30

20

S8

200

200

30

120

o
off

(*) these distances are valid for operating voltages of > 440 V and for
circuit-breakers with breaking capacity level L.

GSIS0038

C
A

3 POL 3 POL

S2X100

25

20

20

169

135

73

S3X

50

25.5

30

340

161

196

112

S4X

60

25.5

30

430

161

196

112

S6X

60

30.5

30

500

275

345

152

A - B - C = Distances inside compartment walls


D - E - F = Distances outside compartment

Insulation distances for installation in insulated


compartment
Insulated wall [mm]

S1

25

20

S2

25

20

S3

35

20

S4

35

20

S5

35

20

S6

35

10

20

S7

50

10

20

S8

120

15

120

6/38

D
I
O

o
off

GSIS0071

The dimensions shown apply for operating voltages Ub of up


to 690 V.
The dimensions to be respected must be added to the
maximum dimensions of the various different versions of the
circuit-breakers, including the terminals.

ABB SACE

Minimum distance between centres for two horizontally


or vertically-installed circuit-breakers
For horizontal or vertical installation, make sure that the connection busbars or cables dont reduce the air insulation distan ces.

Minimum distance between centres for horizontallyinstalled circuit-breakers


Circuit-breaker

width [mm]

[mm]

3 POL

4 POL

3 POL

4 POL

S1

78

103

78/93(*)

103/118(*)

S2

90

120

90/105 (*)

120/135(*)

S3

105

140

105/119(*)

140

S4

105

140

105/119(*)

140

S5

140

184

140

185

S6

210

280

210

280

S7

210

280

210

280

S8

435

585

435

585

on

on

off

off

l
Y

(*) these are the distances to be respected for circuit-breakers fitted


with a flange for the compartment door or side conductor outlets.

The distances between centres are for the installation of fixed


and plug in circuit-breakers. When installing withdrawable
SACE S3, S4, S5, S6, S7 circuit-breakers you should also take
into account the dimensions of the metal supporting channel
that needs to be fitted between the guides of the fixed parts of
two adjacent circuit-breakers.

Minimum distance between centres for verticallyinstalled circuit-breakers


H [mm]
60

S2

90

S3

140

S4

140

S5

140

S6

180

S7

180

S8

300

ABB SACE

GSIS0040

S1

Connection not insulated

Insulated cable

Cable terminals

6/39

6/40

ABB SACE

Circuit-diagrams

Index
Operating status shown ................................................................................................. 6/42
Duty releases ..................................................................................................................... 6/44
Auxiliary contacts ............................................................................................................. 6/46
Position contacts ............................................................................................................. 6/48
Auxiliary circuits of electronic releases ........................................................................ 6/50
Motor operators ................................................................................................................ 6/53
Graphic symbols for circuit-diagrams (IEC 617 and CEI 3-14 3-26) ..................... 6/54
Key and reference notes ................................................................................................. 6/55

ABB SACE

6/41

Circuit diagrams
Operating status shown

The circuit is shown in the following conditions:


-

fixed, plug in or withdrawable circuit-breaker (depending

motor operator with springs loaded (for S6-S7 circuit-breakers)

on type of circuit-breaker), open and racked in

The circuit-breaker is only fitted with those accessories speci-

circuits de-energised

fied in the ABB SACE confirmation of order. Consult this cata-

releases not tripped

logue for information on how to make out an order.

SACE S1-S2-S3-S5-S6

SACE S3D-S6D-S7D-S8D
Three-pole or four-pole
switch-disconnector

GSIS0046

GSIS0045

Three-pole or four-pole circuit-breaker


with thermomagnetic release

SACE S1-S2-S3
Four-pole fixed circuit-breaker
with vertically-installed residual-current release
SACE RC211 o RC212

Four-pole fixed circuit-breaker with


horizontally-installed residual-current release
SACE RC210, RC211 o RC212

6/42

RC210
RC211
RC212
GSIS0048

RC211
RC212

GSIS0047

ABB SACE

SACE S4-S5-S6-S7
Three-pole or four-pole circuit-breaker
with SACE PR212/P
microprocessor-based release

Three-pole circuit-breaker
with SACE PR212/MP

GSIS0051

microprocessor-based release

GSIS0050

GSIS0049

Three-pole or four-pole circuit-breaker


with SACE PR211/P
microprocessor-based release

SACE S4-S5-S6-S7
Three-pole plug-in or withdrawable
circuit-breaker with current transformer on
neutral conductor outside circuit-breaker

Circuit of current
transformer on neutral
conductor outside circuitbreaker (for withdrawable
circuit-breaker)

External
circuit

Three-pole fixed circuit-breaker


with current transformer on neutral
conductor outside circuit-breaker

If using a fixed circuit-breaker with a current trans-

breaker, you must short-circuit the terminals of the TI/N


transformer when you want to remove the circuit-

Term.X5

breaker.

ABB SACE

6/43

GSIS0053

former on the neutral conductor outside the circuit-

External
circuit

N.B.

Internal
circuit

GSIS0052

Term.X5

Circuit diagrams
Duty releases
SACE S1-S2
Opening
solenoid of
SACE RC211
residualcurrent
release

Opening solenoid
of SACE RC212
residual-current
release

Instantaneous
undervoltage
release

Opening
release

Opening
solenoid of
SACE RC211
residualcurrent
release

Opening solenoid
of SACE RC212
residual-current
release

Instantaneous Version of instantaneous


undervoltage undervoltage release for
machine tools
release

External
circuit

Opening
release

Internal
circuit

Conn. X1

GSIS0054

External
circuit

Conn. X1

SACE S3

External
circuit

Undervoltage release with


electronic time-lag device
outside the circuit-breaker

Term. XV

Internal
circuit

6/44

GSIS0055

External
circuit

Term. XV

ABB SACE

Incompatibility

SACE S4-S5

The circuits indicated in the fol-

Opening
release

Instantaneous Version of instantaneous


undervoltage undervoltage release for
release
machine tools

Undervoltage release with


electronic time-lag device
outside the circuit-breaker

lowing figures cannot be powered


simultaneously on the same circuit-breaker
1 - 4 - 5 - 6

2 - 3

Availability
External
circuit

Connectors X1 and X2 are only


supplied to order for circuit-breakers S1 - S2.

Notes
(*A) The undervoltage release is

Conn. X1

powered from upstream of the circuit-breaker or by an independent

Term. XV

power supply: closing of the circuit-breaker is only allowed when


the release is energised (the clos-

Internal
circuit

ing lock is implemented mechanically).

(*B) Contact S4 shown in Fig. 5


opens the circuit when the circuitbreaker is open and closes it again
upon a manual closing command
from the rotary handle, in con-

Term. XV

formity with the Standards governing machine tools (the circuit-

Conn. X1

External
circuit

breaker will not close, however, if


the undervoltage release is not

GSIS0056

powered).

SACE S6-S7
Instantaneous
undervoltage
release

Undervoltage release with


electronic time-lag device
outside the circuit-breaker

External
circuit

Opening
release

Conn. X1
Term. XV

Internal
circuit

Term. XV

ABB SACE

GSIS0057

External
circuit

Conn. X1

6/45

Circuit diagrams
Auxiliary contacts
SACE S1-S2
One change-over contact for electrical signalling
of circuit-breaker open or closed and one changeover contact for electrical signalling of circuitbreaker open due to tripping of thermomagnetic
releases YO, YO1, YU (tripped position)

External
circuit

Two change-over
contacts for electrical
signalling of circuitbreaker open/closed

Internal
circuit

Conn. X2

GSIS0058

External
circuit

Conn. X2

SACE S3-S4-S5-S6-S7
One change-over contact for electrical signalling
of circuit-breaker open or closed and one changeover contact for electrical signalling of circuitbreaker open due to tripping of thermomagnetic
releases YO, YO1, YU (tripped position)

External
circuit

Two change-over
contacts for electrical
signalling of circuitbreaker open/closed

Conn. X2
Term. XV

Internal
circuit

Term. XV

6/46

GSIS0059

External
circuit

Conn. X2

ABB SACE

Incompatibility

SACE S6-S7

The circuits indicated in the fol-

One contact for electrical signalling of circuit-breaker open, one change-over


contact for electrical signalling of circuit-breaker closed and one contact for
electrical signalling of circuit-breaker not open due to tripping of thermomagnetic releases YO1, YO1, YU (not tripped/tripped position) to be used, for
example,
for the enabling shown in Fig.8

lowing figures cannot be powered


simultaneously

on

the

same

circuit-breaker:
11-12-13-14

External
circuit

Availability
Connectors X1 and X2 are only
supplied to order for circuit-breakers S1 - S2.

Notes
Conn. X2

(*C) The electrical signalling contact for the microprocessor-based

Term. XV

overcurrent release, shown in Fig.


41, has the following electrical
characteristics:
rated voltage = 125V AC /

Internal
circuit

30V DC
breaking capacity (resistive
load = 3 W/VA)
maximum interrupted current =
0.5 A

Term. XV

GSIS0080

External
circuit

Conn. X2

SACE S4-S5-S6-S7

External
circuit

Contact for
signalling release
Y01 tripped

Internal
circuit

Term. X6
Term. X5

Term. X5

ABB SACE

GSIS0060

External
circuit

Term. X6

6/47

Circuit diagrams
Position contacts
SACE S2

Second circuitbreaker position


contact, for
electrical signalling
of inserted

Third circuitbreaker position


contact, for
electrical
signalling of
inserted

First circuitbreaker position


contact, for
electrical
signalling of
inserted

Second circuitbreaker position


contact, for
electrical signalling
of inserted

First circuit-breaker
position contact, for
electrical signalling of
racked out or removed

External
circuit

First circuitbreaker position


contact, for
electrical
signalling of
inserted

Internal
circuit

Term. XV

GSIS0061

External
circuit

Term. XV

External
circuit

SACE S3

Term. XV

Internal
circuit

6/48

GSIS0062

External
circuit

Term. XV

ABB SACE

SACE S4-S5

Second circuitbreaker position


contact, for
electrical
signalling of
inserted

Third circuitbreaker position


contact, for
electrical
signalling of
inserted

First circuit-breaker
position contact, for
electrical signalling of
racked out or
removed

Second circuitbreaker position


contact, for electrical
signalling of racked
out or removed

Third circuit-breaker
position contact, for
electrical signalling of
racked out or
removed

External
circuit

First circuitbreaker position


contact, for
electrical
signalling of
inserted

Internal
circuit

Term. XV

GSIS0063

External
circuit

Term. XV

SACE S6-S7

Incompatibility
The circuits

Fifth circuit-breaker position


contact, for electrical signalling of
racked out

Fourth circuit-breaker position


contact, for electrical signalling of
racked out

Third circuit-breaker position


contact, for electrical signalling of
racked out

Second circuit-breaker position


contact, for electrical signalling of
racked out

First circuit-breaker position


contact, for electrical signalling of
racked out

Fifth circuit-breaker position


contact, for electrical signalling of
inserted

Fourth circuit-breaker position


contact, for electrical signalling of
inserted

Third circuit-breaker position


contact, for electrical signalling of
inserted

Second circuit-breaker position


contact, for electrical signalling of
inserted

First circuit-breaker position


contact, for electrical signalling of
inserted

indicated in the
following figures
cannot be powered
simultaneously on
the same circuitbreaker:
20 - 21 - 31
22 - 32

23 - 33

24 - 34

25 - 35

Notes
(*D) The circuitbreaker can be
fitted with position

Term. XV

contacts S75I and


S75S in any
combination up to a
maximum of

Internal
circuit

total of 2 contacts
for S3
total of 3 contacts
for S4, S5
total of 5 contacts

Term. XV

ABB SACE

GSIS0064

for S6, S7

6/49

Circuit diagrams
Auxiliary circuits of SACE PR212/P electronic releases

SACE PR212/P release connected to the dialogue unit SACE PR212/D and actuator unit SACE PR212/T

SACE S4-S5-S6-S7

SACE PR212/P release connected to the dialogue unit SACE PR212/D, signalling unit SACE PR010/K
and actuator unit SACE PR212/T

GSIS0161

SACE S4-S5-S6-S7

GSIS0162

6/50

ABB SACE

Circuit diagrams
Auxiliary circuits of SACE PR212/MP electronic releases
for motor protection
SACE PR212/MP release connected to the dialogue unit SACE PR212/D-L and actuator unit
SACE PR212/T

SACE S4-S5-S6-S7

SACE PR212/MP release connected to the dialogue unit SACE PR212/D-L, actuator unit
SACE PR212/T and contactor operator unit SACE PR212/CI

GSIS0164

SACE S4-S5-S6-S7

GSIS0163

ABB SACE

6/51

Circuit diagrams
Auxiliary circuits of SACE PR212/MP electronic releases
for motor protection
SACE PR212/MP release connected to the signalling unit SACE PR010/K and contactor operator unit
SACE PR212/CI

SACE S4-S5-S6-S7

SACE PR212/MP release connected to the dialogue unit SACE PR212/D-L, actuator unit
SACE PR212/T, signalling unit SACE PR010/K and contactor operator unit SACE PR212/CI

GSIS0165

GSSC0318

SACE S4-S5-S6-S7

6/52

GSIS0166

GSSC0319

ABB SACE

SACE PR212/MP release connected to the dialogue unit SACE PR212/D-L and actuator unit
SACE PR212/T

GSIS0167

SACE S4-S5-S6-S7

ABB SACE

6/53

Circuit diagrams
Motor operators
SACE S1-S2

SACE S3-S4-S5

External
circuit

External
circuit

Solenoid operator

Conn. X2

Conn. X2

Direct action motor operator

Internal
circuit

Internal
circuit

Term. XV

Term. XV
Conn. X2

GSIS0065

External
circuit

GSIS0081

External
circuit

Conn. X2

SACE S6-S7

External
circuit

Stored-energy motor operator

Conn. X2

Internal
circuit

Term. XV

Term. XV

6/54

GSIS0066

External
circuit

Conn. X2

ABB SACE

Circuit diagrams
Graphic symbols for circuit diagrams
(Standards IEC 617 and CEI 3-14...3-26)

ABB SACE

Thermal effect

Terminal or clamp

Make contact with


held position

Electromagnetic effect

Socket (female) or pole of a


socket

Make position contact


(limit contact)

Time delay

Socket and plug (female and


male)

Opening position contact (limit


contact)

Mechanical
connection

Temperature dependent
resistor

Change-over position contact


with temporary interruption (limit
contact)

Manual mechanical control


(general case)

Resistor (general symbol)

Switch-disconnector

Pushbutton actuator

Induction motor, threephase,


squirrel cage

Contactor (closing contact)

Key control

Motor (general symbol)

Circuit-breaker with automatic


release

Cam control

Brush

Control coil (general symbol)

Earth (general symbol)

Motor energised
in series

Instantaneous overcurrent
relay

Equipotentiality

Current transformer with primary


formed by 4 through conductors
and wound secondary, with
socket

Overcurrent relay with


adjustable short time-delay trip

Galvanically separated
converter

Current transformer

Overcurrent relay with short


inverse time-delay trip

Shielded cable conductors


(example: two conductors)

Make contact

Overcurrent relay with inverse


long time delay

Conductors or stranded cables


(example: two conductors)

Break contact

Earth fault overcurrent relay with


inverse short time-delay trip

Connection of conductors

Change-over contact with


temporary interruption

Residual current relay

6/55

Circuit diagrams
Key and notes

Figure number of diagram

= Main switch

= See the note indicated by the letter

Q/0 ... 2

= Auxiliary contacts of the circuit-breaker

A1

= Applications of the circuit-breaker

= Resistor outside the circuit-breaker, supplied for motor

A2

= Applications of the motor operators

A4

= Example switchgear and connections for control and

S1

= For S3 - S4 - S5: position contact operated by a circuit-

A11

= PR212/D-L dialogue unit, for connection to a centralised

power supply voltages of more than 220 V

signalling, outside the circuit-breaker

breaker cam For S6 - S7: contact controlled by the


motor operator cam: closes when the circuit-breaker

control system
A12

reaches its closed position and opens when the circuit-

= PR212/T actuator unit, with auxiliary relays for execut-

breaker reaches its open position (doesnt switch when

ing commands from the dialogue unit


A12/KC

= Actuator unit closing control

the circuit-breaker goes into its tripped position)


S2

= For S3 - S4 - S5: safety contact operated by:

A12/KO

= Actuator unit opening control

- key lock (if fitted)

A13

= PR010/K signalling unit with auxiliary relays for electrical

- padlock device

signalling of the protection functions of the microproc-

- manual control selector.

essor-based overcurrent release

For S6 - S7: contact controlled by the motor operator

A14

= Interface unit with SACE PR212/CI operator unit

cam: opens when the circuit-breaker reaches its closed

= Electronic time-lag device of undervoltage release (out-

position and closes when the circuit-breaker reaches

side the circuit-breaker)


K51

its open position (doesnt switch when the circuit-breaker

= PR211, PR212/P or PR212/MP microprocessor-based


overcurrent release

goes into its tripped position).The contact is also oper-

with the following protection func-

tions:

ated by the key lock device (if present)


S3

= Contact controlled by the motor operator cam: opens

- L overload protection with inverse long time-delay trip

after contact KO has closed and closes when the cir-

- S short-circuit protection with inverse or definite short

cuit-breaker reaches its open position (doesnt switch

time-delay trip (only available with PR212/P release)

when the circuit-breaker goes into its tripped position)

- I short-circuit protection with instantaneous trip

S4

- G earth fault protection with inverse short time-delay

S75I/1...5 =

trip (only available with PR212/P release)


K51/X

K51/X

cuit-breakers)
S75S/1...5 = Contacts for electrical signalling of circuit-breaker in

= Electrical signalling of alarm for protection function G in

removed or racked-out position (only for plug in or with-

tripping zone
K51/X

= Electrical signalling of alarm for protection function I in

K51/X

= Electrical signalling of alarm for protection function L in

drawable circuit-breakers)
SC

tripping zone

= Electrical signalling for protection function L in pre-alarm

K51/X

= Electrical signalling of alarm for protection function S in

K51/X

= Electrical signalling of alarm for release YO1 tripped

operating mechanism must have a time of not less than


100ms
SO

zone

or for motor stop

For circuit-breakers S3 - S4 - S5, the operating mechanism must have a time of not less than 100 ms (see

due to overcurrent or trip test (Fig. 41)

KO

Instructions for resetting the circuit-breaker after the

= RC211-RC212 residual-current release (for circuitbreakers S1-S2-S3) or RC210 (for circuit-breaker S1)

releases have tripped)


SY

= For S3 - S4 - S5: auxiliary opening relay.

= Contact for electrical signalling of circuit-breaker open


due to tripping of thermomagnetic releases, YO, YO1,

For S6 - S7: opening and spring-loading relay with held-

= Pushbutton or contact for opening the circuit-breaker

SO1, S02 = Pushbuttons or contacts for opening the circuit-breaker.

tripping zone

K87

= Pushbutton or contact for closing the circuit-breaker or


for motor start. For circuit-breakers S3 - S4 - S5, the

tripping zone
K51/X

Contacts for electrical signalling of circuit-breaker in


inserted position (only for plug in or withdrawable cir-

= Electrical signalling of alarm for internal communication


fault

= Contact operated by the circuit-breaker rotary handle

YU (tripped position)

position make contact, released by a cam of the motor

TI

= Toroidal current transformer

operator when the circuit-breaker reaches its open po-

TI/L1

= Current transformer located on phase L1

sition and the closing springs have been loaded

TI/L2

= Current transformer located on phase L2

TI/L3

= Current transformer located on phase L3

TI/N

= Current transformer located on neutral

= For S3 - S4 - S5: motor with energising in series for


opening and closing of the circuit-breaker. For S6 - S7:
motor for opening the circuit-breaker and loading the
closing springs of the circuit-breaker

M1

6/56

= Three-phase asinchronous motor

ABB SACE

Circuit diagrams
Graphic symbols for circuit diagrams
(Standards IEC 617 and CEI 3-14...3-26)
W1

= Serial interface with monitoring system (EIA RS485 interface)

X1, X2

The electrical opening control (contact SO2) is connected in se-

= Connectors for the auxiliary circuits of the circuit-breaker.


For circuit-breakers S1 - S2 supplied to order only.

X3, X4

= Connectors for the circuits of the microprocessor-based


overcurrent release (with plug in or withdrawable circuit-breakers, the connectors are pulled out at the same
time as the circuit-breaker)

X5, X6

3) Electrical resetting always enabled

= Terminal deliver y block for microprocessor-based


overcurrent release circuits

XO

= Connector for the opening solenoid YO1

XV

= Terminal blocks for accessories

YC

= Closing release

YO

= Opening release

YO1

= Opening solenoid of the RC211 or RC212 residual cur-

ries directly to relay KO for S3 - S4 - S5 or connected directly to


pole A3 of connector X2 (for S6 - S7) and is therefore always
enabled.
Example of use: automatic resetting of the circuit-breaker immediately after the releases have been tripped
N.B. If an overcurrent release is fitted, it will be necessary to
identify the causes that brought it to its tripped position in order
to prevent it from closing again in short-circuit conditions.

Manual resetting is always allowed in each of these examples.

rent release (for S1 - S2 - S3) and of the overcurrent


release (for S4 ... S8)
= Undervoltage release

Instructions for resetting the circuit-breaker after the releases


have tripped
The circuit-breaker can open both through the action of the motor
operator and due to the following releases tripping:

External
circuit

YU

overcurrent
undervoltage
opening

Conn.X1

with consequent opening of contact SY (if fitted) in series with relay

Term.XV

KO.
A reset operation involving manual or electric opening will have to be

Contact SY closes again at the end of the operation. The type of


resetting should be chosen to suit the design requirements and duty

Internal
circuit

carried out in order to close the circuit-breaker again after tripping.

conditions. A number of possible solutions are suggested below:

1) Manual resetting only


GSIS0067

Term.XV
(contact SO1) must be connected

in series with contact SY. Opening (for S3 - S4 - S5 using the


auxiliary relay KO) is therefore prevented until the circuit-breaker
is in its tripped position. To reset the circuit-breaker one needs to
operate the related lever until the circuit-breaker is in its open

Conn.X1

External
circuit

The electrical opening control

position and the closing springs are fully loaded.

2) Electrical resetting, responsibility of the operator


The normal electric opening control (contact SO1) must be connected in series with contact SY.
Another opening control is provided (contact SO2), connected
in series directly to relay KO for S3 - S4 - S5 or connected directly
to pole A3 of connector X2 for S6 - S7.
This control must be protected by, for example, a pushbutton
keyswitch. It should only be used if the information relayed to the
control station manager allows one to rule out the possibility of the
tripping having been caused by a short circuit, or if the causes of
the short circuit have been removed.

ABB SACE

6/57

6/58

ABB SACE

Order codes

Index
General information .......................................................................................................... 7/2
Circuit-breakers for power distribution
SACE Isomax S1 ...................................................................................................
SACE Isomax S2 ...................................................................................................
SACE Isomax S3 ...................................................................................................
SACE Isomax S4 ...................................................................................................
SACE Isomax S5 ...................................................................................................
SACE Isomax S6 ...................................................................................................
SACE Isomax S7 ...................................................................................................
SACE Isomax S8 ...................................................................................................

7/3
7/6
7/13
7/26
7/32
7/41
7/47
7/51

Current-limiting circuit-breakers
SACE Isomax S2X 100 .........................................................................................
SACE Isomax S3X .................................................................................................
SACE Isomax S4X .................................................................................................
SACE Isomax S6X .................................................................................................

7/52
7/53
7/56
7/58

Circuit-breakers for motor protection


SACE Isomax S2X 80 ...........................................................................................
SACE Isomax S3 ...................................................................................................
SACE Isomax S4 ...................................................................................................
SACE Isomax S5 ...................................................................................................
SACE Isomax S6 ...................................................................................................
SACE Isomax S7 ...................................................................................................
SACE Isomax S3X-S4X-S6X ................................................................................

7/60
7/61
7/62
7/63
7/63
7/63
7/64

Circuit-breakers for applications up to 1000 V .............................................................. 7/65


Switch-disconnectors
SACE Isomax S2D
SACE Isomax S3D
SACE Isomax S6D
SACE Isomax S7D
SACE Isomax S8D

................................................................................................
................................................................................................
................................................................................................
................................................................................................
................................................................................................

7/67
7/68
7/70
7/71
7/72

Accessories ....................................................................................................................... 7/73

7
ABB SACE

7/1

Order codes
General information
Interpretation of abbreviations used for article description

Im

F = Front
terminals

FC Cu = Front
terminals for
copper cables

RC = Rear
terminals for
cables

EF = Extended
front terminals

FC CuAl = Front
terminals for
copper /
aluminium cables

VR = Vertical
flat-bar rear
terminals

ES = Spreaded
extended front
terminals

R = Threaded
rear terminals

HR = Horizontal
flat-bar rear
terminals

Magnetic
trip current

PR211
P

Microprocessorbased electronic
release SACE
PR211/P (functions I
- LI)

PR212
P

Microprocessorbased electronic
release SACE
PR212/P (functions
LSI - LSIG)

Im = 3 Ith

Im = 5 Ith

Im = 10 Ith

Im = 5...10
Ith

PR212
MP

Microprocessorbased electronic
release for motor
protection SACE
PR212/MP
(functions LRIU)

DC

Direct current
circuit-breakers for
applications up to
1000V

AC ~

Alternate current
circuit-breakers for
applications up to
1000V

Iu

Rated uninterrupted
current of the circuitbreaker

In

Rated current of
electronic release

Ith

Rated current of
thermomagnetic
release

Icw

Rated short-time
withstand current

Icu

Rated ultimate
short-circuit
breaking capacity

Icm

Rated duty shortcircuit making


capacity (peak
value)

7
7/2

ABB SACE

Order codes
SACE Isomax S1 circuit-breaker

F = FIXED

S1B 125

Iu (40 C) =

PSIS9601

Thermomagnetic
release
FC Cu = Front terminals
for copper cables
S1B 125 F FC Cu
R 10
S1B 125 F FC Cu
R 12.5
S1B 125 F FC Cu
R 16
S1B 125 F FC Cu
R 20
S1B 125 F FC Cu
R 25
S1B 125 F FC Cu
R 32
S1B 125 F FC Cu
R 40
S1B 125 F FC Cu
R 50
S1B 125 F FC Cu
R 63
S1B 125 F FC Cu
R 80
S1B 125 F FC Cu
R 100
S1B 125 F FC Cu
R 125
R = Terminali posteriori filettati
S1B 125 F R
R 10
S1B 125 F R
R 12.5
S1B 125 F R
R 16
S1B 125 F R
R 20
S1B 125 F R
R 25
S1B 125 F R
R 32
S1B 125 F R
R 40
S1B 125 F R
R 50
S1B 125 F R
R 63
S1B 125 F R
R 80
S1B 125 F R
R 100
S1B 125 F R
R 125

125 A

Im = 5 Ith

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles

16 kA
Im = 10 Ith

code 1SDA0 . . . . . R1
3 poles
4 poles

160A
160A
160A
200A
200A
200A
200A
250A
320A
400A
500A
630A

23645
23647
23649
23651
23653
23655
23657
23659
23661
23663
23665
23667

24245
24247
24249
24251
24253
24255
24257
24259
24261
24263
24265
24267

500A
500A
500A
500A
500A
500A
500A
500A
630A
800A
1000A
1250A

00002
00004
00006
00008
00010
00012
00014
00016
00018
00020
00022
00024

00052
00054
00056
00058
00060
00062
00064
00066
00068
00070
00072
00074

160A
160A
160A
200A
200A
200A
200A
250A
320A
400A
500A
630A

23765
23767
23769
23771
23773
23775
23777
23779
23781
23783
23785
23787

23885
23887
23889
23891
23893
23895
23897
23899
23901
23903
23905
23907

500A
500A
500A
500A
500A
500A
500A
500A
630A
800A
1000A
1250A

00027
00029
00031
00033
00035
00037
00039
00041
00043
00045
00047
00049

00077
00079
00081
00083
00085
00087
00089
00091
00093
00095
00097
00099

7
ABB SACE

7/3

Order codes
SACE Isomax S1 circuit-breaker

F = FIXED

S1N 125

Iu (40 C) =

PSIS9601

Thermomagnetic
release
FC Cu = Front terminals
for copper cables
S1N 125 F FC Cu
R 10
S1N 125 F FC Cu
R 12.5
S1N 125 F FC Cu
R 16
S1N 125 F FC Cu
R 20
S1N 125 F FC Cu
R 25
S1N 125 F FC Cu
R 32
S1N 125 F FC Cu
R 40
S1N 125 F FC Cu
R 50
S1N 125 F FC Cu
R 63
S1N 125 F FC Cu
R 80
S1N 125 F FC Cu
R 100
S1N 125 F FC Cu
R 125
R = Threaded rear terminals
S1N 125 F R
R 10
S1N 125 F R
R 12.5
S1N 125 F R
R 16
S1N 125 F R
R 20
S1N 125 F R
R 25
S1N 125 F R
R 32
S1N 125 F R
R 40
S1N 125 F R
R 50
S1N 125 F R
R 63
S1N 125 F R
R 80
S1N 125 F R
R 100
S1N 125 F R
R 125

Magnetic
release
FC Cu = Front terminals
for copper cables
S1N 125 F FC Cu
In 16A
S1N 125 F FC Cu
In 40A
S1N 125 F FC Cu
In 50A
S1N 125 F FC Cu
In 63A
S1N 125 F FC Cu
In 80A
S1N 125 F FC Cu
In 100A
S1N 125 F FC Cu
In 125A
R = Threaded rear terminals
S1N 125 F R
In 16A
S1N 125 F R
In 40A
S1N 125 F R
In 50A
S1N 125 F R
In 63A
S1N 125 F R
In 80A
S1N 125 F R
In 100A
S1N 125 F R
In 125A

Im = 5 Ith

FC Cu = Front terminals
for copper cables
S1N 125 F FC Cu
R 63A
S1N 125 F FC Cu
R 80A
S1N 125 F FC Cu
R 100A
S1N 125 F FC Cu
R 125A
R = Threaded rear terminals
S1N 125 F R
R 63A
S1N 125 F R
R 80A
S1N 125 F R
R 100A
S1N 125 F R
R 125A

7
7/4

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles

25 kA
Im = 10 Ith

code 1SDA0 . . . . . R1
3 poles
4 poles

160A
160A
160A
200A
200A
200A
200A
250A
320A
400A
500A
630A

23669
23671
23673
23675
23677
23679
23681
23683
23685
23687
23689
23691

24269
24271
24273
24275
24277
24279
24281
24283
24285
24287
24289
24291

500A
500A
500A
500A
500A
500A
500A
500A
630A
800A
1000A
1250A

00152
00154
00156
00158
00160
00162
00164
00166
00168
00170
00172
00174

00202
00204
00206
00208
00210
00212
00214
00216
00218
00220
00222
00224

160A
160A
160A
200A
200A
200A
200A
250A
320A
400A
500A
630A

23789
23791
23793
23795
23797
23799
23801
23803
23805
23807
23809
23811

23909
23911
23913
23915
23917
23919
23921
23923
23925
23927
23929
23931

500A
500A
500A
500A
500A
500A
500A
500A
630A
800A
1000A
1250A

00177
00179
00181
00183
00185
00187
00189
00191
00193
00195
00197
00199

00227
00229
00231
00233
00235
00237
00239
00241
00243
00245
00247
00249

Im = 5 Ith

code 1SDA0 . . . . . R1
3 poles
4 poles

160A
200A
250A
320A
400A

33676
33684
33686
33688
33690

33772
33780
33782
33784
33786

160A
200A
250A
320A
400A

33724
33732
33734
33736
33738

33820
33828
33830
33832
33834

S1N 125 Curva D


Thermomagnetic
release

125 A

Iu (40 C) =

125 A

Im = 10 Ith

code 1SDA0 . . . . . R1
3 poles
4 poles

500A
630A
800A
1000A
1250A

33662
33664
33666
33668
33670

33758
33760
33762
33764
33766

500A
630A
800A
1000A
1250A

33710
33712
33714
33716
33718

33806
33808
33810
33812
33814

Icu (415 V) =
Im = 10 Ith

25 kA

code 1SDA0 . . . . . R1
4 poles

1250A
1250A
1400A
1500A

45084
45087
45089
45091

1250A
1250A
1400A
1500A

45093
45095
45097
45099

ABB SACE

Order codes
SACE Isomax S1 circuit-breaker

Moving part
S1B 125
Iu (40 C) = 125 A
PSIS9601

P = PLUG-IN

Thermomagnetic
release
S1B 125 P MP
S1B 125 P MP
S1B 125 P MP
S1B 125 P MP
S1B 125 P MP
S1B 125 P MP
S1B 125 P MP
S1B 125 P MP
S1B 125 P MP
S1B 125 P MP
S1B 125 P MP
S1B 125 P MP

Im = 5 Ith

R 10
R 12.5
R 16
R 20
R 25
R 32
R 40
R 50
R 63
R 80
R 100
R 125

S1N 125

Iu (40 C) =

Thermomagnetic
release
S1N 125 P MP
S1N 125 P MP
S1N 125 P MP
S1N 125 P MP
S1N 125 P MP
S1N 125 P MP
S1N 125 P MP
S1N 125 P MP
S1N 125 P MP
S1N 125 P MP
S1N 125 P MP
S1N 125 P MP

R 10
R 12.5
R 16
R 20
R 25
R 32
R 40
R 50
R 63
R 80
R 100
R 125

160A
160A
160A
200A
200A
200A
200A
250A
320A
400A
500A
630A

Im = 5 Ith

In
In
In
In
In
In
In

16A
40A
50A
63A
80A
100A
125A

160A
200A
250A
320A
400A

S1N 125 Curva D


Thermomagnetic
release
FC Cu = Front terminals
for copper cables
S1N 125 P MP
R 63A
S1N 125 P MP
R 80A
S1N 125 P MP
R 100A
S1N 125 P MP
R 125A

code 1SDA0 . . . . . R1
3 poles
4 poles
24005
24007
24009
24011
24013
24015
24017
24019
24021
24023
24025
24027

125 A

Im = 5 Ith

Magnetic
release
S1N 125 P MP
S1N 125 P MP
S1N 125 P MP
S1N 125 P MP
S1N 125 P MP
S1N 125 P MP
S1N 125 P MP

160A
160A
160A
200A
200A
200A
200A
250A
320A
400A
500A
630A

Icu (415 V) =

24125
24127
24129
24131
24133
24135
24137
24139
24141
24143
24145
24147

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles
24029
24031
24033
24035
24037
24039
24041
24043
24045
24047
24049
24051

24149
24151
24153
24155
24157
24159
24161
24163
24165
24167
24169
24171

code 1SDA0 . . . . . R1
3 poles
4 poles
33964
33972
33974
33976
33978

Iu (40 C) =

34012
34020
34022
34024
34026

125 A

16 kA
Im = 10 Ith

500A
500A
500A
500A
500A
500A
500A
500A
630A
800A
1000A
1250A

code 1SDA0 . . . . . R1
3 poles
4 poles
00102
00104
00106
00108
00110
00112
00114
00116
00118
00120
00122
00124

00127
00129
00131
00133
00135
00137
00139
00141
00143
00145
00147
00149

25 kA
Im = 10 Ith

500A
500A
500A
500A
500A
500A
500A
500A
630A
800A
1000A
1250A

Im = 10 Ith

500A
630A
800A
1000A
1250A

code 1SDA0 . . . . . R1
3 poles
4 poles
00252
00254
00256
00258
00260
00262
00264
00266
00268
00270
00272
00274

code 1SDA0 . . . . . R1
3 poles
4 poles

33950
33952
33954
33956
33958

Icu (415 V) =
Im = 10 Ith

1250A
1250A
1400A
1500A

00277
00279
00281
00283
00285
00287
00289
00291
00293
00295
00297
00299

33998
34000
34002
34004
34006

25 kA

code 1SDA0 . . . . . R1
4 poles

45101
45103
45105
45107

7
ABB SACE

7/5

Order codes
SACE Isomax S2 circuit-breaker

F = FIXED

S2B 160

Iu (40 C) =

PSIS9604

Thermomagnetic
release
EF = Extended front
terminals
S2B 160 F EF
R 12.5
S2B 160 F EF
R 16
S2B 160 F EF
R 20
S2B 160 F EF
R 25
S2B 160 F EF
R 32
S2B 160 F EF
R 40
S2B 160 F EF
R 50
S2B 160 F EF
R 63
S2B 160 F EF
R 80
S2B 160 F EF
R 100
S2B 160 F EF
R 125
S2B 160 F EF
R 160
FC Cu = Front terminals
for copper cables
S2B 160 F FC Cu
R 12.5
S2B 160 F FC Cu
R 16
S2B 160 F FC Cu
R 20
S2B 160 F FC Cu
R 25
S2B 160 F FC Cu
R 32
S2B 160 F FC Cu
R 40
S2B 160 F FC Cu
R 50
S2B 160 F FC Cu
R 63
S2B 160 F FC Cu
R 80
S2B 160 F FC Cu
R 100
S2B 160 F FC Cu
R 125
S2B 160 F FC Cu
R 160
FC CuAl = Front terminals
for copper/aluminium cables
S2B 160 F FC CuAl* R 12.5
S2B 160 F FC CuAl* R 16
S2B 160 F FC CuAl* R 20
S2B 160 F FC CuAl* R 25
S2B 160 F FC CuAl* R 32
S2B 160 F FC CuAl* R 40
S2B 160 F FC CuAl* R 50
S2B 160 F FC CuAl* R 63
S2B 160 F FC CuAl* R 80
S2B 160 F FC CuAl* R 100
S2B 160 F FC CuAl* R 125
S2B 160 F FC CuAl* R 160
S2B 160 F FC CuAl** R 12.5
S2B 160 F FC CuAl** R 16
S2B 160 F FC CuAl** R 20
S2B 160 F FC CuAl** R 25
S2B 160 F FC CuAl** R 32
S2B 160 F FC CuAl** R 40
S2B 160 F FC CuAl** R 50
S2B 160 F FC CuAl** R 63
S2B 160 F FC CuAl** R 80
S2B 160 F FC CuAl** R 100
S2B 160 F FC CuAl** R 125
S2B 160 F FC CuAl** R 160
R = Threaded rear terminals
S2B 160 F R
R 12.5
S2B 160 F R
R 16
S2B 160 F R
R 20
S2B 160 F R
R 25
S2B 160 F R
R 32
S2B 160 F R
R 40
S2B 160 F R
R 50
S2B 160 F R
R 63
S2B 160 F R
R 80
S2B 160 F R
R 100
S2B 160 F R
R 125
S2B 160 F R
R 160

160 A

Im = 5 Ith

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles

16 kA
Im = 10 Ith

code 1SDA0 . . . . . R1
3 poles
4 poles

160A
160A
200A
200A
200A
200A
250A
320A
400A
500A
630A
800A

34056
34058
34060
34062
34064
34066
34068
34070
34072
34074
34076
34078

34440
34442
34444
34446
34448
34450
34452
34454
34456
34458
34460
34462

500A
500A
500A
500A
500A
500A
500A
630A
800A
1000A
1250A
1600A

34032
34034
34036
34038
34040
34042
34044
34046
34048
34050
34052
34054

34416
34418
34420
34422
34424
34426
34428
34430
34432
34434
34436
34438

160A
160A
200A
200A
200A
200A
250A
320A
400A
500A
630A
800A

23693
23695
23697
23699
23701
23703
23705
23707
23709
23711
23713
23715

24293
24295
24297
24299
24301
24303
24305
24307
24309
24311
24313
24315

500A
500A
500A
500A
500A
500A
500A
630A
800A
1000A
1250A
1600A

00302
00304
00306
00308
00310
00312
00314
00316
00318
00320
00322
00324

00352
00354
00356
00358
00360
00362
00364
00366
00368
00370
00372
00374

160A
160A
200A
200A
200A
200A
250A
320A
400A
500A
630A
800A

34200
34202
34204
34206
34208
34210
34212
34214
34216
34218
34220
34222

34584
34586
34588
34590
34592
34594
34596
34598
34600
34602
34604
34606

500A
500A
500A
500A
500A
500A
500A
630A
800A
1000A
1250A
1600A

34176
34178
34180
34182
34184
34186
34188
34190
34192
34194
34196
34198

34560
34562
34564
34566
34568
34570
34572
34574
34576
34578
34580
34582

160A
160A
200A
200A
200A
200A
250A
320A
400A
500A
630A
800A

34296
34298
34300
34302
34304
34306
34308
34310
34312
34314
34316
34318

34680
34682
34684
34686
34688
34690
34692
34694
34696
34698
34700
34702

500A
500A
500A
500A
500A
500A
500A
630A
800A
1000A
1250A
1600A

34272
34274
34276
34278
34280
34282
34284
34286
34288
34290
34292
34294

34656
34658
34660
34662
34664
34666
34668
34670
34672
34674
34676
34678

160A
160A
200A
200A
200A
200A
250A
320A
400A
500A
630A
800A

23813
23815
23817
23819
23821
23823
23825
23827
23829
23831
23833
23835

23933
23935
23937
23939
23941
23943
23945
23947
23949
23951
23953
23955

500A
500A
500A
500A
500A
500A
500A
630A
800A
1000A
1250A
1600A

00327
00329
00331
00333
00335
00337
00339
00341
00343
00345
00347
00349

00377
00379
00381
00383
00385
00387
00389
00391
00393
00395
00397
00399

* Cable section = 1 x 2.5...50 mm2


** Cable section = 1 x 35...95 mm2

7/6

ABB SACE

Order codes
SACE Isomax S2 circuit-breaker

F = FIXED

S2N 160

Iu (40 C) =

PSIS9604

Thermomagnetic
release
EF = Extended front
terminals
S2N 160 F EF
R 12.5
S2N 160 F EF
R 16
S2N 160 F EF
R 20
S2N 160 F EF
R 25
S2N 160 F EF
R 32
S2N 160 F EF
R 40
S2N 160 F EF
R 50
S2N 160 F EF
R 63
S2N 160 F EF
R 80
S2N 160 F EF
R 100
S2N 160 F EF
R 125
S2N 160 F EF
R 160
FC Cu = Front terminals
for copper cables
S2N 160 F FC Cu
R 12.5
S2N 160 F FC Cu
R 16
S2N 160 F FC Cu
R 20
S2N 160 F FC Cu
R 25
S2N 160 F FC Cu
R 32
S2N 160 F FC Cu
R 40
S2N 160 F FC Cu
R 50
S2N 160 F FC Cu
R 63
S2N 160 F FC Cu
R 80
S2N 160 F FC Cu
R 100
S2N 160 F FC Cu
R 125
S2N 160 F FC Cu
R 160
FC CuAl = Front terminals
for copper/aluminium cables
S2N 160 F FC CuAl* R 12.5
S2N 160 F FC CuAl* R 16
S2N 160 F FC CuAl* R 20
S2N 160 F FC CuAl* R 25
S2N 160 F FC CuAl* R 32
S2N 160 F FC CuAl* R 40
S2N 160 F FC CuAl* R 50
S2N 160 F FC CuAl* R 63
S2N 160 F FC CuAl* R 80
S2N 160 F FC CuAl* R 100
S2N 160 F FC CuAl* R 125
S2N 160 F FC CuAl* R 160
S2N 160 F FC CuAl** R 12.5
S2N 160 F FC CuAl** R 16
S2N 160 F FC CuAl** R 20
S2N 160 F FC CuAl** R 25
S2N 160 F FC CuAl** R 32
S2N 160 F FC CuAl** R 40
S2N 160 F FC CuAl** R 50
S2N 160 F FC CuAl** R 63
S2N 160 F FC CuAl** R 80
S2N 160 F FC CuAl** R 100
S2N 160 F FC CuAl** R 125
S2N 160 F FC CuAl** R 160
R = Threaded rear terminals
S2N 160 F R
R 12.5
S2N 160 F R
R 16
S2N 160 F R
R 20
S2N 160 F R
R 25
S2N 160 F R
R 32
S2N 160 F R
R 40
S2N 160 F R
R 50
S2N 160 F R
R 63
S2N 160 F R
R 80
S2N 160 F R
R 100
S2N 160 F R
R 125
S2N 160 F R
R 160

160 A

Im = 5 Ith

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles

35 kA
Im = 10 Ith

code 1SDA0 . . . . . R1
3 poles
4 poles

160A
160A
200A
200A
200A
200A
250A
320A
400A
500A
630A
800A

34826
34828
34830
34832
34834
34836
34838
34840
34842
34844
34846
34848

35210
35212
35214
35216
35218
35220
35222
35224
35226
35228
35230
35232

500A
500A
500A
500A
500A
500A
500A
630A
800A
1000A
1250A
1600A

34802
34804
34806
34808
34810
34812
34814
34816
34818
34820
34822
34824

35186
35188
35190
35192
35194
35196
35198
35200
35202
35204
35206
35208

160A
160A
200A
200A
200A
200A
250A
320A
400A
500A
630A
800A

23717
23719
23721
23723
23725
23727
23729
23731
23733
23735
23737
23739

24317
24319
24321
24323
24325
24327
24329
24331
24333
24335
24337
24339

500A
500A
500A
500A
500A
500A
500A
630A
800A
1000A
1250A
1600A

00452
00454
00456
00458
00460
00462
00464
00466
00468
00470
00472
00474

00502
00504
00506
00508
00510
00512
00514
00516
00518
00520
00522
00524

160A
160A
200A
200A
200A
200A
250A
320A
400A
500A
630A
800A

34970
34972
34974
34976
34978
34980
34982
34984
34986
34988
34990
34992

35354
35356
35358
35360
35362
35364
35366
35368
35370
35372
35374
35376

500A
500A
500A
500A
500A
500A
500A
630A
800A
1000A
1250A
1600A

34946
34948
34950
34952
34954
34956
34958
34960
34962
34964
34966
34968

35330
35332
35334
35336
35338
35340
35342
35344
35346
35348
35350
35352

160A
160A
200A
200A
200A
200A
250A
320A
400A
500A
630A
800A

35066
35068
35070
35072
35074
35076
35078
35080
35082
35084
35086
35088

35450
35452
35454
35456
35458
35460
35462
35464
35466
35468
35470
35472

500A
500A
500A
500A
500A
500A
500A
630A
800A
1000A
1250A
1600A

35042
35044
35046
35048
35050
35052
35054
35056
35058
35060
35062
35064

35426
35428
35430
35432
35434
35436
35438
35440
35442
35444
35446
35448

160A
160A
200A
200A
200A
200A
250A
320A
400A
500A
630A
800A

23837
23839
23841
23843
23845
23847
23849
23851
23853
23855
23857
23859

23957
23959
23961
23963
23965
23967
23969
23971
23973
23975
23977
23979

500A
500A
500A
500A
500A
500A
500A
630A
800A
1000A
1250A
1600A

00477
00479
00481
00483
00485
00487
00489
00491
00493
00495
00497
00499

00527
00529
00531
00533
00535
00537
00539
00541
00543
00545
00547
00549

* Cable section = 1 x 2.5...50 mm2


** Cable section = 1 x 35...95 mm2

ABB SACE

7/7

Order codes
SACE Isomax S2 circuit-breaker

F = FIXED

PSIS9604

Thermomagnetic
release
EF = Extended front
terminals
S2N 160 F EF
In 16A
S2N 160 F EF
In 40A
S2N 160 F EF
In 50A
S2N 160 F EF
In 63A
S2N 160 F EF
In 80A
S2N 160 F EF
In 100A
S2N 160 F EF
In 125A
S2N 160 F EF
In 160A
FC Cu = Front terminals
for copper cables
S2N 160 F FC Cu
In 16A
S2N 160 F FC Cu
In 40A
S2N 160 F FC Cu
In 50A
S2N 160 F FC Cu
In 63A
S2N 160 F FC Cu
In 80A
S2N 160 F FC Cu
In 100A
S2N 160 F FC Cu
In 125A
S2N 160 F FC Cu
In 160A
FC CuAl = Front terminals
for copper/aluminium cables
S2N 160 F FC CuAl* In 16A
S2N 160 F FC CuAl* In 40A
S2N 160 F FC CuAl* In 50A
S2N 160 F FC CuAl* In 63A
S2N 160 F FC CuAl* In 80A
S2N 160 F FC CuAl* In 100A
S2N 160 F FC CuAl* In 125A
S2N 160 F FC CuAl* In 160A
S2N 160 F FC CuAl** In 16A
S2N 160 F FC CuAl** In 40A
S2N 160 F FC CuAl** In 50A
S2N 160 F FC CuAl** In 63A
S2N 160 F FC CuAl** In 80A
S2N 160 F FC CuAl** In 100A
S2N 160 F FC CuAl** In 125A
S2N 160 F FC CuAl** In 160A
R = Threaded rear terminals
S2N 160 F R
In 16A
S2N 160 F R
In 40A
S2N 160 F R
In 50A
S2N 160 F R
In 63A
S2N 160 F R
In 80A
S2N 160 F R
In 100A
S2N 160 F R
In 125A
S2N 160 F R
In 160A

Im = 5 Ith

code 1SDA0 . . . . . R1
3 poles
4 poles

160A
200A
250A
320A
400A

34876
34884
34886
34888
34890

35260
35268
35270
35272
35274

160A
200A
250A
320A
400A

34924
34932
34934
34936
34938

35308
35316
35318
35320
35322

160A
200A
250A
320A
400A

35020
35028
35030
35032
35034

35404
35412
35414
35416
35418

160A
200A
250A
320A
400A

35116
35124
35126
35128
35130

35500
35508
35510
35512
35514

160A
200A
250A
320A
400A

35164
35172
35174
35176
35178

35548
35556
35558
35560
35562

Im = 10 Ith

code 1SDA0 . . . . . R1
3 poles
4 poles

500A
630A
800A
1000A
1250A
1600A

34862
34864
34866
34868
34870
34872

35246
35248
35250
35252
35254
35256

500A
630A
800A
1000A
1250A
1600A

34910
34912
34914
34916
34918
34920

35294
35296
35298
35300
35302
35304

500A
630A
800A
1000A
1250A
1600A

35006
35008
35010
35012
35014
35016

35390
35392
35394
35396
35398
35400

500A
630A
800A
1000A
1250A
1600A

35102
35104
35106
35108
35110
35112

35486
35488
35490
35492
35494
35496

500A
630A
800A
1000A
1250A
1600A

35150
35152
35154
35156
35158
35160

35534
35536
35538
35540
35542
35544

* Cable section = 1 x 2.5...50 mm2


** Cable section = 1 x 35...95 mm2

7
7/8

ABB SACE

Order codes
SACE Isomax S2 circuit-breaker

F = FIXED

S2S 160

Iu (40 C) =

PSIS9604

Thermomagnetic
release
EF = Extended front
terminals
S2S 160 F EF
R 12.5
S2S 160 F EF
R 16
S2S 160 F EF
R 20
S2S 160 F EF
R 25
S2S 160 F EF
R 32
S2S 160 F EF
R 40
S2S 160 F EF
R 50
S2S 160 F EF
R 63
S2S 160 F EF
R 80
S2S 160 F EF
R 100
S2S 160 F EF
R 125
S2S 160 F EF
R 160
FC Cu = Front terminals
for copper cables
S2S 160 F FC Cu
R 12.5
S2S 160 F FC Cu
R 16
S2S 160 F FC Cu
R 20
S2S 160 F FC Cu
R 25
S2S 160 F FC Cu
R 32
S2S 160 F FC Cu
R 40
S2S 160 F FC Cu
R 50
S2S 160 F FC Cu
R 63
S2S 160 F FC Cu
R 80
S2S 160 F FC Cu
R 100
S2S 160 F FC Cu
R 125
S2S 160 F FC Cu
R 160
FC CuAl = Front terminals
for copper/aluminium cables
S2S 160 F FC CuAl* R 12.5
S2S 160 F FC CuAl* R 16
S2S 160 F FC CuAl* R 20
S2S 160 F FC CuAl* R 25
S2S 160 F FC CuAl* R 32
S2S 160 F FC CuAl* R 40
S2S 160 F FC CuAl* R 50
S2S 160 F FC CuAl* R 63
S2S 160 F FC CuAl* R 80
S2S 160 F FC CuAl* R 100
S2S 160 F FC CuAl* R 125
S2S 160 F FC CuAl* R 160
S2S 160 F FC CuAl** R 12.5
S2S 160 F FC CuAl** R 16
S2S 160 F FC CuAl** R 20
S2S 160 F FC CuAl** R 25
S2S 160 F FC CuAl** R 32
S2S 160 F FC CuAl** R 40
S2S 160 F FC CuAl** R 50
S2S 160 F FC CuAl** R 63
S2S 160 F FC CuAl** R 80
S2S 160 F FC CuAl** R 100
S2S 160 F FC CuAl** R 125
S2S 160 F FC CuAl** R 160
R = Threaded rear terminals
S2S 160 F R
R 12.5
S2S 160 F R
R 16
S2S 160 F R
R 20
S2S 160 F R
R 25
S2S 160 F R
R 32
S2S 160 F R
R 40
S2S 160 F R
R 50
S2S 160 F R
R 63
S2S 160 F R
R 80
S2S 160 F R
R 100
S2S 160 F R
R 125
S2S 160 F R
R 160

160 A

Icu (415 V) =

50 kA
Im = 10 Ith

code 1SDA0 . . . . . R1
3 poles
4 poles

500A
500A
500A
500A
500A
500A
500A
630A
800A
1000A
1250A
1600A

35570
35572
35574
35576
35578
35580
35582
35584
35586
35588
35590
35592

35762
35764
35766
35768
35770
35772
35774
35776
35778
35780
35782
35784

500A
500A
500A
500A
500A
500A
500A
630A
800A
1000A
1250A
1600A

00602
00604
00606
00608
00610
00612
00614
00616
00618
00620
00622
00624

00652
00654
00656
00658
00660
00662
00664
00666
00668
00670
00672
00674

500A
500A
500A
500A
500A
500A
500A
630A
800A
1000A
1250A
1600A

36197
36199
36201
36203
36205
36207
36209
36211
36213
36215
36217
36219

35834
35836
35838
35840
35842
35844
35846
35848
35850
35852
35854
35856

500A
500A
500A
500A
500A
500A
500A
630A
800A
1000A
1250A
1600A

36221
36223
36225
36227
36229
36231
36233
36235
36237
36239
36241
36243

35882
35884
35886
35888
35890
35892
35894
35896
35898
35900
35902
35904

500A
500A
500A
500A
500A
500A
500A
630A
800A
1000A
1250A
1600A

00627
00629
00631
00633
00635
00637
00639
00641
00643
00645
00647
00649

00677
00679
00681
00683
00685
00687
00689
00691
00693
00695
00697
00699

* Cable section = 1 x 2.5...50 mm2


** Cable section = 1 x 35...95 mm2

ABB SACE

7/9

Order codes
SACE Isomax S2 circuit-breaker

F = FIXED

PSIS9604

Magnetic
release
EF = Extended front
terminals
S2S 160 F EF
In 50A
S2S 160 F EF
In 63A
S2S 160 F EF
In 80A
S2S 160 F EF
In 100A
S2S 160 F EF
In 125A
S2S 160 F EF
In 160A
FC Cu = Front terminals
for copper cables
S2S 160 F FC Cu
In 50A
S2S 160 F FC Cu
In 63A
S2S 160 F FC Cu
In 80A
S2S 160 F FC Cu
In 100A
S2S 160 F FC Cu
In 125A
S2S 160 F FC Cu
In 160A
FC CuAl = Front terminals
for copper/aluminium cables
S2S 160 F FC CuAl* In 50A
S2S 160 F FC CuAl* In 63A
S2S 160 F FC CuAl* In 80A
S2S 160 F FC CuAl* In 100A
S2S 160 F FC CuAl* In 125A
S2S 160 F FC CuAl* In 160A
S2S 160 F FC CuAl** In 50A
S2S 160 F FC CuAl** In 63A
S2S 160 F FC CuAl** In 80A
S2S 160 F FC CuAl** In 100A
S2S 160 F FC CuAl** In 125A
S2S 160 F FC CuAl** In 160A
R = Threaded rear terminals
S2S 160 F R
In 50A
S2S 160 F R
In 63A
S2S 160 F R
In 80A
S2S 160 F R
In 100A
S2S 160 F R
In 125A
S2S 160 F R
In 160A

Im = 10 Ith

code 1SDA0 . . . . . R1
3 poles
4 poles

500A
630A
800A
1000A
1250A
1600A

35631
35633
35635
35636
35638
35640

35798
35800
35802
35804
35806
35808

500A
630A
800A
1000A
1250A
1600A

35678
35680
35682
35684
35686
35688

35822
35824
35826
35828
35830
35832

500A
630A
800A
1000A
1250A
1600A

35702
35704
35706
35708
35710
35712

35870
35872
35874
35876
35878
35880

500A
630A
800A
1000A
1250A
1600A

35726
35728
35730
35732
35734
35736

35918
35920
35922
35924
35926
35928

500A
630A
800A
1000A
1250A
1600A

35750
35752
35754
35756
35758
35760

35942
35944
35946
35948
35950
35952

* Cable section = 1 x 2.5...50 mm2


** Cable section = 1 x 35...95 mm2

7
7/10

ABB SACE

Order codes
SACE Isomax S2 circuit-breaker

Moving part
S2B 160
Iu (40 C) = 160 A
PSIS9604

P = PLUG-IN

Thermomagnetic
release
S2B 160 P MP
S2B 160 P MP
S2B 160 P MP
S2B 160 P MP
S2B 160 P MP
S2B 160 P MP
S2B 160 P MP
S2B 160 P MP
S2B 160 P MP
S2B 160 P MP
S2B 160 P MP
S2B 160 P MP

Im = 5 Ith

R 12.5
R 16
R 20
R 25
R 32
R 40
R 50
R 63
R 80
R 100
R 125
R 160

S2N 160

Iu (40 C) =

Thermomagnetic
release
S2N 160 P MP
S2N 160 P MP
S2N 160 P MP
S2N 160 P MP
S2N 160 P MP
S2N 160 P MP
S2N 160 P MP
S2N 160 P MP
S2N 160 P MP
S2N 160 P MP
S2N 160 P MP
S2N 160 P MP

R 12.5
R 16
R 20
R 25
R 32
R 40
R 50
R 63
R 80
R 100
R 125
R 160

160A
160A
200A
200A
200A
200A
250A
320A
400A
500A
630A
800A

Im = 5 Ith

In
In
In
In
In
In
In
In

16A
40A
50A
63A
80A
100A
125A
150A

code 1SDA0 . . . . . R1
3 poles
4 poles
24053
24055
24057
24059
24061
24063
24065
24067
24069
24071
24073
24075

160 A

Im = 5 Ith

Magnetic
release
S2N 160 P MP
S2N 160 P MP
S2N 160 P MP
S2N 160 P MP
S2N 160 P MP
S2N 160 P MP
S2N 160 P MP
S2N 160 P MP

160A
160A
200A
200A
200A
200A
250A
320A
400A
500A
630A
8000A

160A
200A
250A
320A
400A

Icu (415 V) =

24173
24175
24177
24179
24181
24183
24185
24187
24189
24191
24193
24195

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles
24077
24079
24081
24083
24085
24087
24089
24091
24093
24095
24097
24099

24197
24199
24201
24203
24205
24207
24209
24211
24213
24215
24217
24219

code 1SDA0 . . . . . R1
3 poles
4 poles
36076
36084
36086
36088
36090

36124
36132
36134
36136
36138

16 kA
Im = 10 Ith

500A
500A
500A
500A
500A
500A
500A
630A
800A
1000A
1250A
1600A

code 1SDA0 . . . . . R1
3 poles
4 poles
00402
00404
00406
00408
00410
00412
00414
00416
00418
00420
00422
00424

00427
00429
00431
00433
00435
00437
00439
00441
00443
00445
00447
00449

35 kA
Im = 10 Ith

500A
500A
500A
500A
500A
500A
500A
630A
800A
1000A
1250A
1600A

Im = 10 Ith

500A
630A
800A
1000A
1250A
1600A

code 1SDA0 . . . . . R1
3 poles
4 poles
00552
00554
00556
00558
00560
00562
00564
00566
00568
00570
00572
00574

00577
00579
00581
00583
00585
00587
00589
00591
00593
00595
00597
00599

code 1SDA0 . . . . . R1
3 poles
4 poles

36062
36064
36066
36068
36070
36072

36110
36112
36114
36116
36118
36120

7
ABB SACE

7/11

Order codes
SACE Isomax S2 circuit-breaker

Moving part
S2S 160
Iu (40 C) = 160 A
PSIS9604

P = PLUG-IN

Thermomagnetic
release
S2S 160 P MP
S2S 160 P MP
S2S 160 P MP
S2S 160 P MP
S2S 160 P MP
S2S 160 P MP
S2S 160 P MP
S2S 160 P MP
S2S 160 P MP
S2S 160 P MP
S2S 160 P MP
S2S 160 P MP

Im = 5 Ith
R 12.5
R 16
R 20
R 25
R 32
R 40
R 50
R 63
R 80
R 100
R 125
R 160

Icu (415 V) =

50 kA
Im = 10 Ith

500A
500A
500A
500A
500A
500A
500A
630A
800A
1000A
1250A
1600A

Magnetic
release
S2S 160 P MP
S2S 160 P MP
S2S 160 P MP
S2S 160 P MP
S2S 160 P MP
S2S 160 P MP

code 1SDA0 . . . . . R1
3 poles
4 poles
00702
00704
00706
00708
00710
00712
00714
00716
00718
00720
00722
00724

00727
00729
00731
00733
00735
00737
00739
00741
00743
00745
00747
00749

code 1SDA0 . . . . . R1
3 poles
4 poles
In
In
In
In
In
In

50A
63A
80A
100A
125A
150A

500A
630A
800A
1000A
1250A
1600A

36158
36160
36162
36164
36166
36168

36182
36184
36186
36188
36190
36192

7
7/12

ABB SACE

Order codes
SACE Isomax S2 circuit-breaker

F = FIXED

S3N 160

Iu (40 C) =

PSIS9607

Thermomagnetic
release
F = Front terminals
S3N 160 F F
S3N 160 F F
S3N 160 F F
S3N 160 F F (N50%)

Thermomagnetic
release

160 A

Im = 3 Ith

R 100
R 125
R 160
R 160

300A
375A
I480A
I480A

Im = 5 Ith

F = Front terminals
S3N 160 F F
R 32
250A
S3N 160 F F
R 50
250A
S3N 160 F F
R 80
400A
S3N 160 F F
R 100
500A
S3N 160 F F
R 125
625A
S3N 160 F F
R 160
800A
EF = Extended front
terminals
S3N 160 F EF
R 32
250A
S3N 160 F EF
R 50
250A
S3N 160 F EF
R 80
400A
S3N 160 F EF
R 100
500A
S3N 160 F EF
R 125
625A
S3N 160 F EF
R 160
800A
FC Cu = Front terminals
for copper cables
S3N 160 F FC Cu
R 32
250A
S3N 160 F FC Cu
R 50
250A
S3N 160 F FC Cu
R 80
400A
S3N 160 F FC Cu
R 100
500A
S3N 160 F FC Cu
R 125
625A
S3N 160 F FC Cu
R 160
800A
FC CuAl = Front terminals
for copper/aluminium cables
S3N 160 F FC CuAl
R 32
250A
S3N 160 F FC CuAl
R 50
250A
S3N 160 F FC CuAl
R 80
400A
S3N 160 F FC CuAl
R 100
500A
S3N 160 F FC CuAl
R 125
625A
S3N 160 F FC CuAl
R 160
800A
R = Threaded rear terminals
S3N 160 F R
R 32
250A
S3N 160 F R
R 50
250A
S3N 160 F R
R 80
400A
S3N 160 F R
R 100
500A
S3N 160 F R
R 125
625A
S3N 160 F R
R 160
800A
RC = Rear terminals
for cables
S3N 160 F RC
R 32
250A
S3N 160 F RC
R 50
250A
S3N 160 F RC
R 80
400A
S3N 160 F RC
R 100
500A
S3N 160 F RC
R 125
625A
S3N 160 F RC
R 160
800A
R Res. Cur = Threaded rear terminals +
kit of threaded rear terminals
for residual-current release
installed below the circuit-breaker
S3N 160 F R Res. Cur R 32
250A
S3N 160 F R Res. Cur R 50
250A
S3N 160 F R Res. Cur R 80
400A
S3N 160 F R Res. Cur R 100
500A
S3N 160 F R Res. Cur R 125
625A
S3N 160 F R Res. Cur R 160
800A

ABB SACE

Icu (415 V) =

35 kA

code 1SDA0 . . . . . R1
3 poles
4 poles
48539
48540
48541

48549
48550
48551
48559

code 1SDA0 . . . . . R1
3 poles
4 poles

Im = 10 Ith

code 1SDA0 . . . . . R1
3 poles
4 poles

13359
13361
13363
13365
13367
13369

13383
13385
13387
13389
13391
13393

500A
500A
800A
1000A
1250A
1600A

13346
13348
13350
13352
13354
13356

13371
13373
13375
13377
13379
13381

00764
00766
00768
00770
00772
00774

01389
01391
01393
01395
01397
01399

500A
500A
800A
1000A
1250A
1600A

00752
00754
00756
00758
00760
00762

01377
01379
01381
01383
01385
01387

00914
00916
00918
00920
00922
00924

01539
01541
01543
01545
01547
01549

500A
500A
800A
1000A
1250A
1600A

00902
00904
00906
00908
00910
00912

01527
01529
01531
01533
01535
01537

01064
01066
01068
01070
01072
01074

01689
01691
01693
01695
01697
01699

500A
500A
800A
1000A
1250A
1600A

01052
01054
01056
01058
01060
01062

01677
01679
01681
01683
01685
01687

01364
01366
01368
01370
01372
01374

14243
14245
14247
14249
14251
14253

500A
500A
800A
1000A
1250A
1600A

01352
01354
01356
01358
01360
01362

14231
14233
14235
14237
14239
14241

01214
01216
01218
01220
01222
01224

01839
01841
01843
01845
01847
01849

500A
500A
800A
1000A
1250A
1600A

01202
01204
01206
01208
01210
01212

01827
01829
01831
01833
01835
01837

25459
25461
25463
25465
25467
25469

500A
500A
800A
1000A
1250A
1600A

25447
25449
25451
25454
25455
25457

7
7/13

Order codes
SACE Isomax S2 circuit-breaker

F = FIXED

PSIS9607

Magnetic
release
F = Front terminals
S3N 160 F F
In 50A
S3N 160 F F
In 80A
S3N 160 F F
In 100A
S3N 160 F F
In 125A
S3N 160 F F
In 160A
EF = Extended front
terminals
S3N 160 F EF
In 50A
S3N 160 F EF
In 80A
S3N 160 F EF
In 100A
S3N 160 F EF
In 125A
S3N 160 F EF
In 160A
FC Cu = Front terminals
for copper cables
S3N 160 F FC Cu
In 50A
S3N 160 F FC Cu
In 80A
S3N 160 F FC Cu
In 100A
S3N 160 F FC Cu
In 125A
S3N 160 F FC Cu
In 160A
FC CuAl = Front terminals
for copper/aluminium cables
S3N 160 F FC CuAl
In 50A
S3N 160 F FC CuAl
In 80A
S3N 160 F FC CuAl
In 100A
S3N 160 F FC CuAl
In 125A
S3N 160 F FC CuAl
In 160A
R = Threaded rear terminals
S3N 160 F R
In 50A
S3N 160 F R
In 80A
S3N 160 F R
In 100A
S3N 160 F R
In 125A
S3N 160 F R
In 160A
RC = Rear terminals
for cables
S3N 160 F RC
In 50A
S3N 160 F RC
In 80A
S3N 160 F RC
In 100A
S3N 160 F RC
In 125A
S3N 160 F RC
In 160A

Im = 5 Ith

code 1SDA0 . . . . . R1
3 poles
4 poles

250A
400A

25817
25819

25889
25891

625A

25823

25895

250A
400A

27930
27932

29706
29708

625A

27936

29712

250A
400A

28074
28076

29850
29852

625A

28080

29856

250A
400A

28218
28220

29994
29996

625A

28224

30000

250A
400A

28506
28508

30282
30284

625A

28512

30288

250A
400A

28362
28364

30138
30140

625A

28368

30144

Im = 10 Ith

code 1SDA0 . . . . . R1
3 poles
4 poles

500A
800A
1000A
1250A
1600A

25804
25807
25809
25811
25813

25877
25879
25881
25883
25885

500A
800A
1000A
1250A
1600A

27918
27920
27922
27924
27926

29694
29696
29698
29700
29702

500A
800A
1000A
1250A
1600A

28062
28064
28066
28068
28070

29838
29840
29842
29844
29846

500A
800A
1000A
1250A
1600A

28206
28208
28210
28212
28214

29982
29984
29986
29988
29990

500A
800A
1000A
1250A
1600A

28494
28496
28498
28500
28502

30270
30272
30274
30276
30278

500A
800A
1000A
1250A
1600A

28350
28352
28354
28356
28358

30126
30128
30130
30132
30134

7
7/14

ABB SACE

Order codes
SACE Isomax S3 circuit-breaker

F = FIXED

S3H 160

Iu (40 C) =

PSIS9607

Thermomagnetic
release
F = Front terminals
S3H 160 F F
S3H 160 F F
S3H 160 F F
S3H 160 F F (N50%)

Thermomagnetic
release

160 A

Im = 3 Ith

R 100
R 125
R 160
R 160

300A
375A
480A
480A

Im = 5 Ith

F = Front terminals
S3H 160 F F
R 32
250A
S3H 160 F F
R 50
250A
S3H 160 F F
R 80
400A
S3H 160 F F
R 100
500A
S3H 160 F F
R 125
625A
S3H 160 F F
R 160
800A
EF = Extended front
terminals
S3H 160 F EF
R 32
250A
S3H 160 F EF
R 50
250A
S3H 160 F EF
R 80
400A
S3H 160 F EF
R 100
500A
S3H 160 F EF
R 125
625A
S3H 160 F EF
R 160
800A
FC Cu = Front terminals
for copper cables
S3H 160 F FC Cu
R 32
250A
S3H 160 F FC Cu
R 50
250A
S3H 160 F FC Cu
R 80
400A
S3H 160 F FC Cu
R 100
500A
S3H 160 F FC Cu
R 125
625A
S3H 160 F FC Cu
R 160
800A
FC CuAl = Front terminals
for copper/aluminium cables
S3H 160 F FC CuAl
R 32
250A
S3H 160 F FC CuAl
R 50
250A
S3H 160 F FC CuAl
R 80
400A
S3H 160 F FC CuAl
R 100
500A
S3H 160 F FC CuAl
R 125
625A
S3H 160 F FC CuAl
R 160
800A
R = Threaded rear terminals
S3H 160 F R
R 32
250A
S3H 160 F R
R 50
250A
S3H 160 F R
R 80
400A
S3H 160 F R
R 100
500A
S3H 160 F R
R 125
625A
S3H 160 F R
R 160
800A
RC = Rear terminals
for cables
S3H 160 F RC
R 32
250A
S3H 160 F RC
R 50
250A
S3H 160 F RC
R 80
400A
S3H 160 F RC
R 100
500A
S3H 160 F RC
R 125
625A
S3H 160 F RC
R 160
800A
R Res. Cur = Threaded rear terminals +
kit of threaded rear terminals
for residual-current release
installed below the circuit-breaker
S3H 160 F R Res. Cur R 32
250A
S3H 160 F R Res. Cur R 50
250A
S3H 160 F R Res. Cur R 80
400A
S3H 160 F R Res. Cur R 100
500A
S3H 160 F R Res. Cur R 125
625A
S3H 160 F R Res. Cur R 160
800A

ABB SACE

Icu (415 V) =

65 kA

code 1SDA0 . . . . . R1
3 poles
4 poles
48542
48543
48544

48552
48553
48554
48560

code 1SDA0 . . . . . R1
3 poles
4 poles

Im = 10 Ith

code 1SDA0 . . . . . R1
3 poles
4 poles

13407
13409
13411
13413
13415
13417

13431
13433
13435
13437
13439
13441

500A
500A
800A
1000A
1250A
1600A

13395
13397
13399
13401
13403
13405

13419
13421
13423
13425
13427
13429

02089
02091
02093
02095
02097
02099

02689
02691
02693
02695
02697
02699

500A
500A
800A
1000A
1250A
1600A

02077
02079
02081
02083
02085
02087

02677
02679
02681
02683
02685
02687

02239
02241
02243
02245
02247
02249

14268
14270
14272
14274
14276
14278

500A
500A
800A
1000A
1250A
1600A

02227
02229
02231
02233
02235
02237

14256
14258
14260
14262
14264
14266

02364
02366
02368
02370
02372
02374

14343
14345
14347
14349
14351
14353

500A
500A
800A
1000A
1250A
1600A

02352
02354
02356
02358
02360
02362

14331
14333
14335
14337
14339
14341

02664
02666
02668
02670
02672
02674

03139
03141
03143
03145
03147
03149

500A
500A
800A
1000A
1250A
1600A

02652
02654
02656
02658
02660
02662

03127
03129
03131
03133
03135
03137

02514
02516
02518
02520
02522
02524

02989
02991
02993
02995
02997
02999

500A
500A
800A
1000A
1250A
1600A

02502
02504
02506
02508
02510
02512

02977
02979
02981
02983
02985
02987

25483
25485
25487
25489
25491
25493

500A
500A
800A
1000A
1250A
1600A

25471
25473
25475
25477
25479
25481

7
7/15

Order codes
SACE Isomax S3 circuit-breaker

F = FIXED

PSIS9607

Magnetic
release
F = Front terminals
S3H 160 F F
In 50A
S3H 160 F F
In 80A
S3H 160 F F
In 100A
S3H 160 F F
In 125A
S3H 160 F F
In 160A
EF = Extended front
terminals
S3H 160 F EF
In 50A
S3H 160 F EF
In 80A
S3H 160 F EF
In 100A
S3H 160 F EF
In 125A
S3H 160 F EF
In 160A
FC Cu = Front terminals
for copper cables
S3H 160 F FC Cu
In 50A
S3H 160 F FC Cu
In 80A
S3H 160 F FC Cu
In 100A
S3H 160 F FC Cu
In 125A
S3H 160 F FC Cu
In 160A
FC CuAl = Front terminals
for copper/aluminium cables
S3H 160 F FC CuAl
In 50A
S3H 160 F FC CuAl
In 80A
S3H 160 F FC CuAl
In 100A
S3H 160 F FC CuAl
In 125A
S3H 160 F FC CuAl
In 160A
R = Threaded rear terminals
S3H 160 F R
In 50A
S3H 160 F R
In 80A
S3H 160 F R
In 100A
S3H 160 F R
In 125A
S3H 160 F R
In 160A
RC = Rear terminals
for cables
S3H 160 F RC
In 50A
S3H 160 F RC
In 80A
S3H 160 F RC
In 100A
S3H 160 F RC
In 125A
S3H 160 F RC
In 160A

Im = 5 Ith

code 1SDA0 . . . . . R1
3 poles
4 poles

250A
400A

25841
25843

25913
25915

625A

25847

25919

250A
400A

28530
28532

30306
30308

625A

28536

30312

250A
400A

28674
28676

30450
30452

625A

28680

30456

250A
400A

28818
28820

30594
30596

625A

28824

30600

250A
400A

29106
29108

30882
30884

625A

29112

30888

250A
400A

28962
28964

30738
30740

625A

28968

30744

Im = 10 Ith

code 1SDA0 . . . . . R1
3 poles
4 poles

500A
800A
1000A
1250A
1600A

25829
25831
25833
25835
25837

25901
25903
25905
25907
25909

500A
800A
1000A
1250A
1600A

28518
28520
28522
28524
28526

30294
30296
30298
30300
30302

500A
800A
1000A
1250A
1600A

28662
28664
28666
28668
28670

30438
30440
30442
30444
30446

500A
800A
1000A
1250A
1600A

28806
28808
28810
28812
28814

30582
30584
30586
30588
30590

500A
800A
1000A
1250A
1600A

29094
29096
29098
29100
29102

30870
30872
30874
30876
30878

500A
800A
1000A
1250A
1600A

28950
28952
28954
28956
28958

30726
30728
30730
30732
30734

7
7/16

ABB SACE

Order codes
SACE Isomax S3 circuit-breaker

F = FIXED

S3L 160

PSIS9607

Thermomagnetic
release

Iu (40 C) =

160 A

Im = 5 Ith

F = Front terminals
S3L 160 F F
R 32
250A
S3L 160 F F
R 50
250A
S3L 160 F F
R 80
400A
S3L 160 F F
R 100
500A
S3L 160 F F
R 125
625A
S3L 160 F F
R 160
800A
EF = Extended front
terminals
S3L 160 F EF
R 32
250A
S3L 160 F EF
R 50
250A
S3L 160 F EF
R 80
400A
S3L 160 F EF
R 100
500A
S3L 160 F EF
R 125
625A
S3L 160 F EF
R 160
800A
FC Cu = Front terminals
for copper cables
S3L 160 F FC Cu
R 32
250A
S3L 160 F FC Cu
R 50
250A
S3L 160 F FC Cu
R 80
400A
S3L 160 F FC Cu
R 100
500A
S3L 160 F FC Cu
R 125
625A
S3L 160 F FC Cu
R 160
800A
FC CuAl = Front terminals
for copper/aluminium cables
S3L 160 F FC CuAl
R 32
250A
S3L 160 F FC CuAl
R 50
250A
S3L 160 F FC CuAl
R 80
400A
S3L 160 F FC CuAl
R 100
500A
S3L 160 F FC CuAl
R 125
625A
S3L 160 F FC CuAl
R 160
800A
R = Threaded rear terminals
S3L 160 F R
R 32
250A
S3L 160 F R
R 50
250A
S3L 160 F R
R 80
400A
S3L 160 F R
R 100
500A
S3L 160 F R
R 125
625A
S3L 160 F R
R 160
800A
RC = Rear terminals
for cables
S3L 160 F RC
R 32
250A
S3L 160 F RC
R 50
250A
S3L 160 F RC
R 80
400A
S3L 160 F RC
R 100
500A
S3L 160 F RC
R 125
625A
S3L 160 F RC
R 160
800A
R Res. Cur = Threaded rear terminals +
kit of threaded rear terminals
for residual-current release
installed below the circuit-breaker
S3L 160 F R Res. Cur R 32
250A
S3L 160 F R Res. Cur R 50
250A
S3L 160 F R Res. Cur R 80
400A
S3L 160 F R Res. Cur R 100
500A
S3L 160 F R Res. Cur R 125
625A
S3L 160 F R Res. Cur R 160
800A

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles

85 kA
Im = 10 Ith

code 1SDA0 . . . . . R1
3 poles
4 poles

13455
13457
13459
13461
13463
13465

13479
13481
13483
13485
13487
13489

500A
500A
800A
1000A
1250A
1600A

13443
13445
13447
13449
13451
13453

13467
13469
13471
13473
13475
13477

03264
03266
14486
03269
03271
03273

03864
03866
14511
03869
03871
03873

500A
500A
800A
1000A
1250A
1600A

03252
03254
03256
03258
03260
03262

03852
03854
03856
03858
03860
03862

03408
03410
14492
03413
03415
03417

04008
04010
14517
04013
04015
04017

500A
500A
800A
1000A
1250A
1600A

03396
03398
03400
03402
03404
03406

03996
03998
04000
04002
04004
04006

03552
03554
14498
03557
03559
03561

04152
04154
14523
04157
04159
04161

500A
500A
800A
1000A
1250A
1600A

03540
03542
03544
03546
03548
03550

04140
04142
04144
04146
04148
04150

03840
03842
14510
03845
03847
03849

04440
04442
14535
04445
04447
04449

500A
500A
800A
1000A
1250A
1600A

03828
03830
03832
03834
03836
03838

04428
04430
04432
04434
04436
04438

03696
03698
14504
03701
03703
03705

04296
04298
14529
04301
04303
04305

500A
500A
800A
1000A
1250A
1600A

03684
03686
03688
03690
03692
03694

04284
04286
04288
04290
04292
04294

25507
25509
25511
25513
25515
25517

500A
500A
800A
1000A
1250A
1600A

25495
25497
25499
25501
25503
25505

7
ABB SACE

7/17

Order codes
SACE Isomax S3 circuit-breaker

F = FIXED

PSIS9607

Magnetic
release
F = Front terminals
S3L 160 F F
In 50A
S3L 160 F F
In 80A
S3L 160 F F
In 100A
S3L 160 F F
In 125A
S3L 160 F F
In 160A
EF = Extended front
terminals
S3L 160 F EF
In 50A
S3L 160 F EF
In 80A
S3L 160 F EF
In 100A
S3L 160 F EF
In 125A
S3L 160 F EF
In 160A
FC Cu = Front terminals
for copper cables
S3L 160 F FC Cu
In 50A
S3L 160 F FC Cu
In 80A
S3L 160 F FC Cu
In 100A
S3L 160 F FC Cu
In 125A
S3L 160 F FC Cu
In 160A
FC CuAl = Front terminals
for copper/aluminium cables
S3L 160 F FC CuAl
In 50A
S3L 160 F FC CuAl
In 80A
S3L 160 F FC CuAl
In 100A
S3L 160 F FC CuAl
In 125A
S3L 160 F FC CuAl
In 160A
R = Threaded rear terminals
S3L 160 F R
In 50A
S3L 160 F R
In 80A
S3L 160 F R
In 100A
S3L 160 F R
In 125A
S3L 160 F R
In 160A
RC = Rear terminals
for cables
S3L 160 F RC
In 50A
S3L 160 F RC
In 80A
S3L 160 F RC
In 100A
S3L 160 F RC
In 125A
S3L 160 F RC
In 160A

Im = 5 Ith

code 1SDA0 . . . . . R1
3 poles
4 poles

250A
400A

25865
25867

25937
25939

625A

25871

25943

250A
400A

29130
29132

30906
30908

625A

29136

30912

250A
400A

29274
29276

31050
31052

625A

29280

31056

250A
400A

29418
29420

31170
31172

625A

29424

31176

250A
400A

44388
44390

31458
31460

625A

44394

31464

250A
400A

29562
29564

31314
31316

625A

29568

31320

Im = 10 Ith

code 1SDA0 . . . . . R1
3 poles
4 poles

500A
800A
1000A
1250A
1600A

25853
25855
25857
25859
25861

25925
25927
25929
25931
25933

500A
800A
1000A
1250A
1600A

29118
29120
29122
29124
29126

30894
30896
30898
30900
30902

500A
800A
1000A
1250A
1600A

29262
29264
29266
29268
29270

31038
31040
31042
31044
31046

500A
800A
1000A
1250A
1600A

29406
29408
29410
29412
29414

31158
31160
31162
31164
31166

500A
800A
1000A
1250A
1600A

44376
44378
44380
44382
44384

31446
31448
31450
31452
31454

500A
800A
1000A
1250A
1600A

29550
29552
29554
29556
29558

31302
31304
31306
31308
31310

7
7/18

ABB SACE

Order codes
SACE Isomax S3 circuit-breaker

P = PLUG-IN

Moving part
S3N 160
Iu (40 C) = 160 A
PSIS9607

Thermomagnetic
release
S3N 160 P MP
S3N 160 P MP
S3N 160 P MP
S3N 160 P MP
S3N 160 P MP
S3N 160 P MP

Im = 5 Ith

R 32
R 50
R 80
R 100
R 125
R 160

Magnetic
release
S3N 160 P MP
S3N 160 P MP
S3N 160 P MP
S3N 160 P MP
S3N 160 P MP

Im = 5 Ith

In
In
In
In
In

S3H 160

50A
80A
100A
125A
160A

Magnetic
release
S3H 160 P MP
S3H 160 P MP
S3H 160 P MP
S3H 160 P MP
S3H 160 P MP

S3L 160

50A
80A
100A
125A
160A

S3L 160 P MP
S3L 160 P MP
S3L 160 P MP
S3L 160 P MP
S3L 160 P MP
S3L 160 P MP

Magnetic
release
S3L 160 P MP
S3L 160 P MP
S3L 160 P MP
S3L 160 P MP
S3L 160 P MP

31488

31536

160 A

250A
250A
400A
500A
625A
800A

50A
80A
100A
125A
160A

code 1SDA0 . . . . . R1
3 poles
4 poles
03164
03166
03168
03170
03172
03174

03214
03216
03218
03220
03222
03224

code 1SDA0 . . . . . R1
3 poles
4 poles
31578
31580

31626
31628

625A

31584

31632

160 A

250A
250A
400A
500A
625A
800A

Im = 5 Ith

In
In
In
In
In

Icu (415 V) =

250A
400A

Im = 5 Ith

R 32
R 50
R 80
R 100
R 125
R 160

code 1SDA0 . . . . . R1
3 poles
4 poles

625A

Iu (40 C) =

Thermomagnetic
release

02039
02041
02043
02045
02047
02049

31530
31532

Im = 5 Ith

In
In
In
In
In

01989
01991
01993
01995
01997
01999

31482
31484

Im = 5 Ith

R 32
R 50
R 80
R 100
R 125
R 160

code 1SDA0 . . . . . R1
3 poles
4 poles

250A
400A

Iu (40 C) =

Thermomagnetic
release
S3H 160 P MP
S3H 160 P MP
S3H 160 P MP
S3H 160 P MP
S3H 160 P MP
S3H 160 P MP

250A
250A
400A
500A
625A
800A

Icu (415 V) =

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles
04464
04466
14536
04469
04471
04473

04512
04514
14538
04517
04519
04521

code 1SDA0 . . . . . R1
3 poles
4 poles

250A
400A

31674
31676

31722
31724

625A

31680

31728

35 kA
Im = 10 Ith

500A
500A
800A
1000A
1250A
1600A

Im = 10 Ith

500A
800A
1000A
1250A
1600A

code 1SDA0 . . . . . R1
3 poles
4 poles
01977
01979
01981
01983
01985
01987

02027
02029
02031
02033
02035
02037

code 1SDA0 . . . . . R1
3 poles
4 poles
31470
31472
31474
31476
31478

31518
31520
31522
31524
31526

65 kA
Im = 10 Ith

500A
500A
800A
1000A
1250A
1600A

Im = 10 Ith

500A
800A
1000A
1250A
1600A

code 1SDA0 . . . . . R1
3 poles
4 poles
03152
03154
03156
03158
03160
03162

03202
03204
03206
03208
03210
03212

code 1SDA0 . . . . . R1
3 poles
4 poles
31566
31568
31570
31572
31574

31614
31616
31618
31620
31622

85 kA
Im = 10 Ith

500A
500A
800A
1000A
1250A
1600A

Im = 10 Ith

500A
800A
1000A
1250A
1600A

code 1SDA0 . . . . . R1
3 poles
4 poles
04452
04454
04456
04458
04460
04462

04500
04502
04504
04506
04508
04510

code 1SDA0 . . . . . R1
3 poles
4 poles
31662
31664
31666
31668
31670

31710
31712
31714
31716
31718

7
ABB SACE

7/19

Order codes
SACE Isomax S3 circuit-breaker

W = WITHDRAWABLE Moving part


S3N 160
Iu (40 C) = 160 A
PSIS9607

Thermomagnetic
release
S3N 160 W MP
S3N 160 W MP
S3N 160 W MP
S3N 160 W MP
S3N 160 W MP
S3N 160 W MP

Im = 5 Ith

R 32
R 50
R 80
R 100
R 125
R 160

Magnetic
release
S3N 160 W MP
S3N 160 W MP
S3N 160 W MP
S3N 160 W MP
S3N 160 W MP

Im = 5 Ith

In
In
In
In
In

S3H 160

50A
80A
100A
125A
160A

Magnetic
release
S3H 160 W MP
S3H 160 W MP
S3H 160 W MP
S3H 160 W MP
S3H 160 W MP

S3L 160

50A
80A
100A
125A
160A

S3L 160 W MP
S3L 160 W MP
S3L 160 W MP
S3L 160 W MP
S3L 160 W MP
S3L 160 W MP

Magnetic
release
S3L 160 W MP
S3L 160 W MP
S3L 160 W MP
S3L 160 W MP
S3L 160 W MP

31512

31560

160 A

250A
250A
400A
500A
625A
800A

50A
80A
100A
125A
160A

code 1SDA0 . . . . . R1
3 poles
4 poles
03189
03191
03193
03195
03197
03199

03239
03241
03243
03245
03247
03249

code 1SDA0 . . . . . R1
3 poles
4 poles
31602
31604

31650
31652

625A

31608

31656

160 A

250A
250A
400A
500A
625A
800A

Im = 5 Ith

In
In
In
In
In

Icu (415 V) =

250A
400A

Im = 5 Ith

R 32
R 50
R 80
R 100
R 125
R 160

code 1SDA0 . . . . . R1
3 poles
4 poles

625A

Iu (40 C) =

Thermomagnetic
release

02064
02066
02068
02070
02072
02074

31554
31556

Im = 5 Ith

In
In
In
In
In

02014
02016
02018
02020
02022
02024

31506
31508

Im = 5 Ith

R 32
R 50
R 80
R 100
R 125
R 160

code 1SDA0 . . . . . R1
3 poles
4 poles

250A
400A

Iu (40 C) =

Thermomagnetic
release
S3H 160 W MP
S3H 160 W MP
S3H 160 W MP
S3H 160 W MP
S3H 160 W MP
S3H 160 W MP

250A
250A
400A
500A
625A
800A

Icu (415 V) =

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles
04488
04490
14537
04493
04495
04497

04536
04538
14539
04541
04543
04545

code 1SDA0 . . . . . R1
3 poles
4 poles

250A
400A

31698
31700

31746
31748

625A

31704

31752

35 kA
Im = 10 Ith

500A
500A
800A
1000A
1250A
1600A

Im = 10 Ith

500A
800A
1000A
1250A
1600A

code 1SDA0 . . . . . R1
3 poles
4 poles
02002
02004
02006
02008
02010
02012

02052
02054
02056
02058
02060
02062

code 1SDA0 . . . . . R1
3 poles
4 poles
31494
31496
31498
31500
31502

31542
31544
31546
31548
31550

65 kA
Im = 10 Ith

500A
500A
800A
1000A
1250A
1600A

Im = 10 Ith

500A
800A
1000A
1250A
1600A

code 1SDA0 . . . . . R1
3 poles
4 poles
03177
03179
03181
03183
03185
03187

03227
03229
03231
03233
03235
03237

code 1SDA0 . . . . . R1
3 poles
4 poles
31590
31592
31594
31596
31598

31638
31640
31642
31644
31646

85 kA
Im = 10 Ith

500A
500A
800A
1000A
1250A
1600A

Im = 10 Ith

500A
800A
1000A
1250A
1600A

code 1SDA0 . . . . . R1
3 poles
4 poles
04476
04478
04480
04482
04484
04486

04524
04526
04528
04530
04532
04534

code 1SDA0 . . . . . R1
3 poles
4 poles
31686
31688
31690
31692
31694

31734
31736
31738
31740
31742

7
7/20

ABB SACE

Order codes
SACE Isomax S3 circuit-breaker

F = FIXED

S3N 250

Iu (40 C) =

PSIS9607

Thermomagnetic
release
F = Front terminals
S3N 250 F F
S3N 250 F F
S3N 250 F F (N50%)
S3N 250 F F (N50%)

250 A

Im = 3 Ith

R 200
R 250
R 200
R 250

Thermomagnetic
release

600A
750A
600A
750A

Im = 5 Ith

F = Front terminals
S3N 250 F F
R 200
1000A
S3N 250 F F
R 250
1250A
EF = Extended front
terminals
S3N 250 F EF
R 200
1000A
S3N 250 F EF
R 250
1250A
FC Cu = Front terminals
for copper cables
S3N 250 F FC Cu
R 200
1000A
S3N 250 F FC Cu
R 250
1250A
FC CuAl = Front terminals
for copper/aluminium cables
S3N 250 F FC CuAl
R 200
1000A
S3N 250 F FC CuAl
R 250
1250A
R = Threaded rear terminals
S3N 250 F R
R 200
1000A
S3N 250 F R
R 250
1250A
RC = Rear terminals
for cables
S3N 250 F RC
R 200
1000A
S3N 250 F RC
R 250
1250A
R Res. Cur = Threaded rear terminals +
kit of threaded rear terminals
for residual-current release
installed below the circuit-breaker
S3N 250 F R Res. Cur R 200
1000A
S3N 250 F R Res. Cur R 250
1250A

Magnetic
release
F = Front terminals
S3N 250 F F
In 200A
S3N 250 F F
In 250A
EF = Extended front
terminals
S3N 250 F EF
In 200A
S3N 250 F EF
In 250A
FC Cu = Front terminals
for copper cables
S3N 250 F FC Cu
In 200A
S3N 250 F FC Cu
In 250A
FC CuAl = Front terminals
for copper/aluminium cables
S3N 250 F FC CuAl
In 200A
S3N 250 F FC CuAl
In 250A
R = Threaded rear terminals
S3N 250 F R
In 200A
S3N 250 F R
In 250A
RC = Rear terminals
for cables
S3N 250 F RC
In 200A
S3N 250 F RC
In 250A

Icu (415 V) =

35 kA

code 1SDA0 . . . . . R1
3 poles
4 poles
48545
48546

48555
48556
48561
48562

code 1SDA0 . . . . . R1
3 poles
4 poles

Im = 10 Ith

code 1SDA0 . . . . . R1
3 poles
4 poles

13495
13497

13503
13505

2000A
2500A

13491
13493

13499
13501

04552
04554

04777
04779

2000A
2500A

04548
04550

04773
04775

04606
04608

14419
14421

2000A
2500A

04602
04604

14415
14417

04660
04662

14455
14457

2000A
2500A

04656
04658

14451
14453

04768
04770

04912
04914

2000A
2500A

04764
04766

04908
04910

04714
04716

04858
04860

2000A
2500A

04710
04712

04854
04856

25523
25525

2000A
2500A

Im = 10 Ith

25519
25521

code 1SDA0 . . . . . R1
3 poles
4 poles

2000A
2500A

27388
27390

27476
27478

2000A
2500A

31756
31758

32337
32339

2000A
2500A

31804
31806

32385
32387

2000A
2500A

31844
31846

32433
32435

2000A
2500A

31940
31942

32529
32531

2000A
2500A

31892
31894

32481
32483

7
ABB SACE

7/21

Order codes
SACE Isomax S3 circuit-breaker

F = FIXED

S3H 250

Iu (40 C) =

PSIS9607

Thermomagnetic
release
F = Front terminals
S3H 250 F F
S3H 250 F F
S3H 250 F F (N50%)
S3H 250 F F (N50%)

250 A

Im = 3 Ith

R 200
R 250
R 200
R 250

Thermomagnetic
release

600A
750A
600A
750A

Im = 5 Ith

F = Front terminals
S3H 250 F F
R 200
1000A
S3H 250 F F
R 250
1250A
EF = Extended front
terminals
S3H 250 F EF
R 200
1000A
S3H 250 F EF
R 250
1250A
FC Cu = Front terminals
for copper cables
S3H 250 F FC Cu
R 200
1000A
S3H 250 F FC Cu
R 250
1250A
FC CuAl = Front terminals
for copper/aluminium cables
S3H 250 F FC CuAl
R 200
1000A
S3H 250 F FC CuAl
R 250
1250A
R = Threaded rear terminals
S3H 250 F R
R 200
1000A
S3H 250 F R
R 250
1250A
RC = Rear terminals
for cables
S3H 250 F RC
R 200
1000A
S3H 250 F RC
R 250
1250A
R Res. Cur = Threaded rear terminals +
kit of threaded rear terminals
for residual-current release
installed below the circuit-breaker
S3H 250 F R Res. Cur R 200
1000A
S3H 250 F R Res. Cur R 250
1250A

Magnetic
release
F = Front terminals
S3H 250 F F
In 200A
S3H 250 F F
In 250A
EF = Extended front
terminals
S3H 250 F EF
In 200A
S3H 250 F EF
In 250A
FC Cu = Front terminals
for copper cables
S3H 250 F FC Cu
In 200A
S3H 250 F FC Cu
In 250A
FC CuAl = Front terminals
for copper/aluminium cables
S3H 250 F FC CuAl
In 200A
S3H 250 F FC CuAl
In 250A
R = Threaded rear terminals
S3H 250 F R
In 200A
S3H 250 F R
In 250A
RC = Rear terminals
for cables
S3H 250 F RC
In 200A
S3H 250 F RC
In 250A

Icu (415 V) =

65 kA

code 1SDA0 . . . . . R1
3 poles
4 poles
48547
48548

48557
48558
48563
48564

code 1SDA0 . . . . . R1
3 poles
4 poles

Im = 10 Ith

code 1SDA0 . . . . . R1
3 poles
4 poles

13511
13513

13519
13521

2000A
2500A

13507
13509

13515
13517

04957
04959

05182
05184

2000A
2500A

04953
04955

05178
05180

05011
05013

05236
05238

2000A
2500A

05007
05009

05232
05234

05065
05067

05290
05292

2000A
2500A

05061
05063

05286
05288

05173
05175

05398
05400

2000A
2500A

05169
05171

05394
05396

05119
05121

05344
05346

2000A
2500A

05115
05117

05340
05342

25531
25533

2000A
2500A

Im = 10 Ith

25527
25529

code 1SDA0 . . . . . R1
3 poles
4 poles

2000A
2500A

27564
27566

27652
27654

2000A
2500A

31948
31950

32537
32539

2000A
2500A

31996
31998

32585
32587

2000A
2500A

32044
32046

32633
32635

2000A
2500A

32097
32099

32729
32732

2000A
2500A

32089
32091

32681
32683

7
7/22

ABB SACE

Order codes
SACE Isomax S3 circuit-breaker

F = FIXED

S3L 250

Iu (40 C) =

PSIS9607

Thermomagnetic
release

250 A

Im = 5 Ith

F = Front terminals
S3L 250 F F
R 200
1000A
S3L 250 F F
R 250
1250A
EF = Extended front
terminals
S3L 250 F EF
R 200
1000A
S3L 250 F EF
R 250
1250A
FC Cu = Front terminals
for copper cables
S3L 250 F FC Cu
R 200
1000A
S3L 250 F FC Cu
R 250
1250A
FC CuAl = Front terminals
for copper/aluminium cables
S3L 250 F FC CuAl
R 200
1000A
S3L 250 F FC CuAl
R 250
1250A
R = Threaded rear terminals
S3L 250 F R
R 200
1000A
S3L 250 F R
R 250
1250A
RC = Rear terminals
for cables
S3L 250 F RC
R 200
1000A
S3L 250 F RC
R 250
1250A
R Res. Cur = Threaded rear terminals +
kit of threaded rear terminals
for residual-current release
installed below the circuit-breaker
S3L 250 F R Res. Cur R 200
1000A
S3L 250 F R Res. Cur R 250
1250A

Magnetic
release
F = Front terminals
S3L 250 F F
In 200A
S3L 250 F F
In 250A
EF = Extended front
terminals
S3L 250 F EF
In 200A
S3L 250 F EF
In 250A
FC Cu = Front terminals
for copper cables
S3L 250 F FC Cu
In 200A
S3L 250 F FC Cu
In 250A
FC CuAl = Front terminals
for copper/aluminium cables
S3L 250 F FC CuAl
In 200A
S3L 250 F FC CuAl
In 250A
R = Threaded rear terminals
S3L 250 F R
In 200A
S3L 250 F R
In 250A
RC = Rear terminals
for cables
S3L 250 F RC
In 200A
S3L 250 F RC
In 250A

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles

85 kA
Im = 10 Ith

code 1SDA0 . . . . . R1
3 poles
4 poles

13527
13529

13535
13537

2000A
2500A

13523
13525

13531
13533

05443
05445

05668
05670

2000A
2500A

05439
05441

05664
05666

05497
05499

05722
05724

2000A
2500A

05493
05495

05718
05720

05551
05553

05776
05778

2000A
2500A

05547
05549

05772
05774

05659
05661

05884
05886

2000A
2500A

05655
05657

05880
05882

05605
05607

05830
05832

2000A
2500A

05601
05603

05826
05828

25539
25541

2000A
2500A

Im = 10 Ith

25535
25537

code 1SDA0 . . . . . R1
3 poles
4 poles

2000A
2500A

27748
27750

27828
27830

2000A
2500A

32137
32139

32737
32739

2000A
2500A

32185
32187

32785
32787

2000A
2500A

32233
32235

32833
32835

2000A
2500A

32329
32331

32921
32923

2000A
2500A

32281
32283

32761
32763

7
ABB SACE

7/23

Order codes
SACE Isomax S3 circuit-breaker

P = PLUG-IN

Moving part
S3N 250
Iu (40 C) = 250 A
PSIS9607

Thermomagnetic
release
S3N 250 P MP
S3N 250 P MP

R 200
R 250

Icu (415 V) =

Im = 5 Ith

code 1SDA0 . . . . . R1
3 poles
4 poles

1000A
1250A

04921
04923

04939
04941

Magnetic
release
S3N 250 P MP
S3N 250 P MP

S3H 250

In 200A
In 250A

S3L 250

Iu (40 C) =

R 200
R 250

250 A

Icu (415 V) =

Im = 5 Ith

code 1SDA0 . . . . . R1
3 poles
4 poles

1000A
1250A

05407
05409

05425
05427

In 200A
In 250A

R 200
R 250

Magnetic
release
S3L 250 P MP
S3L 250 P MP

Im = 10 Ith

2000A
2500A

2000A
2500A

Iu (40 C) =

250 A

Icu (415 V) =

Im = 5 Ith

code 1SDA0 . . . . . R1
3 poles
4 poles

1000A
1250A

05893
05895

05911
05913

04917
04919

04935
04937

code 1SDA0 . . . . . R1
3 poles
4 poles
32929
32931

32945
32947

code 1SDA0 . . . . . R1
3 poles
4 poles
05403
05405

05421
05423

code 1SDA0 . . . . . R1
3 poles
4 poles
32961
32963

32977
32979

85 kA
Im = 10 Ith

2000A
2500A

Im = 10 Ith

In 200A
In 250A

code 1SDA0 . . . . . R1
3 poles
4 poles

65 kA

Im = 10 Ith

Thermomagnetic
release
S3L 250 P MP
S3L 250 P MP

2000A
2500A

2000A
2500A

Magnetic
release
S3H 250 P MP
S3H 250 P MP

Im = 10 Ith

Im = 10 Ith

Thermomagnetic
release
S3H 250 P MP
S3H 250 P MP

35 kA

2000A
2500A

code 1SDA0 . . . . . R1
3 poles
4 poles
05889
05891

05907
05909

code 1SDA0 . . . . . R1
3 poles
4 poles
32993
32995

33009
33011

7
7/24

ABB SACE

Order codes
SACE Isomax S3 circuit-breaker

W = WITHDRAWABLE Moving part


S3N 250
Iu (40 C) = 250 A
PSIS9607

Thermomagnetic
release
S3N 250 W MP
S3N 250 W MP

R 200
R 250

Icu (415 V) =

Im = 5 Ith

code 1SDA0 . . . . . R1
3 poles
4 poles

1000A
1250A

04930
04932

04948
04950

Magnetic
release
S3N 250 W MP
S3N 250 W MP

S3H 250

In 200A
In 250A

S3L 250

Iu (40 C) =

R 200
R 250

250 A

Icu (415 V) =

Im = 5 Ith

code 1SDA0 . . . . . R1
3 poles
4 poles

1000A
1250A

05416
05418

05434
05436

In 200A
In 250A

R 200
R 250

Magnetic
release
S3L 250 W MP
S3L 250 W MP

Im = 10 Ith

2000A
2500A

2000A
2500A

Iu (40 C) =

250 A

Icu (415 V) =

Im = 5 Ith

code 1SDA0 . . . . . R1
3 poles
4 poles

1000A
1250A

05902
05904

05920
05922

04926
04928

04944
04946

code 1SDA0 . . . . . R1
3 poles
4 poles
32937
32939

32953
32955

code 1SDA0 . . . . . R1
3 poles
4 poles
05412
05414

05430
05432

code 1SDA0 . . . . . R1
3 poles
4 poles
32969
32971

32985
32987

85 kA
Im = 10 Ith

2000A
2500A

Im = 10 Ith

In 200A
In 250A

code 1SDA0 . . . . . R1
3 poles
4 poles

65 kA

Im = 10 Ith

Thermomagnetic
release
S3L 250 W MP
S3L 250 W MP

2000A
2500A

2000A
2500A

Magnetic
release
S3H 250 W MP
S3H 250 W MP

Im = 10 Ith

Im = 10 Ith

Thermomagnetic
release
S3H 250 W MP
S3H 250 W MP

35 kA

2000A
2500A

code 1SDA0 . . . . . R1
3 poles
4 poles
05898
05900

05916
05918

code 1SDA0 . . . . . R1
3 poles
4 poles
33001
33003

33017
33019

7
ABB SACE

7/25

Order codes
SACE Isomax S4 circuit-breaker

F = FIXED

S4N 160

Iu (40 C) =

PR211
P

PSIS9610

Microprocessor-based
release
F = Front terminals
S4N 160 F F

In 100 A

S4N 160 F F

In 160 A

EF = Extended front
terminals
S4N 160 F EF

In 100 A

S4N 160 F EF

In 160 A

FC Cu = Front terminals
for copper cables
S4N 160 F FC Cu
In 100 A
S4N 160 F FC Cu

In 160 A

FC CuAl = Front terminals


for copper/aluminium cables
S4N 160 F FC CuAl
In 100 A
S4N 160 F FC CuAl

In 160 A

R = Threaded rear terminals


S4N 160 F R
In 100 A
S4N 160 F R

In 160 A

RC = Rear terminals
for cables
S4N 160 F RC

In 100 A

S4N 160 F RC

In 160 A

S4H 160

S4H 160 F F

In 160 A

EF = Extended front
terminals
S4H 160 F EF

In 100 A

S4H 160 F EF

In 160 A

FC Cu = Front terminals
for copper cables
S4H 160 F FC Cu
In 100 A
S4H 160 F FC Cu

In 160 A

FC CuAl = Front terminals


for copper/aluminium cables
S4H 160 F FC CuAl
In 100 A
S4H 160 F FC CuAl

7
7/26

In 160 A

code 1SDA0 . . . . . R1
3 poles
4 poles

35 kA
PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles

15548
15550
15549
15551

15836
15838
15837
15839

LSI
LSIG
LSI
LSIG

15553
15558
15554
15559

15841
15846
15842
15847

I
LI
I
LI

15632
15633
05924
05925

15920
15921
06080
06081

LSI
LSIG
LSI
LSIG

15635
15637
05926
05929

15923
15925
06082
06085

I
LI
I
LI

15680
15681
05960
05961

15968
15969
06116
06117

LSI
LSIG
LSI
LSIG

15683
15685
05962
05965

15971
15973
06118
06121

I
LI
I
LI

15728
15729
05996
05997

16016
16017
06152
06153

LSI
LSIG
LSI
LSIG

15731
15733
05998
06001

16019
16021
06154
06157

I
LI
I
LI

15830
15831
06074
06075

16112
16113
06224
06225

LSI
LSIG
LSI
LSIG

15833
15835
06076
06079

16115
16117
06226
06229

I
LI
I
LI

15782
15783
06038
06039

16064
16065
06188
06189

LSI
LSIG
LSI
LSIG

15785
15787
06040
06043

16067
16069
06190
06193

160 A

PR211
P

Microprocessor-based
release
In 100 A

Icu (415 V) =

I
LI
I
LI

Iu (40 C) =

F = Front terminals
S4H 160 F F

160 A

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles

65 kA
PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles

I
LI
I
LI

16142
16144
16143
16145

16424
16426
16425
16427

LSI
LSIG
LSI
LSIG

16146
16152
16147
16153

16428
16434
16429
16435

I
LI
I
LI

16226
16227
06254
06255

16508
16509
06404
06405

LSI
LSIG
LSI
LSIG

16228
16231
06256
06259

16510
16513
06406
06409

I
LI
I
LI

16274
16275
06290
06291

16556
16557
06440
06441

LSI
LSIG
LSI
LSIG

16276
16279
06292
06295

16558
16561
06442
06445

I
LI
I
LI

16322
16323
06326
06327

16604
16605
06476
06477

LSI
LSIG
LSI
LSIG

16324
16327
06328
06331

16606
16609
06478
06481

ABB SACE

Order codes
SACE Isomax S4 circuit-breaker

F = FIXED

PR211
P

Microprocessor-based
release

PSIS9610

R = Threaded rear terminals


S4H 160 F R
In 100 A
S4H 160 F R

In 160 A

RC = Rear terminals
for cables
S4H 160 F RC

In 100 A

S4H 160 F RC

In 160 A

S4L 160

S4L 160 F F

In 160 A

EF = Extended front
terminals
S4L 160 F EF

In 100 A

S4L 160 F EF

In 160 A

FC Cu = Front terminals
for copper cables
S4L 160 F FC Cu
In 100 A
S4L 160 F FC Cu

In 160 A

FC CuAl = Front terminals


for copper/aluminium cables
S4L 160 F FC CuAl
In 100 A
S4L 160 F FC CuAl

In 160 A

R = Threaded rear terminals


S4L 160 F R
In 100 A
S4L 160 F R

In 160 A

RC = Rear terminals
for cables
S4L 160 F RC

In 100 A

S4L 160 F RC

In 160 A

code 1SDA0 . . . . . R1
3 poles
4 poles

16418
16419
06398
06399

16700
16701
06548
06549

LSI
LSIG
LSI
LSIG

16420
16423
06400
06403

16702
16705
06550
06553

I
LI
I
LI

16370
16371
06362
06363

16652
16653
06512
06513

LSI
LSIG
LSI
LSIG

16372
16375
06364
06367

16654
16657
06514
06517

160 A

PR211
P

Microprocessor-based
release
In 100 A

PR212
P

I
LI
I
LI

Iu (40 C) =

F = Front terminals
S4L 160 F F

code 1SDA0 . . . . . R1
3 poles
4 poles

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles

100 kA
PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles

I
LI
I
LI

16730
16732
16731
16733

17012
17014
17013
17015

LSI
LSIG
LSI
LSIG

16734
16740
16735
16741

17016
17022
17017
17023

I
LI
I
LI

16814
16815
06578
06579

17096
17097
06728
06729

LSI
LSIG
LSI
LSIG

16816
16819
06580
06583

17098
17101
06730
06733

I
LI
I
LI

16862
16863
06614
06615

17144
17145
06764
06765

LSI
LSIG
LSI
LSIG

16864
16867
06616
06619

17146
17149
06766
06769

I
LI
I
LI

16910
16911
06650
06651

17192
17193
06800
06801

LSI
LSIG
LSI
LSIG

16912
16915
06652
06655

17194
17197
06802
06805

I
LI
I
LI

17006
17007
06722
06723

17288
17289
06872
06873

LSI
LSIG
LSI
LSIG

17008
17011
06724
06727

17290
17293
06874
06877

I
LI
I
LI

16958
16959
06686
06687

17240
17241
06836
06837

LSI
LSIG
LSI
LSIG

16960
16963
06688
06691

17242
17245
06838
06841

7
ABB SACE

7/27

Order codes
SACE Isomax S4 circuit-breaker

P = PLUG-IN

Moving part
S4N 160
Iu (40 C) = 160 A
PR211
P

Microprocessor-based
release
In 100 A

S4N 160 P MP

In 160 A

PSIS9610

S4N 160 P MP

S4H 160

I
LI
I
LI

S4H 160 P MP

In 100 A

S4H 160 P MP

In 160 A

S4L 160

I
LI
I
LI

In 100 A

S4L 160 P MP

In 160 A

160 A

PR211
P

Microprocessor-based
release
I
LI
I
LI

17294
17295
06878
06879

PR211
P

In 100 A

S4N 160 W MP

In 160 A

PSIS9610

S4N 160 W MP

S4H 160

I
LI
I
LI

S4H 160 W MP

In 100 A

S4H 160 W MP

In 160 A

S4L 160

I
LI
I
LI

7
7/28

In 100 A

S4L 160 W MP

In 160 A

160 A

PR211
P

Microprocessor-based
release
I
LI
I
LI

Icu (415 V) =

17306
17307
06890
06891

Icu (415 V) =

16136
16137
06248
06249

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles
16712
16713
06560
06561

Iu (40 C) =

S4L 160 W MP

160 A

PR211
P

Microprocessor-based
release

16718
16719
06566
06567

code 1SDA0 . . . . . R1
3 poles
4 poles
16124
16125
06236
06237

Iu (40 C) =

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles

W = WITHDRAWABLE Moving part


S4N 160
Iu (40 C) = 160 A
Microprocessor-based
release

16130
16131
06242
06243

code 1SDA0 . . . . . R1
3 poles
4 poles
16706
16707
06554
06555

Iu (40 C) =

S4L 160 P MP

160 A

PR211
P

Microprocessor-based
release

code 1SDA0 . . . . . R1
3 poles
4 poles
16118
16119
06230
06231

Iu (40 C) =

Icu (415 V) =

16724
16725
06572
06573

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles
17300
17301
06884
06885

17312
17313
06896
06897

35 kA
PR212
P
LSI
LSIG
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
16121
16123
06232
06235

16133
16135
06244
06247

65 kA
PR212
P
LSI
LSIG
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
16708
16711
06556
06559

16720
16723
06568
06571

100 kA
PR212
P
LSI
LSIG
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
17296
17299
06880
06883

17308
17311
06892
06895

35 kA
PR212
P
LSI
LSIG
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
16127
16129
06238
06241

16139
16141
06250
06253

65 kA
PR212
P
LSI
LSIG
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
16714
16717
06562
06565

16726
16729
06574
06577

100 kA
PR212
P
LSI
LSIG
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
17302
17305
06886
06889

17314
17317
06898
06901

ABB SACE

Order codes
SACE Isomax S4 circuit-breaker

F = FIXED

S4N 250

Iu (40 C) =

PR211
P

Microprocessor-based
release
F = Front terminals
S4N 250 F F

In 250 A

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles

35 kA
PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles

I
LI

17318
17319

17384
17385

LSI
LSIG

17320
17323

17386
17389

I
LI

06902
06903

07052
07053

LSI
LSIG

06904
06907

07054
07057

I
LI

06938
06939

07088
07089

LSI
LSIG

06940
06943

07090
07093

I
LI

06974
06975

07124
07125

LSI
LSIG

06976
06979

07126
07129

I
LI

07046
07047

07196
07197

LSI
LSIG

07048
07051

07198
07201

RC = Rear terminals for cables


S4N 250 F RC
In 250 A I
LI

07010
07011

07160
07161

LSI
LSIG

07012
07015

07162
07165

EF = Extended front terminals


S4N 250 F EF
In 250 A
PSIS9610

250 A

FC Cu = Front terminals
for copper cables
S4N 250 F FC Cu
In 250 A
FC CuAl = Front terminals
for copper/aluminium cables
S4N 250 F FC CuAl
In 250 A
R = Threaded rear terminals
S4N 250 F R
In 250 A

S4H 250

Iu (40 C) =

PR211
P

Microprocessor-based
release
F = Front terminals
S4H 250 F F

In 250 A

250 A

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles

65 kA
PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles

I
LI

17450
17451

17516
17517

LSI
LSIG

17452
17455

17518
17521

I
LI

07226
07227

07376
07377

LSI
LSIG

07228
07231

07378
07381

I
LI

07262
07263

07412
07413

LSI
LSIG

07264
07267

07414
07417

I
LI

07298
07299

07448
07449

LSI
LSIG

07300
07303

07450
07453

I
LI

07370
07371

07520
07521

LSI
LSIG

07372
07375

07522
07525

RC = Rear terminals for cables


S4H 250 F RC
In 250 A I
LI

07334
07335

07484
07485

LSI
LSIG

07336
07339

07486
07489

EF = Extended front terminals


S4H 250 F EF
In 250 A
FC Cu = Front terminals
for copper cables
S4H 250 F FC Cu
In 250 A
FC CuAl = Front terminals
for copper/aluminium cables
S4H 250 F FC CuAl
In 250 A
R = Threaded rear terminals
S4H 250 F R
In 250 A

7
ABB SACE

7/29

Order codes
SACE Isomax S4 circuit-breaker

F = FIXED

S4L 250

Iu (40 C) =

Microprocessor-based
release
F = Front terminals
S4L 250 F F

In 250 A

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles

100 kA
PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles

I
LI

17582
17583

17648
17649

LSI
LSIG

17584
17587

17650
17653

I
LI

07550
07551

07700
07701

LSI
LSIG

07552
07555

07702
07705

I
LI

07586
07587

07736
07737

LSI
LSIG

07588
07591

07738
07741

I
LI

07622
07623

07772
07773

LSI
LSIG

07624
07627

07774
07777

I
LI

07694
07695

07844
07845

LSI
LSIG

07696
07699

07846
07849

RC = Rear terminals for cables


S4L 250 F RC
In 250 A I
LI

07658
07659

07808
07809

LSI
LSIG

07660
07663

07810
07813

EF = Extended front terminals


S4L 250 F EF
In 250 A
PSIS9610

250 A

PR211
P

FC Cu = Front terminals
for copper cables
S4L 250 F FC Cu
In 250 A
FC CuAl = Front terminals
for copper/aluminium cables
S4L 250 F FC CuAl
In 250 A
R = Threaded rear terminals
S4L 250 F R
In 250 A

7
7/30

ABB SACE

Order codes
SACE Isomax S4 circuit-breaker

P = PLUG-IN

Moving part
S4N 250
Iu (40 C) = 250 A
PR211
P

Microprocessor-based
release

PSIS9610

S4N 250 P MP

S4H 250

In 250 A

I
LI

S4H 250 P MP

S4L 250

In 250 A

I
LI

In 250 A

250 A

PR211
P
I
LI

07850
07851

PR211
P

PSIS9610

S4N 250 W MP

S4H 250

In 250 A

I
LI

S4H 250 W MP

S4L 250

In 250 A

I
LI

In 250 A

250 A

PR211
P
I
LI

Icu (415 V) =

07862
07863

Icu (415 V) =

07220
07221

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles
07532
07533

Iu (40 C) =

Microprocessor-based
release
S4L 250 W MP

250 A

PR211
P

Microprocessor-based
release

07538
07539

code 1SDA0 . . . . . R1
3 poles
4 poles
07208
07209

Iu (40 C) =

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles

W = WITHDRAWABLE Moving part


S4N 250
Iu (40 C) = 250 A
Microprocessor-based
release

07214
07215

code 1SDA0 . . . . . R1
3 poles
4 poles
07526
07527

Iu (40 C) =

Microprocessor-based
release
S4L 250 P MP

250 A

PR211
P

Microprocessor-based
release

code 1SDA0 . . . . . R1
3 poles
4 poles
07202
07203

Iu (40 C) =

Icu (415 V) =

07544
07545

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles
07856
07857

07868
07869

35 kA
PR212
P
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
07204
07207

07216
07219

65 kA
PR212
P
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
07528
07531

07540
07543

100 kA
PR212
P
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
07852
07855

07864
07867

35 kA
PR212
P
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
07210
07213

07222
07225

65 kA
PR212
P
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
07534
07537

07546
07549

100 kA
PR212
P
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
07858
07861

07870
07873

7
ABB SACE

7/31

Order codes
SACE Isomax S5 circuit-breaker

F = FIXED

S5N 400

Iu (40 C) =

PSIS9613

Thermomagnetic
release

Im = 5...10
Ith

F = Front terminals
S5N 400 F F
R 320
S5N 400 F F
R 400
EF = Extended front
terminals
S5N 400 F EF
R 320
S5N 400 F EF
R 400
FC Cu = Front terminals
for copper cables
S5N 400 F FC Cu
R 320
S5N 400 F FC Cu
R 400
FC CuAl = Front terminals
for copper/aluminium cables
S5N 400 F FC CuAl* R 320
S5N 400 F FC CuAl* R 400
S5N 400 F FC CuAl** R 320
S5N 400 F FC CuAl** R 400
R = Threaded rear terminals
S5N 400 F R
R 320
S5N 400 F R
R 400
RC = Rear terminals
for cables
S5N 400 F RC
R 320
S5N 400 F RC
R 400

F = Front terminals
S5N 400 F F

In 320 A

S5N 400 F F

In 400 A

EF = Extended front
terminals
S5N 400 F EF

In 320 A

S5N 400 F EF

In 400 A

FC Cu = Front terminals
for copper cables
S5N 400 F FC Cu
In 320 A
In 400 A

FC CuAl = Front terminals


for copper/aluminium cables
S5N 400 F FC CuAl* In 320 A
S5N 400 F FC CuAl*

In 400 A

S5N 400 F FC CuAl** In 320 A


S5N 400 F FC CuAl** In 400 A

R = Threaded rear terminals


S5N 400 F R
In 320 A

S5N 400 F R

In 400 A

RC = Rear terminals
for cables
S5N 400 F RC

In 320 A

S5N 400 F RC

In 400 A

Icu (415 V) =

38438
38439

38440
38441

3200A
4000A

38442
38443

38444
38445

3200A
4000A

38446
38447

38448
38449

3200A
4000A
3200A
4000A

38450
38451
38466
38467

38452
38453
38480
38481

3200A
4000A

38486
38487

38488
38489

3200A
4000A

38482
38483

38484
38485

PR211
P

35 kA

code 1SDA0 . . . . . R1
3 poles
4 poles

3200A
4000A

Microprocessor-based
release

S5N 400 F FC Cu

400 A

code 1SDA0 . . . . . R1
3 poles
4 poles

PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles

I
LI
I
LI

17714
17716
17715
17717

17846
17848
17847
17849

LSI
LSIG
LSI
LSIG

17718
17724
17719
17725

17850
17856
17851
17857

I
LI
I
LI

07874
07876
07875
07877

08174
08176
08175
08177

LSI
LSIG
LSI
LSIG

07878
07884
07879
07885

08178
08184
08179
08185

I
LI
I
LI

07946
07948
07947
07949

08246
08248
08247
08249

LSI
LSIG
LSI
LSIG

07950
07956
07951
07957

08250
08256
08251
08257

I
LI
I
LI
I
LI
I
LI

08018
08020
08019
08021
38454
38456
38455
38457

08318
08320
08319
08321
38468
38470
38469
38471

LSI
LSIG
LSI
LSIG
LSI
LSIG
LSI
LSIG

08022
08028
08023
08029
38458
38464
38459
38465

08322
08328
08323
08329
38472
38478
38473
38479

I
LI
I
LI

08162
08164
08163
08165

08450
08452
08451
08453

LSI
LSIG
LSI
LSIG

08166
08172
08167
08173

08454
08460
08455
08461

I
LI
I
LI

08090
08092
08091
08093

08390
08392
08391
08393

LSI
LSIG
LSI
LSIG

08094
08100
08095
08101

08394
08400
08395
08401

* Cable section = 1 x 240 mm2


** Cable section = 2 x 120 mm2

7/32

ABB SACE

Order codes
SACE Isomax S5 circuit-breaker

F = FIXED

S5H 400

Iu (40 C) =

Im = 5...10
Ith

PSIS9613

Thermomagnetic
release
F = Front terminals
S5H 400 F F
R 320
S5H 400 F F
R 400
EF = Extended front terminals
S5H 400 F EF
R 320
S5H 400 F EF
R 400
FC Cu = Front terminals
for copper cables
S5H 400 F FC Cu
R 320
S5H 400 F FC Cu
R 400
FC CuAl = Front terminals
for copper/aluminium cables
S5H 400 F FC CuAl*
R 320
S5H 400 F FC CuAl*
R 400
S5H 400 F FC CuAl** R 320
S5H 400 F FC CuAl** R 400
R = Threaded rear terminals
S5H 400 F R
R 320
S5H 400 F R
R 400
RC = Rear terminals for cables
S5H 400 F RC
R 320
S5H 400 F RC
R 400

Microprocessor-based
release
F = Front terminals
S5H 400 F F

In 320 A

S5H 400 F F

In 400 A

EF = Extended front terminals


S5H 400 F EF
In 320 A
S5H 400 F EF

In 400 A

FC Cu = Front terminals
for copper cables
S5H 400 F FC Cu
In 320 A
S5H 400 F FC Cu

In 400 A

FC CuAl = Front terminals


for copper/aluminium cables
S5H 400 F FC CuAl*
In 320 A
S5H 400 F FC CuAl*

In 400 A

S5H 400 F FC CuAl**

In 320 A

S5H 400 F FC CuAl**

In 400 A

R = Threaded rear terminals


S5H 400 F R
In 320 A
S5H 400 F R

In 400 A

RC = Rear terminals for cables


S5H 400 F RC
In 320 A
S5H 400 F RC

400 A

In 400 A

Icu (415 V) =

65 kA

code 1SDA0 . . . . . R1
3 poles
4 poles

3200A
4000A

38522
38523

38524
38525

3200A
4000A

38526
38527

38528
38529

3200A
4000A

38530
38531

38532
38533

3200A
4000A
3200A
4000A

38534
38535
38550
38551

38536
38537
38564
38565

3200A
4000A

38570
38571

38572
38573

3200A
4000A

38566
38567

38568
38569

PR211
P

code 1SDA0 . . . . . R1
3 poles
4 poles

PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles

I
LI
I
LI

17990
17992
17991
17993

18122
18124
18123
18125

LSI
LSIG
LSI
LSIG

17994
18000
17995
18001

18126
18132
18127
18133

I
LI
I
LI

08510
08512
08511
08513

08810
08812
08811
08813

LSI
LSIG
LSI
LSIG

08514
08520
08515
08521

08814
08820
08815
08821

I
LI
I
LI

08582
08584
08583
08585

08882
08884
08883
08885

LSI
LSIG
LSI
LSIG

08586
08592
08587
08593

08886
08892
08887
08893

I
LI
I
LI
I
LI
I
LI

08654
08656
08655
08657
38538
38540
38539
38541

08954
08956
08955
08957
38552
38554
38553
38555

LSI
LSIG
LSI
LSIG
LSI
LSIG
LSI
LSIG

08658
08664
08659
08665
38542
38548
38543
38549

08958
08964
08959
08965
38556
38563
38557
38562

I
LI
I
LI

08798
08800
08799
08801

09098
09100
09099
09101

LSI
LSIG
LSI
LSIG

08802
08808
08803
08809

09102
09108
09103
09109

I
LI
I
LI

08726
08728
08727
08729

09026
09028
09027
09029

LSI
LSIG
LSI
LSIG

08730
08736
08731
08737

09030
09036
09031
09037

* Cable section = 1 x 240 mm2


** Cable section = 2 x 120 mm2

ABB SACE

7/33

Order codes
SACE Isomax S5 circuit-breaker

F = FIXED

S5L 400

Iu (40 C) =

PSIS9613

Thermomagnetic
release

Im = 5...10
Ith

F = Front terminals
S5L 400 F F
R 320
S5L 400 F F
R 400
EF = Extended front terminals
S5L 400 F EF
R 320
S5L 400 F EF
R 400
FC Cu = Front terminals
for copper cables
S5L 400 F FC Cu
R 320
S5L 400 F FC Cu
R 400
FC CuAl = Front terminals
for copper/aluminium cables
S5L 400 F FC CuAl*
R 320
S5L 400 F FC CuAl*
R 400
S5L 400 F FC CuAl** R 320
S5L 400 F FC CuAl** R 400
R = Threaded rear terminals
S5L 400 F R
R 320
S5L 400 F R
R 400
RC = Rear terminals for cables
S5L 400 F RC
R 320
S5L 400 F RC
R 400

Microprocessor-based
release
F = Front terminals
S5L 400 F F

In 320 A

S5L 400 F F

In 400 A

EF = Extended front terminals


S5L 400 F EF
In 320 A
S5L 400 F EF

In 400 A

FC Cu = Front terminals
for copper cables
S5L 400 F FC Cu
In 320 A
S5L 400 F FC Cu

In 400 A

FC CuAl = Front terminals


for copper/aluminium cables
S5L 400 F FC CuAl*
In 320 A
S5L 400 F FC CuAl*

In 400 A

S5L 400 F FC CuAl**

In 320 A

S5L 400 F FC CuAl**

In 400 A

R = Threaded rear terminals


S5L 400 F R
In 320 A
S5L 400 F R

In 400 A

RC = Rear terminals for cables


S5L 400 F RC
In 320 A
S5L 400 F RC

400 A

In 400 A

Icu (415 V) =

100 kA

code 1SDA0 . . . . . R1
3 poles
4 poles

3200A
4000A

38606
38607

38608
38609

3200A
4000A

38610
38611

38612
38613

3200A
4000A

38614
38615

38616
38617

3200A
4000A
3200A
4000A

38618
38619
38634
38635

38620
38621
38648
38649

3200A
4000A

38654
38655

38656
38657

3200A
4000A

38650
38651

38652
38653

PR211
P

code 1SDA0 . . . . . R1
3 poles
4 poles

PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles

I
LI
I
LI

18254
18256
18255
18257

18386
18388
18387
18389

LSI
LSIG
LSI
LSIG

18258
18264
18259
18265

18390
18396
18391
18397

I
LI
I
LI

09158
09160
09159
09161

09458
09460
09459
09461

LSI
LSIG
LSI
LSIG

09162
09168
09163
09169

09462
09468
09463
09469

I
LI
I
LI

09230
09232
09231
09233

09530
09532
09531
09533

LSI
LSIG
LSI
LSIG

09234
09240
09235
09241

09534
09540
09535
09541

I
LI
I
LI
I
LI
I
LI

09302
09304
09303
09305
38622
38624
38623
38625

09602
09604
09603
09605
38636
38638
38637
38639

LSI
LSIG
LSI
LSIG
LSI
LSIG
LSI
LSIG

09306
09312
09307
09313
38626
38628
38627
38629

09606
09612
09607
09613
38640
38646
38641
38647

I
LI
I
LI

09446
09448
09447
09449

09746
09748
09747
09749

LSI
LSIG
LSI
LSIG

09450
09456
09451
09457

09750
09756
09751
09757

I
LI
I
LI

09374
09376
09375
09377

09674
09676
09675
09677

LSI
LSIG
LSI
LSIG

09378
09384
09379
09385

09678
09684
09679
09685

* Cable section = 1 x 240 mm2


** Cable section = 2 x 120 mm2

7/34

ABB SACE

Order codes
SACE Isomax S5 circuit-breaker

P = PLUG-IN

Moving part
S5N 400
Iu (40 C) = 400 A
Im = 5...10
Ith

Thermomagnetic
release

PSIS9613

S5N 400 P MP
S5N 400 P MP

R 320
R 400

Microprocessor-based
release
S5N 400 P MP

In 320 A

S5N 400 P MP

In 400 A

S5H 400
S5H 400 P MP
S5H 400 P MP

R 320
R 400

S5H 400 P MP

In 320 A

S5H 400 P MP

In 400 A

code 1SDA0 . . . . . R1
3 poles
4 poles
08462
08464
08463
08465

400 A

In 320 A

S5L 400 P MP

In 400 A

Icu (415 V) =

LSI
LSIG
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
08466
08472
08467
08473

08490
08496
08491
08497

65 kA

code 1SDA0 . . . . . R1
3 poles
4 poles
09110
09112
09111
09113

400 A

43904
43905

09134
09136
09135
09137

Icu (415 V) =

PR212
P
LSI
LSIG
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
09114
09120
09115
09121

09138
09144
09139
09145

100 kA

code 1SDA0 . . . . . R1
3 poles
4 poles

3200A
4000A

43900
43901

PR211
P

code 1SDA0 . . . . . R1
3 poles
4 poles

I
LI
I
LI

PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles

PR211
P
I
LI
I
LI

Microprocessor-based
release
S5L 400 P MP

08486
08488
08487
08489

43898
43899

Im = 5...10
Ith

R 320
R 400

43902
43903

3200A
4000A

Iu (40 C) =

Thermomagnetic
release
S5L 400 P MP
S5L 400 P MP

PR211
P

Im = 5...10
Ith

Microprocessor-based
release

S5L 400

43896
43897

I
LI
I
LI

35 kA

code 1SDA0 . . . . . R1
3 poles
4 poles

3200A
4000A

Iu (40 C) =

Thermomagnetic
release

Icu (415 V) =

09758
09760
09759
09761

43906
43907

09782
09784
09783
09785

PR212
P
LSI
LSIG
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
09762
09768
09763
09769

09786
09792
09787
09793

7
ABB SACE

7/35

Order codes
SACE Isomax S5 circuit-breaker

W = WITHDRAWABLE Moving part


S5N 400 Iu (40 C) = 400 A
Im = 5...10
Ith

Thermomagnetic
release

PSIS9613

S5N 400 W MP
S5N 400 W MP

R 320
R 400

In 320 A

38414
38415

PR211
P

code 1SDA0 . . . . . R1
3 poles
4 poles

S5N 400 W MP

In 400 A

S5H 400

Iu (40 C) =

R 320
R 400

S5H 400 W MP

In 320 A

S5H 400 W MP

In 400 A

Iu (40 C) =

S5L 400 W MP
S5L 400 W MP

R 320
R 400

In 320 A

S5L 400 W MP

In 400 A

PR212
P
LSI
LSIG
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
08478
08484
08479
08485

08502
08508
08503
08509

code 1SDA0 . . . . . R1
3 poles
4 poles
38490
38491

PR211
P

code 1SDA0 . . . . . R1
3 poles
4 poles

I
LI
I
LI

09122
09124
09123
09125

38492
38493

09146
09148
09147
09149

PR212
P
LSI
LSIG
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
09126
09132
09127
09133

09150
09156
09151
09157

400 A Icu (415 V) = 100 kA


code 1SDA0 . . . . . R1
3 poles
4 poles

3200A
4000A

38574
38575

PR211
P

code 1SDA0 . . . . . R1
3 poles
4 poles

Microprocessor-based
release
S5L 400 W MP

08498
08500
08499
08501

3200A
4000A

Im = 5...10
Ith

Thermomagnetic
release

38416
38417

400 A Icu (415 V) = 65 kA

Microprocessor-based
release

S5L 400

08474
08476
08475
08477

Im = 5...10
Ith

Thermomagnetic
release
S5H 400 W MP
S5H 400 W MP

I
LI
I
LI

35 kA

code 1SDA0 . . . . . R1
3 poles
4 poles

3200A
4000A

Microprocessor-based
release
S5N 400 W MP

Icu (415 V) =

I
LI
I
LI

09770
09772
09771
09773

38576
38577

09794
09796
09795
09797

PR212
P
LSI
LSIG
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
09774
09780
09775
09781

09798
09804
09799
09805

7
7/36

ABB SACE

Order codes
SACE Isomax S5 circuit-breaker

W = WITHDRAWABLE Moving part (1)


S5N 400
Iu (40 C) = 400 A
Im = 5...10
Ith

Thermomagnetic
release

PSIS9613

S5N 400 W MP
S5N 400 W MP

R 320
R 400

In 320 A

38426
38427

PR211
P

code 1SDA0 . . . . . R1
3 poles
4 poles

S5N 400 W MP

In 400 A

S5H 400

R 320
R 400

S5H 400 W MP

In 320 A

S5H 400 W MP

In 400 A

In 320 A

S5L 400 W MP

In 400 A

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles

I
LI
I
LI

LSI
LSIG
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
38422
38424
38423
38425

38432
38434
38433
38435

65 kA

38494
38496
38495
38497

400 A

38520
38521

38508
38510
38509
38511

Icu (415 V) =

PR212
P
LSI
LSIG
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
38498
38504
38499
38505

38512
38518
38513
38519

100 kA

code 1SDA0 . . . . . R1
3 poles
4 poles

3200A
4000A

38590
38591

PR211
P

code 1SDA0 . . . . . R1
3 poles
4 poles

I
LI
I
LI

PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles

PR211
P

Microprocessor-based
release
S5L 400 W MP

38428
38430
51608
38431

38506
38507

Im = 5...10
Ith

R 320
R 400

38436
38437

3200A
4000A

Iu (40 C) =

Thermomagnetic
release
S5L 400 W MP
S5L 400 W MP

400 A

Im = 5...10
Ith

Microprocessor-based
release

S5L 400

38418
38420
38419
38421

Iu (40 C) =

Thermomagnetic
release
S5H 400 W MP
S5H 400 W MP

I
LI
I
LI

35 kA

code 1SDA0 . . . . . R1
3 poles
4 poles

3200A
4000A

Microprocessor-based
release
S5N 400 W MP

Icu (415 V) =

38578
38580
38579
38581

38604
38605

38592
38594
38593
38595

PR212
P
LSI
LSIG
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
38582
38588
38583
38589

38596
38602
38597
38603

(1) The S5 400 mobile parts indicated on this page can be used in conjunction with S5 630 W FP fixed parts.
Two different fixed parts are available for circuit-breakers S5 400 and S5 630.
Fixed circuit-breaker S5 400:
converted into the mobile part of a withdrawable circuit-breaker using kit 1SDA0 13718 R1 (three-pole), 1SDA0 13719 R1
(four-pole) can be used in conjunction with the fixed part for S5 400 (see codes on pages 7/81).
converted into the mobile part of a withdrawable circuit-breaker using kit 1SDA0 38778 R1 (three-pole), 1SDA0 38779 R1
(four-pole) can be used in conjunction with the fixed part for S5 630. This page shows the codes for the mobile parts of
withdrawable circuit-breakers which have already been converted and can be used in conjunction with the fixed parts for
S5 630.
Circuit-breaker S5 630 can be converted into the mobile part of a withdrawable circuit-breaker using kit 1SDA0 38778 R1
(three-pole), 1SDA0 38779 R1 (four-pole) and used in conjunction exclusively with the fixed parts for S5 630 (see codes on
page 7/81).

ABB SACE

7/37

Order codes
SACE Isomax S5 circuit-breaker

F = FIXED

S5N 630

Iu (40 C) =

PSIS9613

Thermomagnetic
release
F = Front terminals
S5N 630 F F
R 500
ES = Spreaded extended
front terminals
S5N 630 F ES
R 500
FC Cu = Front terminals
for copper cables
S5N 630 F FC Cu
R 500
R = Threaded rear terminals
S5N 630 F R
R 500

Microprocessor-based
release
F = Front terminals
S5N 630 F F

In 630 A

ES = Spreaded extended
front terminals
S5N 630 F ES
In 630 A
FC Cu = Front terminals
for copper cables
S5N 630 F FC Cu
In 630 A
R = Threaded rear terminals
S5N 630 F R
In 630 A

S5H 630

38683

5000A

38684

38685

5000A

38686

38687

5000A

38690

38691

PR211
P

code 1SDA0 . . . . . R1
3 poles
4 poles

R = Threaded rear terminals


S5H 630 F R
In 630 A

code 1SDA0 . . . . . R1
3 poles
4 poles

38674
38675

38679
38680

LSI
LSIG

38676
38677

38681
38682

I
LI

14575
14576

14725
14726

LSI
LSIG

14577
14580

14727
14730

I
LI

14611
14612

14761
14762

LSI
LSIG

14613
14616

14763
14766

I
LI

14719
14720

14869
14870

LSI
LSIG

14721
14724

14871
14874

Microprocessor-based
release

FC Cu = Front terminals
for copper cables
S5H 630 F FC Cu
In 630 A

PR212
P

I
LI

F = Front terminals
S5H 630 F F
R 500
ES = Spreaded extended
front terminals
S5H 630 F ES
R 500
FC Cu = Front terminals
for copper cables
S5H 630 F FC Cu
R 500
R = Threaded rear terminals
S5H 630 F R
R 500

ES = Spreaded extended
front terminals
S5H 630 F ES
In 630 A

35 kA

code 1SDA0 . . . . . R1
3 poles
4 poles
38678

630 A

Im = 5...10
Ith

In 630 A

Icu (415 V) =

5000A

Iu (40 C) =

Thermomagnetic
release

F = Front terminals
S5H 630 F F

630 A

Im = 5...10
Ith

Icu (415 V) =

65 kA

code 1SDA0 . . . . . R1
3 poles
4 poles

5000A

38708

38713

5000A

38714

38715

5000A

38716

38717

5000A

38720

38721

PR211
P

code 1SDA0 . . . . . R1
3 poles
4 poles

PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles

I
LI

38704
38705

38709
38710

LSI
LSIG

38706
38707

38711
38712

I
LI

14899
14900

15049
15050

LSI
LSIG

14901
14904

15051
15054

I
LI

14935
14936

15085
15086

LSI
LSIG

14937
14940

15087
15090

I
LI

15043
15044

15193
15194

LSI
LSIG

15045
15048

15195
15198

7
7/38

ABB SACE

Order codes
SACE Isomax S5 circuit-breaker

F = FIXED

S5L 630

Iu (40 C) =

PSIS9613

Thermomagnetic
release
F = Front terminals
S5L 630 F F
R 500
ES = Spreaded extended
front terminals
S5L 630 F ES
R 500
FC Cu = Front terminals
for copper cables
S5L 630 F FC Cu
R 500
R = Threaded rear terminals
S5L 630 F R
R 500

Microprocessor-based
release
F = Front terminals
S5L 630 F F

630 A

Im = 5...10
Ith

In 630 A

ES = Spreaded extended
front terminals
S5L 630 F ES
In 630 A
FC Cu = Front terminals
for copper cables
S5L 630 F FC Cu
In 630 A
R = Threaded rear terminals
S5L 630 F R
In 630 A

Icu (415 V) =

100 kA

code 1SDA0 . . . . . R1
3 poles
4 poles

5000A

38740

38745

5000A

38746

38747

5000A

38748

38749

5000A

38752

38753

PR211
P

code 1SDA0 . . . . . R1
3 poles
4 poles

PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles

I
LI

38736
38737

38741
38742

LSI
LSIG

38738
38739

38743
38744

I
LI

15223
15224

15373
15374

LSI
LSIG

47991
15228

43801
15378

I
LI

15259
15260

15409
15410

LSI
LSIG

43748
15264

43815
15414

I
LI

15367
15368

15517
15518

LSI
LSIG

43775
15372

43843
15522

7
ABB SACE

7/39

Order codes
SACE Isomax S5 circuit-breaker

W = WITHDRAWABLE Moving part


S5N 630 Iu (40 C) = 630 A Icu (415 V) = 35 kA
Im = 5...10
Ith

Thermomagnetic
release

PSIS9613

S5N 630 W MP

R 500

5000A

38666

PR211
P

code 1SDA0 . . . . . R1
3 poles
4 poles

Microprocessor-based
release
S5N 630 W MP

S5H 630

In 630 A

S5H 630 W MP

I
LI

S5L 630

R 500

In 630 A

In 630 A

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles

I
LI

LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
38662
38665

38669
38672

65 kA

38693
38694

630 A

38703

38699
38700

Icu (415 V) =

PR212
P
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
38695
38696

38701
38702

100 kA

code 1SDA0 . . . . . R1
3 poles
4 poles

5000A

38729

PR211
P

code 1SDA0 . . . . . R1
3 poles
4 poles

I
LI

PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles

PR211
P

Microprocessor-based
release
S5L 630 W MP

38667
38668

38697

Im = 5...10
Ith

R 500

38673

5000A

Iu (40 C) =

Thermomagnetic
release
S5L 630 W MP

630 A

Im = 5...10
Ith

Microprocessor-based
release
S5H 630 W MP

38660
38661

Iu (40 C) =

Thermomagnetic
release

code 1SDA0 . . . . . R1
3 poles
4 poles

38723
38724

38754

38730
38731

PR212
P
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
38725
38728

38732
38734

7
7/40

ABB SACE

Order codes
SACE Isomax S6 circuit-breaker

F = FIXED

S6N 630

Iu (40 C) =

PSIS9616

Thermomagnetic
release
F = Front terminals
S6N 630 F F
R 630
EF = Extended front terminals
S6N 630 F EF
R 630
FC CuAl = Front terminals
for copper/aluminium cables
S6N 630 F FC CuAl*
R 630
R = Threaded rear terminals
S6N 630 F R
R 630
RC = Rear terminals for cables
S6N 630 F RC
R 630

Microprocessor-based
release
F = Front terminals
S6N 630 F F

In 630 A

EF = Extended front terminals


S6N 630 F EF
In 630 A
FC CuAl = Front terminals
for copper/aluminium cables
S6N 630 F FC CuAl*
In 630 A
R = Threaded rear terminals
S6N 630 F R
In 630 A
RC = Rear terminals for cables
S6N 630 F RC
In 630 A

S6S 630

38788

6300A

38789

38790

6300A

38791

38792

6300A

38795

38796

6300A

38793

38794

PR211
P

code 1SDA0 . . . . . R1
3 poles
4 poles

R = Threaded rear terminals


S6S 630 F R
In 630 A
RC = Rear terminals for cables
S6S 630 F RC
In 630 A

code 1SDA0 . . . . . R1
3 poles
4 poles

18518
18519

18572
18573

LSI
LSIG

18520
18523

18574
18577

I
LI

09806
09807

09902
09903

LSI
LSIG

09808
09811

09904
09907

I
LI

09836
09837

09932
09933

LSI
LSIG

09838
09841

09934
09937

I
LI

09896
09897

09992
09993

LSI
LSIG

09898
09901

09994
09997

I
LI

09866
09867

09962
09963

LSI
LSIG

09868
09871

09964
09967

Microprocessor-based
release

FC CuAl = Front terminals


for copper/aluminium cables
S6S 630 F FC CuAl*
In 630 A

PR212
P

I
LI

F = Front terminals
S6S 630 F F
R 630
EF = Extended front terminals
S6S 630 F EF
R 630
FC CuAl = Front terminals
for copper/aluminium cables
S6S 630 F FC CuAl*
R 630
R = Threaded rear terminals
S6S 630 F R
R 630
RC = Rear terminals for cables
S6S 630 F RC
R 630

EF = Extended front terminals


S6S 630 F EF
In 630 A

35 kA

code 1SDA0 . . . . . R1
3 poles
4 poles
38787

630 A

Im = 5...10
Ith

In 630 A

Icu (415 V) =

6300A

Iu (40 C) =

Thermomagnetic
release

F = Front terminals
S6S 630 F F

630 A

Im = 5...10
Ith

Icu (415 V) =

50 kA

code 1SDA0 . . . . . R1
3 poles
4 poles

6300A

38799

38800

6300A

38801

38802

6300A

38817

38818

6300A

38957

38959

6300A

38819

38820

PR211
P

code 1SDA0 . . . . . R1
3 poles
4 poles

PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles

I
LI

18626
18627

18680
18681

LSI
LSIG

18628
18631

18682
18685

I
LI

10010
10011

10106
10107

LSI
LSIG

10012
10015

10108
10111

I
LI

10040
10041

10136
10137

LSI
LSIG

10042
10045

10138
10141

I
LI

10100
10101

10196
10197

LSI
LSIG

10102
10105

10198
10201

I
LI

10070
10071

10166
10167

LSI
LSIG

10072
10075

10168
10171

* Cable section = 1 x 240 mm2

ABB SACE

7/41

Order codes
SACE Isomax S6 circuit-breaker

F = FIXED

S6H 630

Iu (40 C) =

PSIS9616

Thermomagnetic
release
F = Front terminals
S6H 630 F F
R 630
EF = Extended front terminals
S6H 630 F EF
R 630
FC CuAl = Front terminals
for copper/aluminium cables
S6H 630 F FC CuAl*
R 630
R = Threaded rear terminals
S6H 630 F R
R 630
RC = Rear terminals for cables
S6H 630 F RC
R 630

Microprocessor-based
release
F = Front terminals
S6H 630 F F

In 630 A

EF = Extended front terminals


S6H 630 F EF
In 630 A
FC CuAl = Front terminals
for copper/aluminium cables
S6H 630 F FC CuAl*
In 630 A
R = Threaded rear terminals
S6H 630 F R
In 630 A
RC = Rear terminals for cables
S6H 630 F RC
In 630 A

S6L 630

6300A

38825

38826

6300A

38827

38835

6300A

38958

38960

6300A

38843

38844

PR211
P

code 1SDA0 . . . . . R1
3 poles
4 poles

FC CuAl = Front terminals


for copper/aluminium cables
S6L 630 F FC CuAl*
In 630 A
R = Threaded rear terminals
S6L 630 F R
In 630 A
RC = Rear terminals for cables
S6L 630 F RC
In 630 A

PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles

18734
18735

18788
18789

LSI
LSIG

18736
18739

18790
18793

I
LI

10214
10215

10310
10311

LSI
LSIG

10216
10219

10312
10315

I
LI

10244
10245

10340
10341

LSI
LSIG

10246
10249

10342
10345

I
LI

10304
10305

10400
10401

LSI
LSIG

10306
10309

10402
10405

I
LI

10274
10275

10370
10371

LSI
LSIG

10276
10279

10372
10375

Microprocessor-based
release

38824

I
LI

F = Front terminals
S6L 630 F F
R 630
EF = Extended front terminals
S6L 630 F EF
R 630
FC CuAl = Front terminals
for copper/aluminium cables
S6L 630 F FC CuAl*
R 630
R = Threaded rear terminals
S6L 630 F R
R 630
RC = Rear terminals for cables
S6L 630 F RC
R 630

EF = Extended front terminals


S6L 630 F EF
In 630 A

65 kA

code 1SDA0 . . . . . R1
3 poles
4 poles
38823

630 A

Im = 5...10
Ith

In 630 A

Icu (415 V) =

6300A

Iu (40 C) =

Thermomagnetic
release

F = Front terminals
S6L 630 F F

630 A

Im = 5...10
Ith

Icu (415 V) =

100 kA

code 1SDA0 . . . . . R1
3 poles
4 poles

6300A

38847

38848

6300A

38849

38850

6300A

38851

38859

6300A

38961

38962

6300A

38867

38868

PR211
P

code 1SDA0 . . . . . R1
3 poles
4 poles

PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles

I
LI

18842
18843

18896
18897

LSI
LSIG

18844
18847

18898
18901

I
LI

10418
10419

10514
10515

LSI
LSIG

10420
10423

10516
10519

I
LI

10448
10449

10544
10545

LSI
LSIG

10450
10453

10546
10549

I
LI

10508
10509

10604
10605

LSI
LSIG

10510
10513

10606
10609

I
LI

10478
10479

10574
10575

LSI
LSIG

10480
10483

10576
10579

* Cable section = 2 x 240 mm2

7/42

ABB SACE

Order codes
SACE Isomax S6 circuit-breaker

W = WITHDRAWABLE Moving part


S6N 630
Iu (40 C) = 630 A
Im = 5...10
Ith

Thermomagnetic
release

PSIS9616

S6N 630 W MP

R 630

S6S 630

In 630 A

38785

PR211
P

code 1SDA0 . . . . . R1
3 poles
4 poles

S6H 630

R 630

In 630 A

S6L 630

In 630 A

I
LI

S6L 630 W MP

630 A

R 630

In 630 A

10208
10209

Icu (415 V) =

PR211
P

code 1SDA0 . . . . . R1
3 poles
4 poles

10006
10009

50 kA

PR212
P
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
10204
10207

10210
10213

65 kA

10406
10407

630 A

38822

10412
10413

Icu (415 V) =

PR212
P
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
10408
10411

10414
10417

100 kA

code 1SDA0 . . . . . R1
3 poles
4 poles

6300A

38845

PR211
P

code 1SDA0 . . . . . R1
3 poles
4 poles

I
LI

10000
10003

code 1SDA0 . . . . . R1
3 poles
4 poles
38821

Im = 5...10
Ith

LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles

38798

6300A

Microprocessor-based
release
S6L 630 W MP

10202
10203

I
LI

PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles

code 1SDA0 . . . . . R1
3 poles
4 poles

Iu (40 C) =

Thermomagnetic
release

Icu (415 V) =

PR211
P

Microprocessor-based
release
S6H 630 W MP

10004
10005

38797

Im = 5...10
Ith

R 630

38786

6300A

Iu (40 C) =

Thermomagnetic
release
S6H 630 W MP

630 A

Im = 5...10
Ith

Microprocessor-based
release
S6S 630 W MP

09998
09999

Iu (40 C) =

Thermomagnetic
release
S6S 630 W MP

I
LI

35 kA

code 1SDA0 . . . . . R1
3 poles
4 poles

6300A

Microprocessor-based
release
S6N 630 W MP

Icu (415 V) =

10610
10611

38846

10616
10617

PR212
P
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
10612
10615

10618
10621

7
ABB SACE

7/43

Order codes
SACE Isomax S6 circuit-breaker

F = FIXED

S6N 800

Iu (40 C) =

PSIS9616

Thermomagnetic
release
F = Front terminals
S6N 800 F F
R 800
EF = Extended front terminals
S6N 800 F EF
R 800
FC CuAl = Front terminals
for copper/aluminium cables
S6N 800 F FC CuAl*
R 800
R = Threaded rear terminals
S6N 800 F R
R 800
RC = Rear terminals for cables
S6N 630 F RC
R 800

Microprocessor-based
release
F = Front terminals
S6N 800 F F

In 800 A

EF = Extended front terminals


S6N 800 F EF
In 800 A
FC CuAl = Front terminals
for copper/aluminium cables
S6N 800 F FC CuAl*
In 800 A
R = Threaded rear terminals
S6N 800 F R
In 800 A
RC = Rear terminals for cables
S6N 800 F RC
In 800 A

S6S 800

8000A

38873

38874

8000A

38875

38876

8000A

38879

38880

8000A

38877

38878

PR211
P

code 1SDA0 . . . . . R1
3 poles
4 poles

FC CuAl = Front terminals


for copper/aluminium cables
S6S 800 F FC CuAl*
In 800 A
R = Threaded rear terminals
S6S 800 F R
In 800 A
RC = Rear terminals for cables
S6S 800 F RC
In 800 A

PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles

18950
18951

19004
19005

LSI
LSIG

18952
18955

19006
19009

I
LI

10622
10623

10718
10719

LSI
LSIG

10624
10627

10720
10723

I
LI

10652
10653

10748
10749

LSI
LSIG

10654
10657

10750
10753

I
LI

10712
10713

10808
10809

LSI
LSIG

10714
10717

10810
10813

I
LI

10682
10683

10778
10779

LSI
LSIG

10684
10687

10780
10783

Microprocessor-based
release

38872

I
LI

F = Front terminals
S6S 800 F F
R 800
EF = Extended front terminals
S6S 800 F EF
R 800
FC CuAl = Front terminals
for copper/aluminium cables
S6S 800 F FC CuAl*
R 800
R = Threaded rear terminals
S6S 800 F R
R 800
RC = Rear terminals for cables
S6S 800 F RC
R 800

EF = Extended front terminals


S6S 800 F EF
In 800 A

35 kA

code 1SDA0 . . . . . R1
3 poles
4 poles
38871

800 A

Im = 5...10
Ith

In 800 A

Icu (415 V) =

8000A

Iu (40 C) =

Thermomagnetic
release

F = Front terminals
S6S 800 F F

800 A

Im = 5...10
Ith

Icu (415 V) =

50 kA

code 1SDA0 . . . . . R1
3 poles
4 poles

8000A

38883

38884

8000A

38885

38886

8000A

38887

38895

8000A

38963

38964

8000A

38903

38904

PR211
P

code 1SDA0 . . . . . R1
3 poles
4 poles

PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles

I
LI

19058
19059

19112
19113

LSI
LSIG

19060
19063

19114
19117

I
LI

10826
10827

10922
10923

LSI
LSIG

10828
10831

10924
10927

I
LI

10856
10857

10952
10953

LSI
LSIG

10858
10861

10954
10957

I
LI

10916
10917

11006
11007

LSI
LSIG

10918
10921

11008
11011

I
LI

10886
10887

10976
10977

LSI
LSIG

10888
10891

10978
10981

* Cable section = 3 x 185 mm2

7/44

ABB SACE

Order codes
SACE Isomax S6 circuit-breaker

F = FIXED

S6H 800

Iu (40 C) =

PSIS9616

Thermomagnetic
release
F = Front terminals
S6H 800 F F
R 800
EF = Extended front terminals
S6H 800 F EF
R 800
FC CuAl = Front terminals
for copper/aluminium cables
S6H 800 F FC CuAl*
R 800
R = Threaded rear terminals
S6H 800 F R
R 800
RC = Rear terminals for cables
S6H 800 F RC
R 800

Microprocessor-based
release
F = Front terminals
S6H 800 F F

In 800 A

EF = Extended front terminals


S6H 800 F EF
In 800 A
FC CuAl = Front terminals
for copper/aluminium cables
S6H 800 F FC CuAl*
In 800 A
R = Threaded rear terminals
S6H 800 F R
In 800 A
RC = Rear terminals for cables
S6H 800 F RC
In 800 A

S6L 800

38908

8000A

38909

38910

8000A

38911

38919

8000A

38965

38966

8000A

38927

38928

PR211
P

code 1SDA0 . . . . . R1
3 poles
4 poles

R = Threaded rear terminals


S6L 800 F R
In 800 A
RC = Rear terminals for cables
S6L 800 F RC
In 800 A

code 1SDA0 . . . . . R1
3 poles
4 poles

19166
19167

19220
19221

LSI
LSIG

19168
19171

19222
19225

I
LI

11024
11025

11120
11121

LSI
LSIG

11026
11029

11122
11125

I
LI

11054
11055

11150
11151

LSIG
LSIG

11056
11059

11152
11155

I
LI

11114
11115

11210
11211

LSIG
LSIG

11116
11119

11212
11215

I
LI

11084
11085

11180
11181

LSI
LSIG

11086
11089

11182
11185

Microprocessor-based
release

FC CuAl = Front terminals


for copper/aluminium cables
S6L 800 F FC CuAl*
In 800 A

PR212
P

I
LI

F = Front terminals
S6L 800 F F
R 800
EF = Extended front terminals
S6L 800 F EF
R 800
FC CuAl = Front terminals
for copper/aluminium cables
S6L 800 F FC CuAl*
R 800
R = Threaded rear terminals
S6L 800 F R
R 800
RC = Rear terminals for cables
S6L 800 F RC
R 800

EF = Extended front terminals


S6L 800 F EF
In 800 A

65 kA

code 1SDA0 . . . . . R1
3 poles
4 poles
38907

800 A

Im = 5...10
Ith

In 800 A

Icu (415 V) =

8000A

Iu (40 C) =

Thermomagnetic
release

F = Front terminals
S6L 800 F F

800 A

Im = 5...10
Ith

Icu (415 V) =

100 kA

code 1SDA0 . . . . . R1
3 poles
4 poles

8000A

38931

38932

8000A

38933

38934

8000A

38935

38943

8000A

38973

38974

8000A

38951

38952

PR211
P

code 1SDA0 . . . . . R1
3 poles
4 poles

PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles

I
LI

19274
19275

19328
19329

LSI
LSIG

19276
19279

19330
19333

I
LI

11228
11229

11324
11325

LSI
LSIG

11230
11233

11326
11329

I
LI

11258
11259

11354
11355

LSI
LSIG

11260
11263

11356
11359

I
LI

11318
11319

11414
11415

LSI
LSIG

11320
11323

11416
11419

I
LI

11288
11289

11384
11385

LSI
LSIG

11290
11293

11386
11389

* Cable section = 3 x 185 mm2

ABB SACE

7/45

Order codes
SACE Isomax S6 circuit-breaker

W = WITHDRAWABLE Moving part


S6N 800
Iu (40 C) = 800 A
Im = 5...10
Ith

Thermomagnetic
release

PSIS9616

S6N 800 W MP

R 800

S6S 800

In 800 A

38869

PR211
P

code 1SDA0 . . . . . R1
3 poles
4 poles

S6H 800

R 800

In 800 A

S6L 800

In 800 A

I
LI

S6L 800 W MP

800 A

R 800

In 800 A

11018
11019

Icu (415 V) =

PR211
P

code 1SDA0 . . . . . R1
3 poles
4 poles

10822
10825

50 kA

PR212
P
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
11014
11017

11020
11023

65 kA

11216
11217

800 A

38906

11222
11223

Icu (415 V) =

PR212
P
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
11218
11221

11224
11227

100 kA

code 1SDA0 . . . . . R1
3 poles
4 poles

8000A

38929

PR211
P

code 1SDA0 . . . . . R1
3 poles
4 poles

I
LI

10816
10819

code 1SDA0 . . . . . R1
3 poles
4 poles
38905

Im = 5...10
Ith

LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles

38882

8000A

Microprocessor-based
release
S6L 800 W MP

11012
11013

I
LI

PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles

code 1SDA0 . . . . . R1
3 poles
4 poles

Iu (40 C) =

Thermomagnetic
release

Icu (415 V) =

PR211
P

Microprocessor-based
release
S6H 800 W MP

10820
10821

38881

Im = 5...10
Ith

R 800

38870

8000A

Iu (40 C) =

Thermomagnetic
release
S6H 800 W MP

800 A

Im = 5...10
Ith

Microprocessor-based
release
S6S 800 W MP

10814
10815

Iu (40 C) =

Thermomagnetic
release
S6S 800 W MP

I
LI

35 kA

code 1SDA0 . . . . . R1
3 poles
4 poles

8000A

Microprocessor-based
release
S6N 800 W MP

Icu (415 V) =

11420
11421

38930

11682
11683

PR212
P
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
11422
11425

11684
11687

7
7/46

ABB SACE

Order codes
SACE Isomax S7 circuit-breaker

F = FIXED

S7S 1250

Iu (40 C) =

1250 A

PR211
P

Microprocessor-based
release

PSIS9620

F = Front terminals
S7S 1250 F F

In 1000 A I
LI
S7S 1250 F F
In 1250 A I
LI
EF = Extended front terminals
S7S 1250 F EF
In 1000 A I
LI
S7S 1250 F EF
In 1250 A I
LI
FC CuAl = Front terminals
for copper/aluminium cables
S7S 1250 F FC CuAl In 1000 A I
LI
S7S 1250 F FC CuAl In 1250 A I
LI
VR = Vertical flat-bar
rear terminals
S7S 1250 F VR
In 1000 A I
LI
S7S 1250 F VR
In 1250 A I
LI
HR = Horizontal flat-bar
rear terminals
S7S 1250 F HR
In 1000 A I
LI
S7S 1250 F HR
In 1250 A I
LI

S7H 1250

Iu (40 C) =

Microprocessor-based
release
F = Front terminals
S7H 1250 F F

In 1000 A I
LI
S7H 1250 F F
In 1250 A I
LI
EF = Extended front terminals
S7H 1250 F EF
In 1000 A I
LI
S7H 1250 F EF
In 1250 A I
LI
FC CuAl = Front terminals
for copper/aluminium cables
S7H 1250 F FC CuAl In 1000 A I
LI
S7H 1250 F FC CuAl In 1250 A I
LI
VR = Vertical flat-bar
rear terminals
S7H 1250 F VR
In 1000 A I
LI
S7H 1250 F VR
In 1250 A I
LI
HR = Horizontal flat-bar
rear terminals
S7H 1250 F HR
In 1000 A I
LI
S7H 1250 F HR
In 1250 A I
LI

ABB SACE

PR211
P

Icu (415 V) =

50 kA
PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles

code 1SDA0 . . . . . R1
3 poles
4 poles

19382
19384
19383
19385

19490
19492
19491
19493

LSI
LSIG
LSI
LSIG

19386
19392
19387
19393

19494
19500
19495
19501

11432
11434
11433
11435

11624
11626
11625
11627

LSI
LSIG
LSI
LSIG

11436
11442
11437
11443

11628
11634
11629
11635

11492
11494
11493
11495

11428
11430
11429
11431

LSI
LSIG
LSI
LSIG

11496
11502
11497
11503

11688
11694
11689
11695

11612
11614
11613
11615

11804
11806
11805
11807

LSI
LSIG
LSI
LSIG

11616
11622
11617
11623

11808
11814
11809
11815

11552
11554
11553
11555

11744
11746
11745
11747

LSI
LSIG
LSI
LSIG

11556
11562
11557
11563

11748
11754
11749
11755

1250 A

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles

65 kA
PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles

19598
19600
19599
19601

19706
19708
19707
19709

LSI
LSIG
LSI
LSIG

19602
19608
19603
19609

19710
19716
19711
19717

11840
11842
11841
11843

12032
12034
12033
12035

LSI
LSIG
LSI
LSIG

11844
11850
11845
11851

12036
12042
12037
12043

11900
11902
11901
11903

12092
12094
12093
12095

LSI
LSIG
LSI
LSIG

11904
11910
11905
11911

12096
12102
12097
12103

12020
12022
12021
12023

12212
12214
12213
12215

LSI
LSIG
LSI
LSIG

12024
12030
12025
12031

12216
12222
12217
12223

11960
11962
11961
11963

12152
12154
12153
12155

LSI
LSIG
LSI
LSIG

11964
11970
11965
11971

12156
12162
12157
12163

7
7/47

Order codes
SACE Isomax S7 circuit-breaker

F = FIXED

S7L 1250

Iu (40 C) =

1250 A

PR211
P

Microprocessor-based
release

PSIS9620

F = Front terminals
S7L 1250 F F

In 1000 A I
LI
S7L 1250 F F
In 1250 A I
LI
EF = Extended front terminals
S7L 1250 F EF
In 1000 A I
LI
S7L 1250 F EF
In 1250 A I
LI
FC CuAl = Front terminals
for copper/aluminium cables
S7L 1250 F FC CuAl
In 1000 A I
LI
S7L 1250 F FC CuAl
In 1250 A I
LI
VR = Vertical flat-bar
rear terminals
S7L 1250 F VR
In 1000 A I
LI
S7L 1250 F VR
In 1250 A I
LI
HR = Horizontal flat-bar
rear terminals
S7L 1250 F HR
In 1000 A I
LI
S7L 1250 F HR
In 1250 A I
LI

PR211
P

S7S 1250 W MP
S7S 1250 W MP

In 1000 A I
LI
In 1250 A I
LI

S7H 1250

19922
19924
19923
19925

LSI
LSIG
LSI
LSIG

19818
19824
19819
19825

19926
19932
19927
19933

12248
12250
12249
12251

12440
12442
12441
12443

LSI
LSIG
LSI
LSIG

12252
12258
12253
12259

12444
12450
12445
12451

12308
12310
12309
12311

12500
12502
12501
12503

LSI
LSIG
LSI
LSIG

12312
12318
12313
12319

12504
12510
12505
12511

12428
12430
12429
12431

12620
12622
12621
12623

LSI
LSIG
LSI
LSIG

12432
12438
12433
12439

12624
12630
12625
12631

12368
12370
12369
12371

12560
12562
12561
12563

LSI
LSIG
LSI
LSIG

12372
12378
12373
12379

12564
12570
12565
12571

PSIS9620

S7H 1250 W MP
S7H 1250 W MP

In 1000 A I
LI
In 1250 A I
LI

S7L 1250
Microprocessor-based
release
S7L 1250 W MP
S7L 1250 W MP

7
7/48

In 1000 A I
LI
In 1250 A I
LI

1250 A

PR211
P

11828
11830
11829
11831

LSI
LSIG
LSI
LSIG

Icu (415 V) =

12236
12238
12237
12239

12632
12634
12633
12635

12644
12646
12645
12647

code 1SDA0 . . . . . R1
3 poles
4 poles
11820
11826
11821
11827

11832
11838
11833
11839

65 kA
PR212
P

LSI
LSIG
LSI
LSIG

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles

50 kA
PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles
12224
12226
12225
12227

Iu (40 C) =

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles

1250 A

PR211
P

Microprocessor-based
release

code 1SDA0 . . . . . R1
3 poles
4 poles

19814
19816
19815
19817

11816
11818
11817
11819

Iu (40 C) =

100 kA
PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles

W = WITHDRAWABLE Moving part


S7S 1250
Iu (40 C) = 1250 A
Microprocessor-based
release

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles
12228
12234
12229
12235

12240
12246
12241
12247

100 kA
PR212
P

LSI
LSIG
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
12636
12642
12637
12643

12648
12654
12649
12655

ABB SACE

Order codes
SACE Isomax S7 circuit-breaker

F = FIXED

S7S 1600

Iu (40 C) =

1600 A

PR211
P

Microprocessor-based
release

PSIS9620

F = Front terminals
S7S 1600 F F

In 1600 A I
LI
EF = Extended front terminals
S7S 1600 F EF
In 1600 A I
LI
VR = Vertical flat-bar
rear terminals
S7S 1600 F VR
In 1600 A I
LI
HR = Horizontal flat-bar
rear terminals
S7S 1600 F HR
In 1600 A I
LI

S7H 1600

Iu (40 C) =

F = Front terminals
S7H 1600 F F

In 1600 A I
LI
EF = Extended front terminals
S7H 1600 F EF
In 1600 A I
LI
VR = Vertical flat-bar
rear terminals
S7H 1600 F VR
In 1600 A I
LI
HR = Horizontal flat-bar
rear terminals
S7H 1600 F HR
In 1600 A I
LI

S7L 1600

Iu (40 C) =

Microprocessor-based
release
F = Front terminals
S7L 1600 F F

In 1600 A I
LI
EF = Extended front terminals
S7L 1600 F EF
In 1600 A I
LI
VR = Vertical flat-bar
rear terminals
S7L 1600 F VR
In 1600 A I
LI
HR = Horizontal flat-bar
rear terminals
S7L 1600 F HR
In 1600 A I
LI

code 1SDA0 . . . . . R1
3 poles
4 poles

20030
20031

20072
20073

LSI
LSIG

20032
20035

20074
20077

12656
12657

12710
12711

LSI
LSIG

12658
12661

12712
12715

12704
12705

12758
12759

LSI
LSIG

12706
12709

12760
12763

12680
12681

12734
12735

LSI
LSIG

12682
12685

12736
12739

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles

65 kA
PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles

20114
20115

20156
20157

LSI
LSIG

20116
20119

20158
20161

12776
12777

12830
12831

LSI
LSIG

12778
12781

12832
12835

12824
12825

12878
12879

LSI
LSIG

12826
12829

12880
12883

12800
12801

12854
12855

LSI
LSIG

12802
12805

12856
12859

1600 A

PR211
P

50 kA
PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles

1600 A

PR211
P

Microprocessor-based
release

Icu (415 V) =

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles

100 kA
PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles

20198
20199

20240
20241

LSI
LSIG

20200
20203

20242
20245

12896
12897

12962
12963

LSI
LSIG

12898
12901

12964
12967

12956
12957

13010
13011

LSI
LSIG

12958
12961

13012
13015

12932
12933

12986
12987

LSI
LSIG

12934
12937

12988
12991

ABB SACE

7/49

Order codes
SACE Isomax S7 circuit-breaker

W = WITHDRAWABLE Moving part


S7S 1600
Iu (40 C) = 1600 A
PR211
P

Microprocessor-based
release
S7S 1600 W MP

In 1600 A I
LI

S7H 1600

PR211
P

Microprocessor-based
release
PSIS9620

S7H 1600 W MP

In 1600 A I
LI

S7L 1600

In 1600 A I
LI

1600 A

PR211
P

12890
12891

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles
13016
13017

LSI
LSIG

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles
12884
12885

Iu (40 C) =

Microprocessor-based
release
S7L 1600 W MP

1600 A

12770
12771

13022
13023

50 kA
PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles
12764
12765

Iu (40 C) =

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles
12766
12769

12772
12775

65 kA
PR212
P

LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
12886
12889

12892
12895

100 kA
PR212
P
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
13018
13021

13024
13027

7/50

ABB SACE

Order codes
SACE Isomax S8 circuit-breaker

F = FIXED

S8H 2000

Iu (40 C) =

2000 A

Icu (415 V) =

PR212
P

Microprocessor-based
release
F = Front terminals
S8H 2000 F F

In 1600 A

S8H 2000 F F

In 2000 A

VR = Vertical flat-bar rear terminals


S8H 2000 F VR
In 1600 A

GSIS9018

S8H 2000 F VR

In 2000 A

S8V 2000

Iu (40 C) =

2000 A

44861
44863
44862
44864

44877
44879
44878
44880

LSI
LSIG
LSI
LSIG

44869
44871
44870
44872

44885
44887
44886
44888

Icu (415 V) =

In 1600 A

S8V 2000 F F

In 2000 A

VR = Vertical flat-bar rear terminals


S8V 2000 F VR
In 1600 A
In 2000 A

S8H 2500

Iu (40 C) =

2500 A

44918
44920
44919
44921

44934
44936
44935
44937

LSI
LSIG
LSI
LSIG

44926
44928
44927
44929

44942
44944
44943
44945

Icu (415 V) =

VR = Vertical flat-bar rear terminals


S8H 2500 F VR
In 2500 A

S8V 2500

Iu (40 C) =

2500 A

44891
44892

44899
44900

LSI
LSIG

44895
44896

44903
44904

Icu (415 V) =

VR = Vertical flat-bar rear terminals


S8V 2500 F VR
In 2500 A

S8H 3200

Iu (40 C) =

3200 A

44948
44949

44956
44957

LSI
LSIG

44952
44953

44960
44961

Icu (415 V) =

Iu (40 C) =

Microprocessor-based
release
VR = Vertical flat-bar rear terminals
S8V 3200 F VR
In 3200 A

ABB SACE

85 kA
PR212
P

VR = Vertical flat-bar rear terminals


S8H 3200 F VR
In 3200 A

LSI
LSIG

3200 A

code 1SDA0 . . . . . R1
3 poles
4 poles

LSI
LSIG

Microprocessor-based
release

S8V 3200

120 kA
PR212
P

In 2500 A

code 1SDA0 . . . . . R1
3 poles
4 poles

LSI
LSIG

Microprocessor-based
release
F = Front terminals
S8V 2500 F F

85 kA
PR212
P

In 2500 A

code 1SDA0 . . . . . R1
3 poles
4 poles

LSI
LSIG
LSI
LSIG

Microprocessor-based
release
F = Front terminals
S8H 2500 F F

120 kA
PR212
P

F = Front terminals
S8V 2000 F F

code 1SDA0 . . . . . R1
3 poles
4 poles

LSI
LSIG
LSI
LSIG

Microprocessor-based
release

S8V 2000 F VR

85 kA

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles
44908
44909

44912
44913

120 kA
PR212
P

LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
44964
44965

44968
44969

7/51

Order codes
SACE Isomax S2X 100 current-limiting circuit-breaker

F = FIXED

S2X 100

Iu (40 C) =

100 A

Icu (415 V) =

Im

GSIS9150

Thermomagnetic
release

P = PLUG-IN

FC Cu = Front terminals
for copper cables
S2X 100 F FC Cu
R1
S2X 100 F FC Cu
R 1.6
S2X 100 F FC Cu
R 2.5
S2X 100 F FC Cu
R4
S2X 100 F FC Cu
R 6.3
S2X 100 F FC Cu
R 10
S2X 100 F FC Cu
R 12.5
S2X 100 F FC Cu
R 16
S2X 100 F FC Cu
R 20
S2X 100 F FC Cu
R 25
S2X 100 F FC Cu
R 32
S2X 100 F FC Cu
R 40
S2X 100 F FC Cu
R 50
S2X 100 F FC Cu
R 63
S2X 100 F FC Cu
R 80
S2X 100 F FC Cu
R 100
R = Threaded rear
terminals
S2X 100 F R
R1
S2X 100 F R
R 1.6
S2X 100 F R
R 2.5
S2X 100 F R
R4
S2X 100 F R
R 6.3
S2X 100 F R
R 10
S2X 100 F R
R 12.5
S2X 100 F R
R 16
S2X 100 F R
R 20
S2X 100 F R
R 25
S2X 100 F R
R 32
S2X 100 F R
R 40
S2X 100 F R
R 50
S2X 100 F R
R 63
S2X 100 F R
R 80
S2X 100 F R
R 100

Moving part
S2X 100
Iu (40 C) = 100 A
GSIS9150

Thermomagnetic
release

7/52

S2X 100 P MP
S2X 100 P MP
S2X 100 P MP
S2X 100 P MP
S2X 100 P MP
S2X 100 P MP
S2X 100 P MP
S2X 100 P MP
S2X 100 P MP
S2X 100 P MP
S2X 100 P MP
S2X 100 P MP
S2X 100 P MP
S2X 100 P MP
S2X 100 P MP
S2X 100 P MP

70 kA

Icu (415 V) =

10A
16A
25A
40A
63A
100A
125A
160A
200A
250A
320A
400A
500A
630A
800A
1000A

50307
50308
50309
50310
50311
50312
50313
50314
50315
50316
50317
50318
50319
50320
50321
50322

10A
16A
25A
40A
63A
100A
125A
160A
200A
250A
320A
400A
500A
630A
800A
1000A

50339
50340
50341
50342
50343
50344
50345
50346
50347
50348
50349
50350
50351
50352
50353
50354

70 kA
Im

R1
R 1.6
R 2.5
R4
R 6.3
R 10
R 12.5
R 16
R 20
R 25
R 32
R 40
R 50
R 63
R 80
R 100

code 1SDA0 . . . . . R1
3 poles

10A
16A
25A
40A
63A
100A
125A
160A
200A
250A
320A
400A
500A
630A
800A
1000A

code 1SDA0 . . . . . R1
3 poles
50371
50372
50373
50374
50375
50376
50377
50378
50379
50380
50381
50382
50383
50384
50385
50386

ABB SACE

Order codes
SACE Isomax S3X current-limiting circuit-breaker

F = FIXED

S3X 125

Iu (40 C) =

GSIS9151

Thermomagnetic
release
F = Front terminals
S3X 125 F F
R 32
S3X 125 F F
R 50
S3X 125 F F
R 80
S3X 125 F F
R 100
S3X 125 F F
R 125
EF = Extended front
terminals
S3X 125 F EF
R 32
S3X 125 F EF
R 50
S3X 125 F EF
R 80
S3X 125 F EF
R 100
S3X 125 F EF
R 125
FC Cu = Front terminals
for copper cables
S3X 125 F FC Cu
R 32
S3X 125 F FC Cu
R 50
S3X 125 F FC Cu
R 80
S3X 125 F FC Cu
R 100
S3X 125 F FC Cu
R 125
FC CuAl = Front terminals
for copper/aluminium cables
S3X 125 F FC CuAl
R 32
S3X 125 F FC CuAl
R 50
S3X 125 F FC CuAl
R 80
S3X 125 F FC CuAl
R 100
S3X 125 F FC CuAl
R 125
R = Threaded rear
terminals
S3X 125 F R
R 32
S3X 125 F R
R 50
S3X 125 F R
R 80
S3X 125 F R
R 100
S3X 125 F R
R 125
RC = Rear terminals
for cables
S3X 125 F RC
R 32
S3X 125 F RC
R 50
S3X 125 F RC
R 80
S3X 125 F RC
R 100
S3X 125 F RC
R 125

125 A

Icu (415 V) =

200 kA
Im

code 1SDA0 . . . . . R1
3 poles
4 poles

500A
500A
800A
1000A
1250A

45197
45199
45201
45203
45205

45207
45209
45211
45213
45215

500A
500A
800A
1000A
1250A

45217
45219
45221
45223
45225

45267
45269
45271
45273
45275

500A
500A
800A
1000A
1250A

45227
45229
45231
45233
45235

45277
45279
45281
45283
45285

500A
500A
800A
1000A
1250A

45237
45239
45241
45243
45245

45287
45289
45291
45293
45295

500A
500A
800A
1000A
1250A

45257
45259
45261
45263
45265

45307
45309
45311
45313
45315

500A
500A
800A
1000A
1250A

45247
45249
45251
45253
45255

45297
45299
45301
45303
45305

ABB SACE

7/53

Order codes
SACE Isomax S3X current-limiting circuit-breaker

F = FIXED

S3X 200

Iu (40 C) =

200 A

Icu (415 V) =

Im

GSIS9151

Thermomagnetic
release

P = PLUG-IN

F = Front terminals
S3X 200 F F
S3X 200 F F
S3X 200 F F
EF = Extended front
terminals
S3X 200 F EF
S3X 200 F EF
S3X 200 F EF
FC Cu = Front terminals
for copper cables
S3X 200 F FC Cu
S3X 200 F FC Cu
S3X 200 F FC Cu
FC CuAl = Front terminals
for copper/aluminium cables
S3X 200 F FC CuAl
S3X 200 F FC CuAl
S3X 200 F FC CuAl
R = Threaded rear
terminals
S3X 200 F R
S3X 200 F R
S3X 200 F R
RC = Rear terminals
for cables
S3X 200 F RC
S3X 200 F RC
S3X 200 F RC

1250A
1600A
2000A

46039
46041
46043

46045
46047
46049

R 125
R 160
R 200

1250A
1600A
2000A

46051
46053
46055

46081
46083
46085

R 125
R 160
R 200

1250A
1600A
2000A

46057
46059
46061

46087
46089
46091

R 125
R 160
R 200

1250A
1600A
2000A

46063
46065
46067

46093
46095
46097

R 125
R 160
R 200

1250A
1600A
2000A

46075
46077
46079

46105
46107
46109

R 125
R 160
R 200

1250A
1600A
2000A

46069
46071
46073

46099
46101
46103

Icu (415 V) =

GSIS9151

R 32
R 50
R 80
R 100
R 125

Iu (40 C) =

200 A

R 125
R 160
R 200

code 1SDA0 . . . . . R1
3 poles
4 poles

500A
500A
800A
1000A
1250A

Icu (415 V) =

45317
45319
45321
45323
45325

45327
45329
45331
45333
45335

200 kA
Im

Thermomagnetic
release
S3X 200 P MP
S3X 200 P MP
S3X 200 P MP

200 kA
Im

Thermomagnetic
release

S3X 200

code 1SDA0 . . . . . R1
3 poles
4 poles

R 125
R 160
R 200

Moving part
S3X 125
Iu (40 C) = 125 A
S3X 125 P MP
S3X 125 P MP
S3X 125 P MP
S3X 125 P MP
S3X 125 P MP

200 kA

1250A
1600A
2000A

code 1SDA0 . . . . . R1
3 poles
4 poles
46111
46113
46115

46117
46119
46121

7/54

ABB SACE

Order codes
SACE Isomax S3X current-limiting circuit-breaker

W = WITHDRAWABLE Moving part


S3X 125
Iu (40 C) = 125 A

Icu (415 V) =

Im

GSIS9151

Thermomagnetic
release
S3X 125 W MP
S3X 125 W MP
S3X 125 W MP
S3X 125 W MP
S3X 125 W MP

S3X 200

R 32
R 50
R8 0
R 100
R 125

Iu (40 C) =

200 A

500A
500A
800A
1000A
1250A

Icu (415 V) =

R 125
R 160
R 200

code 1SDA0 . . . . . R1
3 poles
4 poles
45337
45339
45341
45343
45345

45347
45349
45351
45353
45355

200 kA
Im

Thermomagnetic
release
S3X 200 W MP
S3X 200 W MP
S3X 200 W MP

200 kA

1250A
1600A
2000A

code 1SDA0 . . . . . R1
3 poles
4 poles
46123
46125
46127

46129
46131
46133

ABB SACE

7/55

Order codes
SACE Isomax S4X current-limiting circuit-breaker

F = FIXED

S4X 250

Iu (40 C) =

GSIS9152

Microprocessor-based
release
F = Front terminals
S4X 250 F F

In=100

S4X 250 F F

In=160

S4X 250 F F

In=250

EF = Extended front
terminals
S4X 250 F EF

In=100

S4X 250 F EF

In=160

S4X 250 F EF

In=250

FC Cu = Front terminals
for copper cables
S4X 250 F FC Cu
In=100
S4X 250 F FC Cu

In=160

S4X 250 F FC Cu

In=250

FC CuAl = Front terminals


for copper/aluminium cables
S4X 250 F FC CuAl
In=100
S4X 250 F FC CuAl

In=160

S4X 250 F FC CuAl

In=250

R = Threaded rear
terminals
S4X 250 F R

In=100

S4X 250 F R

In=160

S4X 250 F R

In=250

RC = Rear terminals
for cables
S4X 250 F RC

In=100

S4X 250 F RC

In=160

S4X 250 F RC

In=250

250 A

PR211
P

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles

200 kA
PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles

I
LI
I
LI
I
LI

46582
46584
46583
46585
46524
46525

46592
46594
46593
46595
46528
46529

LSI
LSIG
LSI
LSIG
LSI
LSIG

46586
46588
46587
46589
46526
46527

46596
46598
46597
46599
46530
46531

I
LI
I
LI
I
LI

46657
46660
46658
46661
46659
46662

46707
46710
46708
46711
46709
46712

LSI
LSIG
LSI
LSIG
LSI
LSIG

46663
46668
46664
46669
46665
46670

46713
46716
46714
46717
46715
46718

I
LI
I
LI
I
LI

46671
46674
46672
46675
46673
46676

46719
46722
46720
46723
46721
46724

LSI
LSIG
LSI
LSIG
LSI
LSIG

46677
46680
46678
46681
46679
46682

46725
46728
46726
46729
46727
46730

I
LI
I
LI
I
LI

46830
46833
46831
46834
46832
46835

46842
46845
46843
46846
46844
46847

LSI
LSIG
LSI
LSIG
LSI
LSIG

46836
46839
46837
46840
46838
46841

46848
46851
46849
46852
46850
46853

I
LI
I
LI
I
LI

46695
46698
46696
46699
46697
46700

46743
46746
46744
46747
46745
46748

LSI
LSIG
LSI
LSIG
LSI
LSIG

46701
46704
46702
46705
46703
46706

46749
46752
46750
46753
46751
46754

I
LI
I
LI
I
LI

46683
46686
46684
46687
46685
46688

46731
46734
46732
46735
46733
46736

LSI
LSIG
LSI
LSIG
LSI
LSIG

46689
46692
46690
46693
46691
46694

46737
46740
46738
46741
46739
46742

7/56

ABB SACE

Order codes
SACE Isomax S4X current-limiting circuit-breaker

P = PLUG-IN

Moving part
S4X 250
Iu (40 C) = 250 A
PR211
P

Microprocessor-based
release
In=100

S4X 250 P MP

In=160

S4X 250 P MP

In=250

I
LI
I
LI
I
LI

200 kA

code 1SDA0 . . . . . R1
3 poles
4 poles
46755
46758
46756
46759
46757
46760

46767
46770
46768
46771
46769
46772

PR212
P
LSI
LSIG
LSI
LSIG
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
46761
46764
46762
46765
46763
46766

46773
46776
46774
46777
46775
46778

GSIS9152

S4X 250 P MP

Icu (415 V) =

W = WITHDRAWABLE Moving part


S4X 250
Iu (40 C) = 250 A
PR211
P

Microprocessor-based
release
In=100

S4X 250 W MP

In=160

S4X 250 W MP

In=250

I
LI
I
LI
I
LI

code 1SDA0 . . . . . R1
3 poles
4 poles
46779
46782
46780
46783
46781
46784

46791
46794
46792
46795
46793
46796

200 kA
PR212
P
LSI
LSIG
LSI
LSIG
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
46785
46788
46786
46789
46787
46790

46797
46800
46798
46801
46799
46802

GSIS9152

S4X 250 W MP

Icu (415 V) =

ABB SACE

7/57

Order codes
SACE Isomax S6X current-limiting circuit-breaker

F = FIXED

S6X 400

Iu (40 C) =

GSIS9153

Microprocessor-based
release
F = Front terminals
S6X 400 F F

In=320

S6X 400 F F

In=400

EF = Extended front
terminals
S6X 400 F EF

In=320

S6X 400 F EF

In=400

FC CuAl = Front terminals


for copper/aluminium cables
S6X 400 F FC CuAl
In=320
S6X 400 F FC CuAl

In=400

R = Threaded rear
terminals
S6X 400 F R

In=320

S6X 400 F R

In=400

RC = Rear terminals
for cables
S6X 400 F RC

In=320

S6X 400 F RC

In=400

S6X 630

400 A

PR211
P

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles

200 kA
PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles

I
LI
I
LI

47595
47596
46534
46535

47601
47602
46538
46539

LSI
LSIG
LSI
LSIG

47597
47598
46536
46537

47603
47604
46540
46541

I
LI
I
LI

47661
47663
47660
47662

47693
47695
47692
47694

LSI
LSIG
LSI
LSIG

47665
47667
47664
47666

47697
47699
47696
47698

I
LI
I
LI

47669
47671
47668
47670

47701
47703
47700
47702

LSI
LSIG
LSI
LSIG

47673
47675
47672
47674

47704
47707
47705
47706

I
LI
I
LI

47685
47687
47684
47686

47717
47719
47716
47718

LSI
LSIG
LSI
LSIG

47689
47691
47688
47690

47721
47723
47720
47722

I
LI
I
LI

47677
47679
47676
47678

47709
47711
47708
47710

LSI
LSIG
LSI
LSIG

47681
47683
47680
47682

47713
47715
47712
47714

Iu (40 C) =

630 A

PR211
P

Microprocessor-based
release

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles

200 kA
PR212
P

code 1SDA0 . . . . . R1
3 poles
4 poles

F = Front terminals
S6X 630 F F

In=630

I
LI

46560
46561

46564
46565

LSI
LSIG

46562
46563

46566
46567

EF = Extended front
terminals
S6X 630 F EF

In=630

I
LI

47724
47725

47744
47745

LSI
LSIG

47726
47727

47746
47747

I
LI

47729
47730

47749
47750

LSI
LSIG

47731
47732

47751
47752

FC CuAl = Front terminals


for copper/aluminium cables
S6X 630 F FC CuAl
In=630
R = Threaded rear
terminals
S6X 630 F R

In=630

I
LI

47739
47740

47759
47760

LSI
LSIG

47741
47742

47761
47762

RC = Rear terminals
for cables
S6X 630 F RC

In=630

I
LI

47734
47735

47754
47755

LSI
LSIG

47736
47737

47756
47757

7/58

ABB SACE

Order codes
SACE Isomax S6X current-limiting circuit-breaker

W = WITHDRAWABLE Moving part


S6X 400
Iu (40 C) = 400 A
PR211
P

Microprocessor-based
release
S6X 400 W MP

In=320

S6X 400 W MP

In=400

GSIS9153

S6X 630

I
LI
I
LI

S6X 630 W MP

In=630

630 A

PR211
P

Microprocessor-based
release
I
LI

code 1SDA0 . . . . . R1
3 poles
4 poles
47633
47635
47632
47634

Iu (40 C) =

Icu (415 V) =

47643
47645
47642
47644

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
4 poles
47650
47651

47655
47656

200 kA
PR212
P
LSI
LSIG
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
47637
47641
47636
47640

47647
47649
47646
47648

200 kA
PR212
P
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
4 poles
47652
47653

47657
47658

ABB SACE

7/59

Order codes
SACE Isomax S2X 80 circuit-breaker for motor protection

F = FIXED

S2X 80

Iu (40 C) =

80 A

Icu (415 V) =

70 kA
Im

GSIS9154

Magnetic only
release

P = PLUG-IN

FC Cu = Front terminals for copper cables


S2X 80 F FC Cu
R1
S2X 80 F FC Cu
R 1.6
S2X 80 F FC Cu
R2
S2X 80 F FC Cu
R 2.5
S2X 80 F FC Cu
R 3.2
S2X 80 F FC Cu
R4
S2X 80 F FC Cu
R5
S2X 80 F FC Cu
R 6.5
S2X 80 F FC Cu
R 8.5
S2X 80 F FC Cu
R 11
S2X 80 F FC Cu
R 12.5
S2X 80 F FC Cu
R 16
S2X 80 F FC Cu
R 20
S2X 80 F FC Cu
R 25
S2X 80 F FC Cu
R 32
S2X 80 F FC Cu
R 42
S2X 80 F FC Cu
R 52
S2X 80 F FC Cu
R 63
S2X 80 F FC Cu
R 80
R = Threaded rear terminals
S2X 80 F R
R1
S2X 80 F R
R 1.6
S2X 80 F R
R2
S2X 80 F R
R 2.5
S2X 80 F R
R 3.2
S2X 80 F R
R4
S2X 80 F R
R5
S2X 80 F R
R 6.5
S2X 80 F R
R 8.5
S2X 80 F R
R 11
S2X 80 F R
R 12.5
S2X 80 F R
R 16
S2X 80 F R
R 20
S2X 80 F R
R 25
S2X 80 F R
R 32
S2X 80 F R
R 42
S2X 80 F R
R 52
S2X 80 F R
R 63
S2X 80 F R
R 80

Moving part
S2X 80
Iu (40 C) = 80 A
GSIS9154

Magnetic only
release

7/60

S2X 80 P MP
S2X 80 P MP
S2X 80 P MP
S2X 80 P MP
S2X 80 P MP
S2X 80 P MP
S2X 80 P MP
S2X 80 P MP
S2X 80 P MP
S2X 80 P MP
S2X 80 P MP
S2X 80 P MP
S2X 80 P MP
S2X 80 P MP
S2X 80 P MP
S2X 80 P MP
S2X 80 P MP
S2X 80 P MP
S2X 80 P MP

Icu (415 V) =

13A
21A
26A
32A
42A
52A
65A
84A
110A
145A
163A
210A
260A
325A
415A
545A
680A
820A
1040A

50231
50232
50233
50234
50235
50236
50237
50238
50239
50240
50241
50242
50243
50244
50245
50246
50247
50248
50249

13A
21A
26A
32A
42A
52A
65A
84A
110A
145A
163A
210A
260A
325A
415A
545A
680A
820A
1040A

50250
50251
50252
50253
50254
50255
50256
50257
50258
50259
50260
50261
50262
50263
50264
50265
50266
50267
50268

70 kA
Im

R1
R 1.6
R2
R 2.5
R 3.2
R4
R5
R 6.5
R 8.5
R 11
R 12.5
R 16
R 20
R 25
R 32
R 42
R 52
R 63
R 80

code 1SDA0 . . . . . R1
3 poles

13A
21A
26A
32A
41A
52A
65A
84A
110A
145A
163A
210A
260A
325A
415A
545A
680A
820A
1040A

code 1SDA0 . . . . . R1
3 poles
50269
50270
50271
50272
50273
50274
50275
50276
50277
50278
50279
50280
50281
50282
50283
50284
50285
50286
50287

ABB SACE

Order codes
SACE Isomax S3 circuit-breaker for motor protection

F = FIXED

S3N 160

Iu (40 C) =

160 A

Icu (415 V) =

Im

PSIS9607

Magnetic only
release
F = Front terminals
S3N 160 F F
S3N 160 F F
S3N 160 F F
S3N 160 F F
S3N 160 F F
S3N 160 F F
S3N 160 F F
S3N 160 F F

S3H 160

R3
R5
R 10
R 25
R 50
R 100
R 125
R 160

Iu (40 C) =

160 A

Icu (415 V) =

R 50
R 100
R 125
R 160

Iu (40 C) =

160 A

Magnetic only
release

S3N 250

R 50
R 100
R 125
R 160

Iu (40 C) =

250 A

Magnetic only
release

S3H 250

R 160
R 200

Iu (40 C) =

250 A

Magnetic only
release

S3L 250

R 160
R 200

Iu (40 C) =

250 A

Magnetic only
release
F = Front terminals
S3L 250 F F
S3L 250 F F

48657
48658

85 kA
Im

R 160
R 200

code 1SDA0 . . . . . R1
3 poles

640 ... 1920A


800 ... 2400A

Icu (415 V) =

48651
48654

65 kA
Im

F = Front terminals
S3H 250 F F
S3H 250 F F

code 1SDA0 . . . . . R1
3 poles

640 ... 1920A


800 ... 2400A

Icu (415 V) =

50544
50545
50546
50547

35 kA
Im

F = Front terminals
S3N 250 F F
S3N 250 F F

code 1SDA0 . . . . . R1
3 poles

200 ... 600A


400 ... 1200A
500 ... 1500A
640 ... 1600A

Icu (415 V) =

45185
45186
45187
45188

85 kA
Im

F = Front terminals
S3L 160 F F
S3L 160 F F
S3L 160 F F
S3L 160 F F

code 1SDA0 . . . . . R1
3 poles

200 ... 600A


400 ... 1200A
500 ... 1500A
640 ... 1600A

Icu (415 V) =

47782
47783
47784
47785
47786
47787
47788
47789

65 kA
Im

F = Front terminals
S3H 160 F F
S3H 160 F F
S3H 160 F F
S3H 160 F F

code 1SDA0 . . . . . R1
3 poles

12 ... 36A
20 ... 60A
40 ... 120A
100 ... 300A
200 ... 600A
400 ... 1200A
500 ... 1500A
640 ... 1600A

Magnetic only
release

S3L 160

35 kA

code 1SDA0 . . . . . R1
3 poles

640 ... 1920A


800 ... 2400A

50548
50549

Note
Plug-in and withdrawable version are taken from the corresponding fixed version by means of the conversion
kits indicated on page 80.

ABB SACE

7/61

Order codes
SACE Isomax S4 circuit-breaker for motor protection

F = FIXED

S4N 160

Iu (40 C) =

160 A

Icu (415 V) =

PR212
MP

Microprocessor-based
release

PSIS9610

F = Front terminals
S4N 160 F F
S4N 160 F F

S4H 160

In = 100A
In = 160A

Iu (40 C) =

160 A

LRIU
LRIU

Icu (415 V) =

S4L 160

In = 100A
In = 160A

Iu (40 C) =

160 A

LRIU
LRIU

Icu (415 V) =

F = Front terminals
S4L 160 F F
S4L 160 F F

S4N 250

In = 100A
In = 160A

Iu (40 C) =

250 A

LRIU
LRIU

Icu (415 V) =

F = Front terminals
S4N 250 F F

S4H 250

In = 200A

Iu (40 C) =

250 A

LRIU

Icu (415 V) =

F = Front terminals
S4H 250 F F

S4L 250

In = 200A

Iu (40 C) =

250 A

In = 200A

code 1SDA0 . . . . . R1
3 poles
50550
50551

code 1SDA0 . . . . . R1
3 poles
50141

code 1SDA0 . . . . . R1
3 poles
48662

100 kA
PR212
MP

Microprocessor-based
release
F = Front terminals
S4L 250 F F

LRIU

Icu (415 V) =

45049
45050

65 kA
PR212
MP

Microprocessor-based
release

code 1SDA0 . . . . . R1
3 poles

35 kA
PR212
MP

Microprocessor-based
release

50139
50140

100 kA
PR212
MP

Microprocessor-based
release

code 1SDA0 . . . . . R1
3 poles

65 kA
PR212
MP

Microprocessor-based
release
F = Front terminals
S4H 160 F F
S4H 160 F F

35 kA

LRIU

code 1SDA0 . . . . . R1
3 poles
50552

7
Note
Plug-in and withdrawable version are taken from the corresponding fixed version by means of the conversion
kits indicated on page 80.

7/62

ABB SACE

Order codes
SACE Isomax S5-S6-S7 circuit-breakers for motor protection

F = FIXED

S5N 400

Iu (40 C) =

400 A

Icu (415 V) =

35 kA
PR212
MP

Microprocessor-based
release
F = Front terminals
S5N 400 F F

In = 320A

PSIS9613

S5H 400

Iu (40 C) =

400 A

LRIU

Icu (415 V) =

PR212
MP

S5L 400

In = 320A

Iu (40 C) =

400 A

LRIU

Icu (415 V) =

PR212
MP
In = 320A

S6N 800

Iu (40 C) =

800 A

LRIU

Icu (415 V) =

PR212
MP
In = 630A

PSIS9616

S6H 800

Iu (40 C) =

800 A

LRIU

Icu (415 V) =

PR212
MP

S6L 800

In = 630A

Iu (40 C) =

800 A

LRIU

Icu (415 V) =

PR212
MP

S7S 1250

In = 630A

Iu (40 C) =

1250 A

LRIU

Icu (415 V) =

S7H 1250

In = 1000A

Iu (40 C) =

1250 A

In = 1000A

50143

code 1SDA0 . . . . . R1
3 poles
45052

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles
50554

code 1SDA0 . . . . . R1
3 poles
50144

65 kA

LRIU

code 1SDA0 . . . . . R1
3 poles

45053

PSIS9620

F = Front terminals
S7H 1250 F F

LRIU

PR212
MP

Microprocessor-based
release

code 1SDA0 . . . . . R1
3 poles

50 kA
PR212
MP

Microprocessor-based
release
F = Front terminals
S7S 1250 F F

50553

100 kA

Microprocessor-based
release
F = Front terminals
S6L 800 F F

code 1SDA0 . . . . . R1
3 poles

65 kA

Microprocessor-based
release
F = Front terminals
S6H 800 F F

45051

35 kA

Microprocessor-based
release
F = Front terminals
S6N 800 F F

code 1SDA0 . . . . . R1
3 poles

100 kA

Microprocessor-based
release
F = Front terminals
S5L 400 F F

50142

65 kA

Microprocessor-based
release
F = Front terminals
S5H 400 F F

code 1SDA0 . . . . . R1
3 poles

Note
Withdrawable version are taken from the corresponding fixed version by means of the conversion kits
indicated on page 80.

ABB SACE

7/63

Order codes
SACE Isomax S3X-S4X-S6X current-limiting
circuit-breakers for motor protection

F = FIXED

S3X 125

Iu (40 C) =

125 A

Icu (415 V) =

Magnetic only
release

Im

GSIS9151

F = Front terminals
S3X 125 F F
S3X 125 F F
S3X 125 F F
S3X 125 F F

S3X 200

R 25
R 50
R 100
R 125

Iu (40 C) =

200 A

Icu (415 V) =

R 125
R 160
R 200

Iu (40 C) =

250 A

Microprocessor-based
release
F = Front terminals
S4X 250 F F
S4X 250 F F
S4X 250 F F

S6X 400

In = 100A
In = 160A
In = 200A

400 A

LRIU
LRIU
LRIU

Icu (415 V) =

Microprocessor-based
release
GSIS9152

F = Front terminals
S6X 400 F F

S6X 630

Iu (40 C) =

630 A

Microprocessor-based
release

code 1SDA0 . . . . . R1
3 poles
47780

200 kA
PR212
MP

In = 400A
In = 630A

46590
46591
48661

LRIU
LRIU

code 1SDA0 . . . . . R1
3 poles
47781
48663

GSIS9153

F = Front terminals
S6X 630 F F
S6X 630 F F

LRIU

Icu (415 V) =

code 1SDA0 . . . . . R1
3 poles

200 kA
PR212
MP

In = 320A

46135
48659
48660

200 kA
PR212
MP

Iu (40 C) =

code 1SDA0 . . . . . R1
3 poles

500 ... 1500A


640 ... 1920A
800 ... 2400A

Icu (415 V) =

45387
45388
45389
45390

200 kA
Im

F = Front terminals
S3X 200 F F
S3X 200 F F
S3X 200 F F

code 1SDA0 . . . . . R1
3 poles

100 ... 300A


200 ... 600A
400 ... 1200A
500 ... 1500A

Magnetic only
release

S4X 250

200 kA

7
Note
Plug-in and withdrawable version are taken from the corresponding fixed version by means of the conversion
kits indicated on page 80.

7/64

ABB SACE

Order codes
SACE Isomax S circuit-breakers for applications
up to 1000V

F = FIXED

S3L 160

Iu (40 C) =

160 A

Icu (1000 V) =

6 kA

Thermomagnetic
release

AC ~

PSIS9607

F = Front terminals
S3L 160 F F
S3L 160 F F
S3L 160 F F
S3L 160 F F
S3L 160 F F
S3L 160 F F

S3L 160

R 32
R 50
R 80
R 100
R 125
R 160

Iu (40 C) =

Im
Im
Im
Im
Im
Im

160 A

Icu (1000 V) =

DC

F = Front terminals
S3L 160 F F (N100%)
S3L 160 F F (N100%)
S3L 160 F F (N100%)
S3L 160 F F (N100%)
S3L 160 F F (N100%)
S3L 160 F F (N100%)

R 32
R 50
R 80
R 100
R 125
R 160

Iu (40 C) =

Im
Im
Im
Im
Im
Im

250 A

Icu (1000 V) =

S3X 125

Iu (40 C) =

125 A

Icu (1000 V)=

R 32
R 50
R 80
R 100
R 125

Iu (40 C) =

Microprocessor-based
release

PSIS9610

F = Front terminals
S4L 160 F F

S4L 250

In 100 A

LI

F = Front terminals
S4L 250 F F

S4X 250

In 250 A

F = Front terminals
S4X 250 F F

LI

ABB SACE

PR211
P
LI

Icu (1000 V) =

code 1SDA0 . . . . . R1
3 poles

250 A

Icu (1000 V) =

50449
50450

code 1SDA0 . . . . . R1
3 poles
50451
50452
50453
50454
50455

8 kA
PR212
P

code 1SDA0 . . . . . R1
3 poles
50458
50459

8 kA
PR212
P
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
50463

500A
500A
800A
1000A
1250A

LSI
LSIG

50460

Iu (40 C) =

In 250 A

code 1SDA0 . . . . . R1
3 poles

250 A

PR211
P

Microprocessor-based
release

Icu (1000 V) =

50547

Iu (40 C) =

Microprocessor-based
release

Im
Im
Im
Im
Im

160 A

PR211
P

code 1SDA0 . . . . . R1
4 poles

30 kA
AC ~

F = Front terminals
S3X 125 F F
S3X 160 F F
S3X 160 F F
S3X 160 F F
S3X 160 F F

50443
50444
50445
50446
50447
50448

Im 2000A
Im 2500A

Thermomagnetic
release

S4L 160

500A
500A
800A
1000A
1250A
1600A

DC

R 200
R 250

code 1SDA0 . . . . . R1
4 poles

40 kA

Thermomagnetic
release
F = Front terminals
S3L 250 F F (N100%)
S3L 250 F F (N100%)

50436
50437
50438
50439
50441
50442

40 kA

Thermomagnetic
release

S3L 250

500A
500A
800A
1000A
1250A
1600A

code 1SDA0 . . . . . R1
3 poles

code 1SDA0 . . . . . R1
3 poles
50461
50462

30 kA
PR212
P
LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
50464
50465

7/65

Order codes
SACE Isomax S circuit-breakers for applications
up to 1000V

F = FIXED

S5L 400

Iu (40 C) =

400 A

Icu (1000 V) =

40 kA
DC

Thermomagnetic
release
F = Front terminals
S5L 400 F F (N100%)

R 400

PSIS9613

S6L 630

Iu (40 C) =

Im 4000A

630 A

Icu (1000 V) =

DC

R 630

S6L 800

Iu (40 C) =

800 A

Icu (1000 V) =

R 800

PSIS9616

Iu (40 C) =

S5L 400 F F

In 400 A

S6L 630

LI

S6L 630 F F

In 630 A

S6L 800

LI

PR211
P

Microprocessor-based
release

GSIS9153

F = Front terminals
S6L 800 F F

In 800 A

S6X 630

LI

F = Front terminals
S4X 630 F F

In 630 A

S3D/S6D/S7D

7
PSIS9155

Switch-disconnector

7/66

F = Front terminals
S3D 320 F F
S6D 800 F F
S7D 1600 F F

code 1SDA0 . . . . . R1
3 poles

630 A

PR211
P

LI

Icu (1000 V) =

code 1SDA0 . . . . . R1
3 poles
50472

Iu (40 C) =

PR212
P

50583
50584

code 1SDA0 . . . . . R1
3 poles
50470
50471

12 kA
PR212
P
LSI
LSIG

Icu (1000 V) =

code 1SDA0 . . . . . R1
3 poles

12 kA
LSI
LSIG

50534

Iu (40 C) =

Microprocessor-based
release

Icu (1000 V) =

code 1SDA0 . . . . . R1
3 poles

800 A

PR212
P
LSI
LSIG

50469

Iu (40 C) =

50468

8 kA

code 1SDA0 . . . . . R1
3 poles

630 A

PR211
P

Microprocessor-based
release

Icu (1000 V) =

50582

Iu (40 C) =

code 1SDA0 . . . . . R1
4 poles

Im 8000A

400 A

PR211
P

Microprocessor-based
release

50467

50 kA
DC

S5L 400

code 1SDA0 . . . . . R1
4 poles

Im 6300A

Thermomagnetic
release
F = Front terminals
S6L 800 F F (N100%)

50466

40 kA

Thermomagnetic
release
F = Front terminals
S6L 630 F F (N100%)

code 1SDA0 . . . . . R1
4 poles

code 1SDA0 . . . . . R1
3 poles
50535
50536

30 kA
PR212
P

LSI
LSIG

code 1SDA0 . . . . . R1
3 poles
50473
50474

320/800/1600 A
code 1SDA0 . . . . . R1
3 poles
50446
50475
50479

ABB SACE

Order codes
SACE Isomax S2D switch-disconnectors

F = FIXED

S2D 125

Iu (40 C) =

125 A

Icw (1s) =

2.2 kA

PSIS9604

Switch-disconnector

Iu (40 C) =

160 A

Icw (1s) =

2.2 kA

Switch-disconnector

Moving part
S2D 125
Iu (40 C) = 125 A
PSIS9604

45057

45063

45058
45059

45064
45065

45056

45062

45060

45066

Icm (415 V) =

3.1 kA

code 1SDA0 . . . . . R1
3 poles
4 poles

FC Cu = Front terminals
for copper cables
S2D 160 F FC Cu
FC CuAl = Front terminals
for copper/aluminium cables
S2D 160 F FC CuAl*
S2D 160 F FC CuAl**
EF = Extended front terminals
S2D 160 F EF
R = Threaded rear terminals
S2D 160 F R

P = PLUG-IN

3.1 kA

code 1SDA0 . . . . . R1
3 poles
4 poles

FC Cu = Front terminals
for copper cables
S2D 125 F FC Cu
FC CuAl = Front terminals
for copper/aluminium cables
S2D 125 F FC CuAl*
S2D 125 F FC CuAl**
EF = Extended front terminals
S2D 125 F EF
R = Threaded rear terminals
S2D 125 F R

S2D 160

Icm (415 V) =

Icw (1s) =

2.2 kA

20632

45071

45068
20633

45072
45074

20630

45070

20634

45073

Icm (415 V) =

3.1 kA

Switch-disconnector

code 1SDA0 . . . . . R1
3 poles
4 poles

S2D 125 P MP

45061

45067

Icm (415 V) =

3.1 kA

S2D 160

Iu (40 C) =

160 A

Icw (1s) =

2.2 kA

Switch-disconnector

code 1SDA0 . . . . . R1
3 poles
4 poles

S2D 160 P MP

45069

45075

* Cable section = 1 x 2.5...50 mm2


** Cable section = 1 x 35...95 mm2

ABB SACE

7/67

Order codes
SACE Isomax S3D switch-disconnectors

F = FIXED

S3D 100

Iu (40 C) =

100 A

Icw (1s) =

6.5 kA

PSIS9607

Switch-disconnector

Iu (40 C) =

160 A

Icw (1s) =

6.5 kA

Switch-disconnector

S3D 100

PSIS9607
PSIS9607

7/68

20907

20329

20354

20335

20360

20341

20366

20353

20378

20347

20372

Icm (415 V) =

10 kA

Iu (40 C) =

100 A

Icw (1s) =

6.5 kA

20908

20909

20383

20408

20389

20414

20395

20420

20407

20432

20401

20426

Icm (415 V) =

10 kA

Switch-disconnector

code 1SDA0 . . . . . R1
3 poles
4 poles

S3D 100 P MP

20379

20381

Icm (415 V) =

10 kA

S3D 160

Iu (40 C) =

160 A

Icw (1s) =

6.5 kA

Switch-disconnector

code 1SDA0 . . . . . R1
3 poles
4 poles

S3D 160 P MP

20433

20435

Icm (415 V) =

10 kA

W = WITHDRAWABLE S3D 100

20906

code 1SDA0 . . . . . R1
3 poles
4 poles

F = Front terminals
S3D 160 F F
EF = Extended front terminals
S3D 160 F EF
FC Cu = Front terminals
for copper cables
S3D 160 F FC Cu
FC CuAl = Front terminals
for copper/aluminium cables
S3D 160 F FC CuAl
R = Threaded rear terminals
S3D 160 F R
RC = Rear terminals for cables
S3D 160 F RC

P = PLUG-IN

10 kA

code 1SDA0 . . . . . R1
3 poles
4 poles

F = Front terminals
S3D 100 F F
EF = Extended front terminals
S3D 100 F EF
FC Cu = Front terminals
for copper cables
S3D 100 F FC Cu
FC CuAl = Front terminals
for copper/aluminium cables
S3D 100 F FC CuAl
R = Threaded rear terminals
S3D 100 F R
RC = Rear terminals for cables
S3D 100 F RC

S3D 160

Icm (415 V) =

Iu (40 C) =

100 A

Icw (1s) =

6.5 kA

Switch-disconnector

code 1SDA0 . . . . . R1
3 poles
4 poles

S3D 100 W MP

20380

20382

Icm (415 V) =

10 kA

S3D 160

Iu (40 C) =

160 A

Icw (1s) =

6.5 kA

Switch-disconnector

code 1SDA0 . . . . . R1
3 poles
4 poles

S3D 160 W MP

20434

20436

ABB SACE

Order codes
SACE Isomax S3D switch-disconnectors

F = FIXED

S3D 250

Iu (40 C) =

250 A

Icw (1s) =

6.5 kA

Switch-disconnector

Iu (40 C) =

320 A

Icw (1s) =

6.5 kA

PSIS9607

Switch-disconnector

S3D 250

PSIS9607
PSIS9607

20911

20437

20462

20443

20468

20449

20474

20461

20486

20455

20480

Icm (415 V) =

10 kA

Iu (40 C) =

250 A

Icw (1s) =

6.5 kA

20912

20913

20491

20516

20497

20522

20503

20528

20515

20540

20509

20534

Icm (415 V) =

10 kA

Switch-disconnector

code 1SDA0 . . . . . R1
3 poles
4 poles

S3D 250 P MP

20487

20489

Icm (415 V) =

10 kA

S3D 320

Iu (40 C) =

320 A

Icw (1s) =

6.5 kA

Switch-disconnector

code 1SDA0 . . . . . R1
3 poles
4 poles

S3D 320 P MP

20541

20543

Icm (415 V) =

10 kA

W = WITHDRAWABLE S3D 250

ABB SACE

20910

code 1SDA0 . . . . . R1
3 poles
4 poles

F = Front terminals
S3D 320 F F
EF = Extended front terminals
S3D 320 F EF
FC Cu = Front terminals
for copper cables
S3D 320 F FC Cu
FC CuAl = Front terminals
for copper/aluminium cables
S3D 320 F FC CuAl
R = Threaded rear terminals
S3D 320 F R
RC = Rear terminals for cables
S3D 320 F RC

P = PLUG-IN

10 kA

code 1SDA0 . . . . . R1
3 poles
4 poles

F = Front terminals
S3D 250 F F
EF = Extended front terminals
S3D 250 F EF
FC Cu = Front terminals
for copper cables
S3D 250 F FC Cu
FC CuAl = Front terminals
for copper/aluminium cables
S3D 250 F FC CuAl
R = Threaded rear terminals
S3D 250 F R
RC = Rear terminals for cables
S3D 250 F RC

S3D 320

Icm (415 V) =

Iu (40 C) =

250 A

Icw (1s) =

6.5 kA

Switch-disconnector

code 1SDA0 . . . . . R1
3 poles
4 poles

S3D 250 W MP

20488

20490

Icm (415 V) =

10 kA

S3D 320

Iu (40 C) =

320 A

Icw (1s) =

6.5 kA

Switch-disconnector

code 1SDA0 . . . . . R1
3 poles
4 poles

S3D 320 W MP

20542

20544

7/69

Order codes
SACE Isomax S6D switch-disconnectors

F = FIXED

S6D 400

Iu (40 C) =

400 A

Icw (1s) =

15 kA

GSIS9156

Switch-disconnector

Iu (40 C) =

630 A

Icw (1s) =

15 kA

Switch-disconnector

Iu (40 C) =

800 A

Icw (1s) =

15 kA

Switch-disconnector

GSIS9156

20588

20566

20601

20573

20608

23326

23327

Icm (415 V) =

30 kA

20674

20699

20680

20705

20686

20711

20698

20723

20692

20717

Icm (415 V) =

30 kA

Iu (40 C) =

400 A

Icw (1s) =

15 kA

20724

20749

20730

20755

20736

20761

20748

20773

20742

20767

Icm (415 V) =

30 kA

code 1SDA0 . . . . . R1
3 poles
4 poles

S6D 400 W MP

20617

Iu (40 C) =

630 A

Icw (1s) =

15 kA

Icm (415 V) =

20619

30 kA

Switch-disconnector

code 1SDA0 . . . . . R1
3 poles
4 poles

S6D 630 W MP

20918

S6D 800

7/70

20552

Switch-disconnector

S6D 630

20581

code 1SDA0 . . . . . R1
3 poles
4 poles

F = Front terminals
S6D 800 F F
EF = Extended front terminals
S6D 800 F EF
FC CuAl = Front terminals
for copper/aluminium cables
S6D 800 F FC CuAl
R = Threaded rear terminals
S6D 800 F R
RC = Rear terminals for cables
S6D 800 F RC

W = WITHDRAWABLE S6D 400

20545

code 1SDA0 . . . . . R1
3 poles
4 poles

F = Front terminals
S6D 630 F F
EF = Extended front terminals
S6D 630 F EF
FC CuAl = Front terminals
for copper/aluminium cables
S6D 630 F FC CuAl
R = Threaded rear terminals
S6D 630 F R
RC = Rear terminals for cables
S6D 630 F RC

S6D 800

30 kA

code 1SDA0 . . . . . R1
3 poles
4 poles

F = Front terminals
S6D 400 F F
EF = Extended front terminals
S6D 400 F EF
FC CuAl = Front terminals
for copper/aluminium cables
S6D 400 F FC CuAl
R = Threaded rear terminals
S6D 400 F R
RC = Rear terminals for cables
S6D 400 F RC

S6D 630

Icm (415 V) =

Iu (40 C) =

800 A

Icw (1s) =

15 kA

Icm (415 V) =

20919

30 kA

Switch-disconnector

code 1SDA0 . . . . . R1
3 poles
4 poles

S6D 800 W MP

20920

20921

ABB SACE

Order codes
SACE Isomax S7D switch-disconnectors

F = FIXED

S7D 1000

Iu (40 C) =

1000 A

Icw (1s) =

25 kA

Switch-disconnector

PSIS9625

Iu (40 C) =

1250 A

Icw (1s) =

25 kA

Switch-disconnector

Iu (40 C) =

1600 A

Icw (1s) =

25 kA

Switch-disconnector

20805

20786

20811

20798

20823

20792

20817

Icm (415 V) =

52.5 kA

20824

20849

20830

20855

20836

20861

20848

20873

20842

20867

Icm (415 V) =

52.5 kA

Iu (40 C) =

1000 A

20874

20890

20879

20895

20889
20884

Icw (1s) =

25 kA

Icm (415 V) =

20900

52.5 kA

code 1SDA0 . . . . . R1
3 poles
4 poles

S7D 1000 W MP

20922

Iu (40 C) =

1250 A

Icw (1s) =

25 kA

Icm (415 V) =

20923

52.5 kA

Switch-disconnector

code 1SDA0 . . . . . R1
3 poles
4 poles

S7D 630 W MP

20924

S7D 1600
PSIS9625

20780

Switch-disconnector

S7D 1250

ABB SACE

20799

code 1SDA0 . . . . . R1
3 poles
4 poles

F = Front terminals
S7D 1600 F F
EF = Extended front terminals
S7D 1600 F EF
VR = Vertical flat-bar rear terminals
S7D 1600 F VR
HR = Horizontal flat-bar rear terminals
S7D 1600 F HR

W = WITHDRAWABLE S7D 1000

20774

code 1SDA0 . . . . . R1
3 poles
4 poles

F = Front terminals
S7D 1250 F F
EF = Extended front terminals
S7D 1250 F EF
FC CuAl = Front terminals
for copper/aluminium cables
S7D 1250 F FC CuAl
VR = Vertical flat-bar rear terminals
S7D 1250 F VR
HR = Horizontal flat-bar rear terminals
S7D 1250 F HR

S7D 1600

52.5 kA

code 1SDA0 . . . . . R1
3 poles
4 poles

F = Front terminals
S7D 1000 F F
EF = Extended front terminals
S7D 1000 F EF
FC CuAl = Front terminals
for copper/aluminium cables
S7D 1000 F FC CuAl
VR = Vertical flat-bar rear terminals
S7D 1000 F VR
HR = Horizontal flat-bar rear terminals
S7D 1000 F HR

S7D 1250

Icm (415 V) =

Iu (40 C) =

1600 A

Icw (1s) =

25 kA

Icm (415 V) =

20925

52.5 kA

Switch-disconnector

code 1SDA0 . . . . . R1
3 poles
4 poles

S7D 1600 W MP

20926

20927

7/71

Order codes
SACE Isomax S8D switch-disconnectors

F = FIXED

S8D 2000

Iu (40 C) =

2000 A

Icw (1s) =

40 kA

Switch-disconnector

Iu (40 C) =

2500 A

Icw (1s) =

40 kA

GSIS9149

Switch-disconnector

45158

45159

45160

45161

Icm (415 V) =

85 kA

code 1SDA0 . . . . . R1
3 poles
4 poles

F = Front terminals
S8D 2500 F F
VR = Vertical flat-bar rear terminals
S8D 2500 F VR

S8D 3200

85 kA

code 1SDA0 . . . . . R1
3 poles
4 poles

F = Front terminals
S8D 2000 F F
VR = Vertical flat-bar rear terminals
S8D 2000 F VR

S8D 2500

Icm (415 V) =

Iu (40 C) =

Switch-disconnector
VR = Vertical flat-bar rear terminals
S8D 3200 F VR

3200 A

Icw (1s) =

40 kA

45162

45163

45164

45165

Icm (415 V) =

85 kA

code 1SDA0 . . . . . R1
3 poles
4 poles
45167

45166

7/72

ABB SACE

Order codes
SACE Isomax S accessories

Duty releases

GSIS9001

Shunt opening releases


Type

code 1SDA0 . . . . . R1
S1-S2
S3-S4-S5

24...30 V AC
48 V AC - 60 V DC
110...130 V AC
220...250 V AC
380...400 V AC
12 V DC
24 V DC
48 V DC
110 V DC
220 V DC
250 V DC
12 V DC
24 V AC / DC
48 V AC / DC
60 V AC / DC
60 V AC / 60 ... 72 V DC
110...120 V AC - 110...125 V DC
220...240 V AC - 220...250 V DC
380...400 V AC
480 V AC
24 V DC
30 V DC - 24 V AC
48 V AC / DC
60 V DC
100...127 V DC / AC
127...150 V AC
160 V DC / 150...180 V AC
200...250 V DC / 200...255 V AC
380...500 V AC

13311
13306
13312
13313
13314
50581
13304
13305
13307
13309
13310
23403
13781
13782
23405
13783
13785
13786
37512

S6-S7

S8

23404
14136
14137
23406
14138
14140
14141
37514
50685
46602
46600
46603
47564
46605
47565
46607
46608

Shunt closing releases


Type

code 1SDA0 . . . . . R1

GSIS9003

S8

ABB SACE

24 V AC 50 Hz
30 V AC 50 Hz
48 V AC 50 Hz
60 V AC 50 Hz
127 ...130 V AC 50 Hz
220 V AC 50 Hz
500 V AC 50 Hz
24 V AC 60 Hz
120 V AC 60 Hz
208 ...220 V AC 60 Hz
240 V AC 60 Hz
380 V AC 60 Hz
100 V AC 50 Hz - 110 ...115 V AC 60 Hz
110 ...115 V AC 50 Hz - 125 ...127 V AC 60 Hz
230 ...240 V AC 50 Hz - 277 V AC 60 Hz
380 ...400 V AC 50 Hz - 440 V AC 60 Hz
415 ...440 V AC 50 Hz - 480 V AC 60 Hz
24 V DC
30 V DC
48 V DC
60 V DC
110...125 V DC
220...250 V DC
310 V DC

46636
46643
46637
46638
46646
46633
46644
46649
46647
46641
46648
46645
46639
46634
46640
46635
46642
46650
46655
46651
46656
46652
46653
46654

7
7/73

Order codes
SACE Isomax S accessories

GSIS9002

Undervoltage releases
Type

code 1SDA0 . . . . . R1
S1-S2
S3-S4-S5

24 V AC 50 Hz
30 V AC 50 Hz
48 V AC 50 Hz
60 V AC 50 Hz
110 V AC 50 Hz
127 ...130 V AC 50 Hz
220 V AC 50 Hz
500 V AC 50 Hz
100 V AC 50 Hz - 110 ...115 V AC 60 Hz
110 ...115 V AC 50 Hz - 125 ...127 V AC 60 Hz
230 ...240 V AC 50 Hz - 277 V AC 60 Hz
380 V AC 50 Hz - 380 ...440 V AC 60 Hz
380 ...400 V AC 50 Hz - 440 V AC 60 Hz
415 ...440 V AC 50 Hz - 480 V AC 60 Hz
24 V AC
48 V AC
60 V AC
110 V AC 60 Hz
110 ...127 V AC
120 V AC 60 Hz
208 ...220 V AC 60 Hz
220 ...250 V AC
240 V AC 60 Hz
380 V AC 60 Hz
380 ...440 V AC
480 V AC
24 V DC
30 V DC
48 V DC
60 V DC
110 V DC
110...125 V DC
220 V DC
220...250 V DC

23401

S6-S7

S8
46613
46620
46614
46615

23402
13319

46623
46609
46621
46616
46611
46617

13320

13321
46612
46619
13842
13843
23346

14188
14189
23347

13844

14190

45046
46624
46618
13846

14192
46625
46622

13315
13316
45045
13317

13847
37513
13833

14193
37515
14179

13835
13836

14181
14182

46626
46631
46627
46632

13838

14184

46628

13839

14185

46629

S6-S7

S8

13318

Undervoltage releases + time-lag device

GSIS9042

Type

code 1SDA0 . . . . . R1
S3-S4-S5

110 - 220 V AC
24 V AC/DC
30 V AC/DC
48 V AC/DC
60 V AC/DC
110/125 V AC/DC
220/250 V AC/DC

13840

14186
50737
50738
50739
50740
50741
50742

Connectors for duty releases

GSIS9013

Type

7
7/74

for fixed circuit-breakers - L=1m


for fixed circuit-breakers - L=2m
for fixed circuit-breakers - L=1m
for fixed circuit-breakers - L=2m
for plug-in or withdrawable circuit-breakers - L=1m
for withdrawable circuit-breakers - L=1m
for withdrawable circuit-breakers - L=2m
flying 9-pole socket-plug - L=0,6m
extension for testing auxiliary circuits
with the circuit-breaker racked out

code 1SDA0 . . . . . R1
S1-S2
S3-S4-S5-S6 S7
13865
37523
14209
44752
13866
14210
48949
13333
25552

25552

ABB SACE

Order codes
SACE Isomax S accessories

Electrical signalling

GSIS9004

Auxiliary contacts
Type

code 1SDA0 . . . . . R1
S1-S2
S3-S4-S5

S6-S7

2 open/closed change-over contacts


1 open/closed change-over contacts
and 1 release tripped signal
1 NO, 1 NC and 1 release not tripped signal
1 NO, 1 NC and 1 release tripped signal
3 open/closed change-over contacts

13328

13856

23366

13327

13575

23332
25773
48956

S8

47563

Auxiliary contacts for digital signals


Type

code 1SDA0 . . . . . R1
S1-S2
S3-S4-S5

2 open/closed change-over contacts


1 open/closed change-over contacts
and 1 release tripped signal
1 NO, 1 NC and 1 release not tripped signal

S6-S7

25544

25774

25545

25775
25776

S8

Early making contacts and connectors


Type

code 1SDA0 . . . . . R1
S1-S2
S3-S4-S5-S6 S7

early making contact and connector


for undervoltage release

25551

S8

48106

Connectors for auxiliary contacts

GSIS9015

Type
for fixed circuit-breakers - L=1m
for fixed circuit-breakers - L=2m
for fixed circuit-breakers - L=1m
for fixed circuit-breakers - L=2m
for plug-in or withdrawable circuit-breakers - L=1m
for withdrawable circuit-breakers - L=1m
for withdrawable circuit-breakers - L=2m
flying 9-pole socket-plug - L=0,6m
extension for testing auxiliary circuits with the
circuit-breaker racked out

code 1SDA0 . . . . . R1
S1-S2
S3-S4-S5-S6 S7

S8

13863
37522
14207
44751
13864
14208
48947
13329
25553

25553

Signally contacts
Type

code 1SDA0 . . . . . R1
S8

contact for signalling closing springs charged

47562

7
ABB SACE

7/75

Order codes
SACE Isomax S accessories

Motor operating mechanisms


Solenoid operator
Type

GSIS9022

GSIS9023

at the side of the circuit-breaker


48 V DC
60 V DC - 110 V AC
110 V DC - 220...230 V AC
220 V DC
on the front of the circuit-breaker
48 V DC
60 V DC - 110 V AC
110 V DC - 220...230 V AC
220 V DC

code 1SDA0 . . . . . R1
S1-S2
48025
48026
48027
48028
48015
48016
48017
48018

Direct action motor operating mechanism


Type

code 1SDA0 . . . . . R1
S3-S4-S5

GSIS9021

24 V DC
48...60 V DC
100...127 V AC - 100...125 V DC
220...240 V AC - 220...250 V DC
380 V AC
440 V AC

13873
13874
13875
13876
13877
14545

Stored energy motor operating mechanism


Type

code 1SDA0 . . . . . R1
S6

GSIS9020

24 V DC
48 V DC
60 V DC
110 V AC / DC
120...127 V AC / DC
220...250 V AC / DC
380 V AC

14029
14030
23348
23349
14031
14032
14033

S7
14214
14215
23350
23351
14216
14217
14218

Geared motor for automatic charging of closing springs


Type

code 1SDA0 . . . . . R1

GSIS9007

S8
24/30 V DC
48/60 V DC
100...130 V DC
220...250 V DC

47558
47559
47560
47561

Connectors for motor operating mechanism and auxiliary


contacts

GSIS9014

Type

7
7/76

for fixed circuit-breakers - L=1m


for fixed circuit-breakers - L=2m
for fixed circuit-breakers - L=1m
for fixed circuit-breakers - L=2m
for plug-in or withdrawable circuit-breakers - L=1m
for withdrawable circuit-breakers - L=1m
for withdrawable circuit-breakers - L=2m
flying 9-pole socket-plug - L=0,6m
extension for testing auxiliary circuits with the
circuit-breaker racked out

code 1SDA0 . . . . . R1
S1-S2
S3-S4-S5-S6 S7
13857
37524
14203
44850
13858
14204
48950
13329
25554

25554

ABB SACE

Order codes
SACE Isomax S accessories

Operating mechanism and locks


Direct-mounted rotary handle operating mechanism
GSIS9025

Type

code 1SDA0 . . . . . R1
S1-S2
S3-S4-S5

for fixed/plug-in circuit breakers


for withdrawable circuit breakers
emergency for fixed or plug-in circuit-breakers

13867
13868
13870

S6

S7

14026
14027
46568

14211
14212
46570

Rotary handle operating mechanism with transmission rod


GSIS9024

Type
compartment door, fixed depth for fixed
or plug-in circuit-breakers (L= 119,5 mm)
compartment door, adjustable depth
(Lmax=300 mm) for fixed or plug-in
compartment door, adjustable depth
(Lmax=300 mm) for withdrawable
compartment door, adjustable depth
(Lmax=500 mm) for fixed
compartment door, adjustable depth
(Lmax=500 mm) for withdrawable
compartment door, emergency, fixed depth
for fixed or plug-in circuit-breakers (Lmax= 119.5 mm)
compartment door, emergency, adjustable depth
for fixed or plug-in circuit-breakers (Lmax= 300 mm)
compartment door, emergency, adjustable depth
for fixed circuit-breakers (Lmax= 500 mm)
remote transmission rod with adj. depth (Lmax= 180 mm)
remote transmission rod with adj. depth (Lmax= 500 mm)

code 1SDA0 . . . . . R1
S1-S2
S3-S4-S5

S6

S7

14028

14213

50715

50716

46569

46572

S8

13326
13869
50714

45054
13871

25436
45055

25427

GSIS9026

Front flange
Type

code 1SDA0 . . . . . R1
S3...S5
S6

S7

front flange for operating lever mechanism for fixed or plug-in


front flange for operating lever mechanism for withdrawable
flange for compartment door

13889
13890

14227
14228

14035
14036

45023

GSIS9008

Key lock for open position


Type

code 1SDA0 . . . . . R1
S3...S5
S6-S7

for motor operating mechanism - a different key for each cb.


for motor operating mechanism - the same key for sets of cbs
for motor operating mechanism against manual operation the same key for each circuit-breaker
for front flange / rotary handle a different key for each circuit-breaker
for front flange / rotary handle the same key for sets of circuit-breakers
for front flange
key lock type RONIS

13883
13884

S8

13885
13886
36245

13881

13881

13882

13882

43514

43514

Type

Size

code 1SDA0 . . . . . R1

compartment door lock for front flange


for locks /crank handle operating mechanism
padlock device for operating lever
padlock device on the front of the circuit-breaker
tamper-proof lock for thermal release
tamper-proof lock for thermal release

S3-S4-S5-S6-S7
S1-S2
S8
S2
S3

45024

GSIS9035

GSIS9010

Locks

ABB SACE

13880
13332
45025
36196
25548

7
7/77

Order codes
SACE Isomax S accessories

PSIS9640

Mechanical interlock across two circuit-breakers


Type

code 1SDA0 . . . . . R1
horizontal

S3
S3X
S4
S4X
S5400/630
S6
S7
S3-S4-S5-S6-S7 (circuit-breaker/fixed part for interlocking)

23330
50524
13690
50525
43453
14024
14205
50093

vertical
23331
13691
43454
14025
14206
50093

Connection terminals

PSIS9643

PSIS9642

PSIS9641

PSIS9663

Type

EF=Extended front terminals


S2
S3-S4
S5 400
S6 630
S6 800
S7
ES=Spreaded extended front terminals
S3-S4
S5
S6 (1/2 upper kit)
S6 (1/2 lower kit)
S6
S7 (1/2 upper kit)
S7 (1/2 lowerkit)
S7
FC Cu=Front terminals for copper cables
S3-S4
S5 400
S5 630
FC CuAl=Front terminals for copper/aluminium cables
S2 (2,5-50 mm2) (*)
S2 (35-95 mm2) (*)
S3D 100
S3 160 - S4 160 (1x95 mm2)
S3 250 - S4 250 (1x150 mm2)
S5 400 (2x120 mm2)
S5 400 (1x240 mm2)
S6 630 (2x240 mm2)
S6 800 (3x185 mm2)
S7 1250 (4x240 mm2)
R=Threaded rear terminals
S1
S2
S3-S4
S5 400
S5 630
S6
R Res.Cur.=Threaded rear terminals
for reasidual current-release mounted below
S3
HR/VR=Horizontal or vertical flat-bar rear terminals
S7
S8
RC = Rear terminals for copper/aluminium cables
S3-S4 (1x120 mm2)
S5 400 (1x240 mm2)
S6 630 (2x150 mm2)
S6 800 (3x240 mm2)

code 1SDA0 . . . . . R1
3 pieces 4 pieces 6 pieces

8 pieces

23353
23367
23379
23383
23399

23359
23373
23389
23393
23396

25797
13596
13706
13920
13954
14079

25798
13597
13707
13921
13955
14080

46517
47551
50692
50704

50694
50705

46518
47552

50693

50695

46515
47549

50688

50690

46516
47550

50689

50691

23354
23368
38769

23360
23374
38770

13598
13708
38767

13599
13709
38768

50526
50527
23355
23356
23357
25766
23370
23380
23384
23387

50528
50530
23361
23362
23363
25765
23376
23390
23394
23397

36194
25801
13600
13602
20293
23295
13710
13922
13956
14081

36195
25802
13601
13603
20294
23296
13711
13923
13957
14082

23365
23378
38777
23392

13268
13294
13606
13714
38968
13960

13269
13295
13607
13715
38775
13961

23352
23372
38776
23382

25543
23400

23398

14083
46578

14084
46579

23358
23371
23381
23385

23364
23377
23391
23395

13604
13712
13924
13958

13605
13713
13925
13959

(*) Order also the relevant EF extended front terminals

7/78

ABB SACE

Order codes
SACE Isomax S accessories
Insulating terminal covers

PSIS9638

PSIS9644

Type

code 1SDA0 . . . . . R1
3 poles
4 poles

high for fixed


S1
13290
S2
13340
S3-S4
13695
S5
13897
S6
14040
low for fixed and for moving part of plug-in or withdrawable circuit-breakers
S1
13292
S2
13342
S3-S4
13693
S5
13895
S6
14038
S7
23324

13291
13341
13696
13898
14041
13293
13343
13694
13896
14039
23325

Screws for sealing terminal covers


Type

code 1SDA0 . . . . . R1

S1-S2
S3-S4-S5-S6-S7

13344
13699

GSIS9031

GSIS9005

GSIS9045

GSIS9043

GSIS9041

Accessories for electronic releases

ABB SACE

Type

Model

code
1SDA0 . . . . . R1

Signalling unit SACE PR010/K


Signalling unit SACE PR212/K
Dialogue unit SACE PR212/D-M Modbus + actuator unit SACE PR212/T
for SACE PR212/P (LSI - LSIG)
Dialogue unit SACE PR212/D-M Modbus + actuator unit SACE PR212/T
for SACE PR212/MP (LRIU)
Dialogue unit SACE PR212/D-L Lon + actuator unit SACE PR212/T
for SACE PR212/P (LSI - LSIG)
Dialogue unit SACE PR212/D-L Lon + actuator unit SACE PR212/T
for SACE PR212/MP (LRIU)
Dialogue unit SACE PR212/D + Actuator unit SACE PR212/T
Test unit SACE TT1
Test and configuration unit SACE PR010/T
SACE PR212/CI contactor operating unit (with PR212/MP)
Current transformer for neutral conductor outside circuit-breaker
Current transformer for neutral conductor outside circuit-breaker
Current transformer for neutral conductor outside circuit-breaker
Current transformer for neutral conductor outside circuit-breaker
Current transformer for neutral conductor outside circuit-breaker
Current transformer for neutral conductor outside circuit-breaker
Current transformer for neutral conductor outside circuit-breaker
Current transformer for neutral conductor outside circuit-breaker
Current transformer for neutral conductor outside circuit-breaker
Current transformer for neutral conductor outside circuit-breaker
Current transformer for neutral conductor outside circuit-breaker
Current transformer for neutral conductor outside circuit-breaker
Current transformer for neutral conductor outside circuit-breaker
Current transformer for neutral conductor outside circuit-breaker
Current transformer for neutral conductor outside circuit-breaker
X3 connector for relay tripped signal and neutral protection
for fixed circuit-breaker with PR211/P, PR212/P - LSI
X3, X4 connectors for relay tripped signal and neutral protection
for fixed circuit-breaker with PR212/P - LSIG
X3 connector for relay tripped signal and neutral protection
for plug-in or withdrawable circuit-breaker with PR211/P, PR212/P - LSI
X3, X4 connectors for relay tripped signal and neutral protection
for plug-in or withdrawable circuit-breaker with PR212/P - LSIG
electrical/mechanical signalling and lock for PR212/P tripped

S4-S5-S6-S7
S8

48965
45021

S4-S5-S6-S7

50718

S4-S5-S6-S7

50719

S4-S5-S6-S7

50720

S4-S5-S6-S7
S8
S4-S5-S6-S7
S4-S5-S6-S7
S4-S5-S6-S7
S4 100
S4 160
S4 250
S5 320
S5 400
S5 630
S6 630
S6 800
S7 1000
S7 1250
S7 1600
S8 1600
S8 2000
S8 2500
S8 3200

50721
45020
37121
48964
50708
37114
37115
37117
37118
37119
37120
25777
25778
25779
25780
25781
45015
45016
45017
45018

S4-S5-S6-S7

13702

S4-S5-S6-S7

13704

S4-S5-S6-S7

13703

S4-S5-S6-S7
S8

13705
46581

7
7/79

Order codes
SACE Isomax S accessories

Conversion kits

GSIS9036

from fixed circuit-breaker to moving part of plug-in circuit-breaker


Type

code 1SDA0 . . . . . R1
3 poles
4 poles

S1
S2
S3-S4
S3X
S4X
S5 400

13270
13296
13608
46519
46511
13716

13271
13297
13609
46520
46512
13717

GSIS9037

from fixed circuit-breaker to moving part of withdrawable circuitbreaker


Type

code 1SDA0 . . . . . R1
3 poles
4 poles

S3-S4
S3X
S4X
S5 400
S5 630
S6 630 / 800
S6X
S7

13610
46521
46514
13718
38778
13962
47619
23299

13611
46522
46513
13719
38779
13963
47620
14087

from plug-in circuit-breaker to withdrawable circuit-breaker


Type

code
1SDA0 . . . . . R1

S3-S4

13692

S5

13892

GSIS9047

Guide for preparing the fixed part of a plug-in circuit-breaker for use
as the fixed part of a withdrawable circuit-breaker
Guide for preparing the fixed part of a plug-in circuit-breaker for use
as the fixed part of a withdrawable circuit-breaker

Size

7
7/80

ABB SACE

Order codes
SACE Isomax S accessories

Fixed parts
Plug-in circuit-breaker

GSIS9123

Type
EF = Extended front terminals
S3 P FP EF
S4 P FP EF
S5 400 P FP EF
FC = Front terminals for copper cables
S1 P FP FC
S2 P FP FC
S3 P FP FC
S4 P FP FC
S5 400 P FP FC
R = Threaded rear terminals
S1 P FP R
S2 P FP R
S3 P FP R
S4 P FP R
S5 400 P FP R

code 1SDA0 . . . . . R1
3 poles
4 poles
13539
13612
13720

13548
13621
13729

13272
13298
13543
13616
13724

13274
13300
13550
13625
13733

13273
13299
13547
13620
13728

13275
13540
13554
13629
13737

Withdrawable circuit-breaker

GSIS9124

Type
EF = Extended front terminals
S3 W FP EF
S4 W FP EF
S5 400 W FP EF
S6 W FP EF
S7 W FP EF
ES = Spreaded extended front terminals
S5 630 W FP ES
FC = Front terminals for copper cables
S3 W FP FC
S4 W FP FC
S5 400 W FP FC
R = Threaded rear terminals
S3 W FP R
S4 W FP R
S5 400 W FP R
S5 630 W FP R
VR = Vertical flat-bar rear terminals
S5 630 W FP VR
S6 W FP VR
S7 W FP VR
HR = Horizontal flat-bar rear terminals
S6 W FP HR
S7 W FP HR

code 1SDA0 . . . . . R1
3 poles
4 poles
13555
13630
13738
13964
48951

13564
13639
13747
13973
14097

38761

38762

13559
13634
13742

13568
13643
13751

13563
13638
13746
38763

13572
13647
13755
38970

38971
13972
14096

38972
13981
14105

13968
14092

13977
14101

7
ABB SACE

7/81

Order codes
SACE Isomax S accessories

Accessories for fixed part of plug-in or withdrawable circuit-breakers

PSIS9646

PSIS9655

PSIS9654

PSIS9653

Terminals for the fixed parts of plug-in or withdrawable


circuit-breakers
Type
EF = Extended front terminals
S3-S4
S5 400
S5 630
S6 (with terminals mounted below for S6X)
S7
FC Cu/Al = Front terminals for copper / aluminium cables
S3-S4
S5 400
R = Threaded rear terminals
S3-S4
S5 400
S5 630
HR = Horizontal flat-bar rear terminals
S6
S7
VR = Vertical flat-bar rear terminals
S5 630
S6
S7

code 1SDA0 . . . . . R1
3 poles
4 poles
13650
13759
38780
13984
14108

13651
13760
38781
13985
14109

13652
13761

13653
13762

13654
13763
38969

13655
13764
38782

13986
14110

13987
14111

38763
13988
14112

38784
13989
14113

Insulating covers for fixed parts


Type

code 1SDA0 . . . . . R1
3 poles
4 poles

S3-S4
S5 400

13697
13899

13698
13900

Type

Model

code
1SDA0 . . . . . R1

contacts for signalling circuit-breaker racked out


contacts for signalling circuit-breaker racked out for digital signals
contacts for signalling circuit-breaker racked in
contacts for signalling circuit-breaker racked in for digital signals

S3-S4-S5-S6-S7
S3-S4-S5-S6-S7
S3-S4-S5-S6-S7
S3-S4-S5-S6-S7

GSIS9006

Position contacts

13859
25546
13860
25547

GSIS9009

Lock for fixed part of withdrawable circuit-breakers


Type

Model

key lock for locking in racked in / out position - different key for each cb.
key lock for locking in racked in / out position - same key for sets of cb.
padlock device

S3-S4-S5-S6-S7
S3-S4-S5-S6-S7
S3-S4-S5-S6-S7

code
1SDA0 . . . . . R1
25434
25435
13872

7
7/82

ABB SACE

Order codes
SACE Isomax S accessories

Installation accessories

GSIS9011

Bracket for mounting on DIN rail


Type

Model

DIN EN 50022
DIN EN 50022
DIN EN 50022 (for solenoid operator)
DIN EN 50022 (for solenoid operator)
DIN EN 50023 (complete with DIN front flange H=45 mm)
DIN EN 50023 (complete with DIN front flange H=45 mm)
DIN EN 50023 (complete with DIN front flange H=45 mm)
DIN EN 50023 (complete with DIN front flange H=45 mm)
DIN EN 50023 (complete with DIN front flange H=45 mm)
DIN EN 50023 (complete with DIN front flange H=45 mm)

S1
S2
S1
S2
S3 - 3 poles
S3 - 4 poles
S4 - 3 poles
S4 - 4 poles
S5 - 3 poles
S5 - 4 poles

code
1SDA0 . . . . . R1
23328
23329
48523
48524
13576
13577
13700
13701
13901
13902

PSIS9657

IP54 protection
Type

Model

for fixed-depth rotary handle operating mechanism on door


for adjustable-depth rotary handle operating mechanism on door

S1-S2
S3-S4-S5-S6-S7

code
1SDA0 . . . . . R1
13339
13891

Residual-current releases

PSIS9665

GSIS9027

SACE RC210, RC211, SACE RC212


code 1SDA0 . . . . . R1
side by side
below

RC210/1 for S1 (In=63 A - IDn=0,3 A)


RC210/1 for S1 (In=63 A - IDn=0,5 A)
RC210/1 for S1 (In=63 A - IDn=0,3 A)
RC210/1 for S1 (In=63 A - IDn=0,5 A)

45076
45077
45079
45080

RC211/1 for S1
RC211/2 for S2
RC211/3 for S3

13282
13222
20288

13283
13323
20289

RC212/1 for S1
RC212/2 for S2
RC212/3 for S3

13284
13324
20290

13285
13325
20291

SACE RCQ

GSIS9046

ABB SACE

Type

Type

code 1SDA0 . . . . . R1

release and closed toroid - diameter 60 mm


release and closed toroid - diameter 110 mm
release and closed toroid - diameter 185 mm
release and opening toroid - diameter 110 mm
release and opening toroid - diameter 180 mm
release and opening toroid - diameter 230 mm

37388
37389
50542
37390
37391
37392

release only

37393

closed toroid only - diameter 60 mm


closed toroid only - diameter 110 mm
closed toroid only - diameter 185 mm
opening toroid only - diameter 110 mm
opening toroid only - diameter 180 mm
opening toroid only - diameter 230 mm

37394
37395
50543
37396
37397
37398

7
7/83

ABB SACE S.p.A.


L.V. Breakers Division
Via Baioni, 35
24123 Bergamo - Italy
Tel.: +39 035.395.111 - Telefax: +39 035.395.306-433
http://www.abb.com

604050/012 en
Printed in Italy
Tipografia

Due to possible developments of standards as well as of materials,


the characteristics and dimensions specified in the present catalogue
may only be considered binding after confirmation by ABB SACE.