You are on page 1of 12

Lighting Design

***************

Name   : Thant Zin
Job   : Church Lighting @ Station Street, NantThaGone, Insein
Job Ref.   :Design_1 Main Hall with Metal Halide 400Watts Sys
Date   : 26­Mar­08 
Time  : 12:00:00 AM 

File   : Church_1.xls
?
?ÿ???'Notes.???ÿ???'­­­­­???ÿ??
?'This workshe???ÿ?
?'et is used f???ÿ?
?'or the desig???ÿ?
?'n of general???ÿ?
?' lighting???ÿ???'of interiors???ÿ??' of rooms us???ÿ??'ing the lume???ÿ??'n method.???ÿ???'Units for c
Notes.
­­­­­
This worksheet is used f or the desig n of general  lighting
of interiors of rooms us ing the lume n method.
Units for calculated dat a are shown in column G.
Reference data is provid ed from cell  A121 downwa rds.

New data is entered unde r columns he aded with ==========


Data is calculated under  columns hea ded with **********
Room Data (sheet 1)
­­­­­­­­­­­­­­­­­­­­­ INPUT DATA CALCULATED
========== **********

Room Name           : Main Hall 100'Ø with Height 25'


Room Number           : F103
Room Location           : first floor
Room Use           : Main Hall 100'Ø with Height 25'
Lighting use per day           : 6.0  hours
Lighting use per week           : 7.0  days
Lighting use per year           : 52  weeks
Lighting use, hours per  year      : 2190  hours/year
Cleaning interval           : 26  weeks 1092  hours
Ceiling luminance           : 50  %
Wall luminance           : 50  %
Floor luminance           : 10  %
Room surface maintenance  factor   : 60.61  %
Illuminance required           : 400  lux

Room Data (sheet 2)
­­­­­­­­­­­­­­­­­­­­­ INPUT DATA CALCULATED
========== **********

Room Name           : Main Hall 100'Ø with Height 25'


Room Number           : F103
Room Location           : first floor
Room length        L1 : 26.586  m
Room width        W1 : 26.586  m
Room height        H1 : 8.500  m
Height of working plane
  above floor        H2 : 0.000  m
Height of luminaires
  from working plane        H3 : 8.5  m
Room index        RI : 1.6 
Working plane length        L2 : 26.586  m
Working plane width        W2 : 26.586  m
Working plane area        A1 : 706.8  m2
Room floor area        A2 : 706.8  m2

Lamp Data
­­­­­­­­­ INPUT DATA CALCULATED
========== **********

Type           : Metal Halide


Lamp lumen maintenance f actor     : 92  %
Code BT­37 V
Coating Phosphor Coated
Trade name Metal Halide
Lamp Power 400  Watts
Lamp length 10  mm
Initial luminous flux 28000  lumen
Colour rendering index        Ra : 80 
Corrected Colour tempera ture  CCT : 4000  K
Lamp electrical control system    : 56  Watts

Luminaire Data (sheet 1)
­­­­­­­­­­­­­­­­­­­­­­­­ INPUT DATA CALCULATED
========== **********
Luminaire type           : HP Sodium
No. lamps in luminaire           : 1  lamps
Lamp luminous flux           : 28000  lumen
Luminaire luminous flux           : 28000  lumen
Maximum space to height ratio SHR : 1.50 
Luminaire length        L3 : 10  mm
Luminaire maintenance fa ctor      : 95  %
Ceiling luminance           : 50  %
Wall luminance           : 50  %
Floor luminance           : 10  %
Room index        RI : 1.6 
Utilisation factor        UF : 62  %
Overall Light loss facto r     LLF : 53  %
Working plane area        A1 : 706.8  m2
Illuminance required           : 400  lux

Luminaire Data (sheet 2)
­­­­­­­­­­­­­­­­­­­­­­­­ INPUT DATA CALCULATED
========== **********
Luminaires needed       No. : 30.7 
Luminaires selected       No. : 35 
Illuminance provided           : 455  lux
Luminaire maximum SHR           : 1.50 
Height above working pla ne     H3 : 8.500  m
Maximum luminaire spacin g      S1 : 12.750  m
Luminaires installed par allel
  to room length.
Luminaires in row       No. : 4  2658 
Rows of luminaires       No. : 3  0 
Luminaires calculated       No. : 12 
Row spacing produced        S2 : 8.862  m
Row spacing from wall        S3 : 4.431  m
Design check on spacing           : Correct
Design check on illumina nce       : Acceptable
Installed electrical pow er        : 5472  Watts
Electrical load           : 7.7  W/m2
Reference Data
**************

Typical Values of Illumi nance (Pritchard)


­­­­­­­­­­­­­­­­­­­­­­­­ ­­­­­
Application Illuminance lux
­­­­­­­­­­­ ­­­­­­­­­­­­ ­­­
emergency lighting 0.2 
subdued lighting 50 
corridor 100 
residence 150 
plant room 150 
monitoring 200 
rough tasks 300 
general office 400 
retail shop 400 
drawing office 750 
small detail 1000 
visual inspetion 1500 
finest detail 2000 
Luminance of Painted Sur faces (BS 4800)
­­­­­­­­­­­­­­­­­­­­­­­­ ­­­­­
Surface Colour Luminance %
­­­­­­­ ­­­­­­ ­­­­­­­­­­­

ceiling white, cream 70 ­ 80


ceiling sky blue 50 ­ 60
ceiling light brown 20 ­ 30

walls light stone 50 ­ 60


walls dark grey 20 ­ 30
walls black 10

floor light 20
floor dark 10

Utilisation Factors (Philips)


­­­­­­­­­­­­­­­­­­­
Factors are for a surfac e mounted lu minaire havi ng a metal s quare
mesh louvre and two 36 W att fluoresc ent lamps.
These values can be used  for example  application s only.
Lighting manufacturer's data must be  used for de sign work.

Luminance %        Room Index


­­­­­­­­­­­­­­­­­­­­­­­­ ­­­­­­­­­­­­        ­­­­­ ­­­­­­­­­­­­ ­­­­­­­­­­­­ ­­­­­­­­­­­­ ­­­­­­­­­­­­ ­­­­­­­­­­­­
    Ceiling       Walls       Floor 0.6  0.8  1  1.25  1.5  2 
­­­­­­­­­­­­­­­­­­­­­­­­ ­­­­­­­­­­­­        ­­­­­ ­­­­­­­­­­­­ ­­­­­­­­­­­­ ­­­­­­­­­­­­ ­­­­­­­­­­­­ ­­­­­­­­­­­­
70  50  10  33  40  45  49  52  57 
70  30  10  29  35  40  45  49  54 
70  10  10  26  32  37  42  46  51 
50  50  10  33  39  44  48  51  56 
50  30  10  29  35  40  44  48  53 
50  10  10  26  32  37  42  45  51 
30  30  10  28  34  39  44  47  52 
30  10  10  25  31  36  41  45  50 

Manufacturer's Lamp Data   (Philips)
­­­­­­­­­­­­­­­­­­­­­­­­
Lamp 1 Lamp 2 Lamp 3 Lamp 4 Lamp 5 Lamp 6
=========== =========== =========== =========== =========== ===========
Type           : fluorescent fluorescent fluorescent fluorescent fluorescent fluorescent
Lamp lumen maintenance f actor     : 92  92  92  92  92  92 
Code lamp 1 lamp 2 lamp 3 lamp 4 lamp 5 lamp 6
Coating Triphosphor Triphosphor Triphosphor Triphosphor H/phosphate H/phosphate
Trade name Polylux 840 Polylux 840 Polylux 840 Polylux 840 Warm white Cool white
Lamp Power 18  36  70  100  36  36 
Lamp length 600  1200  1800  2400  1200  1200 
Initial luminous flux 1450  3450  6550  9400  3050  3000 
Colour rendering index        Ra : 80  80  80  80  51  58 
Corrected Colour tempera ture  CCT : 4000  4000  4000  4000  2950  4200 

Note.
­­­­
Copy the block of cells from D185 to  D194 into t he target
range of D65 to D74 in t he lamp data  section.
The units are shown from  cell K186.
END OF WORKSHEET.
­­­­­­­­­­­­ ­­­­­­­­­­­­ ­­­­­­­­­­­­ ­­­­­­­­­­­­
2.5  3  4  5 
­­­­­­­­­­­­ ­­­­­­­­­­­­ ­­­­­­­­­­­­ ­­­­­­­­­­­­
60  62  64  65 
57  60  62  64 
55  58  61  62 
59  61  63  64 
56  59  61  63 
54  57  60  62 
55  58  60  62 
54  56  59  61 

Lamp 7
===========
fluorescent
92  %
lamp 7
Special
Northlight
30  Watts
900  mm
1500  lumen
93 
6500  K

You might also like