PRESSUR E CHANG ES THRO UGH AN AIR DUC T ENLAR GEMENT,  CONTRA CTION O R BRANCH

******* ******* ******* ******* ******* ******* ******* ******* ******* *******

Name: A Student
Job : Assignment 4
Ref : Air Cond 2
Date: 26­Mar 
Time: ###

File: A:DUCTFIT.WK1

NOTES
*****
Duct ca n be re ctangul ar or c ircular .
Calcula tes the  pressu re chan ges thr ough du ct fitt ings.
Refer t o figur es 7.1,  7.2 an d 7.3.
Straigh t throu gh node s are n umbered  1, 2, 3 and 4.
Branch nodes a re numb ered 5 and 6.
Use the  PAGE D OWN key  to mov e to th e next section  of the  sheet.
ALL inp ut data  is in column E; calc ulated is in c olumn G .
Data fo r enlar gement or cont raction
­­­­­­­ ­­­­­­­ ­­­­­­­ ­­­­­­­ ­­­­­­­
  Input Calcula ted
  ­­­­­ ####### ###
Quantit y of ai r flow,  Q1 4  m3/s
Air den sity, r ho 1.19  kg/m3

Section  1 ­ 2:   This  is the inlet d uct.


­­­­­­­ ­­­­­­

total p ressure  at nod e 1 100  Pa


Either,  duct d iameter 800  mm
    or,  duct w idth 0  mm
   and,  duct d epth 0  mm
duct cr oss­sec ional a rea A1, A2 0.503  m2
duct le ngth 20  m
pressur e drop rate 0.7  Pa/m
air vel ocity V1, V2 8.0  m/s

 (enlar gement or cont raction  contin ued)

Section  3 ­ 4:   This is the outlet duct.


­­­­­­­ ­­­­­­
Input Calcula ted
­­­­­ ####### ###
Either,  duct d iameter 1000  mm
    or,  duct w idth 0  mm
   and,  duct d epth 0  mm
duct cr oss­sec ional a rea A3, A4 0.785  m2
duct le ngth 15  m
pressur e drop rate 0.25  Pa/m
air vel ocity V3, V4 5.1  m/s

 (enlar gement or cont raction  contin ued)

Section  2 ­ 3:   This is the data fo r an en largeme nt.


­­­­­­­ ­­­­­­ Input Calcula ted
­­­­­ ####### ###

ENLARGE MENT, (A2/A3)   0.64 

  data   data   data   data


Abrupt enlarge ment, (A2/A3) 0.25  0.40  0.56  0.70 
factor k1 0.56  0.36  0.20  0.09 

  data   data   data


Gradual  enlarg ement, angle, degrees 20  30  40 
factor k2 0.6  0.8  1.0 

Select factor k1 0.20 


Select factor k2 0.80 
Overall  factor  k 0.16 

Section  2 ­ 3:   This is the data fo r a con tractio n.


­­­­­­­ ­­­­­­

Input Calcula ted


­­­­­ ####### ###

CONTRAC TION, (A3/A2)   1.56  This is an enlargement

Abrupt contrac tion, (A3/A2) 0.25  0.40  0.56  0.65 


factor k 0.37  0.28  0.19  0.12 

Gradual  contra ction, angle, degrees 30  45  60 


factor k 0.02  0.04  0.07 

Overall  factor  k 0.04 

Data fo r a bra nch fit ting:


­­­­­­­ ­­­­­­­ ­­­­­­­ ­­­­  
Section  1 ­ 2:   This  is the inlet d uct.
Input Calcula ted
­­­­­ ####### ###
Input a ir flow  Q1 4.000  m3/s
total p ressure  at nod e 1 100  Pa
Either,  duct d iameter 800  mm
    or,  duct w idth 0  mm
   and,  duct d epth 0  mm
duct cr oss­sec tional area A1 , A2 0.503  m2
duct le ngth 20.0  m
pressur e drop rate 0.70  Pa/m
air vel ocity V 1, V2 8.0  m/s

  (data  for a branch fitting  contin ued)

Section  3 ­ 4:   This is the  main th rough f low duc t.

Input Calcula ted


­­­­­ ####### ###
straigh t throu gh flow  Q3 2  m3/s
Either,  duct d iameter 600  mm
    or,  duct w idth 0  mm
   and,  duct d epth 0  mm
duct cr oss­sec tional area A1 , A2 0.283  m2
duct le ngth 15  m
pressur e drop rate 0.25  Pa/m
air vel ocity V 3, V4 7.1  m/s

  (data  for a branch fitting  contin ued)

Section  5 ­ 6:   This is the  branch outlet duct.

Input Calcula ted


­­­­­ ####### ###
branch air flo w Q5 2  m3/s
Either,  duct d iameter 600  mm
    or,  duct w idth 0  mm
   and,  duct d epth 0  mm
duct cr oss­sec tional area A1 , A2 0.283  m2
duct le ngth 15  m
pressur e drop rate 0.25  Pa/m
air vel ocity V 5, V6 7.1  m/s

Flow ch eck:    bran ch flow s are: correct


  (data  for a branch fitting  contin ued)

Section  2 ­ 3:   This is the through  flow f itting resista nce.

Input Calcula ted


­­­­­ ####### ###
velocit y ratio  (V3/V2) 0.89 
straigh t throu gh k fa ctor 0.18 

Section  2 ­ 5:   This is the branch fitting  resist ance.

Input Calcula ted


­­­­­ ####### ###
velocit y ratio  (V5/V2) 0.89 
branch k facto r   0.18 

RESULTS  FOR CO NTRACTI ON: (All th e data on this  table is gene rated
******* ******* ******* **  automa tically ; no us er inpu t neede d).

Press.
Air Duct Duct Drop  Press.  Air Total Vel. Static
Flow Length Area Rate  Drop  Vel. Press. Press. Press.
Node Q m3/s L m A m2 dp Pa/m  dp Pa  v m/s Pt Pa Pv Pa Ps Pa
****** ****** ****** ****** *******  *****  ***** ****** ****** ******

1  4  0.503  8.0  100  38  62 


2  4  20  0.503  0.70  14  8.0  86  38  48 
3  4  0.785  1  5.1  85  15  70 
4  4  15  0.785  0.25  4  5.1  82  15  66 

RESULTS  FOR EN LARGEMENNT: (All th e data on this  table is gene rated


******* ******* ******* **  automa tically ; no us er inpu t neede d).

Press.
Air Duct Duct Drop  Press.  Air Total Vel. Static
Flow Length Area Rate  Drop  Vel. Press. Press. Press.
Node Q m3/s L m A m2 dp Pa/m  dp Pa  v m/s Pt Pa Pv Pa Ps Pa
****** ****** ****** ****** *******  *****  ***** ****** ****** ******
1  4  0.503  8.0  100  38  62 
2  4  20  0.503  0.70  14  8.0  86  38  48 
3  4  0.785  6  5.1  80  15  65 
4  4  15  0.785  0.25  4  5.1  76  15  61 
static regain Ps3­Ps2    = 16  Pa

RESULTS  FOR A BRANCH: (All th e data on this  table is gene rated


******* ******* ******    automa tically ; no us er inpu t neede d).

Press.
Air Duct Duct Drop  Press.  Air Total Vel. Static
Flow Length Area Rate  Drop  Vel. Press. Press. Press.
Node Q m3/s L m A m2 dp Pa/m  dp Pa  v m/s Pt Pa Pv Pa Ps Pa
****** ****** ****** ****** *******  *****  ***** ****** ****** ******
1  4  0.503  8.0  100  38  62 
2  4  20  0.503  0.70  14.0  8.0  86  38  48 
3  2  0.283  5.4  7.1  81  30  51 
4  2  15  0.283  0.25  3.8  7.1  77  30  47 
5  2  0.283  5.4  7.1  72  30  42 
6  2  15  0.283  0.25  3.8  7.1  68  30  38 
static regain Ps3­Ps2    = 3  Pa