You are on page 1of 4

Life safety from fire in

the hospital
Richard M. Patton

Reprinted from The Patton Report, June, 1.97o.


Used with permission.

I listoricall y , tin' most common solution to life safet y from


fire has been a structural solution. With the advent of
fireresistiye construction (reinf)rced concrete, protected
stee l ) t h e r e w a s a belid that fire life safet could be
y

assured through a structure that would not burn. Un-


fortunately, however, content fires and fires involving
combustible interior sheathing and trim readil y produce
sufficient heat and toxic gas to snuff out life long before
the structure itself was endangered.
Public reaction to disasters has now placed us at a
stage of structural fire safet y based on these five factors:
A. Fireresistant design
B. Cmnpartmentation (limitation of spread of fire)
C. Use of relativel y slow-burning interior trim, sheath-
ing and paneling
D. An adequate number of enclosed exitwavs
E. Isolation, or special protection for special hazards—
enclose a carpentr y shop with fireresistive construc-
tion, sprinkler it—or both.
In hospitals and other occupancies where occupants can-
not readil y flee a fire, the value of exitways is reduced.
They are installed, but many occupants cannot use them.
In order to compensate for this, more emphasis is placed
On compartmentation, Fireresistant compartmentation is
employed to the extent that ever y room becomes an en-
closure to contain a fire or, if the fire escapes, an enclosure
to safel y contain the occupant.
Today this is the basic life safet y from fire concept for
a hospital. First, contain the fire. As a backup, if the fire
escapes, contain the man in a safe refuge. Note, however,
that this basic plan runs counter to the normal reaction
of the normal human being. When a fire occurs in a fire-
resistant enclosed room, the conversion of solids to gases
will create an internal pressure within the room that will
send smoke through the cracks around the door into the
corridor. The normal human reaction is to open the door
to see what is going on in there. The fire is no longer
contained. The next reaction usuall y is to try to put the
fire out. Today's fire control equipment provided to fire
discoverers virtually insures that efforts to control the
fire will fail a high percentage of the time.
Once a fire passes from a "small stage" to a "substan-

Mr. Patton, a loss control consultant, is president of


Patton Fire Protection and Research, Inc., Freehold,
New Jersey.

12 The Building Official and Code Administrator, February, 1971


tial" stage, it will produce heat at such rapidly increasing commonly employed suppression s y stems—sprinklers, fire
rates that it will spread suddenly and explosively through- brigade (or trained emplo y ees) and the public fire de-
out the room because when the surface temperatures of partment (paid or volunteer). The suppression concept
exposed combustibles are raised to their ignition points I propose requires three things: a ) that all three s y stems volt
by the general beat content of the room, the fire ‘yill flash be employed; b) that the reliabilit y of each be im-
over all surfaces. The fire often will spread with a rapidity proved; c) that the y be coordinated and simultaneously
and intensity that is completely alien to the man accus- initiated.
tomed to friendly fires in fireplaces or outdoor fires where The industrial sprinkler system is reputed to have an
heat is harmlessly exhausted to the atmosphere. This unreliability record (failure rate) of 3.8 percent. But this
change in the nature and intensity of the fire invariably is an inaccurate statistic in that many successes are not
amazes the amateur fire fighter who is then quite likely reported, while presumably all failures are. However,
to panic and flee, leaving the door open (Ed. note: 7'he there is no doubt that industry is accepting a failure rate
BOCA Basic Code requires automatic door closers). for property protection that is not acceptable in a hospital
The secondary line of defense for the nonmobile occu- where lives are concerned. How can the reliability of the
pancy is the fireresistive room enclosures—the sanctuaries sprinkler system be improved? Fire records also indicate
—for the occupants. When the occupant remains calm, that the sprinkler s y stem that is electrically supervised
keeps his room door closed to the fire and opens the win- has a reliability in excess of 99 percent. Further, there is
dow to let in fresh air, the probability of survival is very clear indication that if electric supervision of the system
good. However, the normal reaction of the normal human is combined with an inspection and maintenance contract
being is to try to leave his room and flee through the with a reputable sprinkler contractor and if, in addition,
smoke- and heat-filled corridor to the outdoors. Isolation the sprinkler s y stem is engineered rather than designed
in a room during a fire must be particularly devastating lw the "book", as is customary, a rdiabilite that is very
to sick people confined to bed, especially if the window close to 100 percent can be achieved. True, this is only
is closed. Note that the present basic concept for fire life near, not total, perfection, but there is no structural solu-
safety through structural design runs counter to normal tion that achieves perfectitm either. Because large piping
human behavior in some important ways. This is why and huge water supplies are not needed for a hospital
fire protection engineers constantly throw up their hands sprinkler s y stem, it is quite possible to install a 99 percent
in amazement at the "weird" behavior of so many people plus reliable system more economically than the presently
under fire conditions. They simply don't behave the way accepted industrial model which is reputed to be 96.2
they are supposed to behave. The problem, however, is percent reliable. It is this concept of mechanical suppres-
not that people are inherentl y unreliable, but that we are sion which I recommend.
establishing a concept of fire safety that runs counter to Near perfect mechanical protection, however, is still
the reactions of the people involved. This is why fires not enough. It must be teamed with a concept of human
such as the recent one in the Marietta, Ohio nursing home fire suppression that is as reliable as we can make it. The
occur periodically. one glaring weakness in connection with the public fire
What is the solution? The solution lies in replacing the department is that too often the professional fire fighter
defensive concept of trying to enclose and trap the fire remains imalerted as the fire destroys lives and property.
with the positive concept of fire suppression. Note. that A direct electrical connection (or through central sta-
even very small scale compartmentation will permit a tion) from the sprinkler system to the fire department will
fire of substantial size to freely develop, so it is far better correct this. A fire department that is given earl y notifica-
to put the fire out. The fire suppression concept (sprin- tion of a fire in a light hazard occupancy can perform a
klers ) has been the backbone of industrial fire protection. superb job of fire control.
There is no structural solution that has had the relia- The third fire control system is the brigade—or em-
bility and cost-effectiveness of automatic fire suppression. ployee with the extinguisher. Here is the notoriously bad
It is now time to incorporate fire suppression as the basic actor—that man or the team that opens the door to let
solution to fire in structures where protection of human the trapped fire loose, that fails to control the fire, that
life, not property, is the primary need. fails to call the fire department until it is too late. Surely
I am recommending the concept of composite protec- it is best not to count too heavily on this human suppres-
tion for all new hospitals. This concept includes fire sup- sion s y stem. Not so. There is one reason—and only one
pression as the primary control for fire, structural design reason—for the consistent failure of the amateur fire
(fireresistance and subdivision) as the secondary control, fighter. We have equipped and trained him for failure.
and horizontal exits as the last resort of all new hospital We have established conditions under which a high rate
construction. But it would be a mistake to simply super- of failure is a certainty. The February, 1970 issue of
impose the existing industrial, property protection ori- Fire Technology, the magazine of the Society of Fire
ented sprinkler system on top of the existing excessively Protection Engineers, contains a report by Salzberg, Ved-
y
compartmented hospital. The blending of suppression arka and Maatman on "Minimum Water Requirements
with structural design should be accomplished with more for Suppression Room Fires." The test program described
finesse. The sprinkler system must be more economical demonstrated that room size fires in which flashover has
and even more reliable. The added safety of suppression already occurred, spreading fire completely throughout
will permit some relaxation in structural requirements. the room, can be readily extinguished by water in the
With these thoughts in mind, I propose the following form of a spray with an application rate of only seven
basic fire life safety design for hospitals. There are three Continued on page 14

The Building Official and Code Administrator, February, 1.971 13


Continued from page 13 Today 'many people pay little more than lip service to
GPM. Extinguishment was achieved with an extremely safety. Some of the blame for this must be shared by those
modest total quantity of water of fourteen to twenty gal- safety "experts" who argue that when it comes to human
lons. This is a very modest water requirement indeed. It life, the cost of protection has no place in the considera-
is available in just about every dwelling, let alone every tions. "When life is at stake, you don't argue dollars,"
hospital. However, what is the tool we provide the non- they say. This philosophy, more often than not, is a cover
professional with to fight these readily controllable fires? up for the fact that costly recommendations are being
The answer is that we give him an extinguisher that puts submitted without evidence of their worth. There is no
out exactly two and one-half gallons of water with a inexhaustible supply of money for safety purposes. Those
duration of discharge of approximately 50 seconds. Clear- who believe that safety does not have to be economically
ly this is inadequate. Further this discharge is in the acceptable usually end up by demanding too much and
form of a straight stream, not a spray. The report cited obtaining too little. Maximum safet y can be achieved only
above also demonstrated that even twenty GPM was by gaining maximum value for each safety dollar spent.
inadequate for room size fires when used as a straight Note that a level of absolute safety is never achieved.
stream. I repeat these statistics for emphasis. With seven When a level of optimum safety per dollar expended is
GPM and a spray nozzle, room size fires are readily con- reached, additional dollars may bu y additional safet y , but
trolled in two or three minutes. But, if a straight stream the law of diminishing returns applies here as it does in
is used, twenty GPM is inadequate. An extinguisher puts all other areas of expenditure.
out two and one-half to three GPM in a straight stream The effects of this law can be seen in structural fire
and is fully exhausted in less than one minute. Some protection for hospitals. Because the structural fire safety
types of extinguishers are fully discharged in as little as has its limitations, disasters have occurred in the corn-
ten seconds. It is as clear as the nose on an elephant that partmented "fireproof" building, and after each disaster,
we are supplying the amateur with a fire suppression tool additional structural requirements have been applied,
that is guaranteed not to control a high percentage of the each adding to the cost but providing reduced increments
fires he is likely to encounter. of additional safet y . It is clear, however, that the inclu-
The concept which I propose for the amateur fire sion of extremely reliable suppression systems will dra-
fighter is a very simple one. Give him a tool that he knows matically improve the overall fire safety of the hospital.
how to use, one that can produce the six to ten gallons In fact, if we could guarantee an absolute certaint y of
of water a minute that is needed to achieve fire control fire suppression, instead of high reliability, the need for
for room size fires and give him the three minutes or more all structural requirements would be voided. Total reli-
of operating time that he needs to do the job. A light- ance on suppression with complete elimination of struc-
weight hose that is flexible, easily operated and equipped tural requirements, of course, is not being recommended.
with a spray nozzle will promptly and efficiently extin- This could prove to be as bad, and possibly worse, than
guish the type of fires that the amateur encounters in the the present practice of putting all the eggs in the struc-
hospital. Further, the water spray will knock down the tural basket. When reliable suppression systems are intro-
heat quite rapidly and permit the amateur to get close duced, the question at hand is this—"What is the proper
to the fire so that he can 'do a job on it. level of structural protection for a hospital in conjunction
One further thing must be done. Just as the sprinkler with high quality suppression systems?" In short, what
is wired to the fire department, so must we wire in the is the proper level of composite protection? The gain in
fire fighter. When we give the fire fighter a tool that can safety per dollar expended on suppression will be great,
control the fire that he is likely to encounter, we also because the present level of fire suppression reliable is
have given him a tool that c. an be electrically supervised. low. The reduction in safety through the reduction in
Just as water flow in a sprinkler system can cause an structural protection expenditures will be low because of
alarm to be transmitted to the public department, so can the redundancy and limited value of some of the struc-
water flow in the hose station. One word of caution is in tural requirements. Thus, on a trade-off basis, there is a
order with regard to the hose, however. Present under- potential for both savings and safety gain. There are also
writer approved hose intended for use by building occu- gains to be made in greater freedom of design and effi-
pants is large, bulky, heavy when filled with water, in- ciency of the physical plant layout. Time and study will
flexible, and extremely difficult to handle and put into reveal the point of maximum safety per expended dollar.
operation in confined areas, and has other disadvantages There is one more thing the suppression concept can
as well. It can be handled by a professional fire fighter, accomplish. It can also bead off more restrictive struc-
but, ironically, the professional always brings his own tural and occupancy requirements in the future. For
hose. There is a need for fire hose that can be put into instance, at present, there is a great deal of concern over
operation and be easily handled by one nurse. This rules the toxicity of the products of combustion produced by
out all presently approved fire hose. Again, it is im- the burning or the decomposition of some plastics and
portant that we not permit antiquated concepts and regu- other building materials. Present laboratory tests that pass
lations to stand in the way of providing the fire safety on the acceptability of building materials measure the
that is so badly needed. rate of flame spread and the amount of smoke generated
Note that when I talk about fire suppression, I am not ( obscuration) but do not deal with toxicity. Some of the
just talking about a sprinkler system. I am talking about chemicals used to reduce the flame spread of some mate-
an improved sprinkler system, a fire brigade and a fire rials, thus qualifying the materials as "firesafe" can actu-
department that will all be simultaneously initiated. ally increase the toxicity of the gases produced. How-

14 The Building Official and Code Administrator, February, 1971


ever, NVIlerl we consider the total fire loading in a hospital C. The fire spread to the hallway.
occupancy, the combustible contents ma y be more sig- D. There were the usual fire suppression weaknesses.
nificant than the combustible portion of the structure E. Li nder panic conditions, people did not think to
itself. But the combustibilit y of the contents (furniture. close doors to the corridor, and open windows to
supplies, ('tc.), generall y is not regulated. The contents tile outdoors.
Call provide the primary fuel which will cause the com- F. During the high stress conditions, there was a delay
bustible sheathing and trim, if anY, to also burn and in a call to the fire department.
release ver y toxic gases if that is the nature of the mate-
rials. ‘Vho can bliu»e humans for failing under the stress of
the conditions? The concept of controlling a fire by trap-
Details on the Marietta nursing home fire are sketchy,
ping it, or enclosing each human it) his own cubicle if
but there is reason to believe that this is exactl y what
the fire escapes, deminals too much of the people in-
happened—there was a content fire that also involved
volved. It was a s y stem failure, of course, because a fire
carpeting. Because heat rises, combustibles burn in in-
control concept that does not effectively deal with the
verse relationship to their height above floor level. There-
critical needs of putting the fire out before it becomes
fore, carpeting ma y have had the least role in the spread
a holocaust is like permitting a tiger to stalk the halls
of fire at Marietta. If this is so, the reader ma y ask, "NVIty
read y to enter anv open door to kill. If we do not deal
then has there been so p inch concern about floor covering
with the s y stem, there will be additional tragedies, and
since this fire?” I think the real reason is that carpeting
was the only "built in - structural feature that could be each time there will be it searching for a "cause" on which
labeled "nonapproved - . If it were not for the carpeting to Itang (lilt's hat and another area for tighter regulations.
in the 11111 - Sing 110111C, there would have been a disaster There \Oil also be charges leveled against employees and
hospital administrators who , fail to control the fire with
in it completel y standard fireresistive compartmented
equipment that often is not capable of controlling fire,
structure. There was also no corridor smoke barrier, but
who do not think to calml y close doors under panic con-
this could only have reduced, not prevented, loss of life.
ditions and who have human reactions under great stress.
So if it were not for the carpeting, the structural system
There will also be innocent victims who die needlessly.
itself would have to be blamed for the failure.
But it was the s y stem that failed. Note that the fire
I do not argue against reasonable controls on the com-
bustibilit y of carpeting. What I do sav is that the carpet-
was a classic fireresistive, compartmented structural fire
ing is being used as a reason not to examine the validity
having the following characteristics:
of prese»t concepts of structural fire safety. A new con-
cept of prompt, positive fire suppression not onl y will
A. Tlw fire, wi tell clisco ‘ •ered, was small and contained guarantee the maximum practicable level of human safety
one fireresistive cobiele. from fire, it will permit the widest practical latitude in
B. Under conditions of stress, the door to the involved St ructural desig», arrangement of operations and use of
room was left open. materials.

The Building Official and Code Administrator, February, 1971 15

You might also like