1.1 Introductions
This lecture will give general guidance for the structural design of unreinforced Autoclaved Aerated
Concrete (ACC) masonry wall by calculation that used in Hong Kong. It gives a broad outline and
indicates the principles of design when using any national or international standard such British
Standard and Codes of Practice. Limit state philosophy has been used.
The factor γ m (partial safety factor for materials) makes allowance for the variation in the
quality of the materials and for the possible difference between the strength of masonry
constructed under sit conditions and that of specimens built in the laboratory for the purpose of
establishing its physical properties.
Possible unusual increase in load beyond those considered in deriving the characteristic
load;
Inaccurate assessment of effects of loading, and unforeseen stress redistribution within the
structure;
The variation in dimensional accuracy achieved in construction.
According to Clause 6.1.6 and 6.1.8 of British Standard 5628 Part I, the partial safety factors
will be taken for the following considerations.
-Page 1-
November 2006
The design should also ensure that there is an adequate margin of safety against a serviceability
limit being reached. In many codes, an adequate margin may be assumed to exist when the
design satisfies the ultimate limit state.
The risk of adverse effects on the structure, including non-loadbearing elements such as
partitions, arising from expansion, or contraction due to thermal and moisture movements, creep,
settlement, etc., should be assessed. When necessary, suitable details should be employed to
maintain an adequate margin of safety against a limit state being reached.
1.3 Stability
The overall stability of the structure should be considered together with the compatibility of the
design and detail of parts and components. There should be no doubt about who is responsible
for the overall design when some or all of the design and details are not made by same designers.
Consideration should be given to the interaction between the masonry wall and the other parts
of the structure and adequate connections should be provided. In many design codes other
general stability considerations are given.
1.4 Loads
Loads should be taken from or calculated in accordance with the relevant standard such as
British Standard.
multiplied by the appropriate partial safety factor, γ f , taken from the relevant international
standard. Where, in the design code, alternative values are shown, that producing the most
severe condition should be selected.
-Page 2-
November 2006
2.0 Design of unreinforced masonry – Walls subjected to lateral load
2.1 General
Masonry wall subjected to mainly lateral loads should be verified to have a design strength
greater than the design load, but are not capable of precise design. However, an approximate
method for assessing the strength of the wall is to consider the wall panel to be supported on a
number of sides. This method is outlined below:-
Figure 6.1 Principles for the design of masonry wall for lateral loading
-Page 3-
November 2006
continuity over supports are taken in account. The reaction along an edge of a wall due to design
load may normally be assumed to be uniformly distributed when designing the means of support.
The connection to the support may be in the form of ties or by the shear resistance of the
masonry taking into account the damp-proof course, if any. Simple supports may be provided by
metal ties after ensuring their adequacy to transmit forces.
(a) two or more sides continuous: height x length equal to 1500 tef2 or less.
(b) all other cases: height x length equal to 1350 tef2 or less.
(a) three or more sides continuous: height x length equal to 2250 tef2 or less.
(b) all other cases: height x length equal to 2025 tef2 or less.
(3) Panel simply supported at top and bottom: height equal to 40 tef or less.
In case (1) and (2), no dimension should exceed 500 times the effective thickness, tef .
above, and may be taken as either αWk γ f L2 ....Eq(1) when the mode of failure is perpendicular
to the bed joints, or µαWk γ f L2 ....Eq(2) when the plane of bending is parallel to bed joints.
-Page 4-
November 2006
µ is the orthogonal ratio of the flexural strengths =
(modified flexural strength parallel to bed joints/ flexural
strength perpendicular to bed joints)….Eq(3)
When a vertical load acts so as to increase the flexural strength in the parallel direction, the
orthogonal strength ratio may be modified by using a flexural strength in the parallel direction,
the orthogonal strength ratio may be modified by using a flexural strength in the parallel
direction of
f kx + γ m g d ….Eq(4)
where f kx is the flexural strength of the parallel direction, γ m is the appropriate partial safety
factor for material, and g d is the design vertical dead load per unit area.
For walls spanning vertically, the design moment per unit length of wall at mid-height of the
panel may be taken as:
Wk γ f h 2
….Eq(5)
8
Unless the end conditions justify treating the panel as partially fixed. In this expression, h is the
distance between supports.
The details are referred to clause 36.4.2 of BS5628: Part I: 1992 (see appendix).
EXAMPLE
-Page 5-
November 2006
An internal partition wall of 3m x 5m is to be constructed with Autoclaved Aerated Concrete (ACC)
blocks of density 700kg/m3. The panel wall is simply supported on three sides as shown in Figure
6.2. Given that:
Dead Load:
γ f = 0.9
Figure 6.2
Solution:
Basic Assumption
Wall = 200mm thick AAC blockwork (700kg/m3)
HeightxLength
∴ min imum t ef = = 100mm
1500
Dead Load:
γ f = 0.9 (Given)
Step (6): increase flexural strength in the plan of failure parallet to bed joints
In parallel direction,
By Eq(7),
( )
Modified f kx + γ m g d = 0.18 + 1.23kN / m 2 × 3 × 2.5 × 10 −3 / 0.2 = 0.20 N / mm 2
2
Remarks: g d = (self weight x material partial safety factor x overall thickness x half
of the height)/ effective thickness.
-Page 7-
November 2006
H 3.0
µ = 0.65 = = 0.6
L 5.0
Taking these values for µ and H/L and referring to British Standard BS5628:Part 1, table 9,
the bending moment coefficient α of 0.059 can be derived.
1
By Eq.(7)…. Z = × 1000 × (200) 2 = 6.67 × 10 6 mm 3 / m
6
Step 10: Calculate moment of resistance
f kx 0.31× 6.67 × 10 6
By Eq(7)….Design moment = Z= × 10 − 6 = 0.83kNm / m
γm 2.5
Step 14: Check that whether the design load is less than capacity
Compared to required design wind load capacity of 0.46 kN/m2 the panel is, therefore,
satisfactory for wind load.
-Page 8-
November 2006
Exercise
An internal partition wall of 2.5m x 5m is to be constructed with autoclaved aerated concrete (ACC)
block of density 700kg/m3. The panel wall is simply supported three sides as shown in Figure 6.3.
Given that
Partial Safety Factor
Horizontal imposed load:
γ f = 1.2
Dead Load:
γ f = 0.9
Figure 6.3
-END OF LECTURE 6-
-Page 9-
November 2006