MIX DESIGN FOR M-30 GRADE

A) Design Stipulations:
1) Minimum compressive strength in the field at 28 days : 30Mpa
2) Minimum flexural strenght reqierd in the field at 28 days : 3.80 Mpa
3) Miximum size of aggregate :25mm
4) Degree of workabillty : 30mm slump
5) Degree of quality control : good
6) Accepted tolerance level : 1 in 20

B) Test Date for Materials :


1) Type of cement , OCP-43 Grade
2) Compressive strength of cement at 7 days : 41.6 Mpa
3) Specitic gravity of cement :3:15
4) Specific gravity of I) coarse aggregate : 2.721
II) fine aggregate : 2.60
5) Water absorption of I) coarse aggregate : 0.54%
II) fine aggregate : 1.20%
6) Type of I) coarse aggragate : Crushed, angular
II) fine aggregate : Natural river and

7) Sieve analysis:
Coarse aggregate fractions Fine aggregate
IS sieve Percent passing IS sieve Percent CumulativeFineness
size 20mm 10mm size passing % retained modolus
26.5mm 100 100 9.50mm 100 0
19mm 55.62 100 4.75mm 93.5 6.5
9.5mm 1.79 80.78 2.36mm 76.8 23.2
4.75mm 0.13 1.96 1.18mm 51.8 48.2 3.45
600micron - - 600micron 26.7 73.3
75micron - - 150micron 4.3 95.7
300micron 2 98
75micron 1.4

( Note : Sand conform to Zone 1. )

C) Target Strenhth for concrete:


Target compressive strength of concrete at 28 days=30+1.65X6 =39.9 Mpa=40Mpa (say)
Equivalent targate flexural strenght of concrete at 28days, S = 4.43 Mpa

D) Selection of water and sand contents:


From Table4 of IRC44,for water-cement ratio of 0.50 , Slump of 25mm, F.M of Sand of 2.60
and angular aggregate, of 25mm maximum size, water content per cum. of concrete=177.5 kg
and sand content as percent of total aggregate by absolute voluma =38%
For changes in the values of water-cement ratio, fineness modolus of sand & slump, the adjustments
required in the mix are:-
Adjustment required in
Changes in condition Water content (kg) sand content (%)

-1%
I) decrease in w/c (0.5-0.45)=0.05 0

II) increase in FM of sand (3.45-2.60)=0.85 0


4.25%
III) slump (30mm-25mm)=5mm 0.80%
Total 0.80% 3.25%
Therefore, required water content per cum. of concrete =179 kg and sand content as
percent of total aggregate by absolute volume = (38+3.25)=41.25% say 42%

E) Combined grading of coarse and fine aggregate (As per Table 1500.1 of MORD:)

Sleve Cumulative %^ Passing. Limts %


passing by
size Coarse aggregate Fins aggr. 20mm 10mm Sand Total wt.
20mm 10mm Sand 29.0% 29.0% 42% aggregates
26.5mm 100 100 100 29 29 42 100 100
19mm 55.62 100 100 16.13 29 42 87.13 50-100
9.5mm 1.79 80.78 100 0.52 23.43 42 65.95 88-80
4.75mm 0.13 1.96 93.5 0.04 0.57 39.27 39.88 36-60
600micron - 26.7 - - 11.21 11.21 10.-35
75micron - 1.4 - - 0.59 0.59 0-8

Note: Copmbined grading of total aggregates conforms to specified limits.

F) Deternination of Cement Content:

Water-cement ratio=W/C= 0.42


Water content= 179 kg
Therefore, cement content,C=426kg=425 kg (say)

G) Determination of Aggregate- Cement Ratio:

For the specified maximum size of aggregate of 25mm, the amount of entrapped air in the wet concrete
is 1.50%. Taking this factor into account,

0.985cum.=(179+425/3.15+1/0.42xS/2.60)x1/1000
Therefor, S=733 kg

0985 cum=(179+425/3.15+1/0.58xA/2.721)x1/1000
Therefore A=1059 kg

The mix proportios are therefore:

Water Cement Sand Coarse aggregate Total aggregate


179 kg : 425 kg : 733 1069 kg 1792 kg
or 0.42 : 1:00 1.72 2.49 4.21

Therefore, Aggregate-Cement ratio= 4.21:1

Note: The aggregates weights (coarse & fine) derived are dry weights. During site batching suitable
corrections for water absorption and surface moisture (If any) in aggregate shall be considered and
adjustments in water content be made to maintain the free W/C ratio at its specified value .

H) Trial Mixes:

Trial mixes were carried out the above propotion of various ingredients and the compressive strenght
and slump values observed. The details of trial mix test results are tabulated below:
Trial Mix Grade of Cube Mass of Age Comp. Av.Comp. Slump Remarks
No. Concrete. Id Mark. cube (Kg) days Stret.Mpa Stret.Mpa (mm)
1 2 3 4 5 6 7 8 9
TM-1 M-30 TM-1A 8224 7 29.8 30
TM-1B 8110 7 26.1 27.64 7 days
TM-1C 8090 7 27.03
TM-1D 8114 14 31.39
TM-1E 8232 14 31.69 31.03 14 days
TM-1F 8222 14 30.08
TM-1G 8101 28 43.16
TM-1H 8244 28 43.6 43.4 28 days
TM-1I 8204 28 43.38

Remark :- The mix proportions recommended above should be trried in the field using
the proposed materials and finalised by observing the actual performance of the concrete mix.
Sutaible modifications may be necessary to suit field conditions in the light of experience as
well as for the particular materials used at the site in each case.
SUMMARY OF AGGREGATE TEST RESULTS

Source of coarse aggregate : Pathalgaon crusher.


Source of fine aggregate :- Mand River.
Type of a) Coarse aggregate :- Crushed

b) Coarse aggregate :- Uncrushed

GRADATION:

Percentage passing Sieve size (mm)


size 20mm 10mm Sand

40 100 100 100


26.5 100 100 100
19 55.62 100 100
9.5 1.79 80.78 100
4.76 0.13 1.96 93.5
2.38 - 0.66 76.8
1.18 - - 51.8
0.8 - - 26.7
0.3 - - 4.3
0.15 - - 2
0.08 - - 1.4

Note: Sand conforms to Zone 1. FM-3.45

Combined gradation of coaree and fine aggregates(As per table 1500.1 of MORD)

Sieve Cumulative % passing Limits %


passing by
size Coarse aggregate Fine aggr. 20mm 10mm Sand Total
wt.
20mm 10mm Sand 29.0% 29.0% 42% aggregates
26.5mm 100 100 100 29 29 42 100 100
19mm 55.62 100 100 16.13 29 42 87.13 80-100
9.5mm 1.79 80.78 100 0.52 23.43 42 65.95 85-80
4.75mm 0.13 1.96 93.5 0.04 0.57 39.27 39.88 35-60
600micron - - 26.7 - - 11.21 11.21 .10-35
75micron - - 1.4 - - 0.59 0.59 0-8

AGGREGATE PROPERTIES:

Specific Gravity Water Flakiness AIV Passing


absorptio 0.075mm
Material Oven dry Apparent n% (%) (%) (%)
Crushed 20mm 2.72 2.74 0.21
Crushed 10mm 2.72 2.76 0.54 33 16
River Sand 2.6 2.67 1.2 - - 1.4
SUMMARY OF AGGREGATE TEST RESULTS

Sou
izfr]
dk;Zikyu vfHk;ark lg lnL; lfpo
ifj;kstuk fØ;kUo;u bZdkbZ ¼1½
iz/kku ea=h xzke lM+d ;kstuk
jk;x<+ ftyk jk;x<+ ¼N-x-½

fo"k;& vuqca/k gsrq cSad xkjaVh tek djus ckor

mijksDr fo"k;kUrxrZ ys[k gS fd esa- lquhy dqekj vxzoky pkanuh pkSd jk;x<+ }kjk
vuqca/k gsrq fuEu iSdstks ds fy, cSad xkjaVh tek fd tk jgh gSA

Ø- iSdst Ø- cSad xkjaVh Øekad jkf'k


1 CG-13-09 M-01 853610BG 000060 2,65,000
2 CG-13-01 M-01 853610BG000053 7,87,000
3 CG-13-08 M-02 853610BG 000058 6,32,000
4 CG-13-06 M-01 853610BG 000055 10,34,000
5 CG-13-07 M-01 853610BG 000058 4,92,000
6 CG-13-04M-01 853610BG 000054 3,70,000
7 CG 13-08 M-01 853610BG 000057 3,73,000

lknj lwpukZFk

lg i= mijksDrkuqlkj
Hkofn;

esa- lwuhy dqekj vxzoky


pkanuh pkSd jk;x<+
65

h pkSd jk;x<+ }kjk

You might also like