Test Method:
Ensure that the main switch, RCD and MCB are open
circuited (switched off ) and all loads are disconnected;
Connected the test leads as in the Figure 1;
The meter reading shall be less than 1 ohm.
Protection Conductor Continuity
Test
Figure 1
Final Ring Circuit Conductor
Continuity Test
To ensure that all conductors around the ring circuit
have continuity;
• Test Equipment – Multimeter (Ohm range) or Ohm
Meter
• Test Method:
Disconnect both the supply source live conductors from the
MCB, the neutral conductor from the neutral terminals and
the earth conductor from the earth terminal in the
distribution fuse box;
Connect the test leads as in the Figure 2(EE);
Repeat the procedure for (L-L) and (N-N);
The meter reading value shall be less than 1 ohm.
Final Ring Circuit Conductor
Continuity Test
Figure 2
Live and Neutral Conductor
Continuity Test
To ensure that each conductor in the circuit has
continuity;
Test Equipment – Multimeter (Ohm range) or Ohm
Meter
Test Method:
Switch off the Main switch, RCD and MCB;
Disconnect all loads;
Switch on all switches in the circuit;
Disconnect the fuses/final circuit breakers and close the
circuit;
Carry out the test as shown in Figure 3;
The meter reading value shall be less than 1 ohm.
Live and Neutral Conductor
Continuity Test
Figure 3