You are on page 1of 7

Battery Alarm 300

Publication I6009K
The Company
and its Products

GEC ALSTHOM T&D Protection & Control Limited is part of GEC ALSTHOM,
one of the largest electrical power generation, transmission and distribution
groups in the world.
It is an acknowledged world leader in the design and production of relays and
instrumentation. This position has been achieved through a continuing policy of
increasing investment in new product development.
The company is represented all over the world and has its British base at
Stafford where approximately 1,600 personnel are employed.
GEC ALSTHOM T&D Protection & Control markets a quality range of electrical
instrumentation serving the control requirements of the power generation,
transmission, distribution and industrial process markets.
This product range includes:
● Panel instruments (conforming to DIN, BS and ANSI standards)
● Istat electrical transducers
● MotorMaster motor protection relays
● Novar capacitor controllers
● R30 Chart recorders
● Battery alarms
● Rotary switches
● Prima Auxiliary Relays
Expert technical support for product selection, application and after sales
service is available through a network of over 80 established representatives
around the world.

2
Substation battery installations are required to provide not only dc auxiliary supplies for protection and control
equipment, but also to supply trip and close currents to breakers under tripping conditions. Monitoring of the
performance of the dc system is therefore fundamental to the efficient operation of the substation.
Battery Alarm 300 is designed to provide comprehensive continuous battery monitoring and to give local and remote
indication of alarm conditions, including an impedance alarm. This alarm is designed to monitor the ability of the battery
to supply a large current for trip/close requirements, failure of which could result in extensive damage.
Early detection of such problems using Battery Alarm 300 allows effective maintenance to be scheduled to help maintain
the integrity of the dc system.

Product Features Customer Benefits


● Monitors ability of battery to supply load current ● Ensures dc powered equipment such as critical
protection relays and SCADA systems remain
operative
● Provides continuous in-service monitoring of the battery ● The need for time consuming and costly site visits and
battery servicing by maintenance engineers is
minimized
Batteries may remain safely in service after perceived
useful life has expired, thus reducing replacement costs
● Over and Under voltage alarms ● Ensures battery charge is sufficient to support the
required voltage level
Ensures battery charger is performing correctly
● High Impedance alarm ● Guards against high battery circuit impedance, caused
by corroded terminals or internal build-up of plate
deposits, which would prevent the battery from
supplying the required load current
Improves security of remote unmanned installations
against theft
● Earth Fault alarm ● Protects against earth leakage which could prevent the
battery supplying sufficient load current and would
also result in increased charging costs
● Fault indication LEDs and relay contacts ● Local and remote alarms to facilitate fast and
efficient fault diagnosis
● Models available for each of seven standard ● Security of supply available for all dc powered
dc voltages up to 220V dc equipment
● Wide voltage alarm setting ranges ● Suitable for all types of battery including lead-acid
and alkaline
● Loss of supply volts indicated via drop-off of normally ● Battery Alarm does not require expensive
energized relay, providing self checking maintenance
● Self-powered with minimal burden ● Easily retrofitted to existing installations

3
Application
Optional choke(Required when battery charger has capacitor filtered output)
For substations it is important that the
security of the supply is maintained.
FS1 2A rating Busbars to
This means not only that the battery battery loads
voltage is within required limits, but
3
that earth leakage and any latent 1
faults in the battery and connections 2
will not result in failure to initiate Non-urgent 6
4
tripping when a heavy current is

Charger

Battery
5
demanded. For external wiring 8 To telemetry
diagram see Figure 1. 7
9
Battery Alarm 300 has been designed Urgent 11
specifically for electrical substation E 10
batteries and has become a standard 12
for many utilities both for new
installations and for retro-fit to existing FS2 2A rating
batteries. It is suitable for all batteries
with an internal impedance exceeding Note: The Battery Alarm is shown in the energised state. Under healthy
0.1Ω. operating conditions the urgent relay is operated and the non-urgent
relay is released.
For battery charger systems fitted with
capacitor filtered outputs, the Battery Figure 1: External wiring diagram
Alarm requires a choke of >2 mH to
be fitted at the output of the battery
charger to ensure correct operation Description ● Power supply operative

of the high impedance alarm ● Earth fault positive


(see Figure 1). The Battery Alarm is designed for flush ● Earth fault negative
panel mounting and connection to the
● High impedance
battery bus wiring. This forms the
Warnings source of supply for the electronics ● Over voltage
and also enables the device to monitor ● Under voltage
Caution. Refer to the Operation & battery performance. The window and front panel are cut
Maintenance Manual (I9-100) away to provide easy access to three
The outputs provided are volt free
before installing, commissioning contacts from two separate relays. circuit adjustment potentiometers for
or operating the equipment. setting-up the following:
The first, designated URGENT, is
1 Installation, commissioning and normally energized and will ● High impedance trip level
maintenance should only be de-energize if the monitored ● Over voltage alarm point
carried out by qualified parameters deviate beyond preset
● Under voltage alarm point
personnel. limits.
2 Battery charger systems with an The second relay, designated
inductive output element only, NON-URGENT, is normally High impedance alarm
should have a suitable load de-energized and will energize if the
The high impedance alarm circuit
connected, such as a battery, monitored parameters deviate beyond
monitors the ability of the battery,
during commissioning and normal preset limits. Each relay channel is
together with the charger and
operation. This is to avoid fitted with a preset timer which serves
associated wiring, to provide a heavy
resonance of the output inductor to inhibit alarms of a transient nature.
current pulse.
with the system capacitance Each relay can be configured to
which may produce damaging monitor any, or all, of the battery The impedance monitoring circuit
high peak output voltages. parameters. Two sets of changeover operates by drawing a series of heavy
contacts are available on each relay. current pulses (approx. 1A) from the
3 Terminations exposed during battery busbars. The values of these
installation and maintenance may A version is available with both relays
pulses are stored and, if a succession
present a hazard unless the designated NON-URGENT. Both
of pulses is low, the alarm will
equipment is electrically isolated. relays are normally de-energised and
operate. The circuit is driven by a low
will energise if the monitored
4 The equipment should only be frequency oscillator which gives a
parameters deviate beyond preset
operated as intended e.g. with pulse rate of two per second.
limits.
covers in place and the earth The pulse duration is approximately
conductor connected to maintain The unit has six LED indicators so that 50 microseconds.
the incorporated safety features. fault recognition is possible in the The high impedance monitoring circuit
event of a sustained fault. can be adjusted to monitor battery
These indicators display: impedances in the range of 0.1Ω to

4
5Ω. It should be noted that the Parameter (per cell) Lead acid Alkaline
resistance of the fuses and connecting Nominal volts 2.00 1.20
cables will have an effect on the
potentiometer setting. Fuses should be Max volts on boost 2.60 1.68
rated at 2A and all wiring should be Working volts on charge 2.27 1.46
kept as short and direct as possible. Minimum volts 1.85 1.00
Low alarm operation 2.14 1.32
Voltage alarm level settings High alarm operation 2.40 1.52
For example: For a 55-cell lead acid battery
The voltage levels specified will
depend on the operating conditions Low alarm setting = 55 x 2.14 = 117.7V
of the battery installation and the High alarm setting = 55 x 2.40 = 132V
purpose for which the alarms are
The over and under voltage alarm levels are adjustable (see technical
required. However, the working
specification).
voltage range of the Battery Alarm
must be taken into account when Note
deciding on a specification. The over and under voltage alarms have built-in hysteresis to prevent contact
chatter. This hysteresis (or pick up/drop off differential) will result in a high
The Battery Alarm power supply can
alarm reset voltage of (0.995 x Vtrip) ±0.5% and a low alarm reset voltage of
accommodate a maximum variation
(1.005 x Vtrip) ±0.5%.
of 80…140% in the input from the
battery. The power supply is generally
designed to operate over a voltage
range from maximum boost voltage
down to a minimum voltage below
which a battery would not normally be
allowed to deteriorate. The over and Earth fault alarm Alarm indications and relay
under voltage alarm settings must be outputs
The earth terminal on the Battery
within this range.
Alarm is connected to the case back A popular configuration for alarm
The adjacent figures can be used as a plate and also to the earth fault circuit relay outputs is:
guide to suitable settings. input.
– URGENT alarm for over voltage,
A leakage path from either the under voltage and high
High voltage cut-off facility positive or the negative pole of the impedance;
A high voltage cut-off facility is battery to earth will cause a current
– NON-URGENT alarm for earth
achieved by routing the over voltage to flow in the input to the earth fault
faults.
alarm through the NON-URGENT circuit. If this current exceeds a
relay with a short time delay setting predetermined value, the earth fault On detection of an over voltage,
eg. 2s and also through the URGENT relay will operate and the relevant under voltage or high impedance
relay with a longer time setting LED will illuminate. fault, the associated panel LED will
eg. 50s. light immediately. At this stage the
The earth fault trip level is preset
urgent alarm delay will start to time
This provides a means of switching within the range 5…90kΩ and is
out and, if the fault persists, the urgent
off the charger or performing other symmetrical for both positive and
alarm relay will release after the delay
switching operations on detection of negative earth faults, irrespective
time.
a high voltage alarm condition. of battery voltage.
On detection of an earth fault, the
A similar low voltage cut-off version If either the positive or negative of the
associated panel LED will light and the
can also be provided. battery is earthed, the Battery Alarm
NON-URGENT delay timer (usually
300 will indicate an earth fault alarm.
1s for earth faults) will start.
In the case when an earth fault relay is
The NON-URGENT relay will pick-up
already fitted, then a Battery Alarm
when the timer times-out.
300 model without earth fault is
recommended. Each relay channel is fitted with a
timer and each channel can be
configured to monitor any of the
battery parameters.
Both relays have two sets of volt-free
changeover contacts which can be
used for local and remote alarms,
SCADA inputs etc.

5
Technical Specifications

Battery Voltage Ranges


Battery voltages (VB) 24V, 30V, 32V, 48V, 50V, 60V,
110V, 125V, 220V.
Operating Range 80…140%VB
Burden 20mA nominal
Voltage alarm levels (adjustable)
Under voltage range 80…110%VB
Over voltage range 105…140%VB
Accuracy of setting ±0.5%
Hysteresis on setting 0.5%
Earth leakage protection (preset)
Trip level range 5kΩ to 90kΩ
Accuracy of trip level ±10%
Hysteresis on trip level 5%
Short circuit current <5mA
High impedance alarm (adjustable)
Setting range 0.1Ω …5.0Ω
Accuracy of setting ±0.05Ω
Hysteresis on setting 0.05Ω

Temperature
Nominal range of use –20°…+60°C
Reference temperature 23°C
Temperature coefficient
Voltage alarms ±0.006%/°C
Earth leakage alarm ±0.06%/°C
Timer settings ±0.06%/°C
High impedance alarm <0.1Ω deviation in setting over
temperature range

Electromagnetic Compatibility Directive 89/336/EEC


Emissions standard EN50081-2 1994 Industrial environment
Immunity standard EN50082-2 1995 Industrial environment
(IEC801 parts 2, 3 and 4)
Susceptibility to Electrostatic
Discharge 8kV air discharge/4kV contact.
WARNING: This specification applies when the front cover is fitted. If the
front cover is removed to gain access to the adjustment potentiometers then
appropriate ESD protection must be taken.

Low Voltage Directive 72/23/EEC


Designed to EN61010-1 1993 safety requirements.

Timers
Alarm time delay settings 1, 2, 4, 8, 16, 32, 64, 128s
(other settings available on request)
Accuracy of setting ±10% (±0.25s)

Output relays
URGENT alarm relay 2 changeover contacts
NON-URGENT alarm relay 2 changeover contacts

Contact ratings
Max. switching power 60W; 62.5VA
Max. switching voltage 220V DC; 250V AC
Max. switching current 2A

6
Max. carrying current 3A
Isolation 750Vrms across open contacts
Insulation resistance >100MΩ at 500V DC

Miscellaneous
Series mode noise (ripple) 10%VB(pk-pk) 50…120Hz
Common mode noise 100Vrms 45…65Hz

Isolation 1kVrms between inputs and alarm


contacts
Impulse 5kV (1.2/50µs) to IEC60-1/BS923
and IEC255-5/BS5992-3
High frequency disturbance To IEC255-22-1/BS142 Section 1.5.1
Overload ratings 2 x VB continuous or 200V dc
whichever is lower
220V version 350V dc continuous
Humidity 0…93% +2% –3% RH
Terminals Barrier type M3.5

LED indications
Power on Green LED
Earth fault (positive) Red LED
Earth fault (negative) Red LED
High impedance Red LED
Over voltage Red LED
Under voltage Red LED

Fail to safety and power on reset of URGENT alarm relay. If the supply voltage
falls below 66%VB for longer than 50ms, an instantaneous URGENT alarm is
given. When the supply voltage returns to above 66%VB, a power on reset
occurs after a time delay of 1 second.

Information required with order


Nominal battery voltage
Battery type (eg lead acid, nickel cadmium, etc.)
Number of cells
High and low voltage alarm points
Earth fault trip level
Relay alarm designations (if different from configuration shown on page 5)
Alarm time delays
Outline dimensions

96 5 104 24

96

+0.8
Panel cut-out 92 –0 square (Dimensions in mm)

You might also like