MAGNUM

Cutler-Hammer, a part of Eaton Corporation, is a worldwide leader providing LOW VOLTAGE AIR CIRCUIT BREAKERS
customer-driven solutions. From power distribution and electrical control products
to industrial automation, Cutler-Hammer utilizes advanced product development, Achieving the Industry’s Highest
world-class manufacturing, and offers global engineering services and support. Interruption and Withstand Ratings

B22F01SU
In a New Compact Design
For more information on Cutler-Hammer products and services,
call 1-800-525-2000 or 1-616-982-1059, or visit our website at
www.cutlerhammer.eaton.com

Pittsburgh, Pennsylvania U.S.A.

Publication No. B.22F.01.S.U


September 1998
Printed in U.S.A. / CMS 2301
Magnum

Reliability Information and More Information


and Uptime Systems Integration

Visit our Website


If Your System’s Not Up…It’s Down Power for Productivity Magnum is accessible on-line through
the Cutler-Hammer Internet site. Visit
In today’s electrical distribution systems, Energy costs are rising an average eight the Cutler-Hammer homepage at
the demand for higher standards of pro- to 10 percent per year…maintenance and www.cutlerhammer.eaton.com
tection and coordination are driven by engineering staffs are trying to do more
and click on Magnum.
demands for a more reliable, more accu- with less…and electrical power quality is
rate distribution system. A distribution decreasing. These situations are provid-
system that eliminates unnecessary trips, ing increased pressure on electrical staff Magnum Literature
isolates a fault to ensure minimum down- personnel to improve quality. Additional product literature is avail-
time, and provides system information able from your local Cutler-Hammer
A solution is power distribution monitor-
to assist the user to better manage the
ing because it provides information from sales office.
system.
the utility substation all the way down to a
Magnum Breaker Product Aid
Cutler-Hammer has developed a com- small kW motor…quickly and reliably, em-
(PA.22F.02.S.U) – Bulletised two-
plete family of microprocessor-based de- powering maintenance and engineering
vices to meet the demands of users and to take control of the distribution system.
page format, including unique
designers of electrical distribution sys- Data on energy consumption, mainte- breaker features, ratings, and
tems. Our Digitrip OPTIM Programmable nance requirements, and troubleshooting dimensional data.
and Digitrip RMS Electronic Trip Units are at their fingertips, providing savings in Magnum Product Guide
offer circuit protection, information, inte- both time and money. The Cutler-Hammer (PG.22F.01.T.U) – Detailed mate-
gral testing, remote communications, IMPACC System uniquely interrogates rial on Magnum functions, tech-
and energy monitoring functions for low the electrical system for necessary first-
nology, ratings, dimensions, and
voltage breakers…while a Digitrip 1150i hand information and displays it with
ordering information.
Programmable Trip Unit has been engi- easy-to-understand software.
neered exclusively for Magnum Breakers.
Cutler-Hammer Sales Offices
For a detailed presentation on the
additional benefits and cost savings
that Magnum can create for you,
call your nearest Cutler-Hammer
sales office or distributor.

Copyright Cutler-Hammer Corporation, 1998.


All Rights Reserved

A result is information that is used to


assess the on-line performance of an
installed power system, followed by
intelligent action to keep the system
on-line and productive.

Magnum 15
Cutler-Hammer
Magnum Power for Productivity
For Greater Reliability, Increased Productivity,
and Significant Cost Savings...
Cutler-Hammer has the Solutions

Cutler-Hammer…
Power Quality Energy Management
A Global Provider of
In today’s sophisticated Electrical Power Distribution Solutions
distribution systems, providing
For nearly 70 years Cutler-Hammer has designed, engineered, and manu-
power requires more than just Technology factured low voltage circuit breakers and trip units. Our unique product
Advancements developments have continually set the standard for quality, reliability, and
meeting minimum standards. extended operating life.
and Innovative We’re an industry leader in air circuit breaker innovations such as the first
It necessitates implementation
Features solid-state trip unit, the first microprocessor-based trip unit, zone selective
of solutions that range from interlocking, and the DE-ION® arc extinguisher that provides superior arc
Our Customers quenching. We also innovated the Series C® Moulded Case Circuit Breaker
efficient distribution to family that meets all major electrical world standards.
A Key to Distribution System Reliability Energy: If You Can’t Measure It, Asked For
You Can’t Manage It As a result of our extensive experience and worldwide installed base, we’ve
coordination to power quality Nonlinear loads, momentary voltage
in an learned that air circuit breaker requirements constantly change. System de-
transients, and surges can cause signifi- Energy consumption is a major opera-
cant power quality problems in both in- tions cost for any building and a signifi-
signers continually demand increased performance, necessitating innova-
to energy management to Air Circuit tive solutions that provide higher ratings in less space, enhanced safety, and
dustrial and commercial facilities. Many cant part of every tenant’s rent. Electric
industrial processes and solid-state de- utilities, reacting to increased demands, allow for easier maintenance…plus the increasingly important capabilities
communications! The end result vices are extremely sensitive to power Breaker
have developed programmes that provide of communications and power quality monitoring and measurement.
quality problems…and manufacturing cost reductions for energy conservation
is the production of cost-effective, operations can be disrupted by voltage ...but penalise for usage during peak de-
Anticipating future electrical distribution system design requirements and in-
or frequency variances. Poor power mand hours. Additionally, re-regulation dustry trends worldwide, Cutler-Hammer engineers and scientists combined their extensive
high quality products. quality can result in expensive downtime of the utility industry is creating new air and moulded case circuit breaker expertise with input from industry-leading customers.
and costly equipment failures. Computer opportunities to save energy and signifi- The result is the next generation of air circuit breakers…the revolutionary Magnum.™
data centres are very sensitive and minor cantly reduce energy expenses.
power disturbances can result in down- Highest Ratings, Greater Strength, and Expanded Capabilities…in Less Space
time and significant operational problems. Tenants have the option to decrease
consumption if they can monitor energy
The negative effect of harmonics can re- We designed the Magnum Air Circuit Breaker with a rigid frame housing, making it struc-
usage. By reducing their consumption,
sult in overheated neutrals in panelboards, peak demand charges (often a substan- turally stronger while providing greater interrupting and withstand ratings in less space
switchboards, overheated transformers, tial portion of a building’s electric bill) than any other air circuit breaker. The innovative arc running system enables Magnum to
and nuisance tripping of breakers and will be lowered, thus making the building control the arc direction while also providing for higher interrupting capacity in a smaller
adjustable frequency drives. more attractive to prospective tenants. space. This system provides for longer contact life and increased interrupting ratings.
Decreases in energy consumption are Increased ratings in less space provide opportunities to design more rugged electrical
also important in manufacturing facility distribution systems that can handle larger available fault currents, and provide for better
departments or “lines”. Many manufac- coordination with downstream devices.
turing companies are now placing the
responsibility for energy budgeting at the We also included capabilities for our customers to use Cutler-Hammer industry-leading
line foreman level…and this includes cal- communications and power quality measurement technologies.
culating energy costs just the same as for
labor, materials, and other direct expenses. ■ Highest Interruption and Withstand Ratings. Magnum provides the industry’s highest
interrupting ratings available in a physically smaller size. Magnum:
■ Through-the-Door Design. All controls, indicators, and the trip unit are visible and can The New
be safely accessed without opening the compartment door.
Cutler-Hammer Engineering Services and Systems Low Voltage
■ Common Height and Depth. Each Magnum breaker frame size has the identical height
and depth, a feature unique in the industry. Air Circuit
Enhancing Existing Equipment Reliability ■ A New Family of Trip Units. A full range of Digitrip® Electronic and Programmable Trip
Increased system loads and normal Units has been developed to provide customers a choice of expanded protection, infor- Breaker from
equipment wear can alter performance mation, power quality measurement, and communication capabilities to meet specific
characteristics and introduce unexpected
Cutler-Hammer
requirements.
line variables. Cutler-Hammer Engineer-
ing Services and Systems provides a Magnum Application Flexibility
solution with skilled engineers and tech-
nicians that conduct power quality site Magnum Breakers are designed for use in low voltage assemblies including switchgear,
surveys, and monitoring and evaluation switchboards, motor control centres, and transfer switch equipment.
studies in addition to providing mainte-
nance and retrofit services for existing
equipment.

14 Magnum Magnum 3
Magnum Magnum
The Air Circuit Breaker IMPACC Communications

Introducing Another Air Circuit Breaker First! Highly Reliable, Comprehensive Communications Through IMPACC, information communicated
2 that will Improve Your Operating Efficiency from a Magnum Breaker includes breaker status
The Highest Interrupting and Withstand Ratings… (open/close/trip), cause and magnitude of trip,
Your main objective is to produce a cost-effective, metering values, trip rating, and time stamping of
in the Smallest Physical Unit Size high quality product or service. Several things stand events. The breaker itself can be remotely opened
Our Cutler-Hammer design team innovations, coupled in your way – unexpected equipment downtime, or closed.
with customer focus group input, provided the re-defi- energy costs, reduced maintenance personnel,
nition of what is needed in an air circuit breaker: tighter budgets, and limited capital or cash flow.
Downtime or power outage costs can cause signifi-
Software Solutions to Match Your Needs
■ The capability to design more flexible systems cant lost production time and related expenses.
3 IMPACC software is available to meet specific re-
4 that can withstand larger available fault currents.
quirements, providing for easy expansion as sys-
■ Better coordination with downstream devices. How Can You Excel in this Environment? tem requirements
■ Integral arc hood means zero clearance for draw- increase. This soft-
out cassette. By obtaining information and making it available ware ranges from
5 in real time to the people who need to have it…
6 ■ Reduced size of the switchgear assembly. simple monitoring
provided cost-effectively in a simple format that to complex power
■ Integrally designed breaker levering mechanism
each person can understand and use. You can management appli-
and cassette for drawout breakers provides clear in-
obtain this information from your electrical distri- cations. IMPACC
7 dication of connect, test, and disconnect positions.
bution system with a Cutler-Hammer IMPACC brings intelligence
8
9 Cutler-Hammer Met the Challenge Communications System. to any distribution
With Magnum, for example, a master control unit system for energy
Magnum is designed and engineered specifically for monitoring, preven-
is used to communicate with the breaker’s Digitrip
10 use in low voltage assemblies applied at nominal volt- tive maintenance,
RMS 1150i Trip Unit, and other IQ devices such as
ages of 380/415, 440 and 500/690V ac. Nine continuous expert system diag-
an IQ Analyzer and IQ DP-4000. The master control
ratings – 800 amperes through 6300 amperes – are nostics, and custom
11 unit may be a personal computer, an existing build-
covered by only two breaker sizes. Drawout and fixed control applications.
12 ing management system, a programmable logic
mounting available in 3 or 4 pole designs.
controller, or a distributed control system.
Controls and indicators are functionally grouped on
the front escutcheon of the breakers where they can
13 IMPACC Software ONE LINE DIAGRAM ELEVATION DISPLAY
be easily viewed and accessed through a cutout door.
IMPACC features a suite of client-server software

1 Integral Arc Hood products. Cutler-Hammer designed IMPACC specifi-
cally as a complete electrical distribution system

2 Front Mounted Secondary Contacts
monitoring programme that includes graphical
14 15 ■
3 Trip Flag one-line and elevation displays, waveform analysis,
trip curve coordination, historical trending, event

4 Three Accessory Windows
and alarm management.

5 Spring Status Indicator (Charged or Discharged)
IMPACC was designed to communicate using an

6 Contact Status Indicator (Open or Closed) existing or dedicated plant TCP/IP Ethernet network.

7 Digitrip RMS Trip Unit Client software will operate on Microsoft® Windows®
NT and 95 operating systems. Server software op- WAVEFORM ANALYSIS TRIP CURVE COORDINATION

8 “Push On” to Close Breaker Button
erates on Windows® NT exclusively for maximum

9 “Push Off” to Open Breaker Button system reliability.

10 Manual Charging Handle


11 Drawout Cassette


12 Optional Operations Counter


13 Optional “Off” Key Lock


14 Integral Padlockable Levering Device


15 Colour-Coded Breaker Position Indicators

E-Bill Software E-BILL E-TREND


E-Bill is an exclusive metering and analysis package
designed to gather data for improved allocation and
management of energy costs. As an enhancement
to E-Bill, Cutler-Hammer offers E-Track, which pro-
vides the capability to track industrial production
energy costs on a per unit basis. For those users
interested in graphics, E-Trend software provides
historical energy usage information in a Windows®-
based graphical display.

Rear view of integrally-designed The independently operated The drawout breaker can be The breaker spring charging
cassette showing generous and lockable shutter design conveniently racked in or out, handle is designed with suffi-
spacing for customer bus provides a safe environment stopping at the various positions cient space for operation even
connections. when the breaker is removed with the door closed. with a gloved hand.
from the cassette.

4 Magnum Magnum 13
Magnum
Metering and Protection Products

Factory or OEM Installed in Low Voltage Equipment 100 Percent Rated…Meets or Exceed Standards
and protection devices to the basic levels of plant
Cutler-Hammer was the first manufacturer to cost- operation. These devices provide more usable in- ■ Magnum Breakers are 100% rated, meaning no ■ Units are built and tested in an ISO 9000 certified
effectively bring microprocessor-based metering formation with greater accuracy. thermal derating is required when applying the facility to the applicable IEC 947-2 standards.
breaker in an enclosure. ■ Suitable for use in IEC 947-1/439-1 LV Switchgear.
■ Full third party KEMA certification. The only air
IQ Analyzer circuit breaker to carry this certification for both
Viewed parameters include current, voltage, power short circuit and endurance test requirements. 3 Pole Breaker
A Highly Accurate Meter that Provides ■
Energy Management and Power Quality Information (watts, vars, and VA), energy, frequency, demand, Amperes Dimensions – Millimeters (Inches)
on an Easy-to-Read Display power factor, percentage THD current, percentage Magnum Breaker Ratings H D* W
THD voltage, K Factor, CBEMA derating factor, crest Breaker Ratings at 380/415, 440 and 500/690 Volts
■ Meets rigid Class 10 accuracy specification for 800-3200 416.56 (16.40) 391.16 (15.40) 414.02 (16.30)
factor, discrete I/O status, and analog input reading.
revenue meters. Maximum Volts Breaker Interrupting Withstand 4000-6300 416.56 (16.40) 391.16 (15.40) 868.68 (34.20)
■ Easy-to-use. All programming is completed by Amperes Rating
■ Waveform display includes the ability to detect Rating Time Seconds
the operator on the faceplate. A PC is not required. * Drawout breaker with finger clusters.
subcycle voltage disturbances, including voltage 800 690 MWI408 40 kA 40 kA 1
transients and subcycle voltage interruptions. ■ Provides true rms sensing through the 50th har- 690 MWI608 65 kA 65 kA 1
monic and displays even and odd multiples of 690 MWI808 85 kA 85 kA 1
410.21 340.11
■ Analysis screens provide detailed information on 256.64 133.35 31.62
the fundamental current and voltage through the
trends, recorded events/alarms, harmonic distor- 1250 690 MWI412 40 kA 40 kA 1 77.98
50th harmonic.
tion, and peak demands of current and power. 690 MWI612 65 kA 65 kA 1
■ Nonvolatile memory.
690 MWI812 85 kA 85 kA 1
■ Optional IMPACC communications capability.
1600 690 MWI616 65 kA 65 kA 1 351.89 416.56
690 MWI816 85 kA 85 kA 1
IQ DP-4000™ 2000 690 MWI620 65 kA 65 kA 1
Replaces individually mounted and wired amme- 690 MWI820 85 kA 85 kA 1
A Full Function Meter Ideal ■
414.02 391.16
ters, voltmeters, ammeter and voltmeter switches, 440 MWIC20 100 kA 85 kA 1
for Complete System Monitoring 800-3200 Ampere Fixed Frame
wattmeters, varmeters, power factor meters, fre- 690 MWI620 65 kA 50 kA 3
■ Direct reading metered values including watts, watt 690 MWI820 85 kA 65 kA 3
quency meters, watthour and demand meters. 864.87 340.11
demand, watthours, power factor, VA, VA hours, 2500 690 MWI625 65 kA 65 kA 3 256.64 133.35 31.62
varhours, percentage THD, and load shedding. ■ Nonvolatile memory. 77.98
690 MWI825 85 kA 85 kA 3
■ Other direct reading metered values include ac ■ Optional IMPACC communications capability.
■ True rms sensing. 3200 690 MWI632 65 kA 65 kA 1
amperes, ac voltage, and frequency.
690 MWI832 85 kA 85 kA 1
■ Protection functions include phase loss, phase 440 MWIC32 100 kA 85 kA 1 351.89 416.56
unbalance, phase reversal, overvoltage, under- 690 MWI832 85 kA 65 kA 3
voltage, and delay.
4000 690 MWI640 65 kA 65 kA 1
690 MWI840 85 kA 85 kA 1
Breaker Interface Module 690 MWIC40 100 kA 100 kA 1
868.68 391.16
4000-6300 Ampere Fixed Frame
690 MWIE40 150 kA 100 kA 1
Centralised Local or Remote Monitoring ■ Monitored locally at the switchgear or, for example,
and Information Display remotely at the maintenance engineer’s office. 5000 690 MWI850 85 kA 85 kA 1
3 Pole Cassette
690 MWIC50 100 kA 100 kA 1
■ A communications centre that monitors up to ■ Centralised alternative to individually mounted Amperes Dimensions – Millimeters (Inches)
690 MWIE50 150 kA 100 kA 1
50 Magnum Breakers equipped with Digitrip and wired ammeters and ammeter switches, H* D W
watthour meters, circuit breaker position indicat- 6300 690 MWI863 85 kA 85 kA 1
RMS Electronic or Programmable Trip Units. 800-3200 483.88 (19.05) 460.11 (18.11) 416.50 (16.40)
ing lights, alarm contacts, and test/programmers. 690 MWIC63 100 kA 100 kA 1
■ Can be used to programme/test programmable 690 MWIE63 150 kA 100 kA 1 4000-6300 483.88 (19.05) 460.11 (18.11) 889.35 (35.01)
trip units. ■ Monitors harmonic information.
■ User friendly functions displayed by an LED * If vertical adapters are used, add 39.81 mm (1.57 inches).
■ Displays status, cause of trip, metered values
(including current at time of trip), and energy to indicate the selected function.
information from each monitored device. ■ Nonvolatile memory.
■ Optional IMPACC communications capability.

Clipper Power System


Transient Voltage Surge Suppression (TVSS) ■ Highest level of filtering in the industry (55 dB at
■ Protects sensitive equipment from the damaging 100 Hz) removes common electrical disturbances
including high and low energy ringing transients.
effects of high and low energy transients as well
■ Withstands over 3000 sequential Category C3 The innovative design and engineer-
as high frequency noise. ing advancements of Magnum
shots (IEEE C62.41 1991) with less than a five Breakers have resulted in dramatic
■ “Zero lead length” direct bus bar connection
percent change in clamping voltage. size reductions and increased inter-
provides superior performance when compared rupting ratings…in just two physi-
to conventional cable connected or nonintegrated ■ Three levels of status monitoring. cal frame sizes.
solutions, resulting in the lowest let-through volt- ■ Standard disconnect.
age in the industry.

4000-6300 Ampere Fixed Breaker

800-3200 Ampere Drawout Breaker

12 Magnum Magnum 5
Magnum
A Look Inside

1 Designed for Easy Access, Inspection,


Magnum Digitrip Trip Units
and Minimal Maintenance
The next generation of proven
The stored energy mechanism, control devices, Digitrip RMS Trip Units is available
2 exclusively on Magnum Breakers.
accessories, and secondary contacts are easily These true rms sensing trip units
accessible by removing the front cover…held in provide accurate coordination with
the conductors and equipment the
place by four captive screws. For safety, this can breaker is designed to protect.
only be done when the breaker is in the disconnect
position or removed from the cell.
The current sensor viewing window on the rear
3 of the breaker allows for easy identification of the TRIP UNIT TYPE DIGITRIP 220 DIGITRIP 520 i DIGITRIP 520M i DIGITRIP 1150 i
current sensor mounted inside. Ampere Range (16) 200A-6300A 200A-6300A 200A-6300A 200A-6300A
Interrupting Rating at 690V 40 through 150kA 40 through 150kA 40 through 150kA 40 through 150kA
A contact wear indicator eliminates the need for rms Sensing Yes Yes Yes Yes
elaborate testing to determine if the contact assem- PROTECTION AND COORDINATION
bly needs replacing. Protection Ordering Options LI LSI, LSIG 0LSI, LSIG, LSIA LSI, LSIG, LSIA
Fixed Rating Plug (In ) Yes Yes Yes Yes
Many minor replacement functions involving the Overtemperature Trip Yes Yes Yes Yes
mechanism, control, and/or accessories can be Long Long Delay Setting Fixed 0.4-1.0 x (ln ) 0.4-1.0 x (In) 0.4-1.0 x (In)
Delay
easily accomplished. Protection
Long Delay Time I2t at 6 x Ir Fixed 2-24 Seconds 2-24 Seconds 2-24 Seconds
Long Delay Time I4t No No No 1-5 Seconds
Long Delay Thermal Memory Yes Yes Yes Yes
Two-Step Stored Energy Mechanism High Load Alarm No No No 0.7-1.0 x I r
5 for Manually and Electrically Operated Breakers Short Short Delay Pick-Up No 200-1000% M1 x (Ir )➀ 200-1000% M1 x (Ir)➀ 150-1000% M1 x (Ir)➀
6 Delay Short Delay Time I2 t at 8 x Ir No 100-500 ms 100-500 ms 100-500 ms
Protection
4 The potential energy is stored in the mechanism Short Delay Time Flat No 100-500 ms 100-500 ms 100-500 ms
to close the breaker in five cycles or less. Sufficient Short Delay Time ZSI No Yes Yes Yes
energy to open the breaker remains available fol- Instan- Instantaneous Pick-Up 200-1000% x (In)➀ 200-1000% x (In)➀ 200-1000% x (In)➀ 200-1000% x (In)➀
taneous Making Current Release Yes Yes Yes Yes
7 lowing the closing operation. Protection
Off Position No Yes Yes Yes
After closing, the charging spring can be recharged Earth Earth Fault Alarm No No Yes Yes
Fault Earth Fault Pick-Up No 025-100% x (In) 025-100% x (In) 25-100% x (In )
to provide potential energy for reclosing follow- Protection
Earth Fault Delay I2t at .625 x In No 100-500 ms 100-500 ms 100-500 ms
ing a fault, providing high continuity of service. Earth Fault Delay Flat No 100-500 ms 100-500 ms 100-500 ms
This feature allows for the following sequence: Earth Fault ZSI No Yes Yes Yes
charge – close – recharge – open – close – open. Earth Fault Memory No Yes Yes Yes
8 Disable Earth Fault No No No Yes
9 On manually operated breakers, closing springs are SYSTEM DIAGNOSTICS
charged by hand. For electrically operated breakers, Cause of Trip LEDs No 0Yes➁ 0Yes➁ 0Yes➁
springs are charged by an electric motor but can be Magnitude of Trip Information No No No Yes
Remote Signal Contacts No No Yes Yes
manually charged if no power is available.
Programmable Contacts No No No 2
SYSTEM MONITORING
10 Digital Display No No 4 Char. LCD 24 Char. LED
Current (%) Full Scale Sensor No No Yes (2%) Yes (1%)

1 Secondary Wiring Points
11 Voltage (%) L to L No No No Yes (1%)

2 Field Installable Accessories Power and Energy (%)
Apparent Power kVA and Demand
No
No
No
No
No
No
Yes (2%)
Yes
(Three Maximum)
Reactive Power kVAR No No No Yes

3 Digitrip RMS Trip Unit Power Factor No No No Yes
Crest Factor No No No Yes

4 Optional Electric
Power Quality – Harmonics No No No Yes
Charging Motor
% THD No No No Yes
■5 Manual Charging Handle SYSTEM COMMUNICATIONS
IMPACC No No No 0Yes➂
■6 Optional Operations Counter Testing Method Test Set Test Set Test Set Integral and Test Set➃
■7 Optional “Off” Key Lock ADDITIONAL FEATURES
Trip Log (3 Events) No No No Yes
■8 Padlockable Levering Device
12 Electronic Operations Counter No No No Yes
Triplink No No No Yes
■9 Breaker Position Indicator Waveform Capture No No No Yes

10 Secondary Contacts 13 Selectable IEC Curves No No No Yes
➀ Addition range up to M1 value: ➁ Cause of trip – L, S, I, G, ➂ Must use NT-based ➃ Tester for secondary

11 Arc Chute Covers
14 <1250-M1=1400%. and making current release. IMPACC software to enable injection.

12 Primary Finger 1600-2500-M1=1200%.
>3000-M1=1000%.
communications.
Cluster Disconnects


13 Current Sensor Window In = Rating plug rating.
Positioning of the secondary contact subassembly is dedicated Ir = LDPU setting.

14 Rigid Frame Housing for installation, maintenance, and testing. Top view shown with
This rear view of a Magnum drawout breaker cover removed, bottom of photo is front of breaker.
breaker shows the designed-in safety
feature of locating the primary discon-
nects and secondary contacts on the
removable breaker element for easy
and safe inspection.

6 Magnum Magnum 11
Magnum Magnum
The Trip Unit Ideal for Any Low Voltage Assembly

A Selection of Trip Units Provides Electronic Trip Units Two Structure Widths Provide
Expanded Protection and Information Capabilities Greater Capacity in Less Space
■ Digitrip RMS 220 provides long time and instan-
Cutler-Hammer introduced the first microprocessor- taneous protection only. Cutler-Hammer engineered Magnum to fit into two
based trip unit and has advanced the technology ■ Digitrip RMS 520i enables the user as many as space-saving structure widths for 3 pole: 414 mm
into a new family of Digitrip RMS Electronic and nine phase and ground current protection settings wide for 800-3200A breaker frames and 869 mm wide
Programmable Trip Units designed and engineered for maximum flexibility in trip-curve shaping and for 4000-6300A breaker frames. Magnum provides
exclusively for Magnum. Magnum can also be sup- multi-unit coordination, and adds earth fault cur- opportunities for more circuit breakers in less space.
plied as a nonautomatic breaker. rent protection settings.
■ Digitrip RMS 520Mi adds phase, neutral, and earth Through-the-Door Design Provides
fault current metering…with a four-character LCD User-Friendly Operation and Optimum Safety
display window.
Through-the-door design provides clear visual and
physical access to the trip unit and all breaker con-
Digitrip 520i/520Mi Digitrip 520i/520Mi
Long and Short Delay Curves Ground Curve
trols and indicators…including open and close but-
CONNECT
tons, the open/close indicating flag, the charging
7000

4000
7000

4000
handle, breaker interlock, and the spring charge/dis-
charge flag. Even breaker levering is accomplished
1000 1000
with the breaker compartment door closed.
For safety and security, the breaker compartment
provides three breaker positions with the door
60 60
closed: connect, test, and disconnect.
Extension rails can be padlocked to prevent a breaker
10 10 from being inserted into a cell, a requirement when
maintenance is being performed. This helps assure

Time in Seconds
Time in Seconds
that no one can install a breaker and energise a circuit
1 1
on which a person may be working.

Convenient Secondary Contact Placement


.1 .1 TEST Facilitates Wiring and Maintenance
Secondary wiring points are located in the top front
.01 .01
portion of each cell. A separate door can be used to
.5 1 2 10 20
Current in Multiples
50 100 .05 .1 .2 1 2
Current in Multiples
5 10
cover the contacts so an operator can safely access
of Rating In
of Long Delay Setting Ir them without opening the breaker compartment
door. Customer contact points are dedicated to the
Programmable Trip Units customer’s interface meaning they are free from
factory connections.
■ Digitrip RMS 1150i provides programmability for
more sophisticated distribution systems including: The secondary terminals have standard finger-proof
hinged covers, providing safety by protecting against
– Increased protection and coordination capabilities.
accidental contact with live secondary contacts.
– Systems monitoring information including
Covers are hinged for making connections and in-
power factor, voltage current, harmonic distor- clude a small hole for circuit testing using a probe.
tion values, and waveform capture with a three-
line, (eight characters per line) LED display. Each secondary contact point is dedicated to a spe-
– Two programmable contacts for customer use.
DISCONNECT cific function, allowing standardised wiring diagrams
– Time stamping of trip events for improved Safety is enhanced by the through-the-door and true electrical interchangeability of common
design that provides for three breaker size breakers. Standard wiring points help improve
troubleshooting and diagnostics. positions with the door closed: connect,
test, and disconnect. The above photos quality while reducing maintenance and inspection
– Accuracy of 1% on metered values and 2% on
show standard enclosure rating of IP42. time for customers.
energy and power.
Digitrip RMS 1150i Programmable Trip Unit – Systems diagnostic information.
The state-of-the-art trip unit with true rms sensing can be pro-
grammed at the faceplate or remotely with a PC using the IMPACC – IMPACC communications.
communications system. All system parameters as well as pro- – Allows for custom curve shaping or selectable
gramming information can be viewed on the easy-to-read three
line digital display window. IEC curves.

Zone Selective Interlocking Capability Provides


Positive System Coordination without Time Delays
Zone Selective Interlocking (ZSI) allows the breaker
closest to the fault to trip without any preset time
delay. The breaker closest to the fault trips first,
while the remainder of the distribution system
remains on-line, thus avoiding unnecessary and In the withdrawn position, the Finger-proof (IP20) secondary All breakers can be padlocked
costly downtime. breaker can be removed from points with easy access for to secure the breaker in all
the cell on integral extension customer wiring. three positions. An optional
rails. key interlock (not shown) can
also secure the breaker in each
position.

10 Magnum Magnum 7
Magnum Magnum
Safety and Reliability Field-Installable Accessories

Rigid Frame Housing ■ Interlocked levering door cannot be opened until A Common Family of Accessories for Both Frame Sizes Factory Installed or Available as Field-Installable Kits
the contacts are in the open condition.
Another Cutler-Hammer innovation is the Magnum’s We designed Magnum accessories to fit both frame Through-the-Window Accessories
■ Three position indicators on the faceplate for
rigid frame housing. This housing provides the sizes, thus reducing inventory parts and the possible
drawout mounting. Specific colours identify the
strength and stability required in the mounting of confusion that can exist when different accessory
breaker position.
the current path and operating mechanism. sizes are required for each individual breaker frame.
■ Increased Uptime. Because the current path is Magnum through-the-window accessories are in-
isolated and insulated inside a two-piece inter- stalled in the right front of the breaker. The unique
connected housing, any potential damage that windows in the breaker cover enable accessories
may occur during arc interruption between the to be quickly identified by name and rating.
poles or outside of the breaker is minimised.
Accessories are plug-in and snapped in place, pro-
■ Increased Breaker Life. By providing rigid
viding for easy mounting and wiring to save both
support for the operating mechanism and the
installation time and cost. This feature facilitates
contact structure, mechanical stress is reduced, Shunt Trip Spring Release Undervoltage
Connect. Both main and secondary contacts accessory changes and replacements by user per-
increasing reliability. Provides remote Remotely closes Release (UVR)
are connected and the breaker is ready for sonnel, eliminating the need to use factory trained
■ Design Reliability. The housing reduces the normal operation. personnel or outside service companies. controlled circuit the breaker when Trips the breaker
number of frame parts in comparison with breaker opening its coil is ener- remotely when
Test. Main disconnects are disengaged, secondary when energised gised by a volt- an existing volt-
conventional air circuit breakers, providing Modular accessories are keyed for fast error-free
contacts are engaged. All functions of the breaker by a voltage input. age input. age signal is lost
increased reliability. mounting in the field. For example, the spring
and trip unit can be tested in this position. or drops below
■ Rigid Frame. The engineered thermoset composite release can only be mounted in the centre cavity. an established
Disconnect. A storage position in the compartment
resin provides excellent structural properties, threshold.
but the breaker is open and disconnected.
dielectric strength, and arc track resistance...
helping to provide the higher interrupting and
Quality and Reliability Internal Accessories
withstand ratings in a smaller size.
Auxiliary Switch Overcurrent Electrical
Cutler-Hammer performs consistent endurance and
Trip Switch Operator
Built-In Safety Features Provide reliability tests on Magnum Air Circuit Breakers. Provides the capa-
(Bell Alarm)
Optimum Operator Safety and System Security bility to remotely An electric motor,
■ Mini-Life Tests. A breaker is randomly selected indicate if the A set of N/Oand internally mount-
■ Improved C-loop current path design provides from the production line daily, and mechanically breaker is open N/C contacts that ed in the circuit
dramatic improvements in both safety and tested to assure performance as required. or closed. Up to six indicate when a breaker, that
N/O and six N/C breaker trips. charges the clos-
efficiency. Higher current ratings increase the ■ Maxi-Life Tests. MTBF testing continuously tests ing springs auto-
auxiliary contacts
blow-on forces on the contact surfaces, allowing Magnum Breakers until they fail. This identifies are available for matically, facilitat-
the proper downstream protective device to potential performance issues with the breaker and customer use. ing remote or
open, isolating the fault and increasing uptime. provides statistical analysis for further improvement. local closing.
■ Positive on is indicated on the breaker faceplate.
This unique interlocking feature prevents the Application Flexibility
levering door from being opened if the contacts
are welded, protecting personnel from exposure Magnum Breakers are suitable for broad applications
to live primary contacts. in Cutler-Hammer or OEM low voltage assemblies.
■ Making current release prevents the breaker
from closing in on a fault with peak current
exceeding 25 times the rms nominal current.
Low Voltage The accessory cavity design, unique to air circuit breakers, is acces-
■ Keyed sensor plug insures error-free installation Switchboard sible in the front of the breaker. Up to three accessories can be
of the sensor in the field. easily installed and wired in the field.
■ Deadfront faceplate isolates the operator
from the primary voltage when the breaker
is energised.
■ Anti-pump prevents any attempts to reclose the
breaker on a short circuit fault if the close signal
(mechanical or electrical) is maintained.
Motor Control Centre

Transfer Switch
Equipment

Viewable through-the- The auxiliary switch is an inter- An electric motor automatically Magnum modular design allows
window electrical access- nal accessory that provides charges the closing springs. In ab- customers to mount accessories
ories are identically sized, remote electrical indication sence of control power, the springs in the field.
yet keyed for error-free of the breaker status. can be manually charged.
mounting.

8 Magnum Magnum 9
Magnum Magnum
Safety and Reliability Field-Installable Accessories

Rigid Frame Housing ■ Interlocked levering door cannot be opened until A Common Family of Accessories for Both Frame Sizes Factory Installed or Available as Field-Installable Kits
the contacts are in the open condition.
Another Cutler-Hammer innovation is the Magnum’s We designed Magnum accessories to fit both frame Through-the-Window Accessories
■ Three position indicators on the faceplate for
rigid frame housing. This housing provides the sizes, thus reducing inventory parts and the possible
drawout mounting. Specific colours identify the
strength and stability required in the mounting of confusion that can exist when different accessory
breaker position.
the current path and operating mechanism. sizes are required for each individual breaker frame.
■ Increased Uptime. Because the current path is Magnum through-the-window accessories are in-
isolated and insulated inside a two-piece inter- stalled in the right front of the breaker. The unique
connected housing, any potential damage that windows in the breaker cover enable accessories
may occur during arc interruption between the to be quickly identified by name and rating.
poles or outside of the breaker is minimised.
Accessories are plug-in and snapped in place, pro-
■ Increased Breaker Life. By providing rigid
viding for easy mounting and wiring to save both
support for the operating mechanism and the
installation time and cost. This feature facilitates
contact structure, mechanical stress is reduced, Shunt Trip Spring Release Undervoltage
Connect. Both main and secondary contacts accessory changes and replacements by user per-
increasing reliability. Provides remote Remotely closes Release (UVR)
are connected and the breaker is ready for sonnel, eliminating the need to use factory trained
■ Design Reliability. The housing reduces the normal operation. personnel or outside service companies. controlled circuit the breaker when Trips the breaker
number of frame parts in comparison with breaker opening its coil is ener- remotely when
Test. Main disconnects are disengaged, secondary when energised gised by a volt- an existing volt-
conventional air circuit breakers, providing Modular accessories are keyed for fast error-free
contacts are engaged. All functions of the breaker by a voltage input. age input. age signal is lost
increased reliability. mounting in the field. For example, the spring
and trip unit can be tested in this position. or drops below
■ Rigid Frame. The engineered thermoset composite release can only be mounted in the centre cavity. an established
Disconnect. A storage position in the compartment
resin provides excellent structural properties, threshold.
but the breaker is open and disconnected.
dielectric strength, and arc track resistance...
helping to provide the higher interrupting and
Quality and Reliability Internal Accessories
withstand ratings in a smaller size.
Auxiliary Switch Overcurrent Electrical
Cutler-Hammer performs consistent endurance and
Trip Switch Operator
Built-In Safety Features Provide reliability tests on Magnum Air Circuit Breakers. Provides the capa-
(Bell Alarm)
Optimum Operator Safety and System Security bility to remotely An electric motor,
■ Mini-Life Tests. A breaker is randomly selected indicate if the A set of N/Oand internally mount-
■ Improved C-loop current path design provides from the production line daily, and mechanically breaker is open N/C contacts that ed in the circuit
dramatic improvements in both safety and tested to assure performance as required. or closed. Up to six indicate when a breaker, that
N/O and six N/C breaker trips. charges the clos-
efficiency. Higher current ratings increase the ■ Maxi-Life Tests. MTBF testing continuously tests ing springs auto-
auxiliary contacts
blow-on forces on the contact surfaces, allowing Magnum Breakers until they fail. This identifies are available for matically, facilitat-
the proper downstream protective device to potential performance issues with the breaker and customer use. ing remote or
open, isolating the fault and increasing uptime. provides statistical analysis for further improvement. local closing.
■ Positive on is indicated on the breaker faceplate.
This unique interlocking feature prevents the Application Flexibility
levering door from being opened if the contacts
are welded, protecting personnel from exposure Magnum Breakers are suitable for broad applications
to live primary contacts. in Cutler-Hammer or OEM low voltage assemblies.
■ Making current release prevents the breaker
from closing in on a fault with peak current
exceeding 25 times the rms nominal current.
Low Voltage The accessory cavity design, unique to air circuit breakers, is acces-
■ Keyed sensor plug insures error-free installation Switchboard sible in the front of the breaker. Up to three accessories can be
of the sensor in the field. easily installed and wired in the field.
■ Deadfront faceplate isolates the operator
from the primary voltage when the breaker
is energised.
■ Anti-pump prevents any attempts to reclose the
breaker on a short circuit fault if the close signal
(mechanical or electrical) is maintained.
Motor Control Centre

Transfer Switch
Equipment

Viewable through-the- The auxiliary switch is an inter- An electric motor automatically Magnum modular design allows
window electrical access- nal accessory that provides charges the closing springs. In ab- customers to mount accessories
ories are identically sized, remote electrical indication sence of control power, the springs in the field.
yet keyed for error-free of the breaker status. can be manually charged.
mounting.

8 Magnum Magnum 9
Magnum Magnum
The Trip Unit Ideal for Any Low Voltage Assembly

A Selection of Trip Units Provides Electronic Trip Units Two Structure Widths Provide
Expanded Protection and Information Capabilities Greater Capacity in Less Space
■ Digitrip RMS 220 provides long time and instan-
Cutler-Hammer introduced the first microprocessor- taneous protection only. Cutler-Hammer engineered Magnum to fit into two
based trip unit and has advanced the technology ■ Digitrip RMS 520i enables the user as many as space-saving structure widths for 3 pole: 414 mm
into a new family of Digitrip RMS Electronic and nine phase and ground current protection settings wide for 800-3200A breaker frames and 869 mm wide
Programmable Trip Units designed and engineered for maximum flexibility in trip-curve shaping and for 4000-6300A breaker frames. Magnum provides
exclusively for Magnum. Magnum can also be sup- multi-unit coordination, and adds earth fault cur- opportunities for more circuit breakers in less space.
plied as a nonautomatic breaker. rent protection settings.
■ Digitrip RMS 520Mi adds phase, neutral, and earth Through-the-Door Design Provides
fault current metering…with a four-character LCD User-Friendly Operation and Optimum Safety
display window.
Through-the-door design provides clear visual and
physical access to the trip unit and all breaker con-
Digitrip 520i/520Mi Digitrip 520i/520Mi
Long and Short Delay Curves Ground Curve
trols and indicators…including open and close but-
CONNECT
tons, the open/close indicating flag, the charging
7000

4000
7000

4000
handle, breaker interlock, and the spring charge/dis-
charge flag. Even breaker levering is accomplished
1000 1000
with the breaker compartment door closed.
For safety and security, the breaker compartment
provides three breaker positions with the door
60 60
closed: connect, test, and disconnect.
Extension rails can be padlocked to prevent a breaker
10 10 from being inserted into a cell, a requirement when
maintenance is being performed. This helps assure

Time in Seconds
Time in Seconds
that no one can install a breaker and energise a circuit
1 1
on which a person may be working.

Convenient Secondary Contact Placement


.1 .1 TEST Facilitates Wiring and Maintenance
Secondary wiring points are located in the top front
.01 .01
portion of each cell. A separate door can be used to
.5 1 2 10 20
Current in Multiples
50 100 .05 .1 .2 1 2
Current in Multiples
5 10
cover the contacts so an operator can safely access
of Rating In
of Long Delay Setting Ir them without opening the breaker compartment
door. Customer contact points are dedicated to the
Programmable Trip Units customer’s interface meaning they are free from
factory connections.
■ Digitrip RMS 1150i provides programmability for
more sophisticated distribution systems including: The secondary terminals have standard finger-proof
hinged covers, providing safety by protecting against
– Increased protection and coordination capabilities.
accidental contact with live secondary contacts.
– Systems monitoring information including
Covers are hinged for making connections and in-
power factor, voltage current, harmonic distor- clude a small hole for circuit testing using a probe.
tion values, and waveform capture with a three-
line, (eight characters per line) LED display. Each secondary contact point is dedicated to a spe-
– Two programmable contacts for customer use.
DISCONNECT cific function, allowing standardised wiring diagrams
– Time stamping of trip events for improved Safety is enhanced by the through-the-door and true electrical interchangeability of common
design that provides for three breaker size breakers. Standard wiring points help improve
troubleshooting and diagnostics. positions with the door closed: connect,
test, and disconnect. The above photos quality while reducing maintenance and inspection
– Accuracy of 1% on metered values and 2% on
show standard enclosure rating of IP42. time for customers.
energy and power.
Digitrip RMS 1150i Programmable Trip Unit – Systems diagnostic information.
The state-of-the-art trip unit with true rms sensing can be pro-
grammed at the faceplate or remotely with a PC using the IMPACC – IMPACC communications.
communications system. All system parameters as well as pro- – Allows for custom curve shaping or selectable
gramming information can be viewed on the easy-to-read three
line digital display window. IEC curves.

Zone Selective Interlocking Capability Provides


Positive System Coordination without Time Delays
Zone Selective Interlocking (ZSI) allows the breaker
closest to the fault to trip without any preset time
delay. The breaker closest to the fault trips first,
while the remainder of the distribution system
remains on-line, thus avoiding unnecessary and In the withdrawn position, the Finger-proof (IP20) secondary All breakers can be padlocked
costly downtime. breaker can be removed from points with easy access for to secure the breaker in all
the cell on integral extension customer wiring. three positions. An optional
rails. key interlock (not shown) can
also secure the breaker in each
position.

10 Magnum Magnum 7
Magnum
A Look Inside

1 Designed for Easy Access, Inspection,


Magnum Digitrip Trip Units
and Minimal Maintenance
The next generation of proven
The stored energy mechanism, control devices, Digitrip RMS Trip Units is available
2 exclusively on Magnum Breakers.
accessories, and secondary contacts are easily These true rms sensing trip units
accessible by removing the front cover…held in provide accurate coordination with
the conductors and equipment the
place by four captive screws. For safety, this can breaker is designed to protect.
only be done when the breaker is in the disconnect
position or removed from the cell.
The current sensor viewing window on the rear
3 of the breaker allows for easy identification of the TRIP UNIT TYPE DIGITRIP 220 DIGITRIP 520 i DIGITRIP 520M i DIGITRIP 1150 i
current sensor mounted inside. Ampere Range (16) 200A-6300A 200A-6300A 200A-6300A 200A-6300A
Interrupting Rating at 690V 40 through 150kA 40 through 150kA 40 through 150kA 40 through 150kA
A contact wear indicator eliminates the need for rms Sensing Yes Yes Yes Yes
elaborate testing to determine if the contact assem- PROTECTION AND COORDINATION
bly needs replacing. Protection Ordering Options LI LSI, LSIG 0LSI, LSIG, LSIA LSI, LSIG, LSIA
Fixed Rating Plug (In ) Yes Yes Yes Yes
Many minor replacement functions involving the Overtemperature Trip Yes Yes Yes Yes
mechanism, control, and/or accessories can be Long Long Delay Setting Fixed 0.4-1.0 x (ln ) 0.4-1.0 x (In) 0.4-1.0 x (In)
Delay
easily accomplished. Protection
Long Delay Time I2t at 6 x Ir Fixed 2-24 Seconds 2-24 Seconds 2-24 Seconds
Long Delay Time I4t No No No 1-5 Seconds
Long Delay Thermal Memory Yes Yes Yes Yes
Two-Step Stored Energy Mechanism High Load Alarm No No No 0.7-1.0 x I r
5 for Manually and Electrically Operated Breakers Short Short Delay Pick-Up No 200-1000% M1 x (Ir )➀ 200-1000% M1 x (Ir)➀ 150-1000% M1 x (Ir)➀
6 Delay Short Delay Time I2 t at 8 x Ir No 100-500 ms 100-500 ms 100-500 ms
Protection
4 The potential energy is stored in the mechanism Short Delay Time Flat No 100-500 ms 100-500 ms 100-500 ms
to close the breaker in five cycles or less. Sufficient Short Delay Time ZSI No Yes Yes Yes
energy to open the breaker remains available fol- Instan- Instantaneous Pick-Up 200-1000% x (In)➀ 200-1000% x (In)➀ 200-1000% x (In)➀ 200-1000% x (In)➀
taneous Making Current Release Yes Yes Yes Yes
7 lowing the closing operation. Protection
Off Position No Yes Yes Yes
After closing, the charging spring can be recharged Earth Earth Fault Alarm No No Yes Yes
Fault Earth Fault Pick-Up No 025-100% x (In) 025-100% x (In) 25-100% x (In )
to provide potential energy for reclosing follow- Protection
Earth Fault Delay I2t at .625 x In No 100-500 ms 100-500 ms 100-500 ms
ing a fault, providing high continuity of service. Earth Fault Delay Flat No 100-500 ms 100-500 ms 100-500 ms
This feature allows for the following sequence: Earth Fault ZSI No Yes Yes Yes
charge – close – recharge – open – close – open. Earth Fault Memory No Yes Yes Yes
8 Disable Earth Fault No No No Yes
9 On manually operated breakers, closing springs are SYSTEM DIAGNOSTICS
charged by hand. For electrically operated breakers, Cause of Trip LEDs No 0Yes➁ 0Yes➁ 0Yes➁
springs are charged by an electric motor but can be Magnitude of Trip Information No No No Yes
Remote Signal Contacts No No Yes Yes
manually charged if no power is available.
Programmable Contacts No No No 2
SYSTEM MONITORING
10 Digital Display No No 4 Char. LCD 24 Char. LED
Current (%) Full Scale Sensor No No Yes (2%) Yes (1%)

1 Secondary Wiring Points
11 Voltage (%) L to L No No No Yes (1%)

2 Field Installable Accessories Power and Energy (%)
Apparent Power kVA and Demand
No
No
No
No
No
No
Yes (2%)
Yes
(Three Maximum)
Reactive Power kVAR No No No Yes

3 Digitrip RMS Trip Unit Power Factor No No No Yes
Crest Factor No No No Yes

4 Optional Electric
Power Quality – Harmonics No No No Yes
Charging Motor
% THD No No No Yes
■5 Manual Charging Handle SYSTEM COMMUNICATIONS
IMPACC No No No 0Yes➂
■6 Optional Operations Counter Testing Method Test Set Test Set Test Set Integral and Test Set➃
■7 Optional “Off” Key Lock ADDITIONAL FEATURES
Trip Log (3 Events) No No No Yes
■8 Padlockable Levering Device
12 Electronic Operations Counter No No No Yes
Triplink No No No Yes
■9 Breaker Position Indicator Waveform Capture No No No Yes

10 Secondary Contacts 13 Selectable IEC Curves No No No Yes
➀ Addition range up to M1 value: ➁ Cause of trip – L, S, I, G, ➂ Must use NT-based ➃ Tester for secondary

11 Arc Chute Covers
14 <1250-M1=1400%. and making current release. IMPACC software to enable injection.

12 Primary Finger 1600-2500-M1=1200%.
>3000-M1=1000%.
communications.
Cluster Disconnects


13 Current Sensor Window In = Rating plug rating.
Positioning of the secondary contact subassembly is dedicated Ir = LDPU setting.

14 Rigid Frame Housing for installation, maintenance, and testing. Top view shown with
This rear view of a Magnum drawout breaker cover removed, bottom of photo is front of breaker.
breaker shows the designed-in safety
feature of locating the primary discon-
nects and secondary contacts on the
removable breaker element for easy
and safe inspection.

6 Magnum Magnum 11
Magnum
Metering and Protection Products

Factory or OEM Installed in Low Voltage Equipment 100 Percent Rated…Meets or Exceed Standards
and protection devices to the basic levels of plant
Cutler-Hammer was the first manufacturer to cost- operation. These devices provide more usable in- ■ Magnum Breakers are 100% rated, meaning no ■ Units are built and tested in an ISO 9000 certified
effectively bring microprocessor-based metering formation with greater accuracy. thermal derating is required when applying the facility to the applicable IEC 947-2 standards.
breaker in an enclosure. ■ Suitable for use in IEC 947-1/439-1 LV Switchgear.
■ Full third party KEMA certification. The only air
IQ Analyzer circuit breaker to carry this certification for both
Viewed parameters include current, voltage, power short circuit and endurance test requirements. 3 Pole Breaker
A Highly Accurate Meter that Provides ■
Energy Management and Power Quality Information (watts, vars, and VA), energy, frequency, demand, Amperes Dimensions – Millimeters (Inches)
on an Easy-to-Read Display power factor, percentage THD current, percentage Magnum Breaker Ratings H D* W
THD voltage, K Factor, CBEMA derating factor, crest Breaker Ratings at 380/415, 440 and 500/690 Volts
■ Meets rigid Class 10 accuracy specification for 800-3200 416.56 (16.40) 391.16 (15.40) 414.02 (16.30)
factor, discrete I/O status, and analog input reading.
revenue meters. Maximum Volts Breaker Interrupting Withstand 4000-6300 416.56 (16.40) 391.16 (15.40) 868.68 (34.20)
■ Easy-to-use. All programming is completed by Amperes Rating
■ Waveform display includes the ability to detect Rating Time Seconds
the operator on the faceplate. A PC is not required. * Drawout breaker with finger clusters.
subcycle voltage disturbances, including voltage 800 690 MWI408 40 kA 40 kA 1
transients and subcycle voltage interruptions. ■ Provides true rms sensing through the 50th har- 690 MWI608 65 kA 65 kA 1
monic and displays even and odd multiples of 690 MWI808 85 kA 85 kA 1
410.21 340.11
■ Analysis screens provide detailed information on 256.64 133.35 31.62
the fundamental current and voltage through the
trends, recorded events/alarms, harmonic distor- 1250 690 MWI412 40 kA 40 kA 1 77.98
50th harmonic.
tion, and peak demands of current and power. 690 MWI612 65 kA 65 kA 1
■ Nonvolatile memory.
690 MWI812 85 kA 85 kA 1
■ Optional IMPACC communications capability.
1600 690 MWI616 65 kA 65 kA 1 351.89 416.56
690 MWI816 85 kA 85 kA 1
IQ DP-4000™ 2000 690 MWI620 65 kA 65 kA 1
Replaces individually mounted and wired amme- 690 MWI820 85 kA 85 kA 1
A Full Function Meter Ideal ■
414.02 391.16
ters, voltmeters, ammeter and voltmeter switches, 440 MWIC20 100 kA 85 kA 1
for Complete System Monitoring 800-3200 Ampere Fixed Frame
wattmeters, varmeters, power factor meters, fre- 690 MWI620 65 kA 50 kA 3
■ Direct reading metered values including watts, watt 690 MWI820 85 kA 65 kA 3
quency meters, watthour and demand meters. 864.87 340.11
demand, watthours, power factor, VA, VA hours, 2500 690 MWI625 65 kA 65 kA 3 256.64 133.35 31.62
varhours, percentage THD, and load shedding. ■ Nonvolatile memory. 77.98
690 MWI825 85 kA 85 kA 3
■ Other direct reading metered values include ac ■ Optional IMPACC communications capability.
■ True rms sensing. 3200 690 MWI632 65 kA 65 kA 1
amperes, ac voltage, and frequency.
690 MWI832 85 kA 85 kA 1
■ Protection functions include phase loss, phase 440 MWIC32 100 kA 85 kA 1 351.89 416.56
unbalance, phase reversal, overvoltage, under- 690 MWI832 85 kA 65 kA 3
voltage, and delay.
4000 690 MWI640 65 kA 65 kA 1
690 MWI840 85 kA 85 kA 1
Breaker Interface Module 690 MWIC40 100 kA 100 kA 1
868.68 391.16
4000-6300 Ampere Fixed Frame
690 MWIE40 150 kA 100 kA 1
Centralised Local or Remote Monitoring ■ Monitored locally at the switchgear or, for example,
and Information Display remotely at the maintenance engineer’s office. 5000 690 MWI850 85 kA 85 kA 1
3 Pole Cassette
690 MWIC50 100 kA 100 kA 1
■ A communications centre that monitors up to ■ Centralised alternative to individually mounted Amperes Dimensions – Millimeters (Inches)
690 MWIE50 150 kA 100 kA 1
50 Magnum Breakers equipped with Digitrip and wired ammeters and ammeter switches, H* D W
watthour meters, circuit breaker position indicat- 6300 690 MWI863 85 kA 85 kA 1
RMS Electronic or Programmable Trip Units. 800-3200 483.88 (19.05) 460.11 (18.11) 416.50 (16.40)
ing lights, alarm contacts, and test/programmers. 690 MWIC63 100 kA 100 kA 1
■ Can be used to programme/test programmable 690 MWIE63 150 kA 100 kA 1 4000-6300 483.88 (19.05) 460.11 (18.11) 889.35 (35.01)
trip units. ■ Monitors harmonic information.
■ User friendly functions displayed by an LED * If vertical adapters are used, add 39.81 mm (1.57 inches).
■ Displays status, cause of trip, metered values
(including current at time of trip), and energy to indicate the selected function.
information from each monitored device. ■ Nonvolatile memory.
■ Optional IMPACC communications capability.

Clipper Power System


Transient Voltage Surge Suppression (TVSS) ■ Highest level of filtering in the industry (55 dB at
■ Protects sensitive equipment from the damaging 100 Hz) removes common electrical disturbances
including high and low energy ringing transients.
effects of high and low energy transients as well
■ Withstands over 3000 sequential Category C3 The innovative design and engineer-
as high frequency noise. ing advancements of Magnum
shots (IEEE C62.41 1991) with less than a five Breakers have resulted in dramatic
■ “Zero lead length” direct bus bar connection
percent change in clamping voltage. size reductions and increased inter-
provides superior performance when compared rupting ratings…in just two physi-
to conventional cable connected or nonintegrated ■ Three levels of status monitoring. cal frame sizes.
solutions, resulting in the lowest let-through volt- ■ Standard disconnect.
age in the industry.

4000-6300 Ampere Fixed Breaker

800-3200 Ampere Drawout Breaker

12 Magnum Magnum 5
Magnum Magnum
The Air Circuit Breaker IMPACC Communications

Introducing Another Air Circuit Breaker First! Highly Reliable, Comprehensive Communications Through IMPACC, information communicated
2 that will Improve Your Operating Efficiency from a Magnum Breaker includes breaker status
The Highest Interrupting and Withstand Ratings… (open/close/trip), cause and magnitude of trip,
Your main objective is to produce a cost-effective, metering values, trip rating, and time stamping of
in the Smallest Physical Unit Size high quality product or service. Several things stand events. The breaker itself can be remotely opened
Our Cutler-Hammer design team innovations, coupled in your way – unexpected equipment downtime, or closed.
with customer focus group input, provided the re-defi- energy costs, reduced maintenance personnel,
nition of what is needed in an air circuit breaker: tighter budgets, and limited capital or cash flow.
Downtime or power outage costs can cause signifi-
Software Solutions to Match Your Needs
■ The capability to design more flexible systems cant lost production time and related expenses.
3 IMPACC software is available to meet specific re-
4 that can withstand larger available fault currents.
quirements, providing for easy expansion as sys-
■ Better coordination with downstream devices. How Can You Excel in this Environment? tem requirements
■ Integral arc hood means zero clearance for draw- increase. This soft-
out cassette. By obtaining information and making it available ware ranges from
5 in real time to the people who need to have it…
6 ■ Reduced size of the switchgear assembly. simple monitoring
provided cost-effectively in a simple format that to complex power
■ Integrally designed breaker levering mechanism
each person can understand and use. You can management appli-
and cassette for drawout breakers provides clear in-
obtain this information from your electrical distri- cations. IMPACC
7 dication of connect, test, and disconnect positions.
bution system with a Cutler-Hammer IMPACC brings intelligence
8
9 Cutler-Hammer Met the Challenge Communications System. to any distribution
With Magnum, for example, a master control unit system for energy
Magnum is designed and engineered specifically for monitoring, preven-
is used to communicate with the breaker’s Digitrip
10 use in low voltage assemblies applied at nominal volt- tive maintenance,
RMS 1150i Trip Unit, and other IQ devices such as
ages of 380/415, 440 and 500/690V ac. Nine continuous expert system diag-
an IQ Analyzer and IQ DP-4000. The master control
ratings – 800 amperes through 6300 amperes – are nostics, and custom
11 unit may be a personal computer, an existing build-
covered by only two breaker sizes. Drawout and fixed control applications.
12 ing management system, a programmable logic
mounting available in 3 or 4 pole designs.
controller, or a distributed control system.
Controls and indicators are functionally grouped on
the front escutcheon of the breakers where they can
13 IMPACC Software ONE LINE DIAGRAM ELEVATION DISPLAY
be easily viewed and accessed through a cutout door.
IMPACC features a suite of client-server software

1 Integral Arc Hood products. Cutler-Hammer designed IMPACC specifi-
cally as a complete electrical distribution system

2 Front Mounted Secondary Contacts
monitoring programme that includes graphical
14 15 ■
3 Trip Flag one-line and elevation displays, waveform analysis,
trip curve coordination, historical trending, event

4 Three Accessory Windows
and alarm management.

5 Spring Status Indicator (Charged or Discharged)
IMPACC was designed to communicate using an

6 Contact Status Indicator (Open or Closed) existing or dedicated plant TCP/IP Ethernet network.

7 Digitrip RMS Trip Unit Client software will operate on Microsoft® Windows®
NT and 95 operating systems. Server software op- WAVEFORM ANALYSIS TRIP CURVE COORDINATION

8 “Push On” to Close Breaker Button
erates on Windows® NT exclusively for maximum

9 “Push Off” to Open Breaker Button system reliability.

10 Manual Charging Handle


11 Drawout Cassette


12 Optional Operations Counter


13 Optional “Off” Key Lock


14 Integral Padlockable Levering Device


15 Colour-Coded Breaker Position Indicators

E-Bill Software E-BILL E-TREND


E-Bill is an exclusive metering and analysis package
designed to gather data for improved allocation and
management of energy costs. As an enhancement
to E-Bill, Cutler-Hammer offers E-Track, which pro-
vides the capability to track industrial production
energy costs on a per unit basis. For those users
interested in graphics, E-Trend software provides
historical energy usage information in a Windows®-
based graphical display.

Rear view of integrally-designed The independently operated The drawout breaker can be The breaker spring charging
cassette showing generous and lockable shutter design conveniently racked in or out, handle is designed with suffi-
spacing for customer bus provides a safe environment stopping at the various positions cient space for operation even
connections. when the breaker is removed with the door closed. with a gloved hand.
from the cassette.

4 Magnum Magnum 13
Cutler-Hammer
Magnum Power for Productivity
For Greater Reliability, Increased Productivity,
and Significant Cost Savings...
Cutler-Hammer has the Solutions

Cutler-Hammer…
Power Quality Energy Management
A Global Provider of
In today’s sophisticated Electrical Power Distribution Solutions
distribution systems, providing
For nearly 70 years Cutler-Hammer has designed, engineered, and manu-
power requires more than just Technology factured low voltage circuit breakers and trip units. Our unique product
Advancements developments have continually set the standard for quality, reliability, and
meeting minimum standards. extended operating life.
and Innovative We’re an industry leader in air circuit breaker innovations such as the first
It necessitates implementation
Features solid-state trip unit, the first microprocessor-based trip unit, zone selective
of solutions that range from interlocking, and the DE-ION® arc extinguisher that provides superior arc
Our Customers quenching. We also innovated the Series C® Moulded Case Circuit Breaker
efficient distribution to family that meets all major electrical world standards.
A Key to Distribution System Reliability Energy: If You Can’t Measure It, Asked For
You Can’t Manage It As a result of our extensive experience and worldwide installed base, we’ve
coordination to power quality Nonlinear loads, momentary voltage
in an learned that air circuit breaker requirements constantly change. System de-
transients, and surges can cause signifi- Energy consumption is a major opera-
cant power quality problems in both in- tions cost for any building and a signifi-
signers continually demand increased performance, necessitating innova-
to energy management to Air Circuit tive solutions that provide higher ratings in less space, enhanced safety, and
dustrial and commercial facilities. Many cant part of every tenant’s rent. Electric
industrial processes and solid-state de- utilities, reacting to increased demands, allow for easier maintenance…plus the increasingly important capabilities
communications! The end result vices are extremely sensitive to power Breaker
have developed programmes that provide of communications and power quality monitoring and measurement.
quality problems…and manufacturing cost reductions for energy conservation
is the production of cost-effective, operations can be disrupted by voltage ...but penalise for usage during peak de-
Anticipating future electrical distribution system design requirements and in-
or frequency variances. Poor power mand hours. Additionally, re-regulation dustry trends worldwide, Cutler-Hammer engineers and scientists combined their extensive
high quality products. quality can result in expensive downtime of the utility industry is creating new air and moulded case circuit breaker expertise with input from industry-leading customers.
and costly equipment failures. Computer opportunities to save energy and signifi- The result is the next generation of air circuit breakers…the revolutionary Magnum.™
data centres are very sensitive and minor cantly reduce energy expenses.
power disturbances can result in down- Highest Ratings, Greater Strength, and Expanded Capabilities…in Less Space
time and significant operational problems. Tenants have the option to decrease
consumption if they can monitor energy
The negative effect of harmonics can re- We designed the Magnum Air Circuit Breaker with a rigid frame housing, making it struc-
usage. By reducing their consumption,
sult in overheated neutrals in panelboards, peak demand charges (often a substan- turally stronger while providing greater interrupting and withstand ratings in less space
switchboards, overheated transformers, tial portion of a building’s electric bill) than any other air circuit breaker. The innovative arc running system enables Magnum to
and nuisance tripping of breakers and will be lowered, thus making the building control the arc direction while also providing for higher interrupting capacity in a smaller
adjustable frequency drives. more attractive to prospective tenants. space. This system provides for longer contact life and increased interrupting ratings.
Decreases in energy consumption are Increased ratings in less space provide opportunities to design more rugged electrical
also important in manufacturing facility distribution systems that can handle larger available fault currents, and provide for better
departments or “lines”. Many manufac- coordination with downstream devices.
turing companies are now placing the
responsibility for energy budgeting at the We also included capabilities for our customers to use Cutler-Hammer industry-leading
line foreman level…and this includes cal- communications and power quality measurement technologies.
culating energy costs just the same as for
labor, materials, and other direct expenses. ■ Highest Interruption and Withstand Ratings. Magnum provides the industry’s highest
interrupting ratings available in a physically smaller size. Magnum:
■ Through-the-Door Design. All controls, indicators, and the trip unit are visible and can The New
be safely accessed without opening the compartment door.
Cutler-Hammer Engineering Services and Systems Low Voltage
■ Common Height and Depth. Each Magnum breaker frame size has the identical height
and depth, a feature unique in the industry. Air Circuit
Enhancing Existing Equipment Reliability ■ A New Family of Trip Units. A full range of Digitrip® Electronic and Programmable Trip
Increased system loads and normal Units has been developed to provide customers a choice of expanded protection, infor- Breaker from
equipment wear can alter performance mation, power quality measurement, and communication capabilities to meet specific
characteristics and introduce unexpected
Cutler-Hammer
requirements.
line variables. Cutler-Hammer Engineer-
ing Services and Systems provides a Magnum Application Flexibility
solution with skilled engineers and tech-
nicians that conduct power quality site Magnum Breakers are designed for use in low voltage assemblies including switchgear,
surveys, and monitoring and evaluation switchboards, motor control centres, and transfer switch equipment.
studies in addition to providing mainte-
nance and retrofit services for existing
equipment.

14 Magnum Magnum 3
Magnum

Reliability Information and More Information


and Uptime Systems Integration

Visit our Website


If Your System’s Not Up…It’s Down Power for Productivity Magnum is accessible on-line through
the Cutler-Hammer Internet site. Visit
In today’s electrical distribution systems, Energy costs are rising an average eight the Cutler-Hammer homepage at
the demand for higher standards of pro- to 10 percent per year…maintenance and www.cutlerhammer.eaton.com
tection and coordination are driven by engineering staffs are trying to do more
and click on Magnum.
demands for a more reliable, more accu- with less…and electrical power quality is
rate distribution system. A distribution decreasing. These situations are provid-
system that eliminates unnecessary trips, ing increased pressure on electrical staff Magnum Literature
isolates a fault to ensure minimum down- personnel to improve quality. Additional product literature is avail-
time, and provides system information able from your local Cutler-Hammer
A solution is power distribution monitor-
to assist the user to better manage the
ing because it provides information from sales office.
system.
the utility substation all the way down to a
Magnum Breaker Product Aid
Cutler-Hammer has developed a com- small kW motor…quickly and reliably, em-
(PA.22F.02.S.U) – Bulletised two-
plete family of microprocessor-based de- powering maintenance and engineering
vices to meet the demands of users and to take control of the distribution system.
page format, including unique
designers of electrical distribution sys- Data on energy consumption, mainte- breaker features, ratings, and
tems. Our Digitrip OPTIM Programmable nance requirements, and troubleshooting dimensional data.
and Digitrip RMS Electronic Trip Units are at their fingertips, providing savings in Magnum Product Guide
offer circuit protection, information, inte- both time and money. The Cutler-Hammer (PG.22F.01.T.U) – Detailed mate-
gral testing, remote communications, IMPACC System uniquely interrogates rial on Magnum functions, tech-
and energy monitoring functions for low the electrical system for necessary first-
nology, ratings, dimensions, and
voltage breakers…while a Digitrip 1150i hand information and displays it with
ordering information.
Programmable Trip Unit has been engi- easy-to-understand software.
neered exclusively for Magnum Breakers.
Cutler-Hammer Sales Offices
For a detailed presentation on the
additional benefits and cost savings
that Magnum can create for you,
call your nearest Cutler-Hammer
sales office or distributor.

Copyright Cutler-Hammer Corporation, 1998.


All Rights Reserved

A result is information that is used to


assess the on-line performance of an
installed power system, followed by
intelligent action to keep the system
on-line and productive.

Magnum 15
MAGNUM
Cutler-Hammer, a part of Eaton Corporation, is a worldwide leader providing LOW VOLTAGE AIR CIRCUIT BREAKERS
customer-driven solutions. From power distribution and electrical control products
to industrial automation, Cutler-Hammer utilizes advanced product development, Achieving the Industry’s Highest
world-class manufacturing, and offers global engineering services and support. Interruption and Withstand Ratings

B22F01SU
In a New Compact Design
For more information on Cutler-Hammer products and services,
call 1-800-525-2000 or 1-616-982-1059, or visit our website at
www.cutlerhammer.eaton.com

Pittsburgh, Pennsylvania U.S.A.

Publication No. B.22F.01.S.U


September 1998
Printed in U.S.A. / CMS 2301

You might also like