A B C D E F G H I J K L M N O P Q R S

1 Fill data only in coloured areas


2 Project Name : Building No. one West wing Altitude 600 Mt Latitude 30
Estimated by Ghaleb
3 Date July28,2000
Abu Saa'
4 Reference Dimensions Space used for Lb H2O/Lb dry air
5 Unit L W H Area Volume Office Outside Room
Office two
6 Ft 17 22 10 376 3,696 Special conditions 0.01 0.01
7 Mt 5.25 6.65 3.00 34.91 104.74 Temp. not to exceed 74 oF Grains/Lb H2O 6000
8 Summer Cooling Load NOTES
9 Condition Unit DB WB %RH Gr/Lb SUN LIGHT GAIN
10 oF 115 84 29% 126 1 For rooms or zones having more than one exposure, use
Outside
11 oC 46 28.9 29% 126 north values for all exposures except the one having the
12 oF 70 50.0 50 38 largest solar gain. Usually greatest solar area.
Inside Figures shown are based on an average of 17 Hrs
13 oC 21 10.0 50 38 2
operation.
14 oF 45 88 3 Multiply by factor 1.2for very light construction, 0.9 for
Difference very heavy construction & 1.25 for hotels to allow for
15 oC 25 88
pull-down & individual rooms preference on outside air
16 Outside Air/Fresh
Tota air data temperature.
17 Variable Qty l Air changes % to A/C TRANSMISSION GAIN
18 Persons 2 CF per Hr CFM 1 Ceiling type one is under finished room
M Ceiling type two is un-insulated frame or heavy masonary with
19 CFM/Person 15 30 0.49 4.05% 2 ceiling
20 Room heat load 3 Ceiling type three is un-insulated frame or heavey
21 Sensible heat load masonery without ceiling
Ceiling type four is un-insulated light masonary with
22 Sun light gain BTUH 1,824 4
ceiling
Ceiling type five is un-insulated light masonary without
23 Sourse Sq FtFactor BTUH W1 5
ceiling
24 Glass N 0 23 0 ### 6 Ceiling type six is insulated all kinds with ceiling
25 Glass E 0 80 0 7 Ceiling type seven is insulated all kinds without ceiling
26 Glass S 0 68 0 8 Floor type one is over finished floor
27 Glass W 19.4 94 1823.6 W3 215 215 W4 9 Floor type two is over basement with finished ceiling
28 Glass NE 0 66 0 10 Floor type three is on ground.
29 Glass SE 0 70 0 W3 Safety Factors
30 Glass SW 0 81 0 W2 Glass SAFETY FACTOR "A" 5%
31 Glass NW 0 74 0 ### 19.4 Re-heat supply duct heat gain 5%
32 Transmission heat gain BTUH 10,357 1 Supply duct leakage loss 2%
33 type Sq Ft u To-Ti BTU/Hr Fan factor 3%
34 Sunlit walls 150 0.3 45 2,026 Safety factor used 5%
35 Shaded wall 0 0.2 0 0 SAFETY FACTOR "B" 2%
36 Partition 169 0.2 45 1,525 2 Supply duct leakage loss 2%
37 Ceiling type one 0 0.24 0 0 Safety factor used 2%
38 Ceiling type two 0 1.07 0 0 SAFETY FACTOR "C" 0%
39 Ceiling type three 0 1.2 0 0 Return duct heat gain 2%
40 Ceiling type four 0 1.6 0 0 Return duct leakage gain 3%
3
41 Ceiling type five 0 1.7 0 0 Pump Hp 2%
42 Ceiling type six 376 0.2 45 3,380 Dehumidufication & piping loss 3%
43 Ceiling type seven 0 0.9 0 0 Safety factor used 0%
44 Floor type one 376 0.24 38 3,425 Latent heat load
45 Floor type two 0 0.2 0 0 Sourse No. Factor BTU/Hr
46 Floor type three 0 0 0 0 people seated at rest 0 150 0
People seated, very light
47 Internal heat gain BTUH 1,663 2 155 310
work
48 Sourse No. Factor BTU/Hr People moderately active 0 250 0
Standing light
49 people seated at rest 0 180 0 0 300 0
work/walking
Sedentary slowly
& light bench
50 People seated, very light work 2 193 386 0 330 0
work.
51 People moderately active 0 200 0 Moderate & heavy work. 0 980 0
Standing light work/walking
52 0 200 0 Steam rate in Lb/Hr 0 1000 0
slowly
53 Sedentary & light bench work. 0 220 0 Room latent heat sub total 310
54 Moderate & heavy work. 0 450 0 Safety factor "B" 1.02%
55 Motors in KW 0 3412 0 Room latent heat 316
56 Lights in Watt 376 3.4 1,277 Outside air heat load
A B C D E F G H I J K L M N O P Q R S
57 Room sensible heat sub total 13,843 Sensible heat CFM Delta "T" Factor BTU/Hr
58 Safety factor "A" 1.05% 30 45.0 1.08 1,458
59 Room sensible heat 14,535 Latent CFM "Gr/Lb" Factor BTU/Hr
60 Grand total sensible heat 15,993 30 88 0.67 1,769
61 Room total heat load BTUH 18,078 Safety factor "C" 1.00%
62 Q = mCpDelta"T" Tons 1.51 Out side air total sensible heat load 1,458
63 (1.2*2.2/35)*60*0.24*Delta "T" KW 5.30 Out side air total latent heat load 1,769
64 1.08 Kcal/Hr 4,535 Grand total latent heat 2,085
Assume delta "t" (temperature difference between room temperature & air off coil dry bulb
65 oF 20
temperature to be :-
66 Room supply air C.F.M. = room sensible heat divided over (1.08*delta "t") = 740