Professional Documents
Culture Documents
26 March 2011
Prepared By:
ACKNOWLEDGEMENT
We are thankful to the management of the XYZ Pvt. Ltd for giving us this opportunity to contribute
in their endeavor for Better Power Quality at Electrical System. We thank XYZ Pvt. Ltd team
When receive power compensation (in the form of passive power factor
improving capacitors) is used with non-linear loads, resonance condition can
occur that may result in even higher levels of harmonic voltage and current
distortion, thereby causing equipment failure, disruption of power services, and
fire hazards in extreme conditions.
The electrical environment has absorbed most of these problems in the past.
However, the problem has now reached a magnitude where Europe, the US, and
other countries have proposed standards to responsible engineer system
considering the electrical environment. IEEE 519-1992 and IEC 555 have
evolved to become a common requirement cited when specifying equipment on
newly engineered projects. The broad band harmonic filter was designed in
part, to meet this specification. The present IEEE 519-1992 document
establishes acceptable levels of harmonics (voltage and current) that can be
introduced into the incoming feeders by commercial and industrial users. Where
there may have been little cooperation previously from manufacturing to meet
such specification, the adoption of IEEE 519-1992 and other similar world
standards now attract the attention of everyone.
• Harmonic Overheating:
• Generation of harmonics:
Harmonic protection filters are used for improvement of power factor and part
elimination of harmonics. They are nothing but a combination of reactors and
capacitors, suitably detuned. They are useful when distortion is 15 to 40 %.
This system can be configured to operate in fully automatic mode. The object is
to eliminate high level of harmonic current to acceptable level to comply with
utility regulation. They provide traps for individual harmonics frequency and
provide reactive power compensation at fundamental frequency.
0.800
0.600
0.400
0.200
0.000
-0.200
-0.400
700.0
650.0
600.0
550.0
500.0
450.0
A
400.0
350.0
300.0
250.0
200.0
150.0
100.0
3/17/2011 23:54:40 (h:min:s) 3/18/2011
10:25:40.000 AM 4 h/Div 10:20:20.000 AM
70.00
65.00
60.00
55.00
50.00
45.00
40.00
%
35.00
30.00
25.00
20.00
15.00
10.00
5.000
Total Harmonics Distortion: ‘R’ Phase: 14.2 %, ‘B’ Phase: 13.8% & ‘Y’ Phase: 16%
Total Harmonics Distortion: ‘R’ Phase: 6.9 %, ‘B’ Phase: 7.5% & ‘Y’ Phase: 8.8%
Limit as per
Current THD
IEEE Actual iTHD Remark
per Phase
standard
Note: All above reading were undertaken at PCC panels with APFC panel switched On *
OFF.
Findings:
Recommendation: