Professional Documents
Culture Documents
The behavior of offset mechanical splices is investigated in the not permitted for bars larger than No. 11 (ACI Committee
context of currently-prescribed acceptance test methods and 318 2005) and are often impractical, regardless of the bar
criteria. Two commercially available offset mechanical splice size, in many applications. Alternatives to lap splices include
systems were tested in direct tension with the splice both restrained welded connections or mechanical connections.
and unrestrained from rotating. In this series of tests, the
commonly held belief that the critical case is where the splice is Mechanical connections are divided into two categories
not restrained from rotating is shown to be incorrect. The splices based on the expected mechanical loading applied to the
are additionally tested in air under prescribed fatigue loading splice (ACI Committee 439 2007). Type 1 splices are used
conditions. Finally, the splices are tested in place in 4.7 m (15 ft when there is no expectation of inelastic deformation or
5 in.) long concrete beams under both monotonic and fatigue elevated tensile stress due to seismic loading. Type 2 splices
loading conditions and their behavior is assessed. Significant findings are those that have been demonstrated through accepted
include a classification of splice failure modes and characterization of testing procedures to be able to develop the specified tensile
in-place splice behavior. strength of the spliced reinforcing bars for resistance to
increased tensile forces that may be expected from seismic
Keywords: acceptance test; reinforcement bar; splice. loading. The use of Type 2 mechanical splices is referred to
only in the seismic provisions of ACI 318-05 (ACI
INTRODUCTION Committee 318 2005), whereas Type 1 mechanical splices
The behavior of offset mechanical splices is investigated are addressed in the body of the Code. Proposed revisions of
in the context of currently-prescribed acceptance test ACI 439.3R (ACI Committee 439 2007) recommend the use
methods and criteria. Two commercially available offset of Type 2 mechanical splices over conventional lap splices
mechanical splice systems were tested in direct tension with where inelastic yielding may be experienced. This recommen-
the splice both restrained and unrestrained from rotating. In dation is based on the observation that lap splices typically do
this series of tests, the commonly held belief that the critical not perform well under inelastic yielding conditions.
case is where the splice is not restrained from rotating is There are many situations that require the use of mechanical
shown to be incorrect. The splices are additionally tested in splices over the use of conventional lap splices. Mechanical
air under prescribed fatigue loading conditions. Finally, the splices are an attractive alternative for providing continuity
splices are tested in place in 4.7 m (15 ft 5 in.) long concrete and anchorage to hoop or continuous spiral reinforcement
beams under both monotonic and fatigue loading conditions used to provide confinement in columns. Other applications
and their behavior is assessed. Significant findings include a include relieving congestion and reducing the reinforcement
classification of splice failure modes and characterization of ratio in splice regions and in splicing new reinforcing steel to
in-place splice behavior. existing steel in patches, closure pours, and structural additions.
Current codes do not permit No. 14 or No. 18 bars to be
RESEARCH SIGNIFICANCE spliced using a lap splice, requiring mechanical splices for
The objective of this work was to assess the applicability these bar sizes. Other uses of mechanical splices are in
of performance criteria by which mechanical splices are portions of a structure affected by seismic loads as recom-
assessed in the context of available offset mechanical splice mended by revisions to ACI 439.3R (ACI Committee 439
systems. It will be shown that conventional wisdom associated 2007). Finally, in the case of epoxy-coated or lower tensile
with testing offset splices is apparently incorrect. The splice strength reinforcing bars, mechanical splices may represent
system performance was also evaluated both in terms of a practical alternative to the relatively long lap splices
acceptance-type tests and in-place applications. Significant required in these cases.
findings include a classification of splice failure modes and There are many types of mechanical splicing products
characterization of in-place splice behavior. The present available. In this discussion, they have been categorized as
work is believed to be the only recent study of its kind. 1) in-line splices, in which the centerline of each spliced bar
coincides; and 2) offset splices (also referred to as an offset
REINFORCEMENT BAR SPLICES mechanical splice or a mechanical lap splice), where the
Reinforcement bars are most often spliced in place using centerlines have an eccentricity.
lap splices. Lap splices place two bars adjacent to each other
over a sufficient length to affect full development of both
bars through stress transferred through the surrounding ACI Structural Journal, V. 105, No. 4, July-August 2008.
MS No. S-2007-058 received February 7, 2007, and reviewed under Institute publication
concrete. The typical required length for a tension lap splice policies. Copyright © 2008, American Concrete Institute. All rights reserved, including the
is on the order of 50 to 70 times the diameter of the bars making of copies unless permission is obtained from the copyright proprietors. Pertinent
discussion including author’s closure, if any, will be published in the May-June 2009
being spliced (ACI Committee 318 2005). Lap splices are ACI Structural Journal if the discussion is received by January 1, 2009.
FAILURE MODES
For consistency in reporting, four failure modes were identi-
fied and denoted A through D, as shown in Fig. 4. These
failure modes were only recorded in the DT and RT tests.
Failure Mode A was a rupture of the reinforcing bar at a signif-
icant distance from, and apparently unaffected by, the splice,
similar to a straight bar test. Failure Mode B was a rupture of
the reinforcing bar at the wedge or first bolt; this failure
resulted from the stress raiser induced by the wedge or bolt.
Failure Mode C was a rupture of the reinforcing bar
located just outside of splice caused by the kinking of the bar
at this location. Failure Mode D did not result in a ruptured
bar but rather the bar slipping through the splice a distance
greater than one rib spacing. This failure mode resulted in a
gouge on the spliced bar resulting from the bolts or wedge as Fig. 4—Failure modes of offset mechanical splices tested in
shown in Fig. 4. In the experimental program, Failure Mode D direct or restrained tension.
DT Slip at 200 MPa, mm Average 0.060 0.096 0.112 0.046 0.026 0.050
Criteria II: Standard deviation 58% 58% 78% 133% 60% 40%
Slip < 0.25 mm
Samples passing 5/5 5/5 5/5 5/5 5/5 4/5
Observed failure modes
B/C/D 0/5/0 2/2/1 1/4/0 0/5/0 2/3/0 2/3/0
(number of specimens)
Ultimate stress fu ,exp, MPa Average 670.2 650.2 628.1 537.1 625.4 510.9
Criteria I and III: Standard deviation 5% 2% 3% 11% 10% 3%
fu > 1.25fy = 518 MPa 0.9fu: 1/5 0.9fu: 0/5
fu > 0.90fu = 559 MPa Samples passing 5/5 5/5 5/5 1.25fy: 3/5
6/6
1.25fy: 2/5
RT
Average 0.026 0.040 0.030 0.010 0.020 0.036
Slip at 200 MPa, mm
Criteria II: Standard deviation 60% 88% 150% 50% 50% 43%
Slip < 0.25 mm
Samples passing 5/5 5/5 5/5 5/5 6/6 5/5
Observed failure modes A/D 0/5 0/5 0/5 0/5 1/4 0/5
Average 0.406 0.812 1.220 0.508 1.016 2.286
Slip following 10,000 cycles, mm
F Criteria IV: Standard deviation 63% 69% 121% 90% 100% 40%
Slip < 1.25 mm
Samples passing 5/5 4/5 4/5 5/5 3/5 1/5
Notes: Bold entries indicate average value did not pass criteria. 1 MPa = 145 psi; 1 mm = 0.0394 in.
Specimens L and LF
Specimens L and LF performed similarly with little difference
in stiffness due to the fatigue conditioning. This series had a
Fig. 8—Longitudinal cracking of beam soffits due to coupler
lower stiffness than the other specimens and a peak load of rotation.
only 16.7 kN (3750 lb).
The apparent degradation of behavior of the L specimens Specimens A and AF
as compared with the C specimens may be attributed to the Specimen A performed well initially, reaching a peak load
softer expected response of the lap splice as compared with of 15.6 kN (3510 lb). Upon reloading following holding at
the continuous bar. In a conventional lap splice, relative slip this peak (to record cracking), however, the specimen never
of the bars, in addition to steel strain, contribute to the regained its previous capacity, achieving a capacity of only
measured elongation across the splice. The slip initiates 14.2 kN (3190 lb) before the load began to decrease as the
immediately and increases until the bond stress is exhausted deflection continued to increase, indicating a failure of the
at which point the lap splice can carry no additional load and specimen. Following testing, the splice was recovered and
eventually fails, shedding its load carrying capacity. The cyclic inspected. The splice exhibited clear signs of slip: one bar
loading response of lap splices was observed to be significantly slipped approximately 13 mm (0.5 in.) through the splice.
inferior to the monotonic loading response. The bond stresses Specimen AF showed little sign of degradation resulting
developed in lap splices subject to cyclic loading histories were from fatigue conditioning and achieved a higher load than
the monotonic test, reaching an ultimate load of 17.8 kN
observed to deteriorate more rapidly than bond stresses under
(4000 lb) at a deflection of 133 mm (5.24 in.).
monotonic loading (Viwathanatepa et al. 1979). Additionally,
In Specimens A and AF, the concrete was unable to properly
there is a general consensus (Viwathanatepa et al. 1979; Lukose
confine the splice and there was cracking evident on the soffit of
et al. 1982; and MacKay et al. 1988) that for cyclic loading the specimen caused by the rotation of the splice or slip of
conditions, the effects of confinement reinforcement are the bars through the splice. This cracking demonstrated a
insignificant, although recent work by Harajli (2007) particular problem with offset splices: the cracking of the
contradicts this. For the tests conducted in this study, no cover concrete may have caused particular problems in
transverse confinement was provided and thus the deterioration structural elements exposed to the environment, and especially
due to cycling (or rather the beneficial effects of confinement deicing salts. This cracking is shown on Specimen A in
under monotonic conditions) was not evident. Fig. 8(a) at a load of 15.6 kN (3510 lb).
QUALITATIVE OBSERVATIONS
All mechanical splices were installed at the University of
Pittsburgh’s structural research laboratory following the
manufacturer’s guidelines and specifications. As noted, the
Type B product requires the use of a proprietary hydraulic
wedge driver and the Type A product can be installed using
a hand-held ratchet or torque wrench. The Type A product
presents more options if there are clearance issues when
installing; for example, a simple ratchet could be used to
install the splice. The wedge driver requires time-consuming
adjustments to the driver tool to splice different size bars,
whereas the Type A product simply adds to the number of
screws that need to be tightened—the screw head size
remains constant.
A concern with both of the mechanical splices considered
herein are the dimensions of the product. The Type B splice
is much smaller and encroaches less on the amount of cover
present when the splice is embedded in concrete. Nonetheless,
little difference in concrete behavior was evident.
RECOMMENDATIONS
There is a limited body of knowledge on the testing and
use of offset mechanical splices. There needs to be further
work conducted in this area before the use of these splices
can be widely accepted. Some recommendations resulting
from this study are:
1. Offset mechanical splices are not recommended for use
with bar sizes greater than No. 5 unless they can be shown to
Fig. 9—Soffit of each specimen following testing. satisfy the performance criteria;