You are on page 1of 10

ACI STRUCTURAL JOURNAL TECHNICAL PAPER

Title no. 105-S46

Experimental Study of Offset Mechanical


Lap Splice Behavior
by Keith L. Coogler, Kent A. Harries, and Marcella Gallick

The behavior of offset mechanical splices is investigated in the not permitted for bars larger than No. 11 (ACI Committee
context of currently-prescribed acceptance test methods and 318 2005) and are often impractical, regardless of the bar
criteria. Two commercially available offset mechanical splice size, in many applications. Alternatives to lap splices include
systems were tested in direct tension with the splice both restrained welded connections or mechanical connections.
and unrestrained from rotating. In this series of tests, the
commonly held belief that the critical case is where the splice is Mechanical connections are divided into two categories
not restrained from rotating is shown to be incorrect. The splices based on the expected mechanical loading applied to the
are additionally tested in air under prescribed fatigue loading splice (ACI Committee 439 2007). Type 1 splices are used
conditions. Finally, the splices are tested in place in 4.7 m (15 ft when there is no expectation of inelastic deformation or
5 in.) long concrete beams under both monotonic and fatigue elevated tensile stress due to seismic loading. Type 2 splices
loading conditions and their behavior is assessed. Significant findings are those that have been demonstrated through accepted
include a classification of splice failure modes and characterization of testing procedures to be able to develop the specified tensile
in-place splice behavior. strength of the spliced reinforcing bars for resistance to
increased tensile forces that may be expected from seismic
Keywords: acceptance test; reinforcement bar; splice. loading. The use of Type 2 mechanical splices is referred to
only in the seismic provisions of ACI 318-05 (ACI
INTRODUCTION Committee 318 2005), whereas Type 1 mechanical splices
The behavior of offset mechanical splices is investigated are addressed in the body of the Code. Proposed revisions of
in the context of currently-prescribed acceptance test ACI 439.3R (ACI Committee 439 2007) recommend the use
methods and criteria. Two commercially available offset of Type 2 mechanical splices over conventional lap splices
mechanical splice systems were tested in direct tension with where inelastic yielding may be experienced. This recommen-
the splice both restrained and unrestrained from rotating. In dation is based on the observation that lap splices typically do
this series of tests, the commonly held belief that the critical not perform well under inelastic yielding conditions.
case is where the splice is not restrained from rotating is There are many situations that require the use of mechanical
shown to be incorrect. The splices are additionally tested in splices over the use of conventional lap splices. Mechanical
air under prescribed fatigue loading conditions. Finally, the splices are an attractive alternative for providing continuity
splices are tested in place in 4.7 m (15 ft 5 in.) long concrete and anchorage to hoop or continuous spiral reinforcement
beams under both monotonic and fatigue loading conditions used to provide confinement in columns. Other applications
and their behavior is assessed. Significant findings include a include relieving congestion and reducing the reinforcement
classification of splice failure modes and characterization of ratio in splice regions and in splicing new reinforcing steel to
in-place splice behavior. existing steel in patches, closure pours, and structural additions.
Current codes do not permit No. 14 or No. 18 bars to be
RESEARCH SIGNIFICANCE spliced using a lap splice, requiring mechanical splices for
The objective of this work was to assess the applicability these bar sizes. Other uses of mechanical splices are in
of performance criteria by which mechanical splices are portions of a structure affected by seismic loads as recom-
assessed in the context of available offset mechanical splice mended by revisions to ACI 439.3R (ACI Committee 439
systems. It will be shown that conventional wisdom associated 2007). Finally, in the case of epoxy-coated or lower tensile
with testing offset splices is apparently incorrect. The splice strength reinforcing bars, mechanical splices may represent
system performance was also evaluated both in terms of a practical alternative to the relatively long lap splices
acceptance-type tests and in-place applications. Significant required in these cases.
findings include a classification of splice failure modes and There are many types of mechanical splicing products
characterization of in-place splice behavior. The present available. In this discussion, they have been categorized as
work is believed to be the only recent study of its kind. 1) in-line splices, in which the centerline of each spliced bar
coincides; and 2) offset splices (also referred to as an offset
REINFORCEMENT BAR SPLICES mechanical splice or a mechanical lap splice), where the
Reinforcement bars are most often spliced in place using centerlines have an eccentricity.
lap splices. Lap splices place two bars adjacent to each other
over a sufficient length to affect full development of both
bars through stress transferred through the surrounding ACI Structural Journal, V. 105, No. 4, July-August 2008.
MS No. S-2007-058 received February 7, 2007, and reviewed under Institute publication
concrete. The typical required length for a tension lap splice policies. Copyright © 2008, American Concrete Institute. All rights reserved, including the
is on the order of 50 to 70 times the diameter of the bars making of copies unless permission is obtained from the copyright proprietors. Pertinent
discussion including author’s closure, if any, will be published in the May-June 2009
being spliced (ACI Committee 318 2005). Lap splices are ACI Structural Journal if the discussion is received by January 1, 2009.

478 ACI Structural Journal/July-August 2008


2005) is a new standard addressing testing of mechanical
Keith L. Coogler is a Structural Engineer at Westinghouse Electric Company,
Monroeville, PA. He received his MSCE from the University of Pittsburgh, Pittsburgh, splices. ASTM A1034 (ASTM International 2005) provides
PA, in 2006. only general testing methodologies and does not provide
specific parameters (such as the load at which to measure
Kent A. Harries, FACI, is the William Kepler Whiteford Faculty Fellow and an Assistant
Professor of structural engineering and mechanics at the University of Pittsburgh. He slip or the stresses appropriate for cyclic testing) and does
received his PhD from McGill University, Montreal, QC, Canada, in 1995. He is not quantify any testing acceptance criteria. ASTM A1034
a member of ACI Committees 215, Fatigue of Concrete; 335, Composite and (ASTM International 2005) includes an additional parameter—
Hybrid Structures; 408, Bond and Development of Reinforcement; 439, Steel
Reinforcement; 440, Fiber Reinforced Polymer Reinforcement; and E803, Faculty low temperature testing—where any of the standard tests are
Network Coordinating Committee. additionally conducted at a reduced ambient temperature
Marcella Gallick is the Principal of Rhea Engineers and Consultants, Inc., Gibsonia
(not specified).
PA. She received her MSCE from the University of Pittsburgh. Before the ASTM A1034 (ASTM International 2005) spec-
ification was released in late 2004, the CT670 (Caltrans 2004)
Test Method was the only specification to specifically address
MECHANICAL LAP SPLICE PRODUCTS
Currently, there are two mechanical lap-splicing products the testing of mechanical splices. The CT670 (Caltrans 2004)
available: test methods are outlined in Table 1 along with the acceptance
1. Product A, shown in Fig. 1(a), is a sleeve that allows criteria typically associated with each test. Manufacturers of
two bars to be placed side by side. Allowing a length of bar offset mechanical lap splice Types A and B report having
of at least one bar diameter to protrude from each end, the conducted direct tension testing of their product in the manner
hardened, pointed set screws are tightened through the top of directed by CT670 (Caltrans 2004). Both products are
the sleeve securing the bars in place. The connection is a approved for use by Caltrans for Type 1 splices only.
combination of mechanical (screws penetrating into reinforcing Direct tension testing of offset spliced bar systems results
bar) and friction (far side of bar bearing against sleeve). in a moment being generated at the mechanical splice
When tightened to an appropriate torque, the screw head will resulting from the eccentricity of the bars. This moment will
shear off, indicating uniform tightening of all screws. This place complex stresses on the coupler and result in the
splice is designed to carry tension and compressive forces reinforcing steel kinking at or near the coupler face as the
but is currently only recommended for tension use. A unique applied tension loads try to align. This effect is shown
aspect of this system is that it may be used to splice bars of schematically in Fig. 2.
different sizes provided the bars are only one standard size
removed (No. 3/No. 4, No. 4/No. 5, No.5/No. 6, and No. 6/ REVIEW OF PREVIOUS STUDIES
No. 7); and The body of work addressing mechanical lap splices is
2. Product B, shown in Fig. 1(b), is an oval-shaped sleeve very limited with the only published work conducted by
with a wedge-shaped pin inserted into it. The reinforcing
bars to be spliced are positioned inside the sleeve and the
wedge is inserted using a proprietary hydraulic pin driver.
The wedge drives the bars against the outer walls of the
sleeve affecting a friction connection to hold the bars in
place. Additionally, the hardened wedge deforms the bar as
it is driven resulting in a further mechanical connection. This
splice is currently only recommended for tension use.
The splicing sleeve, in each case, is sized according to the
bar size to be spliced. The physical size of the body of both
mechanical lap splice types result in reduced concrete cover.
In the case of Product A, the clear cover to the splice is 20 mm
(0.79 in.) less than that to the spliced bar. The smaller
Product B results in a 6 to 9 mm (0.24 to 0.35 in.) reduction
in clear cover to the spliced bar.
Fig. 1—Offset mechanical reinforcing bar splice systems.
PERFORMANCE SPECIFICATIONS
The performance of mechanical splice systems is evaluated
with different testing procedures and requirements varying
by specifying agency. Typical requirements are listed in
Table 1. Some jurisdictions have other related requirements;
for example, Oregon requires a completed mechanical splice
to achieve a tensile capacity of 1.35fy rather than the typical
1.25fy required by others. It is noted that California Test
CT670 (Caltrans 2004) is a test method and does not specifically
recommend acceptance criteria. The performance criteria
associated with CT670 (Caltrans 2004) are those applied by
Caltrans.

Test methods for mechanical splices


Assessing the performance of mechanical bar splices is
difficult and only recently has there been a uniform specification
governing these tests. ASTM A1034 (ASTM International Fig. 2—Effects of direct tension loading on mechanical splice.

ACI Structural Journal/July-August 2008 479


Paulson and Hanson (1989 and 1991). Paulson and Hanson tension tests conducted on a No. 5 Type B splice. The ultimate
(1989) provided a summary and review of fatigue data of stress values observed are reported as 438 and 614 MPa (63.5
welded and mechanically spliced reinforcing bars. This and 89 ksi). The reinforcing bar fracture of the first specimen
survey of existing research focused solely on fatigue data. It occurred inside the splice at the wedge, the second specimen
was noted that, at the time, there was no specification that fractured just outside the splice. The first specimen did not
contained provisions for the evaluation of fatigue of reinforcing achieve an ultimate capacity of 1.25fy, failing Criteria I of
bar splices. Comparisons were made with AASHTO LRFD Table 1. The authors state that due to the offset of the spliced
(2004) design specifications for fatigue of straight unspliced reinforcing bars, axial open air tension tests may not reflect the
bars. Paulson and Hanson (1991) showed that mechanically behavior of the splice embedded in concrete.
spliced reinforcing bars may have a shorter fatigue life, Open air fatigue tests were only conducted on in-line
although the fatigue life varies greatly based on the type of spliced bars. Fatigue tests of Type B offset splices were
splice considered. Nonetheless, Paulson and Hanson performed on bars embedded in concrete beams. The beams
(1991) concluded that for the splice systems tested, a fatigue were 2133 mm (84 in.) long, 152 mm (6 in.) wide, and 203 mm
fracture would occur in the bar near the spliced region, not in (8 in.) deep with a nominal effective depth d of 152 mm
the splice itself. Thus, the splicing hardware was sufficiently (6 in.). Each beam had a single No. 5 bar as the primary flexural
strong although it affected the spliced bars in a manner reinforcement and each specimen was tested in third-point
flexure. There was heavy shear reinforcement located in the
affecting fatigue resistance.
shear span but none in the constant moment region where the
Paulson and Hanson (1991) report an extensive study of the splice was located. The beams also included crack formers to
fatigue behavior of welded and mechanical splices. This study induce flexural cracking at each end of the coupler. Five of
tested mechanical lap splices using in-place beam tests and the nine reported fatigue-induced reinforcing bar ruptures
open air axial tension tests. The authors report two open air initiated at the junction of the splice wedge and the bar; the
remaining four occurred immediately outside the splice.
Table 1—Mechanical reinforcing bar splice Stress versus number of cycles to failure (S-N) behavior of
performance criteria the specimens having spliced bars was notably degraded as
Standard compared with the bare bars tested in direct tension fatigue
1 2 3 4 5 Criteria Descriptor Performance (Paulson and Hanson 1991).
Criteria I: tensile strength of Paulson and Hanson (1991) attempted to establish limits for
• • • • •* > 1.25fy
mechanical coupler design stress ranges appropriate for different classes of
Criteria II: allowable slip resulting splices. The AASHTO (2004) specified limit for the fatigue
from applied stress of 0.50fy then 0.25 mm
• • • <
(0.01 in.) stress range on straight reinforcing bars for service loads was
relaxed to 0.05fy
138 MPa (20 ksi). The authors classified mechanical connec-
Criteria III: tensile strength of 0.90fu tions into three categories assigning maximum allowable
• >
mechanical coupler
stress ranges of 28, 83, and 124 MPa (4, 12, and 18 ksi) as indi-
Criteria IV: allowable slip resulting cated in Table 2. All coupling methods were assumed to
1.25 mm
• from +172 MPa to –172 MPa <
(0.05 in.) reduce the fatigue limit of the reinforcing bars to some degree.
(±25 ksi) for 10,000 cycles
Criteria V: allowable slip resulting Based on the limited testing, Type B offset mechanical
from cycling between 0.90fy and 1.25 mm couplers were assigned the same category as swaged and
• <
(0.05 in.)
0.05fy for 100 cycles threaded in-line couplers, having a maximum allowable
*
Tensile strength of mechanical coupler > 1.20fy . fatigue stress range of 83 MPa (12 ksi). Couplers in this group
Notes: Standards cited: ACI 318-05 (ACI Committee 318 2005), AASHTO LRFD are characterized as causing a reduction in area of the spliced
(2004), AASHTO ASD (1996), CT 670 (Caltrans 2004), and CSA S6-00 (CSA
International 2000). bar as results from machining threads, swaging the bar or
installing the wedge. The results obtained by Paulson and
Table 2—Splice categories according to Paulson Hanson (1991), although limited, point to a significant
and Hanson (1991) difference in behavior between offset mechanical couplers
tested in air and those tested in place in concrete beams.
Maximum 28 MPa 83 MPa 124 MPa 138 MPa
stress level (4 ksi) (12 ksi) (18 ksi) (20 ksi)
Cold swaged steel coupling Grout- and
EXPERIMENTAL PROGRAM
All Straight The two commercially-available offset mechanical splice
Splice type welded sleeves; taper- and straight- steel-filled
threaded steel couplers; steel cou- coupling bar (no systems, previously designated Types A and B, were evaluated
splices splice)
pling sleeve with wedge (Type B) sleeves
in four series of tests. In each series (except the beam tests),
at least five samples of each bar size (No. 4, No. 5, and
Table 3—Reinforcing bar material properties No. 6) were tested. The performance of each specimen
Nominal was evaluated in accordance with Criteria I-IV given in
value* No. 4 No. 5 No. 6 Table 1. The experimentally determined material properties
414 MPa 448 MPa 414 MPa 414 MPa for the reinforcing steel used in all tests in this study are
Yield strength fy
(60 ksi) (65 ksi) (60 ksi) (60 ksi) listed in Table 3. The tests conducted on each splice system
Yield strain εy 0.002 0.003 0.003 0.0035 are shown schematically in Fig. 3 and described as follows.
Tensile strength fu 621 MPa 717 MPa 690 MPa 662 MPa
(90 ksi) (104 ksi) (100 ksi) (96 ksi) Direct tension
Elongation at rupture 11%† 19%‡ 19%‡ 23%‡ Direct tension (DT) tested the reinforcement bar splice in
*AASHTO M31 (1996).
open-air direct tension and allowed the splice to freely rotate

Elongation calculated over 203 mm (8 in.). (Fig. 2). Each specimen was instrumented to record the slip

Elongation calculated over 76 mm (3 in.). component over the spliced region. The specimens were

480 ACI Structural Journal/July-August 2008


loaded monotonically at a rate of approximately 900 N/second was allowed to progress until the resulting slip exceeded
(200 lb/second) until rupture of the bar occurred or the 25 mm (1 in.).
recorded slip exceeded 25.4 mm (1 in.).
Slip measurements
Restrained tension To assess bar slip Criteria II and IV (Table 1) in this test
Restrained tension (RT) tested the reinforcement bar splice program, the slip was measured using displacement transducers
in a manner similar to a pullout test that inhibited the splice installed on the unloaded projection of the spliced bar (as shown
from rotating. In these tests, only one spliced bar was subject in Fig. 3). In this manner, the recorded displacement
to tension with the reaction being provided by the coupler included only the slip component over the spliced region and
itself. The uniform reaction between the coupler and loading did not include elastic or inelastic deformation in the bar.
plate effectively restrained the tendency of the coupler to The total slip for an individual specimen was the sum of the
rotate. To ensure that the coupler was correctly engaged, a slip of each bar. In this work, the slip reported in subsequent
dummy bar was provided to mimic the bar engaged in the sections and in Table 4 is calculated as twice the maximum
untested side of the splice. Each of the specimens was loaded single bar slip observed in each specimen. This case is an
monotonically to failure similar to the DT tests and the slip of upper bound, where both bars experience the same
the loaded bar through the splice was measured. maximum slip. Reporting in this manner also permits direct
comparison between the DT and F tests and the RT tests.
Fatigue tests
Fatigue (F) tests were modeled after the CT670 (Caltrans RESULTS OF TENSION TESTS
2004) test method, which requires cycling the specimen A summary of the results of DT, RT, and F tests is
through a 345 MPa (50 ksi) stress range. The minimum provided in Table 4. In this table, average values associated
required fatigue life of 10,000 cycles could not be attained
under the specified test stress range for these specimen types.
The stress range was reduced to 138 MPa (20 ksi) and the
load was cycled from 69 MPa (10 ksi) compression to 69 MPa
(10 ksi) tension for 10,000 cycles. The test setup was the
same as the DT tests and thus the splice was free to rotate, as
shown schematically in Fig. 2. Slip through the splice was
recorded following cycling.

Flexural beam tests


Flexural beam (B) tests were conducted with the reinforcement
bar splice embedded in concrete. Eight reinforced concrete
beams were cast for this testing phase. Each specimen was
254 mm (10 in.) deep, 305 mm (12 in.) wide, and 4743 mm
(187 in.) long. Each beam had a single No. 4 reinforcement
bar as the primary flexural reinforcement. All beams
(monotonic and fatigue) were loaded in four-point flexure
over a 4540 mm (179 in.) simple span. The reinforcing bar
splice was located in the center of the constant moment
region. One beam of each pair was tested monotonically to
failure. The second beam of each pair was subjected to
10,000 cycles of repeated loading intended to result in an
applied stress range in the No. 4 flexural reinforcement bar
of 138 MPa (20 ksi), similar to the FT tests. Companion tests Fig. 3—Schematic illustrations and photographs of test setups
of unspliced straight bars and conventional lapped bar splices used. (Note: 1 mm = 0.039 in.)
were included in this series as described in the following.

FAILURE MODES
For consistency in reporting, four failure modes were identi-
fied and denoted A through D, as shown in Fig. 4. These
failure modes were only recorded in the DT and RT tests.
Failure Mode A was a rupture of the reinforcing bar at a signif-
icant distance from, and apparently unaffected by, the splice,
similar to a straight bar test. Failure Mode B was a rupture of
the reinforcing bar at the wedge or first bolt; this failure
resulted from the stress raiser induced by the wedge or bolt.
Failure Mode C was a rupture of the reinforcing bar
located just outside of splice caused by the kinking of the bar
at this location. Failure Mode D did not result in a ruptured
bar but rather the bar slipping through the splice a distance
greater than one rib spacing. This failure mode resulted in a
gouge on the spliced bar resulting from the bolts or wedge as Fig. 4—Failure modes of offset mechanical splices tested in
shown in Fig. 4. In the experimental program, Failure Mode D direct or restrained tension.

ACI Structural Journal/July-August 2008 481


with the splice assessment Criteria I through IV (Table 1) are DT behavior—Representative stress-versus-bar-strain
presented. Additionally, the number of tests passing the results for the DT tests with No. 4 bars are shown in Fig. 5(a).
criteria and the failure modes are indicated. The strains were recorded from electrical resistance strain
gauges mounted approximately 50 mm (2 in.) from the splice
location. The stress-strain relationship had an initial linear
elastic portion, which is predictable and repeatable at low
stress ranges. At an applied stress of 138 to 207 MPa (20 to
30 ksi) for each specimen, there tends to be softening of the
system indicated by a decrease in the slope of the
stress-strain curve. This apparent change in stiffness is
caused by the rotation of the splice—the system sustains
increasing loads but the reinforcing bar is no longer only in
axial tension. Similarly, stress-versus-slip relationships
(Fig. 5(b)) are also predictable and repeatable. The
stress-slip relationship is generally linear until yield of the
reinforcing bar, near 414 MPa (60 ksi). Following yield, the
slip begins to increase greatly, often to more than 6 mm
(0.24 in.) before eventual bar rupture.
As indicated in Table 4, although all but one specimen
passed both Criteria I and II, the capacity of the splices (as
measured by bar stress developed) is diminished as the bar
size increases. The Type A splices exhibited superior
capacity, satisfactory slip values, and significantly lower
variance as compared with Type B splices. Failure Mode C
was dominant and resulted from the kinking of the bar and
the eventual bearing of the kinked bar against the mechanical
splice. This was more pronounced in smaller bar sizes
because the flexural stiffness of the bar (and thus resistance
to kinking) is reduced.
RT behavior—There is an apparent consensus among
manufacturers and users of mechanical splices that due to the
kinking of the bar, the results of DT tests are conservative;
that is, if a splice passes a DT test, it will perform better in
place where rotation may be restrained (Coogler et al. 2006).
The RT series of tests was formulated to test this hypothesis.
Fig. 5—Representative results for direct tension tests of As indicated in the results presented in Table 4, the capacity
No. 4 bars. (Note: 1 MPa = 145 psi; 1 mm = 0.039 in.) measured using an RT test is lower than a comparable DT

Table 4—Average performance of offset mechanical splice systems tested in air


Splice Type A Splice Type B
Test Performance criteria No. 4 No. 5 No. 6 No. 4 No. 5 No. 6
Ultimate stress fu ,exp, MPa Average 704.7 681.2 641.2 669.5 622.6 602.6
Criteria I and II: Standard deviation 0.5% 2% 1% 6% 5% 5%
fu > 1.25fy = 518 MPa
fu > 0.90fu = 559 MPa Samples passing 5/5 5/5 5/5 5/5 5/5 5/5

DT Slip at 200 MPa, mm Average 0.060 0.096 0.112 0.046 0.026 0.050
Criteria II: Standard deviation 58% 58% 78% 133% 60% 40%
Slip < 0.25 mm
Samples passing 5/5 5/5 5/5 5/5 5/5 4/5
Observed failure modes
B/C/D 0/5/0 2/2/1 1/4/0 0/5/0 2/3/0 2/3/0
(number of specimens)
Ultimate stress fu ,exp, MPa Average 670.2 650.2 628.1 537.1 625.4 510.9
Criteria I and III: Standard deviation 5% 2% 3% 11% 10% 3%
fu > 1.25fy = 518 MPa 0.9fu: 1/5 0.9fu: 0/5
fu > 0.90fu = 559 MPa Samples passing 5/5 5/5 5/5 1.25fy: 3/5
6/6
1.25fy: 2/5
RT
Average 0.026 0.040 0.030 0.010 0.020 0.036
Slip at 200 MPa, mm
Criteria II: Standard deviation 60% 88% 150% 50% 50% 43%
Slip < 0.25 mm
Samples passing 5/5 5/5 5/5 5/5 6/6 5/5
Observed failure modes A/D 0/5 0/5 0/5 0/5 1/4 0/5
Average 0.406 0.812 1.220 0.508 1.016 2.286
Slip following 10,000 cycles, mm
F Criteria IV: Standard deviation 63% 69% 121% 90% 100% 40%
Slip < 1.25 mm
Samples passing 5/5 4/5 4/5 5/5 3/5 1/5
Notes: Bold entries indicate average value did not pass criteria. 1 MPa = 145 psi; 1 mm = 0.0394 in.

482 ACI Structural Journal/July-August 2008


test. The increased DT test capacity is attributed to the (10 ksi) in compression to 69 MPa (10 ksi) in tension. This
kinked bar bearing against the splice and engaging additional stress range: a) permitted 10,000 cycles to be achieved while
friction forces not present in the RT test. Slip values maintaining a through-zero fatigue protocol felt to be critical
reported in the RT tests are reduced and the variance of in assessing the behavior of the splices considered; b) exceeds
both capacity and slip values are similar to that found in the AASHTO-permitted stress range for mechanical couplers;
the DT tests. The failure mode for the RT tests is almost exclu- c) is equal to the AASHTO-permitted stress range for unspliced
sively Mode D, which is a behavior dominated by the reinforcing bars (and thus provides a point of comparison);
nature of the mechanical connection. and d) results in a similar stress range as that considered for the
Representative stress-versus-slip results for the RT tests flexural beam (B) tests reported in the following.
with No. 4 bars are shown in Fig. 6. The stress-slip relationship Similar to the DT and RT tests, an increase in bar size resulted
is predictable and repeatable. The stress-slip relationship is in a decrease in performance. For the Type A specimens, only
generally linear until yield of the reinforcing bar (414 MPa two specimens exhibiting a larger-than-allowable slip. The
[60 ksi]). Following yield, the slip begins to increase greatly, Type B specimens performed generally less well, exhibiting
often to more than 38 mm (1.5 in.). In each of the tests, the more scatter with great variability in the results; six Type B
specimen reaches an ultimate stress, the load begins to specimens experienced slip values greater than allowable.
decrease as the reinforcing bar begins to be pulled through
the splice, indicating a Failure Mode D. After a given Flexural beam (B) tests
displacement, the load increases and then decreases again. To assess the in-place performance of offset mechanical
This effect was more pronounced for the Type B specimens splices, the splices of No. 4 bars were embedded in concrete
but was evident in nearly all of the RT tests. It was determined beams and the beams were tested in two ways: 1) under
that the reinforcing bar ribs contributed to this apparent monotonically increasing load to failure; and 2) subject to
increase in load-carrying capacity: as the bar slipped, the bolt fatigue-conditioning followed by a monotonically increasing
or wedge engaged subsequent reinforcing bar ribs, increasing load to failure. The behavior of the splice was assessed and
the pullout force. This conclusion is confirmed by the Type B compared with the behavior of a straight unspliced No. 4 bar
results where the spacing, in terms of slip measurements, of and a standard 305 mm (12 in.) long lap splice.
the load increases corresponded to the bar rib spacing. Such Eight reinforced concrete beams were cast for this test
behavior was less evident in the Type A splice as the multiple program. Each specimen was 254 mm (10 in.) deep, 305 mm
bolts gouged into the bar as the bar slipped (Fig. 4). (12 in.) wide, and was simply supported over a 4540 mm
Similar to the DT tests, an increase in bar size resulted in a (179 in.) span as shown in Fig. 3(d). Each beam had a single
decrease in performance in the performance Criteria I and III No. 4 reinforcing bar as the primary flexural reinforcement
(Table 1) for the Type A splice specimens as shown in Table and two No. 3 bars in the compression zone. The beams were
4. The Type B specimens did not follow this trend and cast in pairs, two specimens each having: a) straight,
performed marginally overall with respect to Criteria I and III. unspliced bar (designated: C); b) standard 305 mm (12 in.)
The RT test setup used considered only pullout from one side long conventional lapped bar splices (L) (compliant with
of the splice. While not reflecting in-place conditions, this setup ACI 318-05 [ACI Committee 318 2005] and AASHTO
overcame the need for large restraining forces and resulted in [2004] ; c) Type A mechanical splices (A); and d) Type B
accurate pullout capacities not affected by the kinking of the bar mechanical splices (B). One beam of each pair was tested
or the binding of the bar along the edge of the splice thought to monotonically to failure (designated as indicated previously:
affect the DT tests. Thus, for the purposes of product evaluation, C, L, A, and B). The second beam of each pair was subject
it is felt that this simple test is appropriate. to 10,000 cycles of repeated loading intended to result in an
F test protocol and behavior—Performance Criteria IV applied stress range in the No. 4 bar of 138 MPa (20 ksi) as
(Table 1) requires cycling through a stress ranging from measured in the first cycle of load, N = 1. The latter specimens
172 MPa (25 ksi) in compression to 172 MPa (25 ksi) in are referred to as fatigue conditioned and are designated with a
tension, a 345 MPa (50 ksi) stress range S for 10,000 cycles (N = trailing F (that is, CF, LF, AF, and BF). Following fatigue
10,000). Due to the stress raisers induced by the mechanical conditioning, the specimens were loaded monotonically to
splices, the bolts, wedges, and the bar kinking at the coupler failure. The same No. 4 reinforcing steel used for open air
face, this stress range was unachievable if 10,000 cycles of
loading were required. Initial tests conducted at this stress
range resulted in fatigue-induced reinforcing bar rupture
occurring at between 70 and 320 cycles for No. 4 and No. 5
specimens of both splice Type A and B (Coogler et al. 2006).
Commonly accepted S-N relationships for straight,
unspliced reinforcing steel (Helgason and Hanson 1974)
predict a fatigue life of approximately N = 100,000 cycles
corresponding to a stress range of 345 MPa (50 ksi). It is
expected that mechanically-spliced bars having inherent stress
raisers should have significantly reduced fatigue lives, espe-
cially at higher stress ranges. A number of variations in the
fatigue setup were attempted, including varying bar lengths
and stress ranges. Ultimately, the bar lengths had to be much
shorter than DT and RT tests to avoid buckling failures and the
additional stresses induced by buckling. Additionally, the
stress range had to be reduced. The stress range selected for Fig. 6—Restrained tension stress-slip results for No. 4 bars.
fatigue testing was 138 MPa (20 ksi), ranging from 69 MPa (Note: 1 MPa = 145 psi; 1 mm = 0.039 in.)

ACI Structural Journal/July-August 2008 483


tests was used in this test series. The 28-day concrete under each load point (Fig. 3(d)). The hydraulic actuator was
compressive strength was 41.6 MPa (6030 psi) and all beams equipped with an internal load cell.
were tested at ages from 86 to 121 days.
All beams were loaded in four-point flexure with a 910 mm Flexural beam test results
(36 in.) constant moment region located in the center of a The load-versus-displacement results of each beam are
4540 mm (179 in.) simple span. The reinforcing bar splice shown in Fig. 7. The behavior of the load-deflection plots
was located in the center of the constant moment region. The show the ductility of each under-reinforced beam and indicate
setup is shown in Fig. 3(d). Fatigue conditioning was applied evidence of slip in the splicing methods or rotation of the
to the F beams in load control with the total applied load splice within the concrete as described further in the
(actuator load) ranging from 3.6 to 9.8 kN (800 to 2200 lb) following. The jagged behavior of these plots reflect the
in a sinusoidal waveform having a frequency of 1.0 Hz. The relaxation that occurred when the loads were held to assess
load range was selected based on the measured reinforcing cracking behavior. The displacement limitations of the
bar strains from the monotonic test series. The 3.6 kN (800 lb) testing frame prevented testing of the specimens to their
lower limit was selected to represent an applied dead load; the ultimate load-carrying capacity; thus, ultimate load cannot
9.8 kN (2200 lb) upper limit was selected to develop the be a basis of comparison between the different specimens.
desired strain and, therefore, stress levels in the No. 4 rein- Therefore, applied load resulting in a specified deflection is
forcing bar and across the splice. The target stress level was used as a means of comparison. To compare the stiffness for
138 MPa (20 ksi), corresponding to the F tests described each specimen, the load and strain were recorded at specified
previously. All data were reported in terms of total actuator displacements and are presented in Table 5.
applied load P. Thus, the resulting moment in the constant In Column 1 of Table 5, it is evident there was little
moment region was 0.91P (kN-m) (2.98P [lb-ft]). Similarly, the degradation of load-carrying behavior caused by the
maximum shear in the beam was 0.5P (kN or lb). fatigue conditioning of each specimen type. Additionally,
The monotonic tests and final cycle to failure for the the control series (C and CF) exhibited the stiffest behavior,
fatigue tests were conducted in displacement control at a rate whereas the lap splice (L and LF) was the least stiff of all
of 7.3 mm/minute (0.29 in./minute). Due to the stroke limitations specimens. There was little difference in stiffness between
of the actuator and the ductility of the under-reinforced beams, the A (and AF) and B (and BF) specimens, although both
additional spacers were required to test the beam specimens were marginally less stiff than the control beams having a
to failure. In each monotonic test, the beams were loaded to continuous reinforcing bar. The behavior described indicates
a deflection of 75 mm (3 in.), unloaded, and the resulting a marginal reduction in capacity associated with each splice,
permanent deflection was made up with spacer plates which may be attributed to nominal slip or relative movement of
between the actuator and spreader beam. The test was the splice. Column 2 of Table 5 presents the strain values at
continued to a deflection of approximately 127 mm (5 in.) a displacement of 50.8 mm (2 in.). From these values, it is
where the beam came into contact with the test frame. evident there was some accumulated damage due to fatigue
Although not tested to their ultimate failure, the final deflections conditioning in all cases because the monotonic strain is less
were all on the order of L/32 and thus may be reasonably than the fatigue strain. The very large strains for the LF and
assumed to have exceeded the beams’ ultimate limit states AF specimens are likely caused by the presence of a flexural
demands. This load history described results in the loop at a crack very near the gauge location.
displacement of 75 mm (3 in.) evident in the presented load- Column 3 provides the applied load at a displacement of
deflection plots. During monotonic testing, the displacements 127 mm (5 in.) (near the maximum test setup deflection for
were held constant at specified load intervals to document all specimens). The fatigue conditioned control (CF) and the
cracking and investigate the specimens’ behavior. The tests lap splice specimens (L and LF) performed in a similar
were paused less than 10 minutes in each case and the entire manner as the monotonic control Specimen C. For the Type A
testing time (to failure) was kept under 2 hours. It was determined specimens, the fatigue conditioned specimen (AF) had a
that these pauses did not affect the behavior of the specimen. higher load than the monotonic loaded specimen (A). This
Each beam was instrumented with electrical resistance is explained by the fact that the monotonic Specimen A
strain gauges on the No. 4 flexural reinforcement. Gauges clearly exhibited slip of the splice and began to shed load
were located 305 mm (12 in.) on each side of midspan and as a result (described in detail in the following). The B and
thus fell in the constant moment region. Vertical displacements BF specimens performed similar to the A-series with the
were recorded using draw wire transducers (DWT) located fatigue conditioned specimen achieving higher loads than
the monotonic specimen. Again, marginal slip of the splice
Table 5—Flexural beam test results during the monotonic tests is believed to account for this as
at given displacements discussed in the following. The following discusses the
behavior of each test specimen.
Column 1 2 3
Load at 50.8 mm Strain at 50.8 mm Load at 127 mm
Specimen displacement, kN (lb) displacement, με displacement, kN (lb) Specimens C and CF
C 15.1 (3390) 2217 19.0 (4270)
Specimen C had the highest recorded applied load of the
CF 15.2 (3420) 2262 18.1 (4070)
beam tests, which was a result of this specimen having a
higher post-yield stiffness than the other specimens. The
L 12.8 (2880) 2094 16.3 (3660)
peak load was near 20 kN (4500 lb), although this specimen
LF 13.3 (2990) 9133 16.5 (3710)
was loaded to a deflection closer to 152 mm (6 in.). During
A 15.0 (3370) 1282 11.3 (2540) testing of the other specimens, the tests were stopped at
AF 13.9 (3120) 9015 17.5 (3930) deflections of approximately 140 mm (5.5 in.); the load in
B 13.8 (3100) 1349 14.2 (3190) Specimen C at this deflection value was 19 kN (4270 lb).
BF 14.3 (3210) 2149 17.3 (3890) Specimen CF showed little degradation from the fatigue

484 ACI Structural Journal/July-August 2008


Fig. 7—Beam test load-deflection results. (Note: 1 MPa = 145 psi; 1 mm = 0.039 in.)

conditioning, performing similar to Specimen C throughout


most of the test history. Some degradation in the behavior of
Specimen CF was evident at the end of the test at displacements
exceeding 127 mm (5 in.), although this behavior cannot
necessarily be attributed to the effects of fatigue conditioning.

Specimens L and LF
Specimens L and LF performed similarly with little difference
in stiffness due to the fatigue conditioning. This series had a
Fig. 8—Longitudinal cracking of beam soffits due to coupler
lower stiffness than the other specimens and a peak load of rotation.
only 16.7 kN (3750 lb).
The apparent degradation of behavior of the L specimens Specimens A and AF
as compared with the C specimens may be attributed to the Specimen A performed well initially, reaching a peak load
softer expected response of the lap splice as compared with of 15.6 kN (3510 lb). Upon reloading following holding at
the continuous bar. In a conventional lap splice, relative slip this peak (to record cracking), however, the specimen never
of the bars, in addition to steel strain, contribute to the regained its previous capacity, achieving a capacity of only
measured elongation across the splice. The slip initiates 14.2 kN (3190 lb) before the load began to decrease as the
immediately and increases until the bond stress is exhausted deflection continued to increase, indicating a failure of the
at which point the lap splice can carry no additional load and specimen. Following testing, the splice was recovered and
eventually fails, shedding its load carrying capacity. The cyclic inspected. The splice exhibited clear signs of slip: one bar
loading response of lap splices was observed to be significantly slipped approximately 13 mm (0.5 in.) through the splice.
inferior to the monotonic loading response. The bond stresses Specimen AF showed little sign of degradation resulting
developed in lap splices subject to cyclic loading histories were from fatigue conditioning and achieved a higher load than
the monotonic test, reaching an ultimate load of 17.8 kN
observed to deteriorate more rapidly than bond stresses under
(4000 lb) at a deflection of 133 mm (5.24 in.).
monotonic loading (Viwathanatepa et al. 1979). Additionally,
In Specimens A and AF, the concrete was unable to properly
there is a general consensus (Viwathanatepa et al. 1979; Lukose
confine the splice and there was cracking evident on the soffit of
et al. 1982; and MacKay et al. 1988) that for cyclic loading the specimen caused by the rotation of the splice or slip of
conditions, the effects of confinement reinforcement are the bars through the splice. This cracking demonstrated a
insignificant, although recent work by Harajli (2007) particular problem with offset splices: the cracking of the
contradicts this. For the tests conducted in this study, no cover concrete may have caused particular problems in
transverse confinement was provided and thus the deterioration structural elements exposed to the environment, and especially
due to cycling (or rather the beneficial effects of confinement deicing salts. This cracking is shown on Specimen A in
under monotonic conditions) was not evident. Fig. 8(a) at a load of 15.6 kN (3510 lb).

ACI Structural Journal/July-August 2008 485


Specimens B and BF SUMMARY AND CONCLUSIONS
Specimen B performed in a similar manner as Specimen A. Two commercially available offset mechanical splice
During the initial loading, the specimen had a reasonable systems, designated in this paper as splice Types A and B,
stiffness. At the peak load of the initial loading step, the were evaluated in four series of tests: DT, RT, F, and B tests.
splice began to rotate and the cover concrete began to spall. The performance of each specimen was evaluated in accordance
Figure 8(b) shows the effect of the splice rotation on the with a number of performance criteria indicated in Table 1.
cover concrete. The cracking was first documented at 13.8 kN The following conclusions are drawn from this work:
(3100 lb), and the cracking in Fig. 8(b) is shown at a load of 1. An increase in reinforcement bar diameter from No. 4 to
15.1 kN (3390 lb) at the peak of the initial loading cycle. No. 6 resulted in a decrease in performance for each of
During reloading, the specimen’s performance deteriorated the criteria considered, although most specimens still
and was unable to achieve higher loads as the deflections passed the criteria;
continued to increase. Slip failure similar to that observed in 2. Generally, Type A splices outperformed Type B splices;
Specimen A was suspected. Upon post-test inspection, 3. Contrary to manufacturers’ assumptions, the DT test was
however, there was no noticeable slip, although a great deal not necessarily conservative; the splice capacity determined by
of rotation occurred, which would also result in an increase in the DT test was greater than that determined by the RT test
presumably due to friction between the kinked bar and coupler;
deflection without an increase in load. Similar to Specimens A
and AF, the concrete cover was unable to restrain the 4. Failure Mode C: The rupture of the bar at the stress
raiser associated with contact between the kinked bar and
splice from rotating.
coupler was the most commonly observed failure mode in
DT tests;
Splice-induced damage to concrete 5. Failure Mode D: A pullout failure was the most
Splice-induced damage was only significant following common failure mode observed for the RT tests. This mode
yield of the beams. At service load levels, through all fatigue of failure results in a decrease in apparent ultimate stress for
conditioning, and prior to yield, no splice-induced damage to the system because of the inability to develop the full
the concrete was apparent. As deformations increased into the strength of the cross section;
post-yield region, however, significant damage to the concrete 6. A 345 MPa (50 ksi) stress range for F testing results in
cover was evident. Figure 9 shows images of the beam soffits fatigue-induced reinforcing bar rupture at a very low number
following testing. Figure 9(a) and (b) shows the expected of cycles. A more reasonable stress range of 138 MPa (20 ksi) is
flexure-induced transverse cracking evident for Specimens C suggested for assessing the performance of this type of splice;
and L. No other damage is apparent, including longitudinal 7. There was no noticeable degradation of the in-place
cracking in Specimen L, which may indicate lap splice slip. splice behavior resulting from fatigue conditioning at a stress
The rotation and resulting loss of cover associated with each range of 138 MPa (50 ksi) applied for 10,000 cycles; and
mechanical splice is clearly shown in Fig. 9(c) though (f). 8. For all in-place testing, concrete was unable to properly
confine the offset splice near ultimate load levels.

QUALITATIVE OBSERVATIONS
All mechanical splices were installed at the University of
Pittsburgh’s structural research laboratory following the
manufacturer’s guidelines and specifications. As noted, the
Type B product requires the use of a proprietary hydraulic
wedge driver and the Type A product can be installed using
a hand-held ratchet or torque wrench. The Type A product
presents more options if there are clearance issues when
installing; for example, a simple ratchet could be used to
install the splice. The wedge driver requires time-consuming
adjustments to the driver tool to splice different size bars,
whereas the Type A product simply adds to the number of
screws that need to be tightened—the screw head size
remains constant.
A concern with both of the mechanical splices considered
herein are the dimensions of the product. The Type B splice
is much smaller and encroaches less on the amount of cover
present when the splice is embedded in concrete. Nonetheless,
little difference in concrete behavior was evident.

RECOMMENDATIONS
There is a limited body of knowledge on the testing and
use of offset mechanical splices. There needs to be further
work conducted in this area before the use of these splices
can be widely accepted. Some recommendations resulting
from this study are:
1. Offset mechanical splices are not recommended for use
with bar sizes greater than No. 5 unless they can be shown to
Fig. 9—Soffit of each specimen following testing. satisfy the performance criteria;

486 ACI Structural Journal/July-August 2008


2. Offset mechanical splices should not be used in ACI Committee 439, 2007, “Types of Mechanical Splices for Reinforcing
applications subject to seismic load reversals; Bars (ACI 439.3R-07),” American Concrete Institute, Farmington Hills,
MI, 20 pp.
3. Offset mechanical splices should be included in the second
ASTM A1034-05b, 2005, “Standard Test Methods for Testing
category of mechanical splices (having a fatigue limit of 83 MPa
Mechanical Splices for Steel Reinforcing Bars,” ASTM International,
[12 ksi]) in AASHTO LRFD (2004), Table 5.5.3.4-1; West Conshohocken, PA, 6 pp.
4. When used, offset mechanical splices must be designed Caltrans, 2004, California Test 670 Method of Tests for Mechanical and
to transfer 100% of the expected splice forces. They must not Welded Reinforcing Steel Splices, California Department of Transportation,
be used to augment the capacity of traditional embedment Sacramento, CA, 8 pp.
laps splices; Coogler, K. L.; Harries, K. A.; and Gallick, M., 2006, “Evaluation of
5. The presence of confinement is expected to improve Offset Mechanical Reinforcing Bar Splice Systems,” FHWA Report
behavior of these types of splices; a study of this effect is No. FHWA-PA-2006-033-040110, and University of Pittsburgh Report
required. Modifications may need to be made to current No. CE/ST-35, 91 pp.
codes to address the amount of confinement required to allow the CSA International, 2000, “Canadian Highway Bridge Design Code,”
CAN/CSA-S6-00, Toronto, ON, Canada.
splice to properly function embedded in concrete; and
Harajli, M., 2007, “Cyclic Response of Concrete Members with
6. Coogler et al. (2006) have provided recommended revisions Bond-Damaged Zones Repaired using Concrete Confinement,” Materials
to the Pennsylvania Department of Transportation specifications and Structures, V. 21, pp. 937-951.
and ASTM A1034-05b (ASTM International 2005) to allow Helgason, T., and Hanson, J. M., 1974, “Investigation of Design Factors
the inclusion of offset mechanical splices. Affecting Fatigue Strength of Reinforcing Bars—Statistical Analysis,”
Abeles Symposium on Fatigue of Concrete, SP-41 American Concrete
ACKNOWLEDGMENTS Institute, Farmington Hills, MI, pp. 107-138.
The test program described in this paper was sponsored by the Pennsylvania Lukose, K.; Gergely, P.; and White, R. N., 1982, “Behavior of Reinforced
Department of Transportation through Contract #2006-033-040110. The Concrete Lapped Spliced under Inelastic Cyclic Loading,” ACI JOURNAL,
in-kind support of BarSplice Products Inc. and Erico International Inc. is Proceedings V. 75, No. 5, July-Aug., pp. 355-365.
gratefully acknowledged. The authors wish to acknowledge their discussions MacKay, B.; Schmidt, D.; and Rezansoff, T., 1988, “Effectiveness of
with C. Paulson, Chair of ACI Committee 439, Steel Reinforcement; G. Weldon Concrete Confinement on Lap-Splice Perfomance in Concrete Beams
of Caltrans; and S. Holdsworth of BarSplice. under Reversed Inelastic Loading,” Canadian Journal of Civil Engineering,
V. 16, No. 1, pp. 36-44.
REFERENCES Paulson, C., and Hanson, J. M., 1989, “A Summary and Review of
AASHTO ASD, 1996, “ASD Bridge Design Specifications,” seventeenth Fatigue Data for Mechanical and Welded Splices in Reinforcing Bars,
edition, American Association of State Highway and Transportation Officials, Structural Materials,” Proceedings of the Sessions Related to Structural
Washington, DC. Materials at Structures Congress’89, American Society of Civil Engineers,
AASHTO LFRD, 2004, “Bridge Design Specifications,” third edition, pp. 382-391.
American Association of State Highway and Transportation Officials,
Paulson, C., and Hanson, J. M., 1991, “Fatigue Behavior of Welded and
Washington, DC, 1522 pp.
Mechanical Splices in Reinforcing Steel,” Final Report, Project 10-35,
AASHTO M31, 1996, “Deformed and Plan Billet-Steel Bars for
Concrete Reinforcement, American Association of State Highway and National Cooperative Highway Research Program.
Transportation Officials, Washington, DC, 11 pp. Viwathanatepa, S.; Popov, E. P.; and Bertero, V. V., 1979, “Effects of
ACI Committee 318, 2005, “Building Code Requirements for Structural Generalized Loadings on Bond of Reinforcing Bars Embedded in Confined
Concrete (ACI 318-05) and Commentary (318R-05), American Concrete Concrete Blocks,” UCB/EERC-79/22, Earthquake Engineering Research
Institute, Farmington Hills, MI, 430 pp. Center, University of California-Berkeley, Berkeley, CA, 316 pp.

ACI Structural Journal/July-August 2008 487

You might also like