Dimensionarea circuitelor electrice

Calculul circuitelor de lumina


1.Conductoare
In=Pi/(Uf*cos)

Pimax

1196 [W]

Uf
In

5.47 A
=>

230 [V]

cos
s

0.95

1.5

[mm2]

FY

12

[mm]

IPEY

[mm2]

FY

Ima=17A>5.5A
2.Tubul de protectie
Dn
n=2
=>
Alegerea conductorului neutru
sN=sF

sN
=>
1.5
Sectiunea conductorului de protectie P.E.

[-]

sN=sF

=>

sPE

1.5

sF

1.5

[mm2]

FY

sN

1.5

[mm2]

FY

sPE

1.5

[mm2]

FY

[mm2]

FY

=>

5FY1.5

3. Siguranta fuzibila
IFIn
IFK*Ima
IF1

3.59

=>

LF25/4A

P1

784

IF2

3.58

=>

LF25/4A

P2

782

IF3

4.9

=>

LF25/6A

P3

1071

IF4

5.47

=>

LF25/6A

P4

1196

IF5

5.47

=>

LF25/6A

P5

1196

IF6

5.05

=>

LF25/6A

P6

1104

IF7

4.7

=>

LF25/6A

P7

1028

Ima=17A=>IF<k*Ima
k=1; iluminat fluorescent
Calculul circuitelor de priza
Pi

2000

[W]

Uf

230
0.8
0.8

[V]
[-]
[-]

cos

1.Conductoare
In=Pi/(Uf*cos*)
=>
Ima=

In

13.59

24

13.6 A
sF

2.5

=>

FY

2.Tubul de protectie
Dn
n=3
=>
Alegerea conductorului neutru
sN=sF

sN

=>

16

[mm2]

IPEY

2.5

[mm2]

FY

[mm2]

FY

72

Sectiunea conductorului de protectie P.E.


sN=sF

=>

sPE

2.5

sF

2.5

[mm2]

FY

sN

2.5

[mm2]

FY

sPE

2.5

[mm2]

FY

3. Siguranta fuzibila
IFIn
IFk*Ima

IF

=>

[A]

3
IF1

13.59

=>

LF25/16A

P1

2000

IF2

13.59

=>

LF25/16A

P2

2000

IF3

13.59

=>

LF25/16A

P3

2000

=>

LF25/16A
=>IF<51A

P4

2000

IF4

13.59
A
Ima=17A=>IF<k*Ima

uite PARTER

Putere
[W]
784
782
1071
1196
1196
1104
1028
2000
2000
2000
2000
2000
2000
2000
21161

Repartitia pe faze
L1
L2
L3
[W]
[W]
[W]
784
782
1076
1196
1196
1104
1028
2000
2000
2000
2000
2000
2000
2000
7056
7028
7082

Incapere
P02+P03
P04+P06'
P01+P01'+P05+P05'
P06+P07+P15'
P08+P10
P09+P11
P12+P13+P14+P15
P02+P03+P04
P07+P08
P09+P10
P11+P13+P14

cos
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.8
0.8
0.8
0.8
0.8
0.8
0.8

In
[A]
3.59
3.58
4.9
5.47
5.47
5.05
4.7
13.59
13.59
13.59
13.59
13.59
13.59
13.59

IF
[A]
4
4
6
6
6
6
6
16
16
16
16
16
16
16

Fuzibil
LF25/4A
LF25/4A
LF25/6A
LF25/6A
LF25/6A
LF25/6A
LF25/6A
LF25/16A
LF25/16A
LF25/16A
LF25/16A
LF25/16A
LF25/16A
LF25/16A

k
1
1
1
1
1
1
1
0.8
0.8
0.8
0.8
0.8
0.8
0.8

Ima*k>IF Ima
[A]
[A]
17
17
17
17
17
17
17
17
17
17
17
17
17
17
19.2
24
19.2
24
19.2
24
19.2
24
19.2
24
19.2
24
19.2
24

Conductor
2 x FY 1,5
2 x FY 1,5
2 x FY 1,5
2 x FY 1,5
2 x FY 1,5
2 x FY 1,5
2 x FY 1,5
3 x FY 2,5
3 x FY 2,5
3 x FY 2,5
3 x FY 2,5
3 x FY 2,5
3 x FY 2,5
3 x FY 2,5

Tub
Coductor Conductor de
protectie neutru
protectie
IPEY 12 FY1,5
IPEY 12 FY1,5
IPEY 12 FY1,5
IPEY 12 FY1,5
IPEY 12 FY1,5
IPEY 12 FY1,5
IPEY 12 FY1,5
IPEY16
FY2,5
FY2,5
IPEY16
FY2,5
FY2,5
IPEY16
FY2,5
FY2,5
IPEY16
FY2,5
FY2,5
IPEY16
FY2,5
FY2,5
IPEY16
FY2,5
FY2,5
IPEY16
FY2,5
FY2,5

Tip CIL

Nr. CIL

Nr.tuburi Putere/tubPutere reala CIL


[W]
[W]
FIRA-03-236 DP,SP
CIL1
2
36
92
72
FIRA-03-218 LC DP;SP CIL2
2
18
56
36
FIRA-03-118 DP
CIL3
1
18
28
18
FIA-11-136
CIL4
1
36
46
36
FIA-11-218
CIL5
2
18
56
36
FIDA-12-236 P
CIL6
2
36
92
72
FIA-11-236
CIL7
2
36
92
72
FIPA-04-136
CIL8
1
36
46
36
FIRA-11-158
CIL9
1
58
73
58
FIA-11-236
CIL10
2
36
92
72
CORP BAI
CIL11
1
18
28
18

Dimensionarea circuitelor electrice

Calculul circuitelor de lumina


1.Conductoare
In=Pi/(Uf*cos)

Pimax
Uf

In

5.47 A

230 [V]

cos

=>

1196 [W]
0.95

[-]

1.5

[mm2]

FY

12

[mm]

IPEY

Ima=17A>5.5A
2.Tubul de protectie
Dn
n=2
=>
Alegerea conductorului neutru
sN=sF

sN
=>
1.5
[mm2]
Sectiunea conductorului de protectie P.E.
sN=sF

=>

sPE

1.5

sF

1.5

[mm2]

FY

sN

1.5

[mm2]

FY

sPE

1.5

[mm2]

FY

FY

[mm2]

FY

=>

5FY1.5

3. Siguranta fuzibila
IFIn
IFK*Ima
IF1

4.69

=>

LF25/6A

P1

1024

[W]

IF2

2.95

=>

LF25/4A

P2

644

[W]

IF3

4.49

=>

LF25/6A

P3

981

[W]

IF4

3.58

=>

LF25/4A

P4

782

[W]

IF5

5.47

=>

LF25/6A

P5

1196

[W]

IF6

5.05

=>

LF25/6A

P6

1104

[W]

IF7

3.43

=>

LF25/4A

P7

750

[W]

IF8

2.95

=>

LF25/4A

P8

644

[W]

IF9

2.62

=>

LF25/4A

P9

572

[W]

Ima=17A=>IF<k*Ima
k=1; iluminat fluorescent

Circuite SUBSOL

Circuit
C1
C2
C3
C4
C5
C6
C7
C8
C9

LL/LP
16
LL
9
LL
27
LL
15
LL
13
LL
12
LL
15
LL
7
LL
14
LL
REZ
TOTAL

Putere
[W]
1024
644
981
782
1196
1104
750
644
572
1175
8872

L1
[W]
1034

Repartitia pe faze
L2
L3
[W]
[W]

Incapere

644
981
782
1196
1104
750
644
572
1175
2959

2959

2964

S01+S02
S03+S04
S05+S06
S07+S08
S09+S10
S11+S12
S13+S14+S15
S16+S17
S18+S19

Tip CIL

Nr. CIL

FIRA-03-236 DP,SP
FIRA-03-218 LC DP;SP
FIRA-03-118 DP
FIA-11-136
FIA-11-218
FIDA-12-236 P
FIA-11-236
FIPA-04-136
FIRA-11-158
FIA-11-236
CORP BAI

CIL1
CIL2
CIL3
CIL4
CIL5
CIL6
CIL7
CIL8
CIL9
CIL10
CIL11

Nr.tuburi

Putere/tub Putere reala CIL


[W]
[W]
2
36
92
2
18
56
1
18
28
1
36
46
2
18
56
2
36
92
2
36
92
1
36
46
1
58
73
2
36
92
1
18
28

72
36
18
36
36
72
72
36
58
72
18

Calcul de verificare
n
h
lL
Mf
l

2
3.0
1.306
0.7
3350

[lampi]
[m]
[m]
[m]
[lm]
1
OY

(Ie)CDIL

lL

l1

l2

e1

e2

Ep

[m]

[m]

[]

[cd]

[cd]

[-]

[m]

[m]

[m]

[]

[]

[-]

[-]

[lx]

a0

0.00

265

1775.5

396.5

1.306

0.6530

0.6530

0.214

0.214

0.162

0.162

128.17156

b0

0.50

265

1775.5

396.5

1.306

0.1530

1.1530

0.051

0.367

0.039

0.269

121.99786

c0

1.00

265

1775.5

396.5

1.306

-0.3470

1.6530

-0.115

0.504

-0.088

0.355

105.81043

d0

1.50

265

1775.5

396.5

1.306

-0.8470

2.1530

-0.275

0.622

-0.205

0.420

84.94045

e0

2.00

265

1775.5

396.5

1.306

-1.3470

2.6530

-0.422

0.724

-0.305

0.467

64.46589

f0

2.50

265

1775.5

396.5

1.306

-1.8470

3.1530

-0.552

0.810

-0.382

0.501

47.26421

g0

3.00

265

1775.5

396.5

1.306

-2.3470

3.6530

-0.664

0.883

-0.440

0.526

34.08354

h0

3.50

265

1775.5

396.5

1.306

-2.8470

4.1530

-0.759

0.945

-0.482

0.544

24.49267

i0

265

1775.5

396.5

1.306

-3.3470

4.6530

-0.840

0.998

-0.512

0.556

17.68816

Punct OX (a)

4.00

j0

4.50

265

1775.5

396.5

1.306

-3.8470

5.1530

-0.908

1.044

-0.533

0.566

12.90158

a1

0.50

0.00

286.0000

1916.2

416.4

1.306

0.6530

0.6530

0.211

0.211

0.160

0.160

132.86636

b1

0.50

0.50

286.0000

1916.2

416.4

1.306

0.1530

1.1530

0.050

0.362

0.038

0.266

126.61686

c1

0.50

1.00

286.0000

1916.2

416.4

1.306

-0.3470

1.6530

-0.114

0.498

-0.087

0.351

110.18236

d1

0.50

1.50

286.0000

1916.2

416.4

1.306

-0.8470

2.1530

-0.272

0.616

-0.203

0.416

88.87775

e1

0.50

2.00

286.0000

1916.2

416.4

1.306

-1.3470

2.6530

-0.417

0.717

-0.301

0.464

67.82674

f1

0.50

2.50

286.0000

1916.2

416.4

1.306

-1.8470

3.1530

-0.546

0.803

-0.379

0.499

50.00175

g1

0.50

3.00

286.0000

1916.2

416.4

1.306

-2.3470

3.6530

-0.657

0.877

-0.437

0.524

36.23878

h1

0.50

3.50

286.0000

1916.2

416.4

1.306

-2.8470

4.1530

-0.752

0.939

-0.479

0.542

26.15479

i1

0.50

4.00

286.0000

1916.2

416.4

1.306

-3.3470

4.6530

-0.833

0.992

-0.510

0.555

18.95765

j1

0.50

4.50

286.0000

1916.2

416.4

1.306

-3.8470

5.1530

-0.902

1.038

-0.532

0.565

13.86944

a2

1.00

0.00

18

313.000

2097.1

421.5

1.306

0.6530

0.6530

0.204

0.204

0.154

0.154

129.64593

b2

1.00

0.50

18

313.000

2097.1

421.5

1.306

0.1530

1.1530

0.048

0.350

0.037

0.257

123.94941

c2

1.00

1.00

18

313.000

2097.1

421.5

1.306

-0.3470

1.6530

-0.109

0.482

-0.083

0.342

108.84705

d2

1.00

1.50

18

313.000

2097.1

421.5

1.306

-0.8470

2.1530

-0.262

0.598

-0.196

0.407

88.97227

e2

1.00

2.00

18

313.000

2097.1

421.5

1.306

-1.3470

2.6530

-0.403

0.698

-0.292

0.456

68.94190

f2

1.00

2.50

18

313.000

2097.1

421.5

1.306

-1.8470

3.1530

-0.529

0.784

-0.369

0.492

51.60787

g2

1.00

3.00

18

313.000

2097.1

421.5

1.306

-2.3470

3.6530

-0.638

0.857

-0.428

0.518

37.93453

h2

1.00

3.50

18

313.000

2097.1

421.5

1.306

-2.8470

4.1530

-0.733

0.920

-0.471

0.537

27.71872

i2

1.00

4.00

18

313.000

2097.1

421.5

1.306

-3.3470

4.6530

-0.814

0.974

-0.503

0.551

20.30258

j2

1.00

4.50

18

313.000

2097.1

421.5

1.306

-3.8470

5.1530

-0.883

1.020

-0.526

0.561

14.98361

a3

1.50

0.00

27

314.0000

2103.8

375.9

1.306

0.6530

0.6530

0.192

0.192

0.145

0.145

109.32694

b3

1.50

0.50

27

314.0000

2103.8

375.9

1.306

0.1530

1.1530

0.046

0.331

0.035

0.244

104.99830

c3

1.50

1.00

27

314.0000

2103.8

375.9

1.306

-0.3470

1.6530

-0.103

0.458

-0.079

0.327

93.38951

d3

1.50

1.50

27

314.0000

2103.8

375.9

1.306

-0.8470

2.1530

-0.247

0.571

-0.186

0.393

77.78173

e3

1.50

2.00

27

314.0000

2103.8

375.9

1.306

-1.3470

2.6530

-0.382

0.669

-0.279

0.442

61.60079

f3

1.50

2.50

27

314.0000

2103.8

375.9

1.306

-1.8470

3.1530

-0.503

0.755

-0.354

0.480

47.15071

g3

1.50

3.00

27

314.0000

2103.8

375.9

1.306

-2.3470

3.6530

-0.611

0.828

-0.414

0.508

35.38931

h3

1.50

3.50

27

314.0000

2103.8

375.9

1.306

-2.8470

4.1530

-0.704

0.891

-0.458

0.528

26.34307

i3

1.50

4.00

27

314.0000

2103.8

375.9

1.306

-3.3470

4.6530

-0.784

0.946

-0.492

0.544

19.60532

j3

1.50

4.50

27

314.0000

2103.8

375.9

1.306

-3.8470

5.1530

-0.854

0.994

-0.516

0.556

14.66532

a4

2.00

0.00

34

293.0000

1963.1

303.5

1.306

b4

2.00

0.50

34

293.0000

1963.1

303.5

c4

2.00

1.00

34

293.0000

1963.1

303.5

d4

2.00

1.50

34

293.0000

1963.1

e4

2.00

2.00

34

293.0000

f4

2.00

2.50

34

g4

2.00

3.00

h4

2.00

i4

2.00

j4

0.6530

0.6530

0.179

0.179

0.136

0.136

82.39468

1.306

0.1530

1.306

-0.3470

1.1530

0.042

1.6530

-0.096

0.310

0.032

0.230

79.52921

0.430

-0.073

0.310

303.5

1.306

-0.8470

2.1530

71.74435

-0.231

0.538

-0.174

0.375

1963.1

303.5

1.306

-1.3470

61.02214

2.6530

-0.358

0.634

-0.262

0.426

293.0000

1963.1

303.5

1.306

49.54342

-1.8470

3.1530

-0.473

0.719

-0.337

0.465

34

293.0000

1963.1

303.5

38.91456

1.306

-2.3470

3.6530

-0.577

0.792

-0.396

0.495

29.93957

3.50

34

4.00

34

293.0000

1963.1

293.0000

1963.1

303.5

1.306

-2.8470

4.1530

-0.668

0.856

-0.442

0.517

22.79260

303.5

1.306

-3.3470

4.6530

-0.748

0.912

-0.477

0.534

2.00

4.50

34

293.0000

17.30032

1963.1

303.5

1.306

-3.8470

5.1530

-0.818

0.960

-0.504

0.547

a5

2.50

0.00

40

13.16190

235.0000

1574.5

207.5

1.306

0.6530

0.6530

0.166

0.166

0.126

0.126

b5

2.50

0.50

52.17520

40

235.0000

1574.5

207.5

1.306

0.1530

1.1530

0.039

0.287

0.030

0.214

c5

2.50

50.60613

1.00

40

235.0000

1574.5

207.5

1.306

-0.3470

1.6530

-0.089

0.400

-0.068

0.291

d5

46.28827

e5

2.50

1.50

40

235.0000

1574.5

207.5

1.306

-0.8470

2.1530

-0.214

0.504

-0.161

0.355

40.19668

2.50

2.00

40

235.0000

1574.5

207.5

1.306

-1.3470

2.6530

-0.332

0.597

-0.245

0.406

33.46148

f5

2.50

2.50

40

235.0000

1574.5

207.5

1.306

-1.8470

3.1530

-0.442

0.679

-0.317

0.447

26.99031

g5

2.50

3.00

40

235.0000

1574.5

207.5

1.306

-2.3470

3.6530

-0.541

0.752

-0.376

0.479

21.31327

h5

2.50

3.50

40

235.0000

1574.5

207.5

1.306

-2.8470

4.1530

-0.630

0.816

-0.423

0.504

16.62267

i5

2.50

4.00

40

235.0000

1574.5

207.5

1.306

-3.3470

4.6530

-0.709

0.873

-0.460

0.523

12.89354

j5

2.50

4.50

40

235.0000

1574.5

207.5

1.306

-3.8470

5.1530

-0.778

0.922

-0.489

0.537

9.99725

a6

3.00

0.00

45

180.0000

1206.0

134.7

1.306

0.6530

0.6530

0.153

0.153

0.116

0.116

31.25118

b6

3.00

0.50

45

180.0000

1206.0

134.7

1.306

0.1530

1.1530

0.036

0.265

0.028

0.198

30.44470

c6

3.00

1.00

45

180.0000

1206.0

134.7

1.306

-0.3470

1.6530

-0.082

0.372

-0.062

0.272

28.19909

d6

3.00

1.50

45

180.0000

1206.0

134.7

1.306

-0.8470

2.1530

-0.197

0.470

-0.149

0.334

24.95990

e6

3.00

2.00

45

180.0000

1206.0

134.7

1.306

-1.3470

2.6530

-0.307

0.559

-0.228

0.386

21.26893

f6

3.00

2.50

45

180.0000

1206.0

134.7

1.306

-1.8470

3.1530

-0.411

0.639

-0.297

0.428

17.59631

g6

3.00

3.00

45

180.0000

1206.0

134.7

1.306

-2.3470

3.6530

-0.505

0.711

-0.356

0.461

14.25320

h6

3.00

3.50

45

180.0000

1206.0

134.7

1.306

-2.8470

4.1530

-0.591

0.775

-0.403

0.488

11.38854

i6

3.00

4.00

45

180.0000

1206.0

134.7

1.306

-3.3470

4.6530

-0.668

0.831

-0.442

0.509

9.03165

j6

3.00

4.50

45

180.0000

1206.0

134.7

1.306

-3.8470

5.1530

-0.737

0.882

-0.472

0.526

7.14307

a7

3.50

0.00

49

136.0000

911.2

86.2

1.306

0.6530

0.6530

0.141

0.141

0.107

0.107

18.45129

b7

3.50

0.50

49

136.0000

911.2

86.2

1.306

0.1530

1.1530

0.033

0.245

0.025

0.184

18.04351

c7

3.50

1.00

49

136.0000

911.2

86.2

1.306

-0.3470

1.6530

-0.075

0.344

-0.057

0.253

16.89625

d7

3.50

1.50

49

136.0000

911.2

86.2

1.306

-0.8470

2.1530

-0.182

0.437

-0.138

0.314

15.20858

e7

3.50

2.00

49

136.0000

911.2

86.2

1.306

-1.3470

2.6530

-0.284

0.522

-0.212

0.365

13.23309

f7

3.50

2.50

49

136.0000

911.2

86.2

1.306

-1.8470

3.1530

-0.381

0.600

-0.278

0.408

11.20406

g7

3.50

3.00

49

136.0000

911.2

86.2

1.306

-2.3470

3.6530

-0.471

0.670

-0.335

0.443

9.29307

h7

3.50

3.50

49

136.0000

911.2

86.2

1.306

-2.8470

4.1530

-0.553

0.733

-0.383

0.471

7.59843

i7

3.50

4.00

49

136.0000

911.2

86.2

1.306

-3.3470

4.6530

-0.628

0.790

-0.422

0.494

6.15744

j7

3.50

4.50

49

136.0000

911.2

86.2

1.306

-3.8470

5.1530

-0.695

0.841

-0.455

0.512

4.96681

0
a0
b0
c0
d0
e0
f0
g0
h0
i0
j0

128.17156 132.86636 129.64593 109.32694 82.39468 52.17520 31.25118 18.45129


121.99786 126.61686 123.94941 104.99830 79.52921 50.60613 30.44470 18.04351
105.81043 110.18236 108.84705 93.38951 71.74435 46.28827 28.19909 16.89625
84.94045
88.87775 88.97227 77.78173 61.02214 40.19668 24.95990 15.20858
64.46589
67.82674 68.94190 61.60079 49.54342 33.46148 21.26893 13.23309
47.26421
50.00175 51.60787 47.15071 38.91456 26.99031 17.59631 11.20406
34.08354
36.23878 37.93453 35.38931 29.93957 21.31327 14.25320 9.29307
24.49267
26.15479 27.71872 26.34307 22.79260 16.62267 11.38854 7.59843
17.68816
18.95765 20.30258 19.60532 17.30032 12.89354 9.03165 6.15744
12.90158
13.86944 14.98361 14.66532 13.16190 9.99725 7.14307 4.96681

Column Z
Column Y
Column X
Column
Column
S W Column Z
Column
T V
Column
Column U
Column
Column
V U
Column
WT
Column
Column X
Column S
Column Y
1

9 10

Punct
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39

CIL1
34
44
55
69
82
98
108
110
100
82
33
49
63
77
94
103
121
118
102
90
42
53
68
84
103
112
131
126
108
96
43
57
72
88
106
117
133
128
108

CIL2
111
104
87
70
55
42
32
23
17
12
124
110
100
78
62
47
35
26
19
13
129
114
103
84
66
50
38
29
22
15
135
113
103
85
68
52
39
31
23

CIL3
25
18
13
5
0
0
0
0
0
0
29
21
15
10
0
0
0
0
0
0
37
24
17
7
0
0
0
0
0
0
34
25
18
13
0
0
0
0
0

CIL4
0
0
0
0
9
10
10
10
9
0
0
10
12
14
15
16
16
16
14
13
13
15
18
20
23
24
25
24
22
19
13
21
25
31
36
47
45
45
40

CIL5
10
9
0
0
0
0
0
0
0
0
16
15
14
12
10
0
0
0
0
0
24
22
20
18
15
12
8
0
0
0
45
41
34
27
22
18
14
10
0

CIL6
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
12
0
0
0
0
0
0
0
0
0

Edi [lx]
180
175
155
144
146
150
150
143
126
94
202
205
204
191
181
166
172
160
135
116
245
228
226
213
207
198
202
179
152
142
270
257
252
244
232
234
231
214
171

40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70

98
43
52
74
90
106
118
132
126
108
97
42
55
72
88
106
117
132
117
107
90
37
52
67
85
103
115
126
110
102
83

16
135
112
103
84
68
52
39
31
23
17
127
109
98
80
64
50
38
30
22
16
115
107
87
73
60
45
35
27
21
14

0
34
25
18
13
0
0
0
0
0
0
32
24
18
12
0
0
0
0
0
0
31
23
16
11
0
0
0
0
0
0

32
23
28
36
45
53
61
65
65
58
52
29
36
46
58
69
79
86
88
78
67
34
43
55
70
82
100
109
110
100
80

0
65
62
54
44
33
24
18
14
10
0
87
82
70
57
45
33
24
18
13
8
110
104
86
70
55
45
31
23
16
12

0
15
12
0
0
0
0
0
0
0
0
20
14
10
0
0
0
0
0
0
0
25
18
13
0
0
0
0
0
0
0

146
315
291
285
276
260
255
254
236
199
166
337
320
314
295
284
279
280
253
220
181
352
347
324
309
300
305
301
270
239
189
223.91

Calculul coloanei tabloului secundar


PARTER
1
PiL

0 [W]

In=(Ina +Inr )

PiP

0 [W]

Ina=IaL+IaP

Ina=PiL/(3*U)+PiP/(3*U*p)

IaL

0 [A]

IaP

0 [A]

Ina

=>

[A]

cosL

0.95

0.32

cosP

0.8

0.64

tgL

0.33

tgP

0.75

Inr=IrL+IrP

Inr=IaL*tgL+IaP*P
=>

Inr
In

0 [A]
0 [A]

Ima

31 [A]

IPEY 25

sF

FY

sN

FY

sPE

FY

3.Conditii pentru siguranta fuzibila


IFIn
In

0 [A]

IFmax(IF)TL+2tr
IF=50A

LF63/50A
Ima=34A=>IF<k*Ima
k=3; pt coloane

=>IF<93A

4 Intreruptorul
IniIn=28,56A
Aleg un IP 63 cu Ini=40A>28,56A

SUBSOL
1

PiL

0 [W]

=>

IaL

[A]

PiP

0 [W]

=>

IaP

[A]

In

0 [A]

Ima

18 [A]

IPEY 20
sF

2.5

[mm2]

FY

sN

2.5

[mm2]

FY

sPE

2.5

[mm2]

FY

3.Conditii pentru siguranta fuzibila


IFIn
IFmax(IF)TL+2tr
IF=20A

LFi25/20A

Ima=18A=>IF<k*Ima
k=3; pt coloane

=>IF<54A

4 Intreruptorul
IniIn=13,48A
Aleg un IP 25 cu Ini=18A>13,58A

Ina

[A]

Inr

0.00

[A]

Calculul coloanei tabloului general

Pi [W]
8945
18205
18205
18205
18205
18205
99970

TLS
TLP
TL1
TL2
TL3
TL4
TGL

In [A]

Ia [A]

Ir [A]

13.48
28.56
28.56
28.56
28.56
28.56

12.81
24.77
24.77
24.77
24.77
24.77
136.66

4.21
14.22
14.22
14.22
14.22
14.22
75.31

In=(Ina2+Inr2)
- Ia=cs*Iai
- Ir=cs*Iri

cs = 0.7
=>

Ia = 95.66

[A]

=>
=>

Ir = 52.72
In = 109.23

[A]
[A]

cos=Ia/In

=>

Pa=3*U*In*cos

=>

cos= 0.88
Pa = 66276.58

1 Conductoare
sF

50 [mm2]

sN

50 [mm2]

sPE

50 [mm2]

sPEN

35 [mm2]

Ima

135[A]

3CYY50+CY35

2 Tubul de protectie
sF=50

[mm2]

n=4
3 Siguranta fuzibila
In

109.23 [A]

IFIn
IFmax(IF)TG+2tr

=>

Dn =50[mm]
IPEY50

[W]

IF3*Ima =>IF405A
IF=305A =>

MPR 315/305A

4 Intreruptorul
In= 109.23 [A]
IriIn

Ini=200 [A]
Iri=160 [A]
cos
0.7
[A]
Aleg IP 200 cu Iri=160A>109,23A

5 Reductorul de curent
In=
Inp1.1*In

109.23 [A]

1.1*In= 120.15

[A]

=>

Inp=

125

Aleg CIS 3x125/5A

6 Ampermetru
3(0...125A)

7 Contor de curent alternativ trifazat


Aleg cun CAT 43
Acesta foloseste metoda celor 3 wattmetre

[A]

Calculul de verificare la pierderea de tensiune


pentru instalatia de lumina
Calculul se va efectua pentru circuitul C4 care este si cel mai incarcat si cel mai indepartat
circuit. Se va considera circuitul aflat la ultimul nivel.

U1% + U2% + U3%

U% =

< Uadm%

U3%

U2%

L3

U1%

L2

CB

L1

TGL

TL4

U1% = (2*100*SP*l)/(*U2*s)
U=

230

[V]

s=
=

1.5
54

[mm2]
[m/mm]

U1% =

1.38

U2% =

0.93

U3% =

0.23

U2% = (100*P*l)/(*U2*s)
P=
PTL4 =
l=
U=
Ina=
s=
=
PTL4 =

PTL4
3*U*Ina
28
400

[m]
[V]

24.77
6
54

[A]
[mm2]
[m/mm]

17161.16

[w]

U3% = (100*P*l)/(*U2*s)
P=
PTGL=
l=
U=
Ina=
s=
=
PTGL=
U% = U1% + U2% + U3%

PTGL
3*U*Ina
15
400

[W]
[m]
[V]

95.66
50
54

[A]
[mm2]
[m/mm]

66275.19

[W]

U% =
Uadm%=

2.54
3

%
%

U% < Uadm%

tr

P
1
2
3
4
5
6
7
8
9
10
11
12
13
14

92
782
92
874
92
966
92
1058
46
46
92
138
1196
1196

l
8.1
6.5
4.3
8
4.5
8.5
5.1
3.7
2.8
4.3
3.3
2.1
1.8
0.3
SP*l=
D U1=

P*l
745.2
5083
398.36
6992
414
8211
469.2
3914.6
128.8
198.72
303.6
289.8
2152.8
358.8
###
1.38

[w]
%

Punct Termic

TF1
Pi

Pompa apa rece


Pompa apa calda
Pompa recirculare
Pompa recirculare
Circuit de incalzire
Circuit priza monofazat
Circuit priza trifazat
Circuit siguranta 24V

Statie de hidrofor

2
1
2
1
1
2
1
1
P

1.1 [KW]
1.5 [KW]
2.2 [KW]
4 [KW]
7.5 [KW]
4 [KW]
6 [KW]
0.4 [KW]
34
[KW]

2
2
2
1
1
1
1
P

1.1 [KW]
2.2 [KW]
4 [KW]
7.5 [KW]
4 [KW]
6 [KW]
0.4 [KW]
32.5 [KW]

1
3
1
1
1
1
P

2.2 [KW]
4 [KW]
7.5 [KW]
4 [KW]
6 [KW]
0.4 [KW]
32.1 [KW]

TF2

Pompa apa rece


Pompa apa calda
Pompa recirculare
Pompa recirculare
Circuit priza monofazat
Circuit priza trifazat
Circuit siguranta 24V

Camera de ventilare

TF3

Pompa apa calda


Ventilator
Ventilator
Circuit priza monofazat
Circuit priza trifazat
Circuit siguranta 24V

Caracteristicile motoarelor
Motor

Pi

cos

Kp=Ip/In

Ip/K
K=2.5

1
2
3
4

[kw]
1.1
1.5
2.2
4

[rot/min]
1000
1000
1000
1000

73
75
77
81

0.71
0.72
0.74
0.76

4.5
5.5
5.5
6

5.51
6.73
6.73
7.34

7.5

U=

400

1000

84

0.78

7.34

[V]

Motorul cu pornire directa Pi=1,1KW


1

Curentul nominal
In=Pi/(3*U*cos*)
In

3.06 [A]

Ima

14 [A]

=>sF

1.5

Verificare
JP=IP/sF=KP*In/sF
JP

9.18 [A/mm2]
Jp<Jadm=35A/mm2, pentru conductoare din cupru
2

Tubul de protectie
pt n=4
=>
4FY1,5/IPEY 16

IPEY 16

Contactorul
IncIn
Inc=6 A
(IF)c=20A

Se alege un contactor TCA 6

Releul termic
InRT
Ir=In=

3.06
Is=Ir/(0.67-1)

10 [A]
[A]
=> Is=

3.30

[A]

Is=Ir/0.82
Se alege un releu termic TSA32P (Is=3,3A; Ir=3,06A)

Siguranta fuzibila
IF > In=3,06 [A]

K=2.5

[mm2]

IF IP/K=6,73[A]

=>

IF

5.51

[A]

IF (IF)c=20[A]

=>

IF

20

[A]

IF (IF)RT=16[A]

=>

IF

16

[A]

IF 3*Ima=3*14A

=>

IF

42

[A]

=>

IF=6

[A]

LFi25/6A

Motorul cu pornire directa Pi=1.5KW


1

Curentul nominal
In=Pi/(3*U*cos*)
In =

4.18 [A]

Ima

14 [A]

=>sF

1.5

Verificarea
JP=IP/sF=KP*In/sF
JP

15.32

[A/mm2]
Jp<Jadm=35A/mm2, pentru conductoare din cupru
2

Tubul de protectie
pt n=4
=>
4FY1,5/IPEY 16

IPEY 16

Contactorul
IncIn
Inc=6 A
(IF)c=20A

Se alege un contactor TCA 6


4

Releul termic
InRT
Ir=In
Is=Ir/(0.67-1)

10 [A]
4.18 [A]
=>Is

4.50 [A]

Is=Ir/0.84
Se alege un releu termic TSA 32P(Is=4,5A; Ir=4,18A)
5

Siguranta fuzibila

[mm2]

IF > In=4,18[A]

=>

IF>4,18A; K=2.5

IF IP/K=6.69[A]

=>

IF

6.73

[A]

IF (IF)c=20[A]

=>

IF

20

[A]

IF (IF)RT=20[A]

=>

IF

20

[A]

IF 3*Ima=3*14A

=>

IF

42

[A]

IF=10
=>
LFi25/10A

[A]

Motorul cu pornire directa Pi=2.2KW


1

Curentul nominal
In=Pi/(3*U*cos*)
In

5.57 [A]

Ima

14 [A]

=>sF

1.5

Verificarea
JP=IP/sF=KP*In/sF
JP

20.43 [A/mm2]
Jp<Jadm=35A/mm2, pentru conductoare din cupru
2

Tubul de protectie
pt n=4
=>
4FY1,5/IPEY 16

IPEY 16

Contactorul
IncIn
(In)c=10 A
(IF)c=35 A

Se alege un contactor TCA 10


4

Releul termic
InRT
Ir=In
Is=Ir/(0.67-1)

10 [A]
5.57 [A]
=>

Is

6.00

Is=Ir/0.83
Se alege un releu termic TSA 32P(Is=6A; Ir=5.57A)
5

Siguranta fuzibila

[A]

[mm2]

IF > In=5.02 [A]

=>

IF>5.02A; K=2.5

IF IP/K=7,96 [A]

=>

IF

6.73

[A]

IF (IF)c=35 [A]

=>

IF

35

[A]

IF (IF)RT=20 [A]

=>

IF

20

[A]

IF 3*Ima=3*14 [A]

=>

IF

42

[A]

IF=10
=>
LFi25/10 A

[A]

Motorul cu pornire directa Pi=4KW


1

Curent nominal
In=Pi/(3*U*cos*)
In

9.38 [A]

Ima

14 [A]

=>sF

2.5

[mm2]

Verificarea
JP=IP/sF=KP*In/sF
JP

22.51 [A/mm2]
Jp<Jadm=35A/mm2, pentru conductoare din cupru
2

=>Se mareste sectiunea conductorului la 2.5[mm2]


Tubul de protectie
pt n=4
=>
IPEY 20
4FY2,5/IPEY 20
Contactorul
IncIn
(In)c=10 A

Se alege un contactor TCA 10


4

Releul termic
InRT
Ir=In

16 [A]
9.38

Is=Ir/(0.67-1)

[A]
=>Is

11.00 [A]

Is=Ir/0.78
Se alege un releu termic TSA 32P (Is=11A; Ir=9,38A)
5

Siguranta fuzibila
IF > In=9,38 [A]

=>

IF>9,38A; K=2.5

IF IP/K=22.32 [A]

=>

IF

7.34

[A]

IF (IF)c=35 A

=>

IF

35

[A]

IF (IF)RT=35 [A]

=>

IF

35

[A]

IF 3*Ima=3*14 A

=>

IF

42

[A]

IF=10
=>
LFi25/10A

[A]

Motorul cu pornire stea-triunghi Pi=7.5KW


1

Curent nominal
In=Pi/(3*U*cos*)
In

16.52 [A]

Ima

20 [A]

In'=In/3

=>In'

Ipdir

99.12

IpY=

=>sF1

2.5

[mm2]

=>sPE

2.5

[mm2]

9.54
=>sF2

[A]
1.5

[mm2]

Verificarea
JP=IP/sF2=Ip/(3*sF2)=KP*In/(3*sF2)
JP=6.5*15.07/(3*1.5)

JP
=>
22.03 [A/mm2]
Jp<Jadm=35A/mm2, pentru conductoare din cupru

Tubul de protectie
pt n=4
=>
IPEY 20
3FY1,5+FY2,5/IPEY 20

Contactorul
IncIn/3
(In)C

9.54
Se alege un contactor TCA 10
4

Releul termic
InRT
Ir=In

[A]

32 [A]
16.52 [A]

Ir=In/3
Is=Ir/(0.67-1)

=>Ir

9.54 [A]

Is=Ir/0.78
Se alege un releu termic TSA 32P (Is=20A; Ir=16,52A)

33.04

Siguranta fuzibila
IF > In=16,52 [A]

=>

IF>16.52A; K=2

IF IP/K=16,32 [A]

=>

IF

16.52

[A]

IF (IF)c=35 [A]

=>

IF

35

[A]

IF (IF)RT=63 [A]

=>

IF

35

[A]

IF 3*Ima=3*20 A

=>

IF

60

[A]

IF=20
=>
LFi25/20A

[A]

Dimensionarea circuitelor de priza de joasa tensiune


Pi

400

[W]

Uf

230
0.8
0.8

[V]
[-]
[-]

cos

1.Conductoare
In=Pi/(Uf*cos*)
=>
Ima=

In

2.72

[A]

14

2.72
sF

[A]

=>

1.5

FY

16

[mm2]

IPEY

2.5

[mm2]

FY

2.Tubul de protectie
Dn
n=3
=>
Alegerea conductorului neutru
sN=sF
sN
=>

Sectiunea conductorului de protectie P.E.


sF
2.5
[mm2]
FY
sN

2.5

[mm2]

FY

sPE

2.5

[mm2]

FY

3. Siguranta fuzibila
IF In

IF k*Ima
k

IF

=>

42

[A]

3
IF1

2.72 A
=>
Ima= 34A => IF < k*Ima

P1

LF25/4A
=> IF < 52A

k=3; circuite de prize

Dimensionarea circuitelor de priza monofazata


Pi

4000

[W]

Uf

230
0.8
0.8

[V]
[-]
[-]

cos

1.Conductoare
In=Pi/(Uf*cos*)
=>
Ima=

In =

27.17

34

27,17 A
sF=

=>

A
6

FY

2.Tubul de protectie
Dn
n=3
=>
Alegerea conductorului neutru
sN=sF
sN
=>

25

[mm2]

IPEY

[mm2]

FY

102

Sectiunea conductorului de protectie P.E.


sF
6
[mm2]
FY
sN

[mm2]

FY

sPE

[mm2]

FY

3. Siguranta fuzibila
IF In=27,17
IF k*Ima
k= 3

=>

IF

[A]

400

[W]

IF1

27.17

=>

P1 =

LFi 63/35A

4000

[W]

6000

[W]

Dimensionarea circuitelor de priza tifazata


k
Pi
U
cos

6000
400
0.8
0.8

[W]
[V]
[-]
[-]

1.Conductoare
In=Pi/(3*Uf*cos*)
In

=>
Ima=

20

Ima=

20

13.53

[A]

13,53 [A]
sF

=>

2.5

FY

20

[mm2]

IPEY

2.5

[mm2]

FY

60

2.Tubul de protectie
Dn
n=3
=>
Alegerea conductorului neutru
sN=sF
sN
=>

Sectiunea conductorului de protectie P.E.


sF
2.5
[mm2]
FY
sN

2.5

[mm2]

FY

sPE

2.5

[mm2]

FY

3. Siguranta fuzibila
IF In
IF k*Ima
k
IF1

=>

IF

[A]

3
40.76
A
Ima=49A=>IF<k*Ima
k=3; circuite de prize

=>

LFi63/50A
=> IF < 137A

P1

Calculul coloanei tabloului secundar


Punct termic
Pi [W]
1100
1100
1500
2200
2200
4000
7500
4000
4000
6000
400
34000
400

M1
M2
M3
M4
M5
M6
M7
M8
M9
M10
M11
P
U

TF1
cos
0.71
0.71
0.72
0.74
0.74
0.76
0.78
0.8
0.8
0.8
0.8

In [A]

Ia [A]

Ir [A]

3.06
3.06
4.18
5.57
5.57
9.38
16.52
21.17
21.17
13.53
2.72
105.93

2.17
2.17
3.01
4.12
4.12
7.13
12.89
16.94
16.94
10.82
2.18
82.48

2.15
2.15
2.9
3.75
3.75
6.1
10.34
12.7
12.7
8.12
1.63
66.29

In=(Ina2+Inr2)

Ia=Iai
Ir=Iri

Ia=Pi/(3*U*p)
Ir=IaP*P
=>

Ia

82.48

[A]

=>

Ir

66.29

[A]

=>

In

105.82

[A]

Ima

123

[A]

1 Conductoare
sF

50 [mm2]

sN

50 [mm2]

sPE

35 [mm2]

4FY 50+FY35
2 Tubul de protectie
n=5

=>

3 Siguranta fuzibila
In

105.82 [A]

IF In
IF max(IF)TG+2tr; 25/20A
IF 3*Ima

=> IF 369 A

Dn

63

[mm]

IPEY

IF=125 A =>

MPR 315/125A

4 Intreruptorul
In

105.82 [A]

IriIn

=>

Iri

175

[A]

Ini

350
0.7

[A]

cos
Aleg un IPIII 350 cu Iri=175 A
Statie de hidrofor

M1
M2
M3
M4
M5
M6
M7
M8
M9
M10
P
U
In=(Ina2+Inr2)

Ia=Iai
Ir=Iri

Pi [W]
1100
1100
2200
2200
4000
4000
7500
4000
6000
400
32500
400

TF2
cos
0.71
0.71
0.74
0.74
0.76
0.76
0.78
0.8
0.8
0.8

In [A]

Ia [A]

Ir [A]

3.06
3.06
5.57
5.57
9.38
9.38
16.52
21.17
13.53
2.72
89.96

2.17
2.17
4.12
4.12
7.13
7.13
12.89
16.94
10.82
2.18
69.67

2.15
2.15
3.75
3.75
6.1
6.1
10.34
12.7
8.12
1.63
56.78

Ia=Pi/(3*U*p)
Ir=IaL*tgL+IaP*P
=>

Ia

69.67

[A]

=>

Ir

56.78

[A]

=>

In

89.88

[A]

Ima

98

[A]

1 Conductoare
sF

35 [mm2]

sN

35 [mm2]

sPE

25 [mm2]

4FY 35+FY25
2 Tubul de protectie
n=5

=>

Dn

50

[mm]

IPEY

3 Siguranta fuzibila
In

89.96

[A]

IFIn
IFmax(IF)TG+2tr; 25/20A
IF 3*Ima

=> IF 294A

IF=100 A =>

LFi100/100A

4 Intreruptorul
In

89.88

IriIn

=>

[A]
Iri

100

[A]

Ini

200
0.7

[A]

cos
Aleg un IP 200 cu Iri=100A
Centrala de ventilare
Pi [W]
2200
4000
4000
4000
7500
4000
6000
400
32100
400

M1
M2
M3
M4
M5
M6
M7
M8
P
U

TF3

cos
0.74
0.76
0.76
0.76
0.84
0.8
0.8
0.8

In [A]

Ia [A]

Ir [A]

5.57
9.38
9.38
9.38
16.52
21.17
13.53
2.72
87.65

4.12
7.13
7.13
7.13
13.88
16.94
10.82
2.18
69.32

3.75
6.1
6.1
6.1
8.96
12.7
8.12
1.63
53.45

In=(Ina2+Inr2)

Ia=Iai
Ir=Iri

Ia=Pi/(3*U*p)
Ir=IaP*P
=>

Ia

69.32

[A]

=>

Ir

53.45

[A]

=>

In

87.54

[A]

Ima

98

[A]

1 Conductoare
sF

35 [mm2]

sN

35 [mm2]

sPE

25 [mm2]

4FY 35+FY25
2 Tubul de protectie

n=5

Dn

=>

50

[mm]

IPEY

3 Siguranta fuzibila
In

87.65

[A]

IFIn
IFmax(IF)TG+2tr; 25/20A
IF3*Ima

=>IF294A

IF=100A

=>

LFi100/100A

4 Intreruptorul
In

87.54

IriIn

=>

[A]
Iri

175

[A]

Ini

350
0.7

[A]

cos
Aleg un IP 200 cu Iri=100A

Tabloul de forta pentru rezerva


P
U

cos

7.18
400
0.8
0.8

[KW]
[V]
[-]
[-]

In=(Ina2+Inr2)

Ia=Pi/(3*U*p)

Ir=IaP*tgP

=>
1 Conductoare
sF
sN

Ia

12.95

[A]

Ir

9.71

[A]

In

16.18

[A]

Ima

18

[A]

2.5 [mm2]
2.5 [mm2]

sPE

2.5 [mm2]

5FY 2,5
2 Tubul de protectie
n=5

Dn

=>

20

[mm]

IPEY

3 Siguranta fuzibila
In =

16.18

[A]

IF In
IF max(IF)TG+2tr; 25/20A
IF 3*Ima
IF=25A

=>

IF 54A

=>

LFi 25/25A

4 Intreruptorul
In

16.18

IriIn

=>

[A]
Iri

30

[A]

Ini

60
0.7

[A]

cos
Aleg un IPIII 60 cu Iri=30A>14,21A

Iluminat de siguranta
P
U
cos

4.28
400
0.95

[KW]
[V]
[-]

In=(Ina2+Inr2)

Ia=Pi/(U*3*p)

Ir=IaP*tgP

=>
1 Conductoare
sF

Ia

6.50

[A]

Ir

2.14

[A]

In

6.84

[A]

Ima

14

[A]

1.5 [mm2]

sN

1.5 [mm2]

sPE

1.5 [mm2]

3FY 1,5
2 Tubul de protectie
n=3 =>

Dn

16

3 Siguranta fuzibila
In

6.84

[A]

IFIn
IF3*Ima

=>IF54A

IF=16A

=>

LFi 25/16A

4 Contactorul
In
IncIn

6.84

[A]

Inc
=>
6
Aleg un contactor TCA 6

[A]

[mm]

IPEY

25.77

108.26

20.68

86.97

138.86

Repartitia pe faze
Circuit

LL/LP

Putere

L1

L2

L3

[W]

[W]

[W]

[W]

1150

CLS1

23

LL

1150

CLS2

18

LL

828

CLS3

11

LL

506

CLS4

13

LL

598

CLS5

24

LL

1196

PTOT

4278

828
506
598
1196
1656

1426

1196

Calculul coloanei tabloului general de for

Pi

Ia

Ir

[W]
34000
32500
32100
7175
4278

[A]
105.82
89.88
87.54
16.18
6.84

[A]
82.48
69.67
69.32
12.95
6.50

[A]
66.29
56.78
53.45
9.71
2.14

110053

306.26

240.92

188.37

cs=

0.6

TF 1
TF 2
TF 3
TF Rez
Il. Sig.

In

In=(Ina2+Inr2)
Ia = cs * Iai
Ir = cs * Iri

=>

Ina=

144.55 [A]

=>

Inr=

113.02 [A]

=>

In =

183.49 [A]

1 Conductoare
Ima

218

[A]

sF

95

[mm2]

sPEN

70

[mm2]

3CYY95+CYY70
2 Tubul de protectie
s f=
n=

95
4

[mm2]

3 Disjunctor
InD>In
=>InD

183.49 [A]
250

[A]

Aleg un disjunctor USOL250

=>

Dn =63[mm]

4 Intreruptor
In
Ini>In

183.49 [A]
200

[A]

IP 200
5 Reductorul de curent
In
Inp

183.49 [A]
Inp1.1*In =>Inp
200

201.84 [A]

[A]

Inp

200

[A]

Ins

[A]

Cp

0.5 [%]

Cp=Clasa de precizie

Pa

10 [VA]

Pa=Puterea absorbita de secundar

Ct

15 [kA]

Ct=curentul termic

CIRT 3x200/5A
6 Ampermetrul
3(0600)
7 Contor de curent alternativ trifazat
Aleg cun CAT 43

TC 250/6A
3X400/230V
Acesta foloseste metoda celor 3 wattmetre

Calculul de verificare la pierderea de tensiune


pentru instalatia de forta
1) In regim nominal
U=U1+U2+U3

DU3%

DU2%

L3

L2

CB

U1% =

< DUadm%

DU1%
L1

TGF

TF1

M7

(100*Pe*L1)/(*U2*s)

Pn=3*U*In

U2% =

Pn =

11.45

[kW]

L1 =
U=

13.11
400

[m]
[V]

s=
=

2.5
54

U1% =

0.69

U2% =

0.04

U3% =

0.18

U% =
Uadm%=

0.91

% < Uadm%

[mm2]
[m/mmW]

(100*Pe*L2)/(*U2*s)

Pn=3*U*Ina

U3% =

Pn =

57.15

[kW]

L2 =
U=

2.75
400

[m]
[V]

s=
=

50
54

[mm2]
[m/mmW]

(100*Pe*L3)/(*U2*s)

Pn=3*U*Ina
Pe = 100.15 [kW]
L3 =
15
[m]
U = 400 [V]
s=
=

95
54

U=U1+U2+U3

[mm2]
[m/mmW]

2) In regim de pornire
U1% = (100*Pe*L1)/(g*U2*s)
Pe =

3*Ip*Ul*cos
Pe =

22.89

[kW]

L1 =
U=

12.6
400

[m]
[V]

s=
=

2.5
54

[mm2]
[m/mmW]

DU1% =

1.34

DU2% =

0.61

DU3% =

0.18

U% =
Uadm%=

2.13

% < Uadm%

U2% = (100*Pe*L2)/(g*U2*s)
Pe = 31/2*In*Ul*cosj
Pe =

96.21

[kW]

L2 = Feb-75 [m]
U = 400 [V]
s=
=

50
54

[mm2]
[m/mmW]

U3% = (100*Pe*L3)/(g*U2*s)
Pe = 31/2*In*Ul*cosj
Pe = 100.15 [kW]
L3 =
15
[m]
U = 400 [V]
s=
=

95
54

[mm2]
[m/mmW]

U=U1+U2+U3

12

Instalatia de paratrasnet
Frecventa trasnetelor pe sol
Ng=0.04*Nk1,25
Nk=indicele cheraunic
Nk=

Pentru Bucuresti
Ng =

3.6

36.6

[lovituri/Km2 *An]

Nd=Ng*Ae*c1*10-6 [lovituri/an]
Ae= Aria echivalenta de protectie
c1=coeficent; este in functie de amplasare
c1

0.25

constructia fiind amplasata intr-o zona cu alte constructii sau arbori

Ae=f(inaltimea cladirii)
Hcladire=(P+4)Hnivel+1,5m
Hcladire

20.5

Ae

[m]

=>3H=61,5[m]

21679 [m]

Nd

0.02

[lovituri/an]

Probabilitatea loviturilor in zona respectiva


Nc=(5.5*10-3)/(C2*C3*C4*C5)
C2

Structura cladirii si acoperisul sunt din beton

C3

Valori obisnuite si normal combustibile

C4

Evacuare dificila sau risc de panica

C5

Nc

Nu necesita continuarea lucrului si nu are efecte daunatoare asupra mediului

Eficacitatea instalatiei
E=1-Nc/Nd
E=

0.91

Se alege nivelul intarit II de protectie al instalatiei de paratrasnet

Priza de pamant
Calculul rezistentei electrodului vertical
Rv=rv/(nv*uv)
Din anexa "Date de proiectare", volumul II, aleg teava cu l=3m, ingropata la adancimea
h=q+l/2; avand diametrul de 2 1/2"
q=

=>

h=

2.5

[m]

rv=0.366*[lg(2*l/d)+1/2*lg((4h+l)/(4h-l))]*s/l
l
h
d
s

3
[m]
2.5
[m]
2 1/2''=>
0.06 [m]
0.90*104

[cm]

90
[m]
Electrozii sunt plasati la distanta e=1l unul fata de altul
Se folosesc 56 de electrozi verticali, asezati pe un contur inchis
nv
=>
30
rv

20.35 []

uv

0.38 coeficient de utilizare

Rv

1.77 []

Calculul rezistentei electrodului orizontal


Ro=ro/(no*uo)
Aleg bara cu sectiunea dreptunghiulara, avand latimea de 40[mm] asezata la adancimea
q=1[m]
ro=0.366*s/l*lg[(2*l2)/(b*q)]
q

[m]

l
b
s

3
0.04

[m]
[m]

0.90*104
90

[cm]
[m]

Se folosesc 56 de electrozi orizontali, asezati pe un contur inchis6


no
=>
30
ro
uo
Ro

29.13 []
0.2 coeficient de utilizare
4.86 []

RP=Rv*Ro/(Rv+Ro)
RP

1.3