You are on page 1of 197

1.

TRANSFORMER, 60 MVA (50 MVA), 132/33 kV TECHNICAL DATA SCHEDULE TRANSFORMER 60 MVA (50MVA), 132/33 kV

ITEM 1.0 1.1 1.2 2.0 2.1

DESCRIPTION Manufacturer Type Class Rated data and characteristics Rated power: - primary/secondary

UNITS -

REQUIRED Specify Three-phase with 2 windings -

GUARANTEED

MVA kV kV % Hz -

50/60 ONAN/ ONAF 132 33 MR MIII 500-D = HV neutral +4 x 1.25% -12 x 1.25% Rated power on all taps 50 YNd11

2.2 2.3

Cooling Rated voltage - HV winding - LV winding

2.4

Tap changer: - manufacturer - model - type - on-load tap changer location - regulating range - rating

2.5 2.6 2.7

Frequency Connection of the three-phase windings (group of vectors IEC 76) Rated current at ONAF rated power and rated voltage tap: - HV winding - LV winding

A A A A

262 1004 Base: rated

2.8

No-load current through: - HV winding - LV winding

2.9

Short circuit impedance

TECHNICAL DATA SCHEDULE TRANSFORMER 60 MVA (50MVA), 132/33 kV ITEM DESCRIPTION UNITS REQUIRED voltage and 50 (60) MVA 2.9.1 Direct impedance at nominal voltage tap: - HV/LV 2.9.2 Direct impedance at minimum voltage tap: - HV/LV 2.9.3 Direct impedance at maximum voltage tap: - HV/LV 2.9.4 Zero sequence impedance at nominal voltage tap - HV / LV 2.10 Tolerance to be applied to the short circuit impedance, in terms of % of the guaranteed value on: - nominal voltage tap - other taps 2.11 2.11.1 2.11.2 Transformer capacity to withstand external short circuits: Short circuit duration Symmetrical short circuit current withstand during the indicated period and asymmetrical short circuit withstand: - HV winding kA RMS kA (peak) kA RMS kA (peak) kA RMS kA (peak) s 2 % % 7.5 10 % % % % 10 GUARANTEED

- LV winding

- tertiary winding

TECHNICAL DATA SCHEDULE TRANSFORMER 60 MVA (50MVA), 132/33 kV ITEM DESCRIPTION - pre-fault voltage 2.12 2.12.1 2.12.2 Guaranteed losses No-load losses at rated voltage and frequency, with rated voltage tap No-load losses at 110% of the rated voltage, at rated frequency and rated voltage tap No-load losses capitalized value Tolerance to be applied to no-load losses (in % of the guaranteed value) On-load losses at rated voltage and frequency, with rated voltage tap and ONAN rating: - HV winding - LV winding tertiary winding On-load losses capitalized value Tolerance to be applied to total losses (in %of the guaranteed value) for all the windings Auxiliaries consumption at second stage of cooling (ONAF/ONAF) Highest voltage for equipment: - HV winding - LV winding 2.14 2.14.1 Rated insulation level: Short time power frequency withstand: - HV winding - line terminal - LV winding - line terminal - neutral control wiring kV RMS kV RMS kV RMS kV RMS 275 70 38 2.0 kV kV 145 36 kW kW UNITS p.u. REQUIRED 1.05 GUARANTEED

2.12.3 2.12.4

US $/kW %

3000 10

2.12.5

kW kW kW US $/kW %

1080 10

2.12.6 2.12.7

2.12.8 2.13

kW

TECHNICAL DATA SCHEDULE TRANSFORMER 60 MVA (50MVA), 132/33 kV ITEM 2.14.2 DESCRIPTION Basic impulse level: - HV winding - line terminal - LV winding - line terminal neutral point kV (peak) kV (peak) kV (peak) 650 170 95 UNITS REQUIRED GUARANTEED

2.15

Temperature rise limits at maximum power output at ONAN and ONAF ratings and at lowest voltage tap and corresponding voltage: - top oil at ambient temperature average copper at ambient temperature - hot spot windings K K K 45 55 68

2.16

Permissible overload in emergency cases: - permanent permissible overload based on highest winding temperature which exceeds by 5oC the guaranteed limit - permanent permissible overvoltage based on the specified temperature rise limts (in % of the rated voltage)

MVA

110

2.17

Oil: - manufacturer type data sheet attached -

NYNAS NYTRO 10XN (Inhibited) (IEC 60296) -

2.18 2.18.1

Bushings HV bushings: - class manufacturer type designation rated current short circuit withstand kV A kA RMS 145 -

TECHNICAL DATA SCHEDULE TRANSFORMER 60 MVA (50MVA), 132/33 kV ITEM DESCRIPTION basic insulation level power frequency withstand for 1 minute connectors for - creepage distance 2.18.2 LV bushings: - class manufacturer type designation rated current short circuit withstand basic insulation level power frequency withstand for 1 minute connectors for - creepage distance 2.18.3 Neutral bushings: - class manufacturer type designation rated current short circuit withstand basic insulation level power frequency withstand for 1 minute connectors for - creepage distance 2.19 2.19.1 Design data: Maximum flux density in the columns at: - rated voltage 105% of the rated voltage 2.19.2 Maximum flux density in the yokes at: - rated voltage 105% of the rated voltage 2.19.3 Maximum current density at ONAN rated power and rated voltage tap: - HV winding A/mm2 tesla tesla kV A kA RMS kV (peak) kV RMS mm/kV 24 125 50 31 kV A kA RMS kV (peak) kV RMS mm/kV 36 170 70 TBA 31 UNITS kV (peak) kV RMS mm/kV REQUIRED 650 275 TBA 31 GUARANTEED

tesla tesla

TECHNICAL DATA SCHEDULE TRANSFORMER 60 MVA (50MVA), 132/33 kV ITEM 2.19.4 DESCRIPTION - LV winding Winding resistance: - HV winding - LV winding 2.19.5 Voltage regulation at ONAN rating and rated voltage tap (in % of the rated voltage): - with unity power factor: . LV side . TV side - with 0.9 power factor (lagging): . LV side . TV side - with 0.8 power factor (lagging): . LV side . TV side 2.19.6 Primary exciting current, LV side: - at 0.01 second - at 0.1 second kA kA % % % % % % ohms ohms UNITS A/mm
2

REQUIRED -

GUARANTEED

2.19.7 2.19.8 2.20

Core type (core or shell) Winding conductor Audible noise level - Voltage in percent of rated value ONAN rating ONAF maximum rating

Copper

% dB(A) dB(A) V

105 75 max 78 max 2500 max

2.21

Radio Interference Voltage at 0.5 MHz as per IEC 694 Weights and dimensions Total weight of transformer, equipped for service Weight: - oil core and coil assembling

3.0 3.1 3.2

kg

kg kg

TECHNICAL DATA SCHEDULE TRANSFORMER 60 MVA (50MVA), 132/33 kV ITEM DESCRIPTION tank and accessories net copper net core steel 3.3 3.4 Maximum shipping weight (heaviest item) Height from foundation to: - highest point of HV bushing highest point of tank highest point of conservator tank highest point of lifting hook to remove core and coil assembly 3.5 Outline dimensions: - length width 3.6 Layout drawing no mm mm To be enclosed with bid mm mm mm mm UNITS kg kg kg kg REQUIRED GUARANTEED

3.7

Maximum shipping dimensions of tank: - outside height outside width outside length

mm mm mm

3.8

Transportation drawing no

To be enclosed with bid

4.0 4.1 4.2 4.3 4.4 4.5

On-load tap changer Manufacturer Type Rated current Number of steps Short circuit withstand A kA RMS MR MIII 500-D 17 -

TECHNICAL DATA SCHEDULE TRANSFORMER 60 MVA (50MVA), 132/33 kV ITEM 4.6 4.7 DESCRIPTION BIL to ground through the regulating coil Power frequency withstand voltage for 1 minute through the regulating coil Tap transition device UNITS kV (peak) kV RMS REQUIRED GUARANTEED

4.8

Resistance type and BCD

4.9 5.0 5.1 5.1.1 5.1.2 5.1.3 5.1.4

Parallel automatic controller Current transformer incorporated into the power transformer CT in HV phase bushings: Number of cores per bushing Primary rated current Secondary rated current Accuracy class: - protection - metering

masterfollower

A A

4 400 1 To be coordinated

(2)5P20, 20 VA / (1) Class X (1)CL0.2, 20 VA 400:1 -

5.1.5 5.1.6 5.1.7

Ratio Short circuit withstand Continuous secondary current thermal limit

A A

5.2 5.2.1 5.2.2

CT in HV neutral bushing: Number of cores per bushing Primary rated current A 2 400

TECHNICAL DATA SCHEDULE TRANSFORMER 60 MVA (50MVA), 132/33 kV ITEM 5.2.3 5.2.4 DESCRIPTION Secondary rated current Accuracy class protection (to be coordinated) Ratio Short-circuit withstand Continuous secondary current (thermal limit) UNITS A REQUIRED 1 (1) 5P20, 20 VA / (1) Class X 400:1 GUARANTEED

5.2.5 5.2.6 5.2.7

A A

5.3 5.3.1 5.3.2 5.3.3 5.3.4

CT in LV phase bushings: Number of cores per bushing Primary rated current Secondary rated current Accuracy class: - protection - metering A A A A 4 1200 1 (3)5P20, 20VA (1)CL0.2, 20 VA 1200:1 -

5.3.5 5.3.6 5.3.7 6.0 6.1 6.2

Ratio Short-circuit withstand Continuous secondary current (thermal limit) Layout Primary winding bushings Secondary winding bushings

(3) Long. Axis (3) Long. Axis (opposite to HV) Transv. Axis Transv. Axis As per

6.3 6.4 6.5 6.6 6.7

Conservator tank Tap changer Control cabinet Radiators Terminal block connection drawing

TECHNICAL DATA SCHEDULE TRANSFORMER 60 MVA (50MVA), 132/33 kV ITEM DESCRIPTION UNITS REQUIRED enclosed drawings 7.0 7.1 Standards Manufacturing Latest revisions of IEC 60296 IEC 60044 IEC 60076 IEC 60137 IEC 60214 IEC 60529 IEC 60815 IEC 60947 NEMA TR-1 ISO 9001 Outdoor in substation yard GUARANTEED

7.2 8.0

Quality assurance Installation

1.2

A COPY OF TYPE TEST REPORT FOR A SIMILAR TRANSFORMER RECENTLY COMPLETED SHALL BE SUBMITTED

33 kV EARTHING TRANSFORMER TECHNICAL DATA SCHEDULE 33 kV EARTHING TRANSFORMER


ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

1.0 1.1 1.2 2.0 2.1

Manufacturer Type Class Rated data and characteristics Rated voltage: - HV winding - LV winding - Manual off-load taps Rated frequency Connection of the 3 phase windings (group of vectors IEC) Rated capacity: Rated continuous neutral current of HV winding Rated power of secondary winding Cooling Excitation current at rated voltage Impedance Zero-sequence impedance of HV winding Direct sequence impedance of LV winding at rated power Tolerance to be applied to the impedance, in terms of % the guaranteed value Short-circuit withstand HV winding capacity to withstand external short-circuits: - short-circuit duration - short-circuit current withstand the indicated period Short-circuit duration for LV winding Guaranteed losses

Three-phase with 1 winding -

kV V % Hz -

33 kV 415 V 2 x 2.5% on LV winding 50 Znyn1

2.2 2.3 2.4 2.4.1 2.4.2 2.5 2.6 2.7 2.7.1 2.7.2 2.8 2.9 2.9.1

A kVA A ohms %

20 300 ONAN 360 6

% -

7.5 -

Sec. A RMS sec

10 360 2

2.9.2 2.10

TECHNICAL DATA SCHEDULE 33 kV EARTHING TRANSFORMER


ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

2.10.1 2.10.2 2.10.3 2.10.4

No-load losses at rated voltage and frequency No-load losses capitalized value Tolerance to be applied to no-load losses (in % of the guaranteed value) On-load losses at rated voltage and frequency and copper temperature rise at 75: - HV winding at maximum neutral current - LV winding at rated power On-load losses capitalized value Tolerance to be applied to no-load losses (in % of the guaranteed value) Highest voltage for equipment: - HV winding

kW US $/kW %

3000 +10

kW kW US $/kW %

1080 +10

2.10.5 2.10.6 2.11 2.12 2.12.1

kV

36

Rated insulation level: Short time power frequency withstand: - HV winding line terminal - HV winding neutral point - LV winding kV RMS kV RMS kV RMS 70 38 10

2.12.2

Basic impulse level: - HV winding line terminal - HV winding neutral point LV winding kV (peak) kV (peak) kV (peak) 170 95 30

2.13

Temperature rise limits at continuous neutral current and rated voltage: - top oil al ambient temperature - average copper at ambient temperature - hot spot windings K K K A 50 55 68 -

2.14

Permissible overload in emergency cases: - permanent permissible overload based on highest winding temperature which exceeds by 5oC the guaranteed limit - permanent permissible over voltage based on the maximum top oil temperature which exceeds by 5oC the guaranteed limit at rated power (in % of the rated voltage)

TECHNICAL DATA SCHEDULE 33 kV EARTHING TRANSFORMER


ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

2.15

Oil: - manufacturer - type - data sheet attached kV A kA RMS kV (peak) kV RMS mm/kV kV A kA RMS kV (peak) kV RMS mm/kV kV A kA RMS kV (peak) kV RMS mm/kV

NYNAS NYTRO 10XN (Inhibited) (IEC 60296) 36 170 70 31 24 125 50 31 31

2.16 2.16.1

Bushings HV bushings: - class - manufacturer - rated current - short circuit withstand (3 seconds) - basic insulation level - power frequency withstand for 1 minute - connectors for - creepage distance

2.16.2

Neutral bushings: - class manufacturer rated current short circuit withstand (3 seconds) basic insulation level power frequency withstand for 1 minute connectors for - creepage distance

2.16.3

LV bushing: - class manufacturer rated current short circuit withstand (3 seconds) basic insulation level power frequency withstand for 1 minute connectors for - creepage distance

2.17 2.17.1

Design data: Maximum flux density in the columns at: - rated voltage - 105% of the rated voltage tesla tesla tesla tesla -

2.17.2

Maximum flux density in the yokes at: - rated voltage - 105% of the rated voltage

TECHNICAL DATA SCHEDULE 33 kV EARTHING TRANSFORMER


ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

2.17.3

Maximum current density at ONAN rated power and rated voltage tap: - HV winding - LV winding Winding resistance - HV winding - LV winding Primary exciting current, LV side: - at 0.01 second - at 0.1 second

A/mm2 A/mm2 ohms ohms kA kA -

Copper

2.17.4

2.17.5

2.17.6 2.17.7 3.0 3.1

Core type (core or shell) Winding conductor Weights and dimensions Total weight of unit equipped for start-up

kg

3.2

Weight: - oil - core and coil assembling - tank and accessories - net copper - net core steel kg kg kg kg kg kg mm mm mm mm mm mm -

3.3 3.4

Maximum shipping weight (heaviest item) Height from foundation to: - highest point of HV bushing - highest point of tank - highest point of conservator tank - highest point of lifting hook to remove core and coil assembly

To be enclosed with bid -

3.5

Reactor dimensions: - length - width

3.6 3.7

Layout no enclosed Maximum shipping dimensions of tank: - outside height - outside width - outside length

mm mm mm

TECHNICAL DATA SCHEDULE 33 kV EARTHING TRANSFORMER


ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

3.8 4.0 4.1 4.1.1 4.1.2 4.1.3 4.1.4

Transportation drawing no enclosed Current transformer incorporated into the reactor CT in HV neutral bushings: Number of cores per bushing Primary rated current Secondary rated current Accuracy class - protection

A A -

2 1200 1 To be coordinated 5P20, 20 VA 1200:1 number of cores and class to be coordinated

4.1.5 4.1.6 4.1.7 4.2

Ratio Short circuit withstand (3 seconds) Continuous secondary current thermal limit CT in LV neutral bushing

A A -

5.0 5.1 5.2 6.0 6.1

Layout HV winding bushings Terminal block connection drawing Standards Manufacturing IEC 60044 IEC 60137 IEC 60289 IEC 60296 IEC 60815 IEC 60947 ISO 9001 or Latest IEC Standard Outdoor in substation switchyard (3) Long. Axis As per enclosed drawings

6.2

Quality assurance

7.0

Installation

2
2.1

TECHNICAL DATA SCHEDULES


CIRCUIT BREAKER, 362 kV, 40 kA, 2000 A TECHNICAL DATA SCHEDULE CIRCUIT BREAKER, 362 kV, 40 kA, 2000A

ITEM 1.0

DESCRIPTION Manufacturer

UNITS -

REQUIRED Specify

GUARANTEED

1.1 1.2 1.3 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8

Type Model n
o

SF 6 Specify

Country of origin Nominal characteristics Rated system voltage Rated maximum voltage Rated lightning impulse (BIL) Rated switching withstand voltage Power frequency withstand voltage Rated frequency Number of poles Operation

kv kV kV peak kV RMS kV RMS Hz -

330 362 1175 950 510 50 3 Single pole for transmission line feeders and power transformers 2000 40 362 3 45 50 150 O-0,3 s CO-3 min-CO < 1% -

2.9 2.10

Rated current Short circuit breaking current voltage short-time withstand DC component time constant

A kA RMS kV s ms ms ms % Bar

2.11 2.12 2.13 2.14

Breaking time Closing time Operating sequence Annual rate of gas leakage at normal pressure of

TECHNICAL DATA SCHEDULE CIRCUIT BREAKER, 362 kV, 40 kA, 2000A

ITEM

DESCRIPTION

UNITS

REQUIRED

GUARANTEED

2.15 2.16

Creepage distance to earth and between terminals Rated TRV for faults at terminals TRV crest value TRV rate of rise Initial TRV Time to crest of initial TRV

mm/kV

31

kV kV/s kV sec

538 2 3,5 0,8

2.17

Rated TRV for short line faults TRV crest value TRV rate of rise Surge impedance kV kV/s ohms 414 2 450

2.18

Rated out-of-phase breaking capability Rated out-of-phase current Power frequency recovery voltage kA kV 7,8 418

2.19

Rated TRV out-of-phase breaking TRV crest value TRV rate of rise kV kV/s 739 1,54

2.20

Rated line charging breaking capability rated line charging breaking current (no restrike) TRV crest value TRV duration after breaking A kV s V pF 315 800 0,3 2500 -

2.21

Radio Interference Voltage (RIV) R.I.V. max voltage level (IEC 694) at 0,5 MHz and 362 kV test voltage

2.22 2.23

Capacitors across terminals Number of operations without maintenance CO at no load CO at rated current CO at rated breaking current

TECHNICAL DATA SCHEDULE CIRCUIT BREAKER, 362 kV, 40 kA, 2000A

ITEM 2.24 3.0 3.1 3.2 3.3 3.4 3.5 3.6 4.0

DESCRIPTION Closing (Pre-Insertion) resistors Operating mechanism Type Motor voltage Closing and opening coil voltage Number of closing coils Number of opening coils Number of auxiliary contacts available Dimensions and weight: - between poles - total height - support insulator height - metal support height - total weight, 3 poles group - transportation dimensions - transportation weight Accessories in the motor mech. Enclosure Operation counter Local manual control Heater Weatherproof, corrosion resistance enclosure Accessories in the central control cabinet Anti-pumping relay Local/remote command selector switch Local operation push buttons Minimum pressure lock-out and alarm relay Lighting, heating and service outlet Phase discrepancy timer relay Weatherproof, corrosion resistance

UNITS -

REQUIRED Where applicable

GUARANTEED

Vdc Vdc mm mm mm mm kg mm kg

110 110 1 2 min. 7 NO, 6 NC 2500 -

5.0 5.1 5.2 5.3 5.4 6.0 6.1 6.2 6.3 6.4 6.5 6.6 6.7

Yes Yes Yes IP 55

Yes Yes Yes Yes Yes Yes IP55

TECHNICAL DATA SCHEDULE CIRCUIT BREAKER, 362 kV, 40 kA, 2000A

ITEM enclosure 7.0 8.0 9.0

DESCRIPTION

UNITS

REQUIRED

GUARANTEED

Quality control Installation Warranty

ISO 9001 Outdoor, desertic/tropical environment

3.

CIRCUIT BREAKER, 132 kV, 40 kA, 2000 A

TECHNICAL DATA SCHEDULE CIRCUIT BREAKER, 132 kV, 31.5 kA, 2000 A ITEM 1.0 1.1 1.2 1.3 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 DESCRIPTION Manufacturer Type Model n
o

UNITS -

REQUIRED Specify SF 6 Specify

GUARANTEED

Country of origin Nominal characteristics Rated system voltage Rated maximum voltage Rated lightning impulse (BIL) Power frequency withstand voltage Rated frequency Number of poles Operation

kV kV kV peak kV RMS Hz -

132 145 650 275 50 3 Single pole for transmission line and autotransformer feeders 2000 40 145 3 45

2.8 2.9

Rated current

A kA RMS kV s ms

Short circuit breaking current -

voltage
Short time with stand DC component time constant

2.10 2.11 2.12 2.13 2.14

Breaking time Closing time Operating sequence Annual rate of gas leakage at normal pressure of Creepage distance to earth and between terminals

ms ms % Bar mm/kV

50 150 O-0,3 s CO-3 min-CO <1 31

TECHNICAL DATA SCHEDULE CIRCUIT BREAKER, 132 kV, 31.5 kA, 2000 A ITEM 2.15 DESCRIPTION UNITS kV kV/s kV s REQUIRED 215 2 1,4 0,4 GUARANTEED

Rated TRV for faults at terminals -

TRV crest value


TRV rate of rise initial TRV time to crest of initial TRV

2.16

Rated TRV for short line fault - TRV crest value - TRV rate of rise - surge impedance Rated out-of-breaking capability - Rated out-of-phase current - Power frequency recovery voltage Rated TRV out-of-phase breaking - TRV crest value - TRV rate of rise Rated line charging breaking capability - Rated line charging breaking current ( no restrike) - TRV crest value - TRV duration after breaking Radio Interferance Voltage (RIV) - RIV max voltage level (IEC 694) at 0,5 MHz and 145 kV test voltage Capacitors across terminal Number of operations without maintenance - CO at no load - CO at rated current - CO at rated breaking current Operating mechanism Type Motor voltage Closing and opening coil voltage Number of closing coils

kV kV/s ohms kA kV kV kV/s A kV s V pF

166 2 450 7,8 167 296 1,54 50 415 0,3 2500 -

2.17

2.18

2.19

2.20

2.21 2.22

3.0 3.1 3.2 3.3 3.4

Vdc Vdc -

110 110 1

TECHNICAL DATA SCHEDULE CIRCUIT BREAKER, 132 kV, 31.5 kA, 2000 A ITEM 3.5 3.6 3.7 DESCRIPTION Number of opening coils Number of auxiliary contacts available Synchronized pole switching UNITS REQUIRED 2 min. 7 NO, 6 NC Yes (for autotransformer energizing GUARANTEED

4.0

Dimensions and weight: between poles total height support insulator height metal support height total weight, 3 poles group transportation dimensions transportation weight mm mm mm mm kg mm kg 2500 -

5.0 5.1 5.2 5.3 5.4 5.5 6.0 6.1 6.2 6.3 6.4 6.5 6.6 6.7 7.0 9.0

Accessories in the motor mech. Enclosure Operation counter Local manual control Test switches (dc) Heater Weatherproof, corrosion resistance enclosure Accessories in the central control cabinet Anti-pumping relay Local/distance command selector switch Local operation push buttons Minimum pressure lock-out and alarm relay Lighting, heating and service plug Phase discrepancy timer relay Weatherproof, corrosion resistance enclosure Type test reports number Quality control Yes Yes Yes Yes Yes Yes IP 55 Included in Bid Yes Yes Yes Yes IP 55

TECHNICAL DATA SCHEDULE CIRCUIT BREAKER, 132 kV, 31.5 kA, 2000 A ITEM 10.0 11.0 Installation Warranty DESCRIPTION UNITS REQUIRED GUARANTEED

2.2

CIRCUIT BREAKER, 33 kV, 25KA, 1250 A

TECHNICAL DATA SCHEDULE CIRCUIT BREAKER, 33 kV, 25KA, 1250 A


ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

1.0 1.1 1.2 1.3 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7

Manufacturer Type Model n


o

Specify SF6 or vacuum Specify Specify

Country of origin Nominal characteristics Rated system voltage Rated maximum voltage Basic lightning impulse level Power frequency withstand voltage (1 minute) Rated frequency Number of poles Operation

kv kV kV peak kV RMS Hz -

33 36 170 70 50 3
three poles for line feeder or transformers suitable for multiple shots reclosing

2.8 2.9

Rated current Short circuit breaking current voltage Short time withstand DC component time constant

A kA RMS kV s ms ms ms % Bar

1250 25 36 3 45 70 80 O-0,3-CO-3 min CO <1 -

2.10 2.11 2.12 2.13 2.14

Breaking time Closing time Operating sequence Annual rate of gas leakage at normal pressure of Number of operation sequences without maintenance (minimum): - CO at no load - CO at rated current - CO at rated breaking current

TECHNICAL DATA SCHEDULE CIRCUIT BREAKER, 33 kV, 25KA, 1250 A


ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

3.0 3.1 3.2 3.3 3.4 3.5 3.6 4.0 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 5.0

Operating mechanism Type Motor voltage Closing and opening coil voltage Number of closing coils Number of opening coils Number of auxiliary contacts available Bushings Class Manufacturer Type Rated current Short circuit withstand (3 sec) Basic insulation level Power frequency withstand (1 min) Creepage distance Dimensions and weight - between phases - total height - enclosure width - enclosure height - enclosure height including legs - total weight 3 pole unit Accessories Operation counter Local manual control Local/Remote command selector switch Open/Closed indication Test switches (DC) Local operation push button Yes Yes Yes Yes Yes Yes kV A kA RMS kV peak kV RMS mm/kV mm mm mm mm mm kg 36 125 170 70 31 Vdc Vdc 110 110 1 2 6 N.O 6 N.C

6..0 6.1 6.2 6.3 6.4 6.5 6.6

TECHNICAL DATA SCHEDULE CIRCUIT BREAKER, 33 kV, 25KA, 1250 A


ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

6.7 6.8 6.9 8.0 11.0

Heater, light and receptacle plug Free standing weatherproof, corrosion resistant metal enclosure Cranking Handle Type test reports Installation

Yes IP 55

Included in bid Freestanding, Outdoor, desertic/tropical environment 5 (FIVE)

12.0

Warranty

Years

TECHNICAL DATA SCHEDULES

3.1

DISCONNECT SWITCH 362 kV, 40 kA, 2000 A

TECHNICAL DATA SCHEDULE DISCONNECT SWITCH 362 kV, 40 kA, 2000 A ITEM 1.0 1.1 1.2 1.3 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11 2.12 2.13 2.14 3.0 3.1 3.2 DESCRIPTION Manufacturer Type Model n
o

UNITS -

REQUIRED vertical break -

GUARANTEED

Country origin Nominal characteristics Rated System voltage Rated maximum voltage Lightning impulse withstand voltage Switching impulse withstand voltage Power frequency withstand voltage Rated frequency Number of poles Rated current Short time current withstand ability during Creepage distance to earth Opening time Closing time Max level of RIV (IEC 694) at 0,5 MHz and 362 kV test voltage Insulator designation (IEC 273) Operating mechanism Motor voltage Number of auxiliary contacts available

KV KV kV peak kV peak kV RMS Hz A kA s mm/kV s s V -

330 362 1175 950 510 50 3 2000 40 3 31 < 30 < 30 2500 motor and manual

Vdc

110 min. 8 NO 8 NC

TECHNICAL DATA SCHEDULE DISCONNECT SWITCH 362 kV, 40 kA, 2000 A ITEM 3.3 3.4 4.0 4.1 4.2 4.3 4.4 4.5 4.6 4.7 5.0 5.1 5.2 5.3 5.4 5.5 5.8 5.9 6.0 7.0 8.0 DESCRIPTION Number of mechanism Main disconnect hand operated by Weight and dimensions Distance between poles Height of a pole Height of the support structure Total height Length of a pole Weight of a pole Weight of the motor mechanism Accessories Local/remote selector switch Local manual and electrical operation devices Light, heater and service outlet operating mechanism enclosure MCB protected motor and control circuits Motor contactor Weatherproof corrosion resistant enclosure Mounting brackets and hardware Type test reports number Standards Quality control yes yes yes yes yes IP55 yes To be included in bid mm mm mm mm mm kg kg 2500 UNITS REQUIRED wheel or crank GUARANTEED

9.0

Installation

Outdoor in desertic/tropical environment

DISCONNECT SWITCH 362 kV, 40 kA, 2000 A WITH GROUNDING BLADES

TECHNICAL DATA SCHEDULE DISCONNECT SWITCH 362 kV, 40 kA, 2000 A WITH GROUNDING BLADES CODE NO: 4114 ITEM 1.0 1.1 1.2 1.3 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11 2.12 2.13 2.14 2.15 DESCRIPTION Manufacturer Type Model no Country of origin Nominal characteristics Rated System voltage Rated maximum voltage Lightning impulse withstand voltage Switching impulse withstand voltage wet Power frequency withstand voltage Rated frequency Number of poles Rated current Short time current withstand ability during Creepage distance to earth Opening time Closing time Max level of RIV (IEC 694) at 0,5 MHz and 362 kV test voltage Insulator designation (IEC 273) Grounding switch rated inductive (electromagnetic) breaking current breaking voltage Grounding switch rated capacitive (electrostatic) breaking current breaking voltage KV kV kV peak kV peak kV RMS Hz A kA s mm/kV s s V A kV A kV 330 362 1175 950 510 50 3 2000 40 3 31 < 30 < 30 2500 UNITS REQUIRED vertical break GUARANTEED

2.16

TECHNICAL DATA SCHEDULE DISCONNECT SWITCH 362 kV, 40 kA, 2000 A WITH GROUNDING BLADES CODE NO: 4114 ITEM 3.0 3.1 3.2 3.3 3.4 4.0 4.1 4.2 4.3 4.4 4.5 4.6 4.7 5.0 5.1 5.2 5.3 5.4 5.5 5.6 5.7 5.8 5.9 5.10 5.11 DESCRIPTION Operating mechanism Motor voltage Number of auxiliary contacts available Number of mechanism Main disconnector operated by Weight and dimensions Distance between poles Height of a pole Height of the support structure Total height Length of a pole Weight of a pole Weight of the motor mechanism Accessories Local/remote selector switch Local manual and electrical operation devices Light, heater and service plug in operating mechanism enclosure MCB protected motor and control circuits Motor contactor Test switches (dc) Terminal blocks Weatherproof corrosion resistant enclosure Mechanical interlocks between the disconnect switch and ground blade Mounting brackets and hardware Arcing horns Yes Yes Yes Yes Yes Yes Yes IP 55 Yes Yes For grounding blade mm mm mm mm mm kg kg 2500 V dc UNITS REQUIRED motor and manual 110 min. 8 NO, 8 NC wheel or crank GUARANTEED

TECHNICAL DATA SCHEDULE DISCONNECT SWITCH 362 kV, 40 kA, 2000 A WITH GROUNDING BLADES CODE NO: 4114 ITEM 6.0 6.1 6.2 6.3 7.0 10.0 DESCRIPTION Grounding blades Operated by Mounting brackets and hardware Number of auxiliary contacts available Type test reports number Installation wheel or torsion bar yes 8 NO, 8 NC To be included in bid Outdoor, desertic/tropical environment UNITS REQUIRED GUARANTEED

GROUNDING SWITCH 362 kV, 40 kA

TECHNICAL DATA SCHEDULE GROUNDING SWITCH 362 kV, 40 kA CODE NO: 4115 ITEM 1.0 1.1 1.2 1.3 2.0 2.1 22 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11 2.12 2.13 2.14 2.15 DESCRIPTION Manufacturer Type Model no Country of origin Nominal characteristics Rated System voltage Rated maximum voltage Lightning impulse withstand voltage Switching impulse withstand voltage Power frequency withstand voltage Rated frequency Number of poles Rated current Short time current withstand ability during Creepage distance to earth Opening time Closing time Max level of RIV (IEC 694) at 0,5 MHz and 362 kV test voltage Insulator designation (IEC 273) Grounding switch rated inductive (electromagnetic) breaking current at 10 kV breaking voltage Grounding switch rated capacitive (electrostatic) breaking current at 16 kV breaking voltage KV kV kV peak kV peak kV RMS Hz A kA s mm/kV s s V A 330 362 1175 950 450 50 3 N/A 40 3 31 N/A N/A 2500 N/A UNITS REQUIRED vertical break GUARANTEED

2.16

N/A

TECHNICAL DATA SCHEDULE GROUNDING SWITCH 362 kV, 40 kA CODE NO: 4115 ITEM 3.0 3.1 3.2 3.3 4.0 4.1 4.2 4.3 4.4 4.5 4.6 4.7 5.0 5.1 5.2 5.3 5.4 5.5 5.6 5.7 5.8 5.9 5.10 6.0 6.1 6.2 DESCRIPTION Operating mechanism Motor voltage Number of auxiliary contacts available Number of mechanism Weight and dimensions Distance between poles Height of a pole Height of the support structure Total height Length of a pole Weight of a pole Weight of the hand mechanism Accessories Local/remote selector switch Local manual and electrical operation devices Light, heater and service outlet in hand operated mechanism enclosure MCB protected motor and control circuits Motor contactor Test switches (dc) Terminal blocks Weatherproof corrosion resistant enclosure Mounting brackets and hardware Arcing horns Grounding blades Operated by Number of auxiliary contacts available N/A N/A N/A N/A N/A yes IP 65 yes yes Wheel or torsion bar 8 NO, 8 NC mm mm mm mm mm kg kg 2500 Vdc N/A N/A N/A UNITS REQUIRED GUARANTEED

TECHNICAL DATA SCHEDULE GROUNDING SWITCH 362 kV, 40 kA CODE NO: 4115 ITEM 7.0 8.0 DESCRIPTION Type test reports Installation UNITS REQUIRED to be included in bid Outdoor, desertic/tropical environment GUARANTEED

DISCONNECT SWITCH 145 kV, 31.5KA 2000 A

TECHNICAL DATA SCHEDULE DISCONNECT SWITCH 145 kV, 31.5KA,2000 A ITEM 1.0 1.1 1.2 1.3 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11 2.12 3.0 3.1 3.2 3.3 3.4 4.0 4.1 4.2 DESCRIPTION Manufacturer Type Model no Country of origin Nominal characteristics Rated System voltage Rated maximum voltage Lightning impulse withstand voltage Power frequency withstand voltage, 1 m. dry/wet Rated frequency Number of poles Rated current Short time current withstand during Creepage distance to earth Opening time Closing time Insulator designation (IEC 273) Operating mechanism Motor voltage Number of auxiliary contacts available Number of mechanism Main disconnect hand operated by Weight and dimensions Distance between poles Height of a pole mm mm Vdc KV kV kV kV Hz A kA s mm/kV s s 132 145 650 275 50 3 2000 31.5 3 31 < 30 < 30 motor and manual 110 8 NO, 8 NC wheel or crank UNITS REQUIRED Specify Center break GUARANTEED

TECHNICAL DATA SCHEDULE DISCONNECT SWITCH 145 kV, 31.5KA,2000 A ITEM 4.3 4.4 4.5 4.6 4.7 5.0 5.1 5.2 5.3 5.4 5.5 5.6 5.7 5.8 5.9 5.10 DESCRIPTION Height of the support structure Total height Length of a pole Weight of a pole Weight of the motor mechanism Accessories Local/Distance command selector switch Local manual and electrical operation devices Light, heater and service plug in operating mechanism enclosure MCB protected motor and control circuits Motor contactor Test switches (dc) Terminal blocks Weatherproof corrosion resistant enclosure Mounting brackets and hardware Arcing horns Yes Yes Yes Yes Yes Yes Yes IP 65 Yes For power transformer no load switching to be included in bid ISO 9001 UNITS mm mm mm kg kg REQUIRED 2500 GUARANTEED

6.0 7.0

Type test reports Quality control

8.0

Installation

Outdoor, desertic/tropical environment

3.2

DISCONNECT SWITCH 145 kV, 31.5KA, 2000 A WITH GROUNDING BLADES

TECHNICAL DATA SCHEDULE DISCONNECT SWITCH 145 kV, 31.5KA, 2000 A WITH GROUNDING BLADES CODE NO: 4119 ITEM 1.0 1.1 1.2 1.3 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11 2.12 2.13 DESCRIPTION Manufacturer Type Model no Country of origin Nominal characteristics Rated System voltage Rated maximum voltage Lightning impulse withstand voltage Power frequency withstand voltage, 1 m. dry/wet Rated frequency Number of poles Rated current Short time current withstand ability during Creepage distance to earth Opening time Closing time Insulator designation (IEC 273) Grounding switch rated inductive (electromagnetic) breaking current at breaking voltae Grounding switch rated capacitive (electrostatic) breaking current at breaking voltage Operating mechanism Motor voltage Number of auxiliary contacts available Vdc 110 8 NO, 8 NC KV kV kV kV Hz A kA s mm/kV s s A kV A kV 132 145 650 275 50 3 2000 31.5 3 31 < 30 < 30 UNITS REQUIRED center break GUARANTEED

2.14

3.0 3.1 3.2

TECHNICAL DATA SCHEDULE DISCONNECT SWITCH 145 kV, 31.5KA, 2000 A WITH GROUNDING BLADES CODE NO: 4119 ITEM 3.3 3.4 4.0 4.1 4.2 4.3 4.4 4.5 4.6 4.7 5.0 5.1 5.2 5.3 5.4 5.5 5.6 5.7 5.8 5.9 5.10 5.11 6.0 6.1 6.2 6.3 7.0 DESCRIPTION Number of mechanism Main disconnector hand operated by Weight and dimensions Distance between poles Height of a pole Height of the support structure Total height Length of a pole Weight of a pole Weight of the motor mechanism Accessories Local/Distance command selector switch Local manual and electrical operation devices Light, heater and service plug in operating mechanism enclosure MCB protected motor and control circuits Motor contactor Test switches (dc) Terminal blocks Weatherproof corrosion resistant enclosure Mounting brackets and hardware Mechanical interlock between disconnect switch and grounding blades Arcing horns Grounding blades Operated by Mounting brackets and hardware Number of auxiliary contacts available Type test reports Wheel or torsion bar yes 8 NC, 8 NO to be included in bid yes yes yes yes yes yes yes IP 65 yes yes yes mm mm mm mm mm kg kg 2500 UNITS REQUIRED wheel or crank GUARANTEED

TECHNICAL DATA SCHEDULE DISCONNECT SWITCH 145 kV, 31.5KA, 2000 A WITH GROUNDING BLADES CODE NO: 4119 ITEM 9.0 10.0 DESCRIPTION Quality control Installation UNITS REQUIRED ISO 9001 Outdoor, desertic/tropical area GUARANTEED

3.3

DISCONNECT SWITCH 36 kV, 25KA, 1250 A

TECHNICAL DATA SCHEDULE DISCONNECT SWITCH 36 kV, 25KA, 1250 A ITEM 1.0 1.1 1.2 1.3 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 3.0 3.1 DESCRIPTION Manufacturer Type Model n
o

UNITS -

REQUIRED Specify -

GUARANTEED

Country of origin Nominal characteristics Rated system voltage Rated maximum voltage Lightning impulse withstand voltage Power frequency withstand voltage (1 min) Rated frequency Number of poles Rated current Short time current withstandability during Creepage distance to earth Insulator designation (IEC 273) Operating mechanism disconnect switch

KV KV kV peak kV RMS Hz A kA s mm/kV -

33 36 170 70 50 3 1250 17.5 3 31 -

Linkage driven by torsion bar or lever from ground 6 NO, 6 NC

3.2 4.0 4.1 4.2 4.3 4.4

Number of auxiliary contacts available Weight and dimensions Height of a pole Height of support structure Length of a pole Weight of a pole

mm mm mm kg

TECHNICAL DATA SCHEDULE DISCONNECT SWITCH 36 kV, 25KA, 1250 A ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

5.0 5.2 6.0

Standards Quality control Installation ISO 9001 Outdoor, desertic/tropical environment

3.4

DISCONNECT SWITCH 36 kV, 25KA, 1250 A WITH GROUNDING BLADE

TECHNICAL DATA SCHEDULE DISCONNECT SWITCH 36 kV, 25KA, 1250 A WITH GROUNDING BLADE ITEM 1.0 1.1 1.2 1.3 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 3.0 3.1 DESCRIPTION Manufacturer Type Model no Country of origin Nominal characteristics Rated system voltage Rated maximum voltage Lightning impulse withstand voltage Power frequency withstand voltage (1 min) Rated frequency Number of poles Rated current Short time current withstand ability during Creepage distance to earth Insulator designation (IEC 273) Operating mechanism disconnect switch Linkage driven by torsion bar or lever from ground Linkage driven by torsion bar or lever from ground 6 NO, 6 NC kv kV kV peak kV RMS Hz A kA s mm/kV 33 36 170 70 50 3 1250 25 3 31 UNITS REQUIRED Specify GUARANTEED

grounding blade

3.2 4.0 4.1 4.2 4.3 4.4

Number of auxiliary contacts available at each (discon. sw. & grounding blade) Weight and dimensions Height of a pole Height of support structure Length of a pole Weight of a pole

mm mm mm kg

TECHNICAL DATA SCHEDULE DISCONNECT SWITCH 36 kV, 25KA, 1250 A WITH GROUNDING BLADE ITEM 5.2 6.0 DESCRIPTION Quality control Installation UNITS REQUIRED ISO 9001 Outdoor, desertic/tropical environment GUARANTEED

3.5

FUSED DISCONNECT HOLDER 36 kV, 25KA, 200 A

TECHNICAL DATA SCHEDULE FUSED DISCONNECT HOLDER 36 kV, 25KA, 200 A ITEM 1.0 1.1 1.2 1.3 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11 2.12 3.0 3.1 4.0 4.1 4.2 4.3 5.0 DESCRIPTION Manufacturer Type Model n
o

UNITS -

REQUIRED Specify Specify

GUARANTEED

Country of origin Nominal characteristics Rated system voltage Rated maximum voltage Lightning impulse withstand voltage Power frequency withstand voltage (1 min) Rated frequency Number of poles Rated current Short time current withstand ability during Creepage distance to earth Fuseholder provided with fuse Insulator designation (IEC 273) Fuse rating and characteristic Operating mechanism Number of auxiliary contacts available Weight and dimensions Height of a pole Length of a pole Weight of a pole Type test reports number

kv kV kV peak kV RMS Hz A kA s mm/kV A

33 36 170 70 50 1 200 25 3 31 Yes 10 Insulated rod

4 NO, 4 NC

mm mm kg -

To be included in bid

TECHNICAL DATA SCHEDULE FUSED DISCONNECT HOLDER 36 kV, 25KA, 200 A ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

7.0 8.0

Quality control Installation

ISO 9001 Outdoor, desertic/tropical environment to be mounted on substation gantry structure

4.1

SURGE ARRESTER 120 kV, 145KV, WITH DISCHARGE COUNTER

TECHNICAL DATA SCHEDULE SURGE ARRESTER 120 kV, WITH DISCHARGE COUNTER ITEM 1.0 1.1 1.2 1.3 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 3.0 3.1 DESCRIPTION Manufacturer Type Model Country of origin Nominal characteristics Rated max. network operating voltage Rated operating voltage (Ur) Rated continuous operating voltage (Uc) Rated discharge current (peak) Switching impulse current (peak) Line discharge class (IEC 99-4) Rated frequency Protection characteristics Max. residual voltages - for a steep impulse current, 1 s front, 10 kA - for a lightning impulse current, 8/20 s, 10 kA - for a switching impulse current, 30/60 s, 0,5 kA 3.2 4.0 4.1 4.2 4.3 Energy dissipation capacity Operating performances High current impulse withstand (4/10 s) Temporary over voltage withstand (for 10 s) Line discharge current withstand: - Peak duration - Line characteristic impedance - Charging voltage (peak value) s ohms kV kA kV 100 120 Kv Kv kV kJ/kV 350 300 260 kV kV kV kA kA Hz 145 120 92 10 0.5 3 50 UNITS REQUIRED station metal oxide gapless GUARANTEED

TECHNICAL DATA SCHEDULE SURGE ARRESTER 120 kV, WITH DISCHARGE COUNTER ITEM 5.0 DESCRIPTION Insulation levels - Lightning impulse withstand voltage - Power frequency withstand voltage (1m wet) - Creepage distance kV kV mm/kV 550 185 31 UNITS REQUIRED GUARANTEED

- Cantilever strength - Torsion strength 6.0 Pressure relief capacity - Current amplitude (rms) - X/R, asymmetry factor - Current duration 7.0 8.0 External radio interference voltage (RIV) Weights and dimensions: - arrester height - arrester diameter weight 9.0 9.1 9.2 9.3 9.4 10.0 11.0 Accessories Mounting hardware Ground connector Insulating bases Discharge counter model Type test reports number Installation

kN N-m

kA s

31.5 17 0.2 N/A

mm mm kg

Yes Yes Yes To be included with bid Outdoor, in desertic/tropical environment

4.2

SURGE ARRESTER 30 kV, WITH DISCHARGE COUNTER

TECHNICAL DATA SCHEDULE SURGE ARRESTER 30 kV, WITH DISCHARGE COUNTER ITEM 1.0 1.1 1.2 1.3 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 3.0 3.1 DESCRIPTION Manufacturer Type Model Country of origin Nominal characteristics Rated max. network operating voltage Rated operating voltage (Ur) Rated continuous operating voltage (Uc) Rated discharge current (peak) Switching impulse current (peak) Line discharge class (IEC 99-4) Rated frequency Protection characteristics Max. residual voltages - for a steep impulse current, 1 s front, 10 kA - for a lightning impulse current, 8/20 s, 10 kA - for a switching impulse current, 30/60 s, 0,5 kA 3.2 4.0 4.1 4.2 4.3 Energy dissipation capacity Operating performances High current impulse withstand (4/10 s) Temporary over voltage withstand (for 10 s) Line discharge current withstand: - Peak duration - Line characteristic impedance - Charging voltage (peak value) 5.0 Insulation levels s ohms kV kA kV 100 30 kV kV kV kJ/kV 90 80 65 kV kV kV kA kA Hz 36 30 24 10 0.5 3 50 UNITS REQUIRED station metal oxide gapless GUARANTEED

TECHNICAL DATA SCHEDULE SURGE ARRESTER 30 kV, WITH DISCHARGE COUNTER ITEM DESCRIPTION - Lightning impulse withstand voltage - Power frequency withstand voltage (1m wet) - Creepage distance UNITS kV kV mm/kV REQUIRED 170 70 31 GUARANTEED

- Cantilever strength - Torsion strength 6.0 Pressure relief capacity - Current amplitude (rms) - X/R, asymmetry factor - Current duration 7.0 8.0 External radio interference voltage (RIV) Weights and dimensions: - arrester height - arrester diameter weight 9.0 9.1 9.2 9.3 9.4 10.0 11.0 Accessories Mounting hardware Ground connector Insulating bases Discharge counter model Type test reports number Installation

kN N-m

kA s

17.5 17 0.2 N/A

mm mm kg

Yes Yes Yes To be included with bid Outdoor, in desertic/tropical environment

5.1

CAPACITOR VOLTAGE TRANSFORMER 132KV TECHNICAL DATA SCHEDULE CAPACITOR VOLTAGE TRANSFORMER 132 kV

ITEM

DESCRIPTION

UNITS

REQUIRED

GUARANTEED

1.0 1.1 1.2 2.0 2.1 2.1.1 2.1.2 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9

Manufacturer Type Model n


o

Specify -

Nominal characteristics Voltage Rated voltage Rated voltage class Rated frequency Network neutral grounding Rated voltage factor for 30 s Rated lightning impulse withstand Power frequency withstand voltage (1 min) Creepage distance Capacitance C1 and C2 Series reactor - inductance range - resistance range mH ohms 132kV/3 : 0,11kV/3
: 0,11kV/3 (: 0,11kV/3)

kV kV Hz kV kV mm/kV pf

132 145 50 Effective 1,5 650 275 31 -

2.10

Transformation ratio

2.11

Transformer characteristics - HV/LV turn ratio range - Normal operating flux density tesla kV V 132/3 110/3

2.12 2.13 2.14

Primary voltage Secondary voltage Winding accuracy: - metering class - protection class - burden (simultaneous on each winding)

VA -

0,2 3P 50 2 (3)

2.15

Number of secondary winding

TECHNICAL DATA SCHEDULE CAPACITOR VOLTAGE TRANSFORMER 132 kV


ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

2.16 2.17 2.18 3.0 3.1 3.2 3.3 3.4 3.5 4.0 5.0

Winding conductor Circuit Diagram HV Terminal Connector for Weights and Dimensions Weight for operation Weight for transport Height Shipping dimensions (H x W x D) Outline drawing number Type tests reports N Standards

Cu To be enclosed with bid TBA

kg kg m m -

To be enclosed with bid To be enclosed with bid IEC60186 IEC 60694 IEC 60947-1 ISO 9001 Outdoor, in substation switchyard

6.0 7.0

Quality control Installation

5.2

CURRENT TRANSFORMER, 132KV, 300/400/600/800 A TECHNICAL DATA SCHEDULE CURRENT TRANSFORMER 132 kV, 300/400/600/800A

ITEM

DESCRIPTION

UNITS

REQUIRED

GUARANTEED

1.0 1.1 1.2

Manufacturer Type Model no -

Specify Oil or SF6 -

2.0 2.1 2.1.1 2.1.2 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11 2.12 2.13

Nominal characteristics Voltage Rated max. operating voltage Rated voltage class Rated frequency Network neutral grounding Heating limit at maximum ambient temperature Rated current Short-circuit current capability (1 s) Rated lightning impulse withstand Power frequency withstands voltage (1 min.) Creepage distance Primary rated currents Secondary rated current Number of windings Accuracy class: - winding n 1 (metering class) - winding n 2 to 4 (protection class) - burden 0,2 acc. to CT calculation 20 VA Cu kV KV Hz C A kA kV kV mm/kV A A 132 145 50 effective 55 300/400/600/800 31.5 650 275 31 300/400/600/800 1 4

2.14

Winding conductor

TECHNICAL DATA SCHEDULE CURRENT TRANSFORMER 132 kV, 300/400/600/800A


ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

2.15

Transient performance - class - rated S.C. current factor - primary time constant - secondary C.T. time constant - Duty cycle - resistive burden - secondary C.T. resistance - transient dimensioning factor - remanence factor - equivalent limiting secondary EMF - saturation curve

p.u. ms ms ohms ohms V -

TPX or TPY 20 45 C-0,075s-0-0,3sC-0,075s-0 2,5 to be enclosed with bid TBA Yes

2.16 2.17 3.0 3.1 3.2 3.3 3.4 3.5 4.0 5.0

HV Terminal Connector for LV Terminal Voltage Limiting Device Weights and Dimensions Weight for operation Weight for transport Height Shipping dimensions (H x W x D) Outline drawing number Type tests reports N Standards

kg kg m m -

To be enclosed with bid To be enclosed with bid IEC 60044 IEC 60694 IEC 60947-1 IEC 60376 ISO 9001 Outdoor in substation switchyard

6.0 7.0

Quality control Installation

5.3

VOLTAGE TRANSFORMER 33KV 400/600/800/1200A TECHNICAL DATA SCHEDULE VOLTAGE TRANSFORMER 33 kV 400/600/800/1200A

ITEM

DESCRIPTION

UNITS

REQUIRED

GUARANTEED

1.0 1.1 1.2 1.3 2.0 2.1 2.1.1 2.1.2 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10

Manufacturer Type Model no Country of origin Nominal characteristics Voltage Rated voltage Rated maximum voltage class Rated frequency Network neutral grounding Rated voltage factor for 30 s Rated lightning impulse withstand Power frequency withstand voltage (1 min) Creepage distance Design Transformation ratio: Transformer characteristics - HV/LV turn ratio range - Normal operating flux density tesla kV V kV kV Hz kV kV mm/kV -

Specify -

33 36 50 Effective 1,5 170 70 31 Inductive 33kV/3 : 0,11kV/3


: 0,11kV/3

33/3 110/3

2.11 2.12 2.13

Primary voltage Secondary voltage Winding accuracy: - metering class - protection class - burden (simultaneous on each winding)

VA -

0,2 3P 50 2 Cu

2.14 2.15

Number of secondary winding Winding conductor

TECHNICAL DATA SCHEDULE VOLTAGE TRANSFORMER 33 kV 400/600/800/1200A


ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

2.16 2.17 3.0 3.1 3.2 3.3 3.4 3.5 4.0 5.0

Circuit Diagram HV Terminal Connector for Weights and Dimensions Weight for operation Weight for transport Height Shipping dimensions (H x W x D) Outline drawing number Type tests reports N Standards

To be enclosed with bid TBA

kg kg m m -

To be enclosed with bid To be enclosed with bid IEC60186 IEC 60694 IEC 60947-1 ISO 9001 Outdoor, in substation switchyard

6.0 7.0

Quality control Installation

5.4

CURRENT TRANSFORMER, 33KV, 400/600/800/1200 A TECHNICAL DATA SCHEDULE CURRENT TRANSFORMER 33KV, 400/600/800/1200 A CODE NO: 4135

ITEM

DESCRIPTION

UNITS

REQUIRED

GUARANTEED

1.0 1.1 1.2 1.3 2.0 2.1 2.1.1 2.1.2 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11 2.12 2.13

Manufacturer Type Model no Country of origin Nominal characteristics Voltage Rated max. operating voltage Rated voltage class Rated frequency Network neutral grounding Heating limit at maximum ambient temperature Rated current Short-circuit current capability (1 s) Rated lightning impulse withstand Power frequency withstands voltage (1 min.) Creepage distance Primary rated current Secondary rated current Number of windings Accuracy class: - winding n 1 (metering class) - winding n 2 & 3 (protection class) - burden kV KV Hz C A kA kV kV mm/k V A A -

Specify Oil or SF6 -

33 36 50 effective 55 400/600/800/1200 25 170 70 31 400/600/800/1200 1 4

0,2 acc. to CT calculation 20 VA Cu

2.14

Winding conductor

TECHNICAL DATA SCHEDULE CURRENT TRANSFORMER 33KV, 400/600/800/1200 A CODE NO: 4135
ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

2.15

Transient performance - class - rated S.C. current factor - primary time constant - secondary C.T. time constant - Duty cycle - resistive burden - secondary C.T. resistance - transient dimensioning factor - remanence factor - equivalent limiting secondary EMF - saturation curve

p.u. ms ms ohms ohms V -

TPX or TPY 20 45 C-0,075s-0-0,3s-C0,075s-0 2,5 to be enclosed with bid TBA Yes

2.16 2.17 3.0 3.1 3.2 3.3 3.4 3.5 4.0 5.0

HV Terminal Connector for LV Terminal Voltage Limiting Device Weights and Dimensions Weight for operation Weight for transport Height Shipping dimensions (H x W x D) Outline drawing number Type tests reports N Standards

kg kg m m -

To be enclosed with bid To be enclosed with bid IEC 60044 IEC 60694 IEC 60947-1 IEC 60376 ISO 9001 Outdoor in substation switchyard

6.0 7.0

Quality control Installation

6.0
6.1

TECHNICAL DATA SCHEDULES


AUTOMATIC TRANSFER PANEL 415 Vac

TECHNICAL DATA SCHEDULE AUTOMATIC TRANSFER PANEL - 415 Vac ITEM 1.0 1.1 1.2 1.3 2.0 2.1 2.1.1 2.1.2 2.1.3 2.1.4 2.1.5 2.1.6 DESCRIPTION Manufacturer Type Catalogue N Country of origin Nominal Characteristics Busbar Rated voltage Voltage class Rated current Short time withstand (3 s) Frequency Insulated phase buses - dimensions 2.1.7 Insulated neutral bus - dimensions 2.1.8 Bus insulator support: - material - mechanical cantilever strength 2.1.9 Ground bus - dimensions 2.1.10 2.2 2.2.1 2.2.2 2.2.3 Bus material Motorized Circuit Breakers Manufacturer Type Interrupting medium air kN Mm x mm 1 Cu or Al V V A kA RMS Hz mm x mm mm x mm 415/240, 4 W 415 500 14 50 3 1 UNITS REQUIRED GUARANTEED

TECHNICAL DATA SCHEDULE AUTOMATIC TRANSFER PANEL - 415 Vac ITEM 2.2.4 2.2.5 2.2.6 2.2.7 2.2.8 2.2.9 2.2.10 2.2.11 2.2.12 DESCRIPTION Quantity (provision for 1 spare) Number of poles Voltage class Rated voltage Rated current Rated interrupting capacity Interrupting time Closing time Mechanism UNITS V V A kA ms ms REQUIRED 3 (1) 3 415 415 400 14 Motor and spring operated 110 2 NO, 2NC yes yes yes 2 NO, 2 NC yes yes Drawout with safety shutters GUARANTEED

2.2.13 2.2.14 2.2.15 2.2.16

Auxiliary voltage Spring loading time Auxiliary contacts (for each 52 x and 33 x) Breaker protection characteristics - relay type - inverse time phase and ground overcurrent - instantaneous phase and ground overcurrent - signalling contacts - manual reset flag

Vdc S -

2.2.17

Current sensors - ratio and accuracy for phase current - ratio and accuracy for ground current Construction Interlock - no insertion with closed breaker - breaker trip while extracting

2.2.18 2.2.19

yes yes

TECHNICAL DATA SCHEDULE AUTOMATIC TRANSFER PANEL - 415 Vac ITEM 2.3 DESCRIPTION Transfer control features - manufacturer - type - manual and automatic local and remote transfer control - from main to backup or emergency (automatic or manual transfer) with time delay and indication of selection - transfer logic based on voltage and frequency sensing or periodic exercising of backup and emergency - return to normal supply manually or automatically when the main or backup power supply has been restablished after a time delay - blocked transfer upon protective trip with alarm and manual reset - indicating lamps for presence of voltage of main, backup and emergency supply - auxiliary contacts for Purchaser's use - emergency diesel generator periodic exercising - diesel generator starting delay - diesel generator shut down delay 2.4 2.4.1 2.4.2 Enclosures Type Construction Free-standing IP 54 Metal clad with separate compartments To be enclosed with bid Floor 2/0 to 500 MCM Cu UNITS REQUIRED Programmable logic controller yes yes GUARANTEED

yes

yes

yes yes yes yes yes yes

2.4.3 2.4.4 2.4.5

Internal layout drawing No. Cable entrance Connectors for feeder cable

TECHNICAL DATA SCHEDULE AUTOMATIC TRANSFER PANEL - 415 Vac ITEM 2.5 2.6 DESCRIPTION Padlock or key lock breakers Metering and control circuit protection Weight and dimensions Weight For service For transport 3.2 Dimensions (H x W x L) For service For transport 4.0 5.0 5.1 N/A Standards Manufacturing IEC 60439 IEC 60715 IEC 60947 ISO 9001 Indoor, inside control building mm mm kg kg UNITS REQUIRED yes Molded case circuit breakers GUARANTEED

3.0 3.1

5.2 6.0

Quality control Installation

6.2

DISTRIBUTION PANEL, 415/240 Vac, TYPE 2

TECHNICAL DATA SCHEDULE DISTRIBUTION PANEL - 415/240 Vac, TYPE 2 ITEM 1.0 1.1 1.2 1.3 2.0 2.1 2.1.1 2.1.2 2.1.3 2.1.4 2.1.5 2.1.6 DESCRIPTION Manufacturer Type Catalogue N Country of origin Nominal characteristics Busbar Rated voltage Voltage class Rated current Short time withstand (3 s) Frequency Insulated phase buses: - dimensions 2.1.7 Insulated neutral bus: - dimensions 2.1.8 Bus insulator support: - material - mechanical cantilever strength 2.1.9 Ground bus: - dimensions 2.1.10 2.2 2.2.1 Bus material Main breaker Manufacturer KN mm x mm Cu or Al V V A kA RMS Hz mm x mm mm x mm 415/240, 4 W 415 300 14 50 3 1 UNITS REQUIRED Specify Specify GUARANTEED

2.2.2 2.2.3 2.2.4

Type Quantity Voltage class

thermal magnetic 1 415

TECHNICAL DATA SCHEDULE DISTRIBUTION PANEL - 415/240 Vac, TYPE 2 ITEM 2.2.5 2.2.6 2.2.7 2.2.8 2.3 2.3.1 2.3.2 2.3.3 2.3.4 2.3.5 2.3.6 DESCRIPTION Rated voltage Rated current Auxiliary contacts Rated interrupting capacity Distribution breakers Manufacturer Type Voltage class Rated voltage Rated interrupting capacity Rated current: 2.4 2.4.1 3 pole, 100A 3 pole, 50A 3 pole, 30A 1 pole, 15A space provision for 2 5 10 18 4 x 3 P30A, 6 x 1 P15A V V kA RMS 415 415/240 14 UNITS V A kA RMS REQUIRED 415 300 2, type C 14 GUARANTEED

Instruments and control Digital multimeter with RS 232 c interface with current transformers PM 3710 ACM, EI Futura + or equivalent

2.4.2

Undervoltage relay: - manufacturer - type - voltage range setting (typical) - time range setting (typical) % S 50-100 0-20 Yes Yes -

2.4.3 2.4.4

Bus neon or led pilot light Ground fault detector relay - manufacturer - type - setting range - set current sensor ratio and accurancy

TECHNICAL DATA SCHEDULE DISTRIBUTION PANEL - 415/240 Vac, TYPE 2 ITEM 2.5 2.6 2.7 2.7.1 2.7.2 2.7.3 2.7.4 3.0 3.1 Enclosure Cable entrance Lighting Contactors 3p, 20a Photocell Test/Auto Switches Test Push Buttons Weight and dimensions Weight - for service - for transport 3.2 Dimensions (H x W x L) - for service - for transport 4.0 5.0 5.1 5.2 6.0 N/A Standards Manufacturing Quality control Installation IEC 60947 IEC 60715 ISO 9001 indoor, inside control building mm mm kg kg 2 2 2 2 DESCRIPTION UNITS REQUIRED free-standing IP 54 Floor GUARANTEED

6.3

DISTRIBUTION PANEL, 415/240 Vac, TYPE 1

TECHNICAL DATA SCHEDULE DISTRIBUTION PANEL - 415/240 Vac, TYPE 1 CODE NO: 4342 ITEM 1.0 1.1 1.2 1.3 2.0 2.1 2.1.1 2.1.2 2.1.3 2.1.4 2.1.5 2.1.6 DESCRIPTION Manufacturer Type Catalogue N Country of origin Nominal characteristics Busbar Rated voltage Voltage class Rated current Short time withstand (3 s) Frequency Insulated phase buses: - dimensions 2.1.7 Insulated neutral bus: - dimensions 2.1.8 Bus insulator support: - material - mechanical cantilever strength 2.1.9 Ground bus: - dimensions 2.1.10 2.2 2.2.1 2.2.2 2.2.3 2.2.4 2.2.5 Bus material Main breaker Manufacturer Type Quantity Voltage class Rated voltage V V thermal magnetic 1 415 415 kN mm x mm Cu or Al V V A kA RMS Hz mm x mm mm x mm 415/240, 4 W 415 300 14 50 3 1 UNITS REQUIRED Specify GUARANTEED

TECHNICAL DATA SCHEDULE DISTRIBUTION PANEL - 415/240 Vac, TYPE 1 CODE NO: 4342 ITEM 2.2.6 2.2.7 2.2.8 2.3 2.3.1 2.3.2 2.3.3 2.3.4 2.3.5 2.3.6 DESCRIPTION Rated current Auxiliary contacts Rated interrupting capacity Distribution breakers Manufacturer Type Voltage class Rated voltage Rated interrupting capacity Rated current: 2.4 2.4.1 3 pole, 100A 3 pole, 50A 3 pole, 30A 1 pole, 20A space provision for 2 10 10 30 4 x 3 P30A, 6 x 1 P15A V V kA RMS 415 415/240 14 UNITS A kA RMS REQUIRED 300 1, type C 14 GUARANTEED

Instruments and control Digital multimeter with RS 232 c interface with current transformers PM 3710 ACM, EI Futura + or equivalent

2.4.2

Undervoltage relay: - manufacturer - type - voltage range setting (typical) - time range setting (typical) % s 50-100 0-20 Yes Yes -

2.4.3 2.4.4

Bus neon or led pilot light Ground fault detector relay - manufacturer - type - setting range - set current sensor ratio and accuracy

TECHNICAL DATA SCHEDULE DISTRIBUTION PANEL - 415/240 Vac, TYPE 1 CODE NO: 4342 ITEM 2.5 2.6 2.7 2.7.1 2.7.2 2.7.3 2.7.4 3.0 3.1 Enclosure Cable entrance Lighting Contactors 3p, 20a Photocell Test/Auto Switches Test Push Buttons Weight and dimensions Weight - for service - for transport 3.2 Dimensions (H x W x L) - for service - for transport 4.0 5.0 5.1 5.2 6.0 N/A Standards Manufacturing Quality control Installation IEC 60947 IEC 60715 ISO 9001 indoor, inside control building mm mm kg kg 2 2 2 2 DESCRIPTION UNITS REQUIRED free-standing IP 54 Floor GUARANTEED

6.4

DISTRIBUTION PANEL, 110 Vdc, TYPE 2

TECHNICAL DATA SCHEDULE DISTRIBUTION PANEL, 110 Vdc, TYPE 2 ITEM 1.0 1.1 1.2 1.3 2.0 2.1 2.1.1 2.1.2 2.1.3 2.1.4 2.1.5 DESCRIPTION Manufacturer Type Catalogue n Country of origin Nominal Characteristics Busbar Rated voltage Voltage class Rated current Short time withstand (3 s) Positive and negative insulated busses - dimensions 2.1.6 Ground bus - dimensions 2.1.7 Bus insulator support: - material - mechanical strength 2.1.8 2.2 2.2.1 2.2.2 2.2.3 2.2.4 2.2.5 2.2.6 2.2.7 Bus material Main breaker Manufacturer Type Poles Rated voltage Rated current Auxiliary contacts Rated interrupting capacity Vdc Adc kAdc thermal magnetic 2 250 225 2, type C 10 kN Cu or Al Vdc Vdc Adc kAdc mm x mm mm x mm 110 250 225 10 2 1 UNITS REQUIRED Specify Specify GUARANTEED

TECHNICAL DATA SCHEDULE DISTRIBUTION PANEL, 110 Vdc, TYPE 2 ITEM 2.3 2.3.1 2.3.2 2.3.3 2.3.4 2.3.5 DESCRIPTION Distribution breakers Manufacturer Type Number of poles Voltage class Rated current: - 2P 100 A - 2 P 40 A - 2P 20 A - space provision for 2.3.6 2.4 2.4.1 2.4.2 2.4.3 Rated interrupting capacity Instruments and control Digital ammeter with shunt Digital voltmeter Undervoltage relay: - manufacturer - type - voltage range setting (typical) - time range setting (typical) 2.4.4 2.4.5 2.4.6 2.5 2.6 3.0 3.1 Bus neon or led pilot light Protecting fuses Bus voltage transducer 4 - 20 mA Enclosure type Cable entrance Weight and dimensions Weight - for service - for transport 3.2 Dimensions (H x W x L) kg kg V s A yes yes yes 20-150 0-20 yes yes yes free-standing IP 54 floor kAdc 2 10 25 6 x 2P 20 A 10 Vdc thermal magnetic 2 250 UNITS REQUIRED GUARANTEED

TECHNICAL DATA SCHEDULE DISTRIBUTION PANEL, 110 Vdc, TYPE 2 ITEM - for service - for transport 4.0 5.0 5.1 5.2 6.0 N/A Standards Manufacturing Quality control Installation IEC 60715 IEC 60947 ISO 9001 indoor, inside the control building DESCRIPTION UNITS mm mm REQUIRED GUARANTEED

6.5

DISTRIBUTION PANEL, 110 Vdc, TYPE 1

TECHNICAL DATA SCHEDULE DISTRIBUTION PANEL, 110 Vdc, TYPE 1 CODE NO: 4353 ITEM 1.0 1.1 1.2 1.3 2.0 2.1 2.1.1 2.1.2 2.1.3 2.1.4 2.1.5 DESCRIPTION Manufacturer Type Catalogue n Country of origin Nominal Characteristics Busbar Rated voltage Voltage class Rated current Short time withstand (3 s) Positive and negative insulated busses - dimensions 2.1.6 Ground bus - dimensions 2.1.7 Bus insulator support: - material - mechanical strength 2.1.8 2.2 2.2.1 2.2.2 2.2.3 2.2.4 2.2.5 2.2.6 2.2.7 Bus material Main breaker Manufacturer Type Poles Rated voltage Rated current Auxiliary contacts Rated interrupting capacity Vdc Adc kAdc thermal magnetic 2 250 225 2, type C 10 kN Cu or Al Vdc Vdc Adc kAdc mm x mm mm x mm 110 250 225 10 2 1 UNITS REQUIRED Specify Specify GUARANTEED

TECHNICAL DATA SCHEDULE DISTRIBUTION PANEL, 110 Vdc, TYPE 1 CODE NO: 4353 ITEM 2.3 2.3.1 2.3.2 2.3.3 2.3.4 2.3.5 DESCRIPTION Distribution breakers Manufacturer Type Number of poles Voltage class Rated current: - 2P 100 A - 2 P 40 A - 2P 20 A - space provision for 2.3.6 2.4 2.4.1 2.4.2 2.4.3 Rated interrupting capacity Instruments and control Digital ammeter with shunt Digital voltmeter Undervoltage relay: - manufacturer - type - voltage range setting (typical) - time range setting (typical) 2.4.4 2.4.5 2.4.6 2.5 2.6 3.0 3.1 Bus neon or led pilot light Protecting fuses Bus voltage transducer 4 - 20 mA Enclosure type Cable entrance Weight and dimensions Weight - for service - for transport kg kg V s A yes yes yes 20-150 0-20 yes yes yes free-standing IP 54 floor kAdc 2 12 24 6 x 2P 20 A 10 Vdc Specify thermal magnetic 2 250 UNITS REQUIRED GUARANTEED

TECHNICAL DATA SCHEDULE DISTRIBUTION PANEL, 110 Vdc, TYPE 1 CODE NO: 4353 ITEM 3.2 DESCRIPTION Dimensions (H x W x L) - for service - for transport 4.0 5.0 5.1 5.2 6.0 N/A Standards Manufacturing Quality control Installation IEC 60715 IEC 60947 ISO 9001 indoor, inside control building mm mm UNITS REQUIRED GUARANTEED

6.6

DISTRIBUTION PANEL, 48 Vdc

TECHNICAL DATA SCHEDULE DISTRIBUTION PANEL, 48 Vdc ITEM 1.0 1.1 1.2 1.3 2.0 2.1 2.1.1 2.1.2 2.1.3 2.1.4 2.1.5 DESCRIPTION Manufacturer Type Catalogue N Country of origin Nominal Characteristics Busbar Rated voltage Voltage class Rated current Short time withstand (3 s) Positive and negative insulated busses - dimensions 2.1.6 Ground bus - dimensions 2.1.7 Bus insulator support: - material - mechanical strength 2.1.8 2.2 2.2.1 2.2.2 2.2.3 2.2.4 2.2.5 2.2.6 2.2.7 Bus material Main breaker Manufacturer Type Poles Rated voltage Rated current Auxiliary contacts Rated interrupting capacity Vdc Adc kAdc thermal magnetic 2 125 100 2, type C 10 kN Cu or Al Vdc Vdc Adc kAdc mm x mm mm x mm 48 125 100 10 2 1 UNITS REQUIRED GUARANTEED

TECHNICAL DATA SCHEDULE DISTRIBUTION PANEL, 48 Vdc ITEM 2.3 2.3.1 2.3.2 2.3.3 2.3.4 2.3.5 DESCRIPTION Distribution breakers Manufacturer Type Number of poles Voltage Class Rated current: - 2P 100 A - 2P 20 A - space provision for 2.3.6 2.4 2.4.1 2.4.2 2.4.3 Rated interrupting capacity Instruments and control Digital ammeter with shunt Digital voltmeter Undervoltage relay: - manufacturer - type - voltage range setting (typical) - time range setting (typical) 2.4.4 2.4.5 2.4.6 2.5 2.6 3.0 3.1 Bus neon or led pilot light Protecting fuses Bus voltage transducer 4 - 20 mA Enclosure type Cable entrance Weight and dimensions Weight - for service - for transport kg kg V s yes yes yes 10 - 60 0-20 yes yes yes free-standing IP 54 floor kAdc 2 14 8 x 2P 20 A 10 Vdc thermal magnetic 2 125 UNITS REQUIRED GUARANTEED

3.2

Dimensions (H x W x L)

TECHNICAL DATA SCHEDULE DISTRIBUTION PANEL, 48 Vdc ITEM - for service - for transport 4.0 5.0 5.1 5.2 6.0 N/A Standards Manufacturing Quality control Installation IEC 6071 IEC 60947 ISO 9001 indoor, inside control building DESCRIPTION UNITS mm mm REQUIRED GUARANTEED

6.7 CODES AND STANDARDS

IEC 60439 IEC 60715 IEC 60947 ISO 9001

Low-voltage switchgear and controlgear assemblies Dimensions of low-voltage switchgear and controlgear Low-voltage switchgear and controlgear Quality systems Model for Quality Assurance in design, development, production, installation and servicing.

7.0 TECHNICAL DATA SCHEDULES


7.1 STANDARD STEEL

TECHNICAL DATA SCHEDULE STANDARD STEEL ITEM 1.0 1.1 1.2 1.3 1.4 Material Type Use Manufacturer Grade Structural ASTM A 36 OR A 500 or equivalent DESCRIPTION UNITS REQUIRED GUARANTEED

1.5 2.0 2.1 2.2 2.3 2.4 2.5

Country of origin Chemical Composition Carbon Manganese Sulphur Phosphorous Others

% % % % %

3.0 3.1 3.2 3.3

Mechanical Properties Minimum ultimate strength Limit of elasticity Elongation at rupture for 200 mm sample kg/mm2 kg/mm2 % -

4.0 4.1 4.2

Galvanization Average quantity of material Specification g/m2 610 ASTM A123 or equivalent

7.2

HIGH STRENGTH STEEL

TECHNICAL DATA SCHEDULE HIGH STRENGTH STEEL ITEM 1.0 1.1 1.2 1.3 1.4 Material Grade Use Manufacturer Grade Structural ASTM A 572 or equivalent DESCRIPTION UNITS REQUIRED GUARANTEED

1.5 2.0 2.1 2.2 2.3 2.4 2.5

Country of origin Chemical Composition Carbon Manganese Sulphur Phosphorous Others

% % % % %

3.0 3.1 3.2 3.3

Mechanical Properties Minimum ultimate strength Limit of elasticity Elongation at rupture for 200 mm sample kg/mm2 kg/mm2 % -

4.0 4.1 4.2

Galvanisation Average quantity of material Specification g/m2 610 ASTM A123 or equivalent

7.3

NUTS AND BOLTS

TECHNICAL DATA SCHEDULE NUTS AND BOLTS

ITEM 1.0 1.1 1.2 1.3 1.4 Material Type Use

DESCRIPTION

UNITS

REQUIRED

GUARANTEED

Structural ASTM A 325 OR A 394 or equivalent -

Manufacturer Grade

1.5 2.0 2.1 2.2 2.3 2.4 2.5

Country of origin Chemical composition Carbon Manganese Sulphur Phosphorus Others

% % % % %

3.0 3.1 3.2 3.3

Mechanical Properties Minimum ultimate strength Proof load stress Elongation at rupture kg/mm2 kg/mm2 % -

4.0 4.1 4.2

Galvanization Average quantity of material Specification g/m2 500 ASTM A123 or equivalent

8.0 TECHNICAL DATA SCHEDULES


8.1 JUNCTION BOXES

TECHNICAL DATA SCHEDULE JUNCTION BOXES ITEM 1.0 1.1 1.2 1.3 2.0 2.1 2.2 2.3 2.4 2.5 3.0 3.1 3.2 3.3 3.4 3.5 4.0 DESCRIPTION Manufacturer Model Type Country of origin Enclosure Protection Mounting panel Padlockable door with handle Stainless steel Painted steel Accessories Asymmetric rails Plastic cable ducts Fuses and fuse holders Mini moulded circuit breaker Internal wiring Arrangement for C.T. junction box - 3 incoming terminal strips - 1 departing terminal strip - Cross connect wiring - Lamp and switch - Thermostat and space heater - Ground bus bar - Layout and wiring drawings Arrangement for V.T .and CVT junction box - 3 incoming terminal strips - 2 three poles mini circuit breakers (for each winding - 1 departing terminal strip - Lamp and switch - Thermostat and heater Yes Yes Yes Yes Yes Code 4502 yes yes yes yes yes yes see enclosed Code 4501 yes yes yes yes yes yes IP 65 Yes Yes C.Ts, V.Ts J.B. Lighting J.B. UNITS REQUIRED GUARANTEED

5.0

TECHNICAL DATA SCHEDULE JUNCTION BOXES ITEM DESCRIPTION - Ground busbar - Layout and wiring diagram 6.0 Lighting junction box - 1 terminal strip - 1 fuse for lighting fixture - 1 fuse with outlet - Ground busbar - Layout and wiring diagram Standards Quality control Installation UNITS REQUIRED yes see enclosed Code 4507, 4508 yes yes Code 4508 only yes see enclosed IEC 60947 ISO 9001 Outdoor on substation structure in desertic/tropical environment GUARANTEED

7.0 8.0 9.0

8.2

SWITCHYARD LIGHTING FIXTURE

TECHNICAL DATA SCHEDULE SWITCHYARD LIGHTING FIXTURE ITEM 1.0 1.1 1.2 1.3 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 3.0 4.0 5.0 DESCRIPTION Manufacturer Type Model n Country of origin Characteristics Rated voltage Minimum bulb power Bulb type Ballast Fixture components (reflector, refractor, top lens, flange etc) Mounting bracket for substation structure or pedestal Lighting pattem data Standards Quality control Installation V W 240 250 min Hi-pressure sodium Yes Yes To be enclosed with bid IEC 60598 ISO 9001 Outdoor in switchyard desertic/tropical environment substation UNITS REQUIRED GUARANTEED

8.3

POLE MOUNTED LIGHTING FIXTURE

TECHNICAL DATA SCHEDULE POLE MOUNTED LIGHTING FIXTURE ITEM 1.0 1.1 1.2 1.3 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 3.0 4.0 5.0 DESCRIPTION Manufacturer Type Model n Country of origin Characteristics Rated voltage Minimum bulb power Bulb type Ballast Fixture components Mounting bracket for pole Galvanized steel pole with accessories of 12 m height minimum Lighting pattem data Standards Quality control Installation V W 240 250 min Hi-pressure sodium Yes Yes yes yes To be enclosed with bid IEC 60598 ISO 9001 Outdoor in switchyard desertic/tropical environment Pole mounted UNITS REQUIRED GUARANTEED

9.0 TECHNICAL DATA SCHEDULES


9.1 BATTERIES, 110V dc, (400Ah as reference)

TECHNICAL DATA SCHEDULE BATTERIES 110 Vdc, 400 Ah ITEM 1.0 1.1 1.2 1.3 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11 DESCRIPTION Manufacturer Type Catalogue no Country of origin Nominal Characteristics Cell type Number of cells by Rated battery voltage Floating cell voltage per cell Floating charge current Equalizing cell voltage Rated A-h cell capacity at 25C (for 8 h discharge time) Cell end voltage at 25C (for A-h capacity) Number of positive plates Discharge current during 1 minute at rated end voltage Rated equalizing charge current - for 10 hours - for 1 hour 2.12 2.13 2.14 2.15 2.16 2.16.1 2.16.2 Number of charge/discharge cycles Internal cell resistance Short circuit current Life expectancy Container Container type Container material A A A Years > = 20 Vdc V A V A-h Vdc A Lead-Acid 50 110 2,17 to 2,25 2,3 to 2,33 600 min. 1,83 UNITS REQUIRED GUARANTEED

TECHNICAL DATA SCHEDULE BATTERIES 110 Vdc, 400 Ah ITEM 2.16.3 2.16.4 2.17 2.17.1 2.17.2 2.18 2.18.1 2.18.2 2.18.3 2.18.4 2.18.5 2.18.6 2.18.7 2.18.8 2.19 2.19.1 2.19.2 2.19.3 3.0 3.1 DESCRIPTION Terminal type Container dimensions (H x L x D) Electrolyte Type Annual water consumption Accessories Battery support Wall mounted cabinet with enclosed 300 A, 14 kA, 250 Vdc fuse Thermometer Electrolyte densimeter Battery voltmeter with loading resistance Anticorrosive grease Jumper for cell connections Isolated tools Characteristic data or curves charts to be supplied Voltage vs time at rated A-h Current vs time at rated A-h Temperature derating factor for battery capacity Weight and dimensions Weight - weight for service - weight for transport Dimensions (H x L x D) - dimensions for service - dimensions for transport N/A Standards Manufacturing IEC 60896 ANSI/IEEE 450 kg kg mm mm mm Set Set yes yes yes yes yes yes yes yes mL/y acid UNITS Mm REQUIRED GUARANTEED

3.2

4.0 5.0 5.1

TECHNICAL DATA SCHEDULE BATTERIES 110 Vdc, 400 Ah ITEM 5.2 DESCRIPTION Quality assurance UNITS REQUIRED ISO 9001 GUARANTEED

6.0

Installation

indoor, inside control building

9.2

BATTERY, 48 Vdc, (200 Ah as reference)

TECHNICAL DATA SCHEDULE BATTERIES 48 Vdc, 200 Ah ITEM 1.0 1.1 1.2 1.3 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11 DESCRIPTION Manufacturer Type Catalogue n
o

UNITS -

REQUIRED -

GUARANTEED

Country of origin Nominal Characteristics Cell type Number of cells by battery Rated battery voltage Floating cell voltage per cell Floating charge current Equalizing cell voltage Rated A-h cell capacity at 25C (for 8 h discharge time) Cell end voltage at 25C (for A-h capacity) Number of positive plates Discharge current during 1 minute at rated end voltage Rated equalizing charge current - for 10 hours - for 1 hour

Vdc V A V A-h Vdc A A

Lead-Acid 24 48 2,17 to 2,25 2,3 to 2,33 300 min. 1,83 -

A A A Years

> = 20

2.12 2.13 2.14 2.15 2.16 2.16.1 2.16.2 2.16.3

Number of charge/discharge cycles Internal cell resistance Short circuit current Life expectancy Container Container type Container material Terminal type

TECHNICAL DATA SCHEDULE BATTERIES 48 Vdc, 200 Ah ITEM 2.16.4 2.17 2.17.1 2.17.2 2.18 2.18.1 2.18.2 2.18.3 2.18.4 2.18.5 2.18.6 2.18.7 2.18.8 2.19 2.19.1 2.19.2 2.19.3 3.0 3.1 DESCRIPTION Container dimensions (H x L x D) Electrolyte Type Annual water consumption Accessories Battery support Wall mounted cabinet with enclosed 300 A, 14 kA, 250 Vdc fuse Thermometer Electrolyte densimeter Battery voltmeter with loading resistance Anticorrosive grease Jumper for cells connections Isolated tools Characteristic data or curves charts to be supplied Voltage vs time at rated A-h Current vs time at rated A-h Temperature derating factor for battery capacity Weight and dimensions Weight - weight for service - -weight for transport 3.2 Dimensions (H x L x D) - dimensions for service - dimensions for transport 4.0 N/A kg kg Mm mm mm Set Set yes yes yes yes yes yes yes yes mL/y acid UNITS Mm REQUIRED GUARANTEED

5.0 5.1

Standards Manufacturing IEC 60896 ANSI/IEEE

TECHNICAL DATA SCHEDULE BATTERIES 48 Vdc, 200 Ah ITEM DESCRIPTION UNITS REQUIRED 450 5.2 Quality assurance ISO 9001 GUARANTEED

6.0

Installation

Indoor inside control building

9.3

BATTERY CHARGER, 110 Vdc, (80 A as reference)

TECHNICAL DATA SCHEDULE BATTERY CHARGER 110 Vdc, 80A ITEM 1.0 1.1 1.2 1.3 2.0 2.1 DESCRIPTION Manufacturer Type Catalogue no Country of origin Nominal Characteristics Configuration Redundant w/automatic switchover Vac Hz A Vdc % 415/240, 4W 50 110 1 UNITS REQUIRED GUARANTEED

2.2 2.3 2.4 2.5 2.6

AC Supply Frequency of AC supply AC input current DC output voltage DC output voltage regulation with 0 to 100 % load, 10 % input voltage variation and 5 % frequency variation DC output current Maximum ripple without battery Floating range Equalizing range Equalizing time delay setting range Max. recharge time (80 %) of battery Equalizing/floating switching Current limiting adjustment Main-1 to Main-2 charger transfer Rectifier type Transformer: Type Power Two separate primary/secondary windings Primary/secondary voltage

2.7 2.8 2.9 2.10 2.11 2.12 2.13 2.14 2.15 2.16 2.17 2.17.1 2.17.2 2.17.3 2.17.4

A % Vdc Vdc hours hours % -

80 min. 5 max 105 150 105 150 6 48 10 manual and automatic 50 100 Manual and automatic thyristor

kVA Vac

Dry Yes -

TECHNICAL DATA SCHEDULE BATTERY CHARGER 110 Vdc, 80A ITEM 2.18 2.19 2.20 2.21 2.22 2.23 2.24 2.24.1 2.24.2 2.24.3 2.24.4 2.24.5 2.25 2.25.1 2.25.2 2.25.3 2.25.4 2.25.5 2.26 2.26.1 2.26.2 2.26.3 2.26.4 2.26.5 2.26.6 2.26.7 2.26.8 Efficiency Short circuit current proof Surge suppression AC & DC Reverse battery protection Meantime between failures MTBF Mean repair time MTR Input breakers Manufacturer Type Rated voltage Rated current Rated interrupting capacity Output breakers Manufacturer Type Rated voltage Rated current Rated interrupting capacity Instruments and indication Digital ammeter Digital voltmeter Ground fault alarm lamp and contact AC failure alarm lamp and contact Charger failure alarm lamp and contact Max./min. voltage alarm lamp and contact Equalizing/floating signalling lamps and contact AC "ON" signalling lamp and contact yes yes yes yes yes yes yes yes Vdc A kA Thermal magnetic 250 10 Vac A KA sym. Thermal magnetic 600 14 DESCRIPTION UNITS % h h REQUIRED Current limited yes yes > 10 000 <1 GUARANTEED

TECHNICAL DATA SCHEDULE BATTERY CHARGER 110 Vdc, 80A ITEM 2.26.9 2.26.10 2.27 3.0 3.1 DESCRIPTION Low battery voltage lamp and contact Manual operation selector contact Enclosure type Weight and dimensions Weight - weight for service - -weight for transport 3.2 Dimensions (L x W x D) - dimensions for service 4.0 5.0 5.1 - dimensions for transport N/A Standards Manufacturing IEC 60947, ANSI/NEMA PE 5 ISO 9001 indoor, inside control building kg kg mm mm mm UNITS REQUIRED yes yes free-standing, IP 50 GUARANTEED

5.2.2 6.0

Quality assurance Installation

9.4

BATTERY CHARGER, 48 Vdc, (60 A as reference)

TECHNICAL DATA SCHEDULE BATTERY CHARGER 48 Vdc, 60 A ITEM 1.0 1.1 1.2 1.3 2.0 2.1 DESCRIPTION Manufacturer Type Catalogue no Country of origin Nominal Characteristics Configuration Redundant w/automatic switchover Vac Hz A Vdc % 415/240, 4W 60 48 1 UNITS REQUIRED GUARANTEED

2.2 2.3 2.4 2.5 2.6

AC Supply Frequency of AC supply AC input current DC output voltage DC. output voltage regulation with 0 to 100 % load, 10 % input voltage variation and 5 % frequency variation DC output current Maximum ripple without battery Floating range Equalizing range Equalizing time delay setting range Max. recharge time (80 %) of battery Equalizing/floating switching Current limiting adjustment Main to backup charger transfer Rectifier type Transformer: Type Power Two separate primary/secondary windings Primary/secondary voltage

2.7 2.8 2.9 2.10 2.11 2.12 2.13 2.14 2.15 2.16 2.17 2.17.1 2.17.2 2.17.3 2.17.4

A % Vdc Vdc hours hours % -

60 min. 5 max 40 60 40 60 6 48 10 manual and automatic 50 100 Manual and automatic thyristor

kVA Vac

Dry Yes -

TECHNICAL DATA SCHEDULE BATTERY CHARGER 48 Vdc, 60 A ITEM 2.18 2.19 2.20 2.21 2.22 2.23 2.24 2.24.1 2.24.2 2.24.3 2.24.4 2.24.5 2.25 2.25.1 2.25.2 2.25.3 2.25.4 2.25.5 2.26 2.26.1 2.26.2 2.26.3 2.26.4 2.26.5 2.26.6 2.26.7 2.26.8 Efficiency Short-circuit current proof Surge suppression AC & DC Reverse battery protection Meantime between failures MTBF Mean repair time MTR Input breakers Manufacturer Type Rated voltage Rated current Rated interrupting capacity Output breakers Manufacturer Type Rated voltage Rated current Rated interrupting capacity Instruments and indication Digital ammeter Digital voltmeter Ground fault alarm lamp and contact AC failure alarm lamp and contact Charger failure alarm lamp and contact Max./min. voltage alarm lamp and contact Equalizing/floating signalling lamps and contact AC "ON" signalling lamp and contact yes yes yes yes yes yes yes yes Vdc A kA Thermal magnetic 250 10 Vac A kA sym. Thermal magnetic 600 14 DESCRIPTION UNITS % h h REQUIRED Current limited yes yes > 10 000 <1 GUARANTEED

TECHNICAL DATA SCHEDULE BATTERY CHARGER 48 Vdc, 60 A ITEM 2.26.9 2.26.10 2.27 3.0 3.1 DESCRIPTION Low battery voltage lamp and contact Manual operation selector contact Enclosure type Weight and dimensions Weight - weight for service - weight for transport 3.2 Dimensions (L x W x D) - dimensions for service 4.0 5.0 5.1 - dimensions for transport N/A Standards Manufacturing IEC 60947, ANSI/NEMA PE 5 ISO 9001 Indoor inside control building kg kg mm mm mm UNITS REQUIRED yes yes free-standing, IP 50 GUARANTEED

5.2.2 6.0

Quality assurance Installation

10.0

145 kV BUS SUPPORT INSULATOR

TECHNICAL DATA SCHEDULE 145 kV BUS SUPPORT INSULATOR ITEM 1.0 1.1 1.2 1.3 2.0 2.1 2.2 2.3 2.4 2.5 DESCRIPTION Manufacturer Type Model n
o

UNITS -

REQUIRED Station post -

GUARANTEED

Country origin Nominal characteristics Rated maximum voltage Lightning impulse withstand voltage (BIL) Power frequency withstand voltage (wet condition) Creepage distance Radio influence voltage data (IEC60694): - test voltage - max. RIV Cantilever strength: Insulators designation (IEC60273) Weight and dimensions Diameter Height Base bolt circle Cap bolt circle Base bolt size Cap bolt size Weight Test reports

kV kV kV mm/kV kV V kN -

145 650 275 31 145 2500

2.6 2.7 3.0 3.1 3.2 3.3 3.4 3.5 3.6 3.7 4.0

mm mm mm mm mm mm kg -

TECHNICAL DATA SCHEDULE 145 kV BUS SUPPORT INSULATOR ITEM 5.0 Standards DESCRIPTION UNITS REQUIRED IEC 60273 IEC 60694 IEC 60815 GUARANTEED

6.0

Quality control

ISO 9001

9.0

Installation

Outdoor in desertic/tropical environment

10.1 36 kV BUS SUPPORT INSULATOR

TECHNICAL DATA SCHEDULE 36 kV BUS SUPPORT INSULATOR ITEM 1.0 1.1 1.2 1.3 2.0 2.1 2.2 2.3 2.4 2.5 DESCRIPTION Manufacturer Type Model n
o

UNITS -

REQUIRED Station post -

GUARANTEED

Country origin Nominal characteristics Rated maximum voltage Lightning impulse withstand voltage (BIL) Low frequency withstand voltage wet condition Creepage distance Radio influence voltage data (IEC60694): - test voltage - max. RIV Cantilever strength: Insulator designation (IEC60693) Weight and dimensions Diameter Height Base bolt circle Cap bolt circle Base bolt size Cap bolt size Weight Test reports

kV kV kV mm/kV kV V kN -

36 170 70 31 36 2500

2.6 2.7 3.0 3.1 3.2 3.3 3.4 3.5 3.6 3.7 4.0

mm mm mm mm mm mm kg -

TECHNICAL DATA SCHEDULE 36 kV BUS SUPPORT INSULATOR ITEM 5.0 Standards DESCRIPTION UNITS REQUIRED IEC 60273 IEC 60815 IEC 60694 GUARANTEED

6.0

Quality control

ISO 9001

9.0

Installation

Outdoor in desertic/tropical environment

10.2 HV TUBULAR BUSBAR

TECHNICAL DATA SCHEDULE HV TUBULAR BUSBAR ITEM 1.0 1.1 1.2 1.3 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11 3.0 3.1 3.2 3.3 4.0 DESCRIPTION Manufacturer Type Catalogue No. Country of origin Characteristics Material Designation Conductivity (% IACS) Resistance at 20 C Exterior diameter Interior diameter Section Rated Current Bar section length Linear weight Maximum span Transportation Number of tubes per crate Dimensions of crate Weight of crate Standards
o

UNITS -

REQUIRED -

GUARANTEED

% mm mm mm2 A m kg/m m mm kg -

6101T6 4SPS SCH40 53 min. 114.3 102.26 2000 5.6 approx. IEC 60105 ASTM B317 ANSI H35.2 ISO 9001 Outdoor in tropical/desertic environment

5.0 6.0

Quality control Installation

10.3 MV MAIN TUBULAR

TECHNICAL DATA SCHEDULE MV MAIN TUBULAR ITEM 1.0 1.1 1.2 1.3 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11 3.0 3.1 3.2 3.3 4.0 DESCRIPTION Manufacturer Type Catalogue No. Country of origin Nominal characteristics Material Designation Exterior diameter Interior diameter Section Conductivity (% IACS) Rated current Resistance at 20o C Bar section length Linear weight Maximum span Transportation Number of tubes per crate Dimensions of crate Weight of crate Standards m kg/m m mm kg mm mm mm mm2 % A 6101T6 1 SPS SCH 80 48.3 38.14 53 min. 1250 2.0 aprox. IEC 60105 ASTM B317 ANSI H35.2 ISO 9001 UNITS REQUIRED GUARANTEED

5.0

Quality control

6.0

Installation

Outdoor in tropical/desertic environment

10.4 MV FEEDER TUBULAR

TECHNICAL DATA SCHEDULE MV FEEDER TUBULAR ITEM 1.0 1.1 1.2 1.3 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11 3.0 3.1 3.2 3.3 4.0 DESCRIPTION Manufacturer Type Catalogue No. Country of origin Nominal characteristics Material Designation Exterior diameter Interior diameter Section Conductivity (% IACS) Rated current Resistance at 20 oC Bar section length Linear weight Maximum span Transportation Number of tubes per crate Dimensions of crate Weight of crate Standards mm mm mm mm2 % A m kg/m m mm kg 6101T6 1 SPS SCH 40 48.3 40.94 53 min. 1000 1.5 approx. IEC 60105 ASTM B317 ANSI H35.2 ISO 9001 UNITS REQUIRED GUARANTEED

5.0

Quality control

6.0

Installation

Outdoor in tropical/desertic environment

10.5 STRAIN BUSBAR CONDUCTOR

TECHNICAL DATA SCHEDULE STRAIN BUSBAR CONDUCTOR ITEM 1.0 1.1 1.2 1.3 1.4 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11 2.12 2.13 2.14 2.15 3.0 DESCRIPTION Manufacturer Type Code Name Designation Country of Origin Mechanical characteristics and dimensions Stranding Aluminium wire diameter Overall diameter Aluminium area Nominal area Rated current Mass Rated tensile strength Initial lower modulus of elasticity Initial upper modulus of elasticity Transition stress Final modulus of elasticity Creep modulus at 15C Coefficient of linear thermal expansion D.c. resistance at 20C Transport mm mm mm2 mm2 A kg/km kN GPa GPa MPa GPa GPa E-6/C ohms/km 61 4.38 39.5 800 921 1400 2540 271.62 0.0361 UNITS REQUIRED IEC104-D2 800-D2-61 GUARANTEED

TECHNICAL DATA SCHEDULE STRAIN BUSBAR CONDUCTOR ITEM 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9 3.10 3.11 3.12 3.13 4.0 4.1 DESCRIPTION Standard length of conductor per reel Maximum number of standard lengths per reel Flange diameter Inside traverse Overall width Drum diameter Minimum cover from edge of flange Arbor hole diameter Material Empty reel mass Thickness of lagging Shipping mass Shipping volume Standards Manufacturing IEC 61089 IEC 60104 IEC 60889 ISO 9001 Outdoor Desertic/Tropical environment mm mm mm mm mm mm kg mm kg m3 UNITS m REQUIRED 25 Wood 1500 max. GUARANTEED

4.2 5.0

Quality Assurance Installation

10.6 BUSBAR CONNECTORS AND HARDWARE

TECHNICAL DATA SCHEDULE BUSBAR CONNECTORS AND HARDWARE ITEM 1.0 1.1 2.0 2.1 DESCRIPTION Manufacturer Country of origin Characteristics Sizes of bus conductors : - rigid - rigid 33 kV busses - flexible conductor 330/132 kV - flexible conductor 33kV Rated current Resistance vs resistance of the conductor Radio influence voltage (IEC 60694) at 140 % rated voltage at 0.5 MHz Frequency Connectors type (non-limitative) 2.7 2.8 2.9 Shielding rings bus support bus flexible support rigid-flexible connectors angle A, Y connectors T connectors Expansion connectors pad connectors union connectors caps % kA kA mm mm mm mm yes yes yes yes yes yes yes yes yes yes Aluminium Alloy 35 min. 31,5 17,5 AL 7075T73 or equiv.

UNITS -

REQUIRED -

GUARANTEED

mm mm % V Hz

4 SPS AL 1 SPS AL 800-D2-61 800-D2-61 Same as for bus at same temp. rise < 2500 50

2.2 2.3 2.4 2.5 2.6

Material of connectors Conductivity (IACS) Short-circuit withstand - 330/132 kV for 3 s - 33 kV for 3 s Various bolt size used for: - 330/132 kV busbars - 33 kV busbars - Conductors for 330/132 kV - Conductors for 33 kV - Material of bolts

2.10

TECHNICAL DATA SCHEDULE BUSBAR CONNECTORS AND HARDWARE ITEM 2.11 DESCRIPTION Tightening torque for bolts - size and torque bolt #1 - size and torque bolt #2 - size and torque bolt #3 - size and torque bolt #4 - size and torque bolt #5 Resistance to traction - connector on stranded conductor - connector on tube Strength of bus support - stranded conductor (long., vert., trans.) - bus tube (long., vert., trans.) Tests - cyclic heat run test - short circuit current withstand - mechanical strength - resistance to traction - bolts overtightining resistance - radio interference - routine dimensions check - chemical analysis of material - radiography test Weight and dimension Average weight of item Average packing dimension Number of items per crate Dimensions of crate Weight of crate Standards kg mm mm kg NEMA CC-1 ANSI C119.4 ASTM B26/B26M ASTM B108 ASTM B193 ASTM E155 IEC 60694 ISO 9001 Outdoor in tropical/ desertic environment UNITS kN kN kN REQUIRED 10 % of conductor 2 min. 18, 9, 9 2, 9, 18 yes yes yes yes yes yes yes yes yes GUARANTEED

2.12

2.13

2.14

3.0 3.1 3.2 3.3 3.4 3.5 4.0

5.0 6.0

Quality control Installation

11 TECHNICAL DATA SCHEDULES 11.1 GROUNDING CONDUCTOR TYPE 1

TECHNICAL DATA SCHEDULE GROUNDING CONDUCTOR Type 1 ITEM 1.0 1.1 2.0 2.1 2.2 2.3 2.4 2.5 2.6 3.0 3.1 3.2 3.3 4.0 5.0 6.0 DESCRIPTION Manufacturer Country of origin Characteristic Size Material Tinned Number of stands Weight Shape Weight and dimensions Length per reel Weight of reel Dimensions of reel Standards Quality control Installation UNITS mm2 kg/m m kg mm REQUIRED min. 120 Copper soft Yes 19 Round concentric ASTM B8, B33 ISO 9001 Outdoor buried in substation ground GUARANTEED

11.2

GROUNDING CONDUCTOR TYPE 2

TECHNICAL DATA SCHEDULE GROUNDING CONDUCTOR Type 2 ITEM 1.0 1.1 2.0 2.1 2.2 2.3 2.4 2.5 2.6 3.0 3.1 3.2 3.3 4.0 5.0 6.0 DESCRIPTION Manufacturer Country of origin Characteristic Size Material Tinned Number of stands Weight Shape Weight and dimensions Length per reel Weight per reel Dimensions of reel Standards Quality control Installation UNITS mm kg/m m kg mm 2

REQUIRED min. 70 Copper soft Yes 7 Round concentric ASTM B8, B33 ISO 9001 Outdoor buried in substation ground

GUARANTEED

11.3 GROUNDING ROD

TECHNICAL DATA SCHEDULE GROUNDING ROD ITEM 1.0 1.1 2.0 2.1 2.2 2.3 3.0 3.1 3.2 3.3 4.0 5.0 6.0 DESCRIPTION Manufacturer Country of origin Characteristic Material Diameter Length Weight and dimension Weight of pallet of rods Number of rods per pallet Dimensions of pallet Standards Quality control Installation UNITS Mm M Kg Mm REQUIRED Copper clad steel min. 16 3 ANSI, ASTM, IEEE 837 ISO 9001 Outdoor buried in substation ground GUARANTEED

11.4 GROUNDING FUSION CONNECTORS

TECHNICAL DATA SCHEDULE GROUNDING FUSION CONNECTORS ITEM 1.0 1.1 2.0 2.1 2.2 2.3 DESCRIPTION Manufacturer Country of origin Characteristic Powdered metals Accessories Grounding connectors type (nonlimitative) : - splice of horizontal cables - tee of horizontal run-tap cables - cross of horizontal cables - cable tap top of ground rod - through cable to top of ground rod Dimensions and weight Packing for powder of 100 connectors - dimensions - weight Packing for molds and tools for 100 connectors - dimensions - weight Standards Quality control Installation UNITS mm kg REQUIRED Copper oxide and aluminium yes yes yes yes yes yes GUARANTEED

3.0 3.1

3.2

mm kg -

IEEE 837, ANSI, ASTM ISO 9001 Outdoor buried in substation ground

4.0 5.0 6.0

11.5 GROUNDING MECHANICAL CONNECTORS

TECHNICAL DATA SCHEDULE GROUNDING MECHANICALCONNECTORS ITEM 1.0 1.1 2.0 2.1 2.2 2.3 DESCRIPTION Manufacturer Country of origin Characteristics Conductor range Material Grounding connectors type (nonlimitative): - cable to structure connectors - cable to pipe connectors - cable to cable parallel connectors - cable to wire split bolt connectors - cable to pad connector - cable lug Dimensions and weight Crate for 100 connectors - dimensions of crate - weight of crate Standards Quality control Installation UNITS mm 2

REQUIRED 70-120 (min.) Bronze

GUARANTEED

mm kg -

IEEE 837, ANSI, ASTM ISO 9001 Outdoor on substation ground level

3.0 3.1

4.0 5.0 6.0

12

TECHNICAL DATA SCHEDULES

12.1 LOW VOLTAGE CONTROL CABLES

TECHNICAL DATA SCHEDULE LOW VOLTAGE CONTROL CABLES ITEM 1.0 1.1 1.2 2.0 2.1 2.2 2.3 2.4 2.5 DESCRIPTION Manufacturer Type Country of origin Characteristics Rated maximum voltage Frequency Insulation level Strand class Conductor V Hz % 750 50 100
2 (IEC 60228) or B (ASTM B 8)

UNITS -

REQUIRED Armoured multi-conductor -

GUARANTEED

Tinned stranded copper as per ASTM B33

2.6

Size and number of conductors - Specification 5201 4C # 14 AWG or 2.5 mm2 8C # 14 AWG or 2.5 mm2 12C # 14 AWG or 2.5 mm2 4C # 12 AWG or 4 mm2 8C # 12 AWG or 4 mm2 12C # 12 AWG or 4 mm2 4C # 10 AWG or 6 mm2 8C # 10 AWG or 6 mm2 PVC PVC

- Specification 5202
- Specification 5203 - Specification 5204 - Specification 5205 - Specification 5206 - Specification 5207 - Specification 5208 2.7 2.8 Insulation Inner jacket

TECHNICAL DATA SCHEDULE LOW VOLTAGE CONTROL CABLES ITEM 2.9 2.10 2.11 3.0 3.1 Armour Outer jacket Wire identification Weight and dimensions Overall external diameter - Code 5201 - Code 5202 - Code 5203 - Code 5204 - Code 5205 - Code 5206 - Code 5207 - Code 5208 3.2 3.2.1 Dimensions for transport - Size of cable reel (diameter and width) - Code 5201 - Code 5202 - Code 5203 - Code 5204 - Code 5205 - Code 5206 mxm mxm mxm mxm mxm mxm mxm mxm mm mm mm mm mm mm mm mm DESCRIPTION UNITS REQUIRED Aluminium or galvanized steel PVC Number GUARANTEED

- Code 5207
- Code 5208 3.2.2 Weight of cable reel and length of cable per reel - Code 5201 - Code 5202 - Code 5203 - Code 5204 - Code 5205 - Code 5206 - Code 5207

kg, m kg, m kg, m kg, m kg, m kg, m kg, m

TECHNICAL DATA SCHEDULE LOW VOLTAGE CONTROL CABLES ITEM - Code 5208 4.0 4.1 4.2 Installation data Maximum bending radius in terms of cable diameter Maximum pulling tension - Code 5201 - Code 5202 - Code 5203 - Code 5204 - Code 5205 - Code 5206 - Code 5207 - Code 5208 4.3 Cable gland manufacturer and type (enclose documentation) - Code 5201 - Code 5202 - Code 5203 - Code 5204 - Code 5205 - Code 5206 - Code 5207 - Code 5208 N N N N N N N N DESCRIPTION UNITS kg, m REQUIRED GUARANTEED

5.0 5.1

Standards Manufacturing ICEA S73-532 IEC 60227 IEC 60228 ASTM B8, B33

5.2 6.0

Quality Assurance Installation

ISO 9001 Indoor and outdoor in

TECHNICAL DATA SCHEDULE LOW VOLTAGE CONTROL CABLES ITEM DESCRIPTION UNITS REQUIRED substation switchyard in desertic/tropical environment GUARANTEED

12.2 LOW VOLTAGE POWER CABLES

TECHNICAL DATA SCHEDULE LOW VOLTAGE POWER CABLES ITEM 1.0 1.1 1.2 2.0 2.1 2.2 2.3 2.4 2.5 DESCRIPTION Manufacturer Type Country of origin Characteristics Rated maximum voltage Frequency Insulation level Strand class Conductor V Hz % 1000 50 100 2 (IEC 60228) or B (ASTM B8) Stranded copper as per ASTM B33 UNITS REQUIRED Armoured multi-conductor GUARANTEED

2.6

Size and number of conductors - Specification 5223 - Specification 5224 - Specification 5225 - Specification 5226 4C # 8 AWG or 10 mm2 4C # 6 AWG or 16 mm2 1C # 1/0 AWG or 50 mm2 4C # 4/0 AWG or 120 mm2 Cross-link polyethylene PVC Aluminium or galvanized steel PVC Number

2.7 2.8 2.9 2.10 2.11

Insulation Inner jacket Armour Outer jacket Wire identification

3.0

Weight and dimensions

TECHNICAL DATA SCHEDULE LOW VOLTAGE POWER CABLES ITEM 3.1 DESCRIPTION Overall external diameter - Code 5223 - Code 5224 - Code 5225 - Code 5226 mm mm mm mm UNITS REQUIRED GUARANTEED

3.2 3.2.1

Dimensions for transport Size of cable reel (diameter and width) - Code 5223 - Code 5224 - Code 5225 - Code 5226 mxm mxm mxm mxm -

3.2.2

Weight of cable reel and length of cable per reel - Code 5223 - Code 5224 - Code 5225 - Code 5226 kg, m kg, m kg, m kg, m -

4.0 4.1 4.2

Installation data Maximum bending radius in terms of cable diameter Maximum pulling tension - Code 5223 - Code 5224 - Code 5225 - Code 5226 N N N N -

4.3

Cable gland manufacturer and type (enclose documentation) - Code 5223 - Code 5224 - Code 5225 - Code 5226 -

TECHNICAL DATA SCHEDULE LOW VOLTAGE POWER CABLES ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

5.0 5.1

Standards Manufacturing IEC 60502 IEC 60 228 ANSI/ICEA S66-524ASTM B8, B33

5.2

Quality Assurance

ISO 9001

6.0

Installation

Indoor and outdoor in substations

12.3 MEDIUM VOLTAGE POWER CABLES 36 kV

TECHNICAL DATA SCHEDULE MEDIUM VOLTAGE POWER CABLE 36 kV ITEM 1.0 1.1 DESCRIPTION Manufacturer Type UNITS REQUIRED Armoured single conductor GUARANTEE D

1.2 2.0 2.1 2.2 2.3 2.4

Country of origin Characteristics Rated maximum voltage Frequency Insulation level Strand class

kV Hz % -

36 50 100 2 (IEC 60228) or B (ASTM B8) Stranded copper as per ASTM B33

2.5

Conductor

2.6 2.7 2.8 2.9 2.10 2.11 2.12 2.13

Number of conductors and size Insulation Conductor shield Insulation shield Insulation metallic shield Internal/external cable jackets Armour Drawing of cable section

1c 2/0 AWG (or 70 mm2) Cross-link polyethylene semiconductor semiconductor

Copper tape PVC Aluminium To be enclosed

3.0 3.1 3.2

Weight and dimensions Overall external diameter - Code 5241 Dimensions for transport

mm

TECHNICAL DATA SCHEDULE MEDIUM VOLTAGE POWER CABLE 36 kV ITEM 3.2.1 3.2.2 DESCRIPTION Size of cable reel (diameter and width) - Code 5241 Weight of cable reel and length of cable per reel - Code 5241 4.0 4.1 4.2 Installation data Maximum bending radius in terms of cable diameter Maximum pulling tension - Code 5241 4.3 Cable gland manufacturer and type (enclose documentation) - Code 5241 kg, m N mxm UNITS REQUIRED GUARANTEE D

5.0 5.1

Standards Manufacturing IEC 60502 IEC 60228, ANSI/ICEA S66-524ASTM B8, B33 ISO 9001

5.2

Quality Assurance

6.0

Installation

Outdoor in substations desertic/tropical environment

13

TECHNICAL DATA SCHEDULES

13.1 DATA ANALYSIS STATION

TECHNICAL DATA SCHEDULE DATA ANALYSIS STATION ITEM 1.0 1.1 1.2 1.3 2.0 2.1 2.1.1 DESCRIPTION Manufacturer Model Type Country of origin Nominal Characteristics Computer Microprocessor type Intel Centrino,750 MH z min 500min 80min yes 700 Sony multiscan 200 PS or equiv. 21" 1024 x 768 (4) ITU-T V28, EIA RS232c HP CD writer plus 8100 series or equivalent UNITS REQUIRED GUARANTEED

2.1.2. 2.1.3 2.1.4

Ram memory size Hard disk size CD-ROM - number - size - capacity

Mbytes Gbytes inches Mbytes inches -

2.1.5

Colour monitor: - diagonal size - resolution

2.1.6 2.1.7 2.1.8

Alphanumeric keyboard Communication interface ports CD ROM reader/writer

2.2 2.2.1 2.2.2 2.2.3

Printer Manufacturer Model Colour Epson or equiv. Laser Jet yes

TECHNICAL DATA SCHEDULE DATA ANALYSIS STATION ITEM 2.2.4 2.2.5 2.2.6 2.3 2.3.1 2.3.2 2.3.3 2.3.4 2.3.5 2.3.6 Speed Width of print Digital interface port External disk drive unit Manufacturer Model Capacity Access time Data transfer rate Cartridge: - model - removable - size H x W x D 2.4 2.4.1 2.4.2 2.4.3 2.4.4 2.4.5 2.4.6 2.4.7 2.4.8 2.4.9 2.4.10 2.5 2.5.1 Communication modems / ports Manufacturer Model Data rate Connection Frequency range Output interface for Digital interface port Operation Modulation Communication port at analysis station Software Central analysis: - manufacturer - identification kbits/s Hz 33,6 up to 64 manual by operator 2W telephone line ITU-T, V28, EIA RS232c Full duplex ITU-T V series TCP/IP (ftp) Hathaway Replay 97 or equivalent mm Mbytes m/sec Mbytes/sec DESCRIPTION UNITS char./sec columns REQUIRED 400 min 132 GUARANTEED

TECHNICAL DATA SCHEDULE DATA ANALYSIS STATION ITEM DESCRIPTION - version n and date - updating for 1 year - communication to remote units 2.5.2 Short circuit calculation: - manufacturer - identification - version n and date - updating for 1 year 2.5.3 Harmonic analysis: - manufacturer - identification - version n and date - updating for 1 year 2.5.4 Operating system: - manufacturer - identification - version n and date - updating for 1 year 2.5.5 Fault locator - manufacturer - identification - version n and date - updating for 1 year 2.5.6 Others: - manufacturer - identification - version n and date - updating for 1 year 2.6 2.6.1 2.6.2 2.6.3 General Analysis station console Power supply Consumption (max) Vac/Hz W desk and chair 240/50 yes yes yes MS Windows NT 4.0 yes yes UNITS REQUIRED yes yes GUARANTEED

TECHNICAL DATA SCHEDULE DATA ANALYSIS STATION ITEM 3.0 3.1 DESCRIPTION Weight and dimensions Weight - computer - monitor - printer - external disk drive - transport 3.2 Dimensions (H x W x L) - computer - monitor - printer - external disk drive - transport 4.0 5.0 5.1 5.2 6.0 N/A Standards: Manufacturing Quality assurance Installation ITU-T, EIA, IEEE ISO 9001 Indoor in substation control building mm mm mm mm mm kg kg kg kg kg UNITS REQUIRED GUARANTEED

13.2 REMOTE FAULT RECORDER

TECHNICAL DATA SCHEDULE REMOTE FAULT RECORDER ITEM 1.0 1.1 1.2 1.3 2.0 2.1 2.2 2.2.1 2.2.2 2.2.3 DESCRIPTION Manufacturer Model Technology Country of origin Nominal characteristics Micro processor type Analogue input Number of channels (current/voltage) Frequency response Current triggers: - number - setting range - rated current 2.2.4 Voltage triggers: - number - setting range - rated voltage 2.2.5 Analogue/digital converter for each channel: - number of bits/sample per channel 2.2.6 2.3 2.3.1 2.3.2 2.3.3 2.4 2.5 2.6 Calculated parameters triggering Digital input Number of channels Number of triggers (change of position) Voltage Input insulation Sampling range Real-time clock Vdc sample/s 32 32 110 (24-125) galvanic 1920 7680 12 min W, VARS, In V V 8 0-150 110/3, 110 A A 8 1 kHz UNITS REQUIRED Hathaway or equivalent IDM or equivalent digital programmable 8/8 1 20 GUARANTEED

TECHNICAL DATA SCHEDULE REMOTE FAULT RECORDER ITEM 2.6.1 2.6.2 2.6.3 2.6.4 2.7 2.7.1 2.7.2 2.7.3 2.7.4 2.7.5 2.7.6 2.8 2.8.1 2.8.2 2.9 2.9.1 DESCRIPTION Oscillator frequency Time drift Constant memory Time synchronizing Memory Type Size Storage capacity at minimum sampling rate with all channels Storage capacity at max. sampling rate with all channels Constant memory feature support Recording prior to event Control panel Display Keyboard keys Alarm contacts Alarms: - failure - event Contacts capacity: - type - voltage rating - current interruption 2.10 2.10.1 2.10.2 2.10.3 2.10.4 2.10.5 Communication modems / ports Manufacturer Type Data rate Connection Frequency range kbits/s Hz 33,6 up to 64 manual Vdc Adc C 110 Yes Yes LCD alpha-num display functional keypad Mbytes s s ms 16 min 20 min Yes 170 min UNITS kHz ms/hour REQUIRED yes IRIG-B BNC input from GPS GUARANTEED

2.9.2

TECHNICAL DATA SCHEDULE REMOTE FAULT RECORDER ITEM 2.10.6 2.10.7 2.10.8 2.10.9 2.10.19 2.11 2.11.1 2.11.2 2.11.3 2.11.4 2.11.5 2.11.6 2.11.7 2.11.8 2.12 2.12.1 DESCRIPTION Output interface for Digital interface port Operation Modulation Communication port at recorder Printer Manufacturer Model Colour Speed Width of print Digital interface Power supply Consumption Analogue input panel Test switches for inputs: - number of current switches (4 switches of 2 poles per input) - number of voltage switches (2 switches of 4 poles per input) - rated voltage - rated current - thermal withstandability 2.13 2.13.1 2.13.2 Power supply Rated voltage Power consumption: - standby - operation W W Vdc 110 V A A 8 8 110 1 30 for 1 s char/s columns Vac W Yes 220 (240) UNITS REQUIRED 2 wires telephone line ITU-T V28 EIA RS232c full duplex ITU-T V series TCP/IP (ftp) GUARANTEED

2.14.

Enclosure for transient recorder and

free-standing IP54

TECHNICAL DATA SCHEDULE REMOTE FAULT RECORDER ITEM accessories 2.15 2.15.1 2.15.2 2.15.3 2.15.4 2.15.5 2.15.6 2.15.7 2.15.8 2.15.9 Synchronized clock receiver Manufacturer Type Frequency Accuracy Display Signal output Supply Consumption External antenna : -type dimensions Resolution Output & interface Weight and dimensions Weight - for services - for transport 3.2 Dimensions (L x H x W) - for sevice transport N/A Standards: Manufacturing IEC60068, 60255, 61143 ANSI C37.90.1

DESCRIPTION

UNITS

REQUIRED
modular hinged doors cabinet

GUARANTEED

MHz msec Vdc W mm ms -

GPS IRIGB 110 1 -

2.15.10 2.15.11 3.0 3.1

kg kg mm mm

4.0 5.0 5.1

5.2 6.0

Quality assurance Installation

ISO 9001
Indoor in substation control building

13.3 REMOTE FAULT RECORDER

TECHNICAL DATA SCHEDULE REMOTE FAULT RECORDER ITEM 1.0 1.1 1.2 1.3 2.0 2.1 2.2 2.2.1 2.2.2 2.2.3 DESCRIPTION Manufacturer Model Technology Country of origin Nominal characteristics Micro processor type Analogue input Number of channels (current/voltage) Frequency response Current triggers: - number - setting range - rated current 2.2.4 Voltage triggers: - number - setting range - rated voltage 2.2.5 Analogue/digital converter for each channel: - number of bits/sample per channel 2.2.6 2.3 2.3.1 2.3.2 2.3.3 2.4 2.5 Calculated parameters for triggering Digital input Number of channels Number of triggers (change of position) Voltage Input insulation Sampling range Vdc sample/s 128 128 110 (24-125) Galvanic 1920 7680 12 min W, VARS, In V V 12 0-150 110/3, 110 A A 64 0 20 1 kHz UNITS REQUIRED Hathaway or equivalent IDM or equivalent digital programmable 64/16 GUARANTEED

TECHNICAL DATA SCHEDULE REMOTE FAULT RECORDER ITEM 2.6 2.6.1 2.6.2 2.6.3 2.6.4 2.7 2.7.1 2.7.2 2.7.3 2.7.4 2.7.5 2.7.6 2.8 2.8.1 2.8.2 2.9 2.9.1 DESCRIPTION Real-time clock Oscillator frequency Time drift Constant memory Time synchronizing Memory Type Size Storage capacity at minimum sampling rate with all channels Storage capacity at max. sampling rate with all channels Constant memory feature support Recording prior to event Control panel Display Keyboard keys Alarm contacts Alarms: - failure - event Contacts capacity: - type - voltage rating - current interruption 2.10 2.10.1 2.10.2 2.10.3 2.10.4 Communication modems / ports Manufacturer Type Data rate Connection kbits/s 33,6 up to 64 manual Vdc Adc C 110 yes yes LCD alpha-num display functional keypad Mbytes s s ms 16 min 20 min yes 170 min kHz ms/hour yes IRIG-B BNC input from GPS UNITS REQUIRED GUARANTEED

2.9.2

TECHNICAL DATA SCHEDULE REMOTE FAULT RECORDER ITEM 2.10.5 2.10.6 2.10.7 2.10.8 2.10.9 2.10.10 2.11 2.11.1 2.11.2 2.11.3 2.11.4 2.11.5 2.11.6 2.11.7 2.11.8 2.12 2.12.1 DESCRIPTION Frequency range Output interface for Digital interface port Operation Modulation Communication port at recorder Printer Manufacturer Model Colour Speed Width of print Digital interface Power supply Consumption Analogue input panel Test switches for inputs: - number of current switches (4 switches of 4 poles per input) - number of current switches (2 switches of 2 poles per input) - rated voltage - rated current - thermal withstandability 2.13 2.13.1 2.13.2 Power supply Rated voltage Power consumption: - standby - operation 2.14 Enclosure for transient recorder and W W free-standing IP54 Vdc 110 V A A 64 16 110 1 30 for 1s char/s columns Vac W Yes 220 (240) UNITS Hz REQUIRED 2 wires telephone line ITU-T V28 EIA RS232c full duplex ITU-T V series TCP/IP (ftp) GUARANTEED

TECHNICAL DATA SCHEDULE REMOTE FAULT RECORDER ITEM accessories DESCRIPTION UNITS REQUIRED modular hinged doors cabinet GUARANTEED

2.15 2.15.1 2.15.2 2.15.3 2.15.4 2.15.5 2.15.6 2.15.7 2.15.8 2.15.9

Synchronized clock receiver Manufacturer Type Frequency Accuracy Display Signal output Supply Consumption External antenna : - type - dimensions Resolution Output & interface

MHz msec Vdc W mm ms -

GPS IRIGB 110 1 -

2.15.10 2.15.11

3.0 3.1

Weight and dimensions Weight - for services - for transport kg kg -

3.2

Dimensions (L x H x W) - for service - transport mm mm -

4.0 5.0 5.1

N/A Standards: Manufacturing IEC60068, 60255, 61143 ANSI C37.90.1 ISO 9001

5.2

Quality assurance

TECHNICAL DATA SCHEDULE REMOTE FAULT RECORDER ITEM 6.0 Installation DESCRIPTION UNITS REQUIRED Indoor in substation control building GUARANTEED

13.4 REMOTE FAULT RECORDER

TECHNICAL DATA SCHEDULE REMOTE FAULT RECORDER ITEM 1.0 1.1 1.2 2.0 2.1 2.2 2.2.1 2.2.2 2.2.3 DESCRIPTION Manufacturer Model Technology Nominal characteristics Micro processor type Analogue input Number of channels (current/voltage) Frequency response Current triggers: - number - setting range - rated current 2.2.4 Voltage triggers: - number - setting range - rated voltage 2.2.5 Analogue/digital converter for each channel: - number of bits/sample per channel 2.2.6 2.3 2.3.1 2.3.2 2.3.3 2.4 2.5 2.6 2.6.1 Calculated parameters for triggering Digital input Number of channels Number of triggers (change of position) Voltage Input insulation Sampling range Real-time clock Oscillator frequency kHz Vdc sample/s 48 48 110 (24-125) galvanic 1920 7680 12 min W, VARS, In V V 8 0-150 110/3, 110 A A 22 1 20 1 kHz UNITS REQUIRED Hathaway or equivalent IDM or equivalent digital programmable 22/8 GUARANTEED

TECHNICAL DATA SCHEDULE REMOTE FAULT RECORDER ITEM 2.6.2 2.6.3 2.6.4 2.7 2.7.1 2.7.2 2.7.3 2.7.4 2.7.5 2.7.6 2.8 2.8.1 2.8.2 2.9 2.9.1 Time drift Constant memory Time synchronizing Memory Type Size Storage capacity at minimum sampling rate with all channels Storage capacity at max. sampling rate with all channels Constant memory feature support Recording prior to event Control panel Display Keyboard keys Alarm contacts and indication Alarm - failure - event Contacts capacity: - type - voltage rating - current interruption 2.10 2.10.1 2.10.2 2.10.3 2.10.4 2.10.5 2.10.6 Communication modems / ports Manufacturer Type Data rate Connection Frequency range Output interface for Vdc Adc kbytes/s C 110 33,6 up to 64 manual 2 wires yes yes LCD alpha-num display functional keypad Mbytes s s ms 16 min 20 min yes DESCRIPTION UNITS ms/hour REQUIRED yes IRIG-B BNC input from GPS GUARANTEED

2.9.2

TECHNICAL DATA SCHEDULE REMOTE FAULT RECORDER ITEM DESCRIPTION UNITS REQUIRED telephone line 2.10.7 2.10.8 2.10.9 2.10.10 2.11 2.11.1 2.11.2 2.11.3 2.11.4 2.11.5 2.11.6 2.11.7 2.11.8 2.12 2.12.1 Digital interface port Operation Modulation Communication port at recorder Printer Manufacturer Model Colour Speed Width of print Digital interface Power supply Consumption Analogue input panel Test switches for inputs: - number of current switches (4 switches of 2 poles per input) - number of current switches (2 switches of 4 poles per input) - rated voltage - rated current - thermal withstandability 2.13 2.13.1 2.13.2 Power supply Rated voltage Power consumption: - standby - operation 2.14. Enclosure for transient recorder and accessories Vdc W W 110 Free standing IP54 modular hinged door cabinet V A A 22 8 110 1A 30 for 1 s Vac W yes 220 (240) ITU-T-V28, EIA RS232c full duplex ITU-T V series TCP/IP (ftp) GUARANTEED

TECHNICAL DATA SCHEDULE REMOTE FAULT RECORDER ITEM 2.15 2.15.1 2.15.2 2.15.3 2.15.4 2.15.5 2.15.6 2.15.7 2.15.8 2.15.9 DESCRIPTION Synchronized clock receiver Manufacturer Type Frequency Accuracy Display Signal output Supply Consumption External antenna : - type - dimensions Resolution Output & interface Weight and dimensions Dimensions (H x L x H) Weight N/A Standards: Manufacturing IEC60068, 60255, 61143 ANSI C37.90.1 ISO 9001 Indoor in substation control building UNITS MHz msec Vdc W mm ms Mm Kg REQUIRED GPS IRIGB 110 1 GUARANTEED

2.15.10 2.15.11 3.0 3.1 3.2 4.0 5.0 5.1

5.2 6.0

Quality assurance Installation

13.5 REMOTE FAULT LOCATOR

TECHNICAL DATA SCHEDULE REMOTE FAULT LOCATOR ITEM 1.0 1.1 1.2 2.0 2.1 2.2 2.2.1 2.2.2 2.2.3 DESCRIPTION Manufacturer Model Technology Nominal characteristics Microprocessor type Analogue input Number of transmission line input modules Frequency response Current triggers: - number - setting range - rated input current 2.2.4 Voltage triggers: - number - setting range - rated input voltage 2.2.5 Analogue/digital converter for each channel: - number of bits/sample per channel - accuracy 2.3 2.3.1 2.3.2 2.3.3 2.4 2.5 2.6 Digital input Number of channels Number of triggers (change of position) Input voltage Input insulation Sampling rate Real-time clock Vdc MHz 8 8 110 galvanic 0, 1 to 10 % V V 110/3, 110 A A 1 kHz UNITS REQUIRED Hathaway or equivalent TWS Mark III or equivalent digital programmable 2 GUARANTEED

TECHNICAL DATA SCHEDULE REMOTE FAULT LOCATOR ITEM 2.6.1 2.6.2 2.6.3 2.7 2.7.1 2.7.2 2.7.3 2.7.4 2.7.5 2.7.6 2.8 2.8.1 2.8.2 2.9 2.9.1 DESCRIPTION Oscillator frequency Time drift Time synchronizing Memory Type Size Storage capacity per channel Storage capacity at max. sampling rate with all channels Constant memory feature support Recording prior to event Control panel Display Keyboard keys Alarm contacts and indication Alarm - power supply - watchdog - event 2.9.2 Contacts capacity: - type - voltage rating - current interruption 2.10 2.10.1 2.10.2 2.10.3 2.10.4 Communication modem Manufacturer Type Data rate Connection kbits/s 33,6 manual Vdc Adc C 110 yes yes yes LCD alpha-num display functional keypad Mbytes kbytes s ms 120 32 yes UNITS kHz ms/hour REQUIRED IRIG-B BNC input from GPS receiver GUARANTEED

2.10.5

Output interface for

2 wires

TECHNICAL DATA SCHEDULE REMOTE FAULT LOCATOR ITEM DESCRIPTION UNITS REQUIRED telephone line 2.10.6 2.10.7 Digital interface Operation ITU-T V28 EIA RS232c full duplex GUARANTEED

2.11 2.11.1 2.11.2

Communication ports Number Type 2 ITU-T V23, EIA RS232c TCP/IP (ftp)

2.12 2.12.1

Analogue input panel Test switches for inputs: - number of current switches (4 x 2 poles) - number of voltage switches (4 poles) - rated voltage - rated current - thermal withstandability - current sensor type V A A 2 2 100 1 30 FOR 1 s Current clamp

2.13 2.13.1 2.13.2 2.14 3.0 3.1 3.2 4.0 5.0 5.1

Power supply Rated voltage Power consumption: Enclosure Weight and dimensions Weight Dimensions (H x L x H) N/A Standards: Manufacturing IEC60068, 60255, 61143 ANSI C37.90.1 kg mm Vdc W 110 In fault recorder cabinet

TECHNICAL DATA SCHEDULE REMOTE FAULT LOCATOR ITEM 5.2 DESCRIPTION Quality assurance UNITS REQUIRED ISO 9001 GUARANTEED

6.0

Installation

Indoor in substations control building

14.1

132/33 kV Transformer Protection Panel

TECHNICAL DATA SCHEDULE 132/33 kV TRANSFORMER PROTECTION PANEL ITEM 1.0 1.1 1.2 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11 2.12 2.13 2.14 2.15 2.16 3.0 3.1 Manufacturer Type or designation Country of origin Features Main transformer differential protection (87T) Restricted Earthfault Protection (87N) Transformer primary overcurrent protection (50/51, 50/51 N) Transformer secondary overcurrent protection including earthing reactor (50/51, 50/51 N) N/A Two circuit breaker failure protection (48 BF) Mechanical protection signalling and tripping relays (63, 71, 49) Synchrocheck relay (25) Buses over/under voltage protection (59/27) Tripping and lockout relays (86,94) Auxiliary, timing, relays and accessories Signalling relays and lamps Test switches for current and voltage Test switches for dc circuits Nameplates Accessories, wiring, MCB, terminal blocks Weight and dimensions Dimensions (length x width x depth) 3.2 Weight dimensions for service dimensions for transport mm mm Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes DESCRIPTION UNITS REQUIRED GUARANTEED

TECHNICAL DATA SCHEDULE 132/33 kV TRANSFORMER PROTECTION PANEL ITEM 3.3 3.4 4.0 5.0 5.1 DESCRIPTION weight for service weight for transport UNITS kg kg REQUIRED IP54 To be enclosed with bid GUARANTEED

Degree of Protection Outline and layout drawing No. N/A Standards Manufacturing

See listing of complementary prescriptions ISO 9001 Indoor in substation control building

5.2 6.0

Quality assurance Installation

14.2

33 kV Line Feeders Protection Panel

TECHNICAL DATA SCHEDULE 33KV LINE FEEDERS PROTECTION PANEL ITEM 1.0 1.1 1.2 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 3.0 3.1 DESCRIPTION Manufacturer Type or designation Country of origin Features for each of four (4) lines feeders Main phase and neutral overcurrent relay (50/51, 50/51 N) Multi shots auto-reclose relay (79) Tripping auxiliary relays (94) Auxiliary, timing, relays and accessories Signalling relays and lamps Test switches for current and voltage Test switches for dc circuits Nameplates Accessories, wiring, MCB, terminal blocks Weight and dimensions Dimensions (length x width x depth) 3.2 dimensions for service dimensions for transport mm mm yes yes yes yes yes yes yes yes yes UNITS REQUIRED GUARANTEED

Weight weight for service weight for transport kg kg IP54 To be enclosed with bid

3.3 3.3

Degree of Protection Outline and layout drawing No.

4.0

N/A

5.0

Standards

TECHNICAL DATA SCHEDULE 33KV LINE FEEDERS PROTECTION PANEL ITEM 5.1 DESCRIPTION Manufacturing UNITS REQUIRED See listing of complementa ry prescriptions ISO 9001 Indoor in substation control building GUARANTEED

5.2 6.0

Quality assurance Installation

14.2.1

33KV Double Bus Bars Protection Panel

TECHNICAL DATA SCHEDULE 33KV DOUBLE BUS BARS PROTECTION PANEL ITEM 1.0 1.1 1.2 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11 2.12 2.13 2.14 3.0 3.1 DESCRIPTION Manufacturer Type or designation Country of origin Features Double bus bars differential protection (87 B) Over/under voltage protection (59/27) Tripping and lockout relays (94/86) Auxiliary, timing, relays and accessories Signalling relays and lamps Test switches for current and voltage Test switches for dc circuits Nameplates N/A N/A N/A N/A N/A Accessories, wiring, MCB, terminal blocks Weight and dimensions Dimensions (length x width x depth) 3.2 dimensions for service dimensions for transport mm mm Yes Yes Yes Yes Yes Yes Yes Yes Yes UNITS REQUIRED GUARANTEED

Weight weight for service weight for transport kg kg IP54 To be enclosed with bid

3.3 3.4

Degree of Protection Outline and layout drawing No.

TECHNICAL DATA SCHEDULE 33KV DOUBLE BUS BARS PROTECTION PANEL ITEM 4.0 5.0 5.1 N/A Standards Manufacturing See listing of complementary prescriptions ISO 9001 Indoor in substation control building DESCRIPTION UNITS REQUIRED GUARANTEED

5.2 6.0

Quality assurance Installation

14.3 14.3.1

COMPONENTS CHARACTERISTICS

Protection Components

TECHNICAL DATA SCHEDULE PROTECTION COMPONENTS DATA

ITEM 1.0 1.1

DESCRIPTION Line main differential protection # 1 (87 L) Manufacturer

UNITS

REQUIRED

GUARANTEED

AREVA, ABB, SIEMENS, REYROLLE, SEl ms kHz % LFCB, RELXXX or equivalent Current differential Digital microprocessor Percent bias 25 max Yes 12 Yes Yes Yes 10

1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 1.10 1.11 1.12 1.13 1.14

Type Function Technology Characteristics Operation time Single and three phase trip Sampling rate A/D conversion min. number of bits Alphanumeric display Keypad Front panel visual indication Accuracy Tripping contacts - number - rating
voltage current with L/R=40 ms

Vdc A

110

1.15

Signalling and digital output contacts - number - rating


voltage

A A Vdc

5(continuos ) 30 ( for 0.3sec) 110

TECHNICAL DATA SCHEDULE PROTECTION COMPONENTS DATA

ITEM

DESCRIPTION
current with L/R=40 ms

UNITS A

REQUIRED -

GUARANTEED

1.16

Digital input - number - rating


voltage

Vdc A V Hz Vdc

110 1 110(ph - ph) 50 110

1.17

Analogue Input - AC Current - AC Voltage -Frquency - Auxillary Voltage supply

1.18

Burden - voltage input - current input VA VA kbits/s 1 RS 232c 64 max Windows XP, 2xxx, Vister or NT xx Yes

1.19

Digital man-machine interface - number - type (EIA, CCITT) - data rate - protocol - compatibility

1.20 1.21

Other features - relay failure indication and contact Power supply - voltage - consumption

Vdc W

110 -

1.22

Digital interface for 87L operation - number - type (CCITT, EIA) 1 V35, RS 232c as coordinated with multiplexer supplier 64 max Yes

- data rate - modulation - duplex

kbits/s -

TECHNICAL DATA SCHEDULE PROTECTION COMPONENTS DATA

ITEM 1.23 1.22.1 2.0 2.1

DESCRIPTION Integration in Substation Automation System Serial Interface with adequate Communication Protocol Line main differential protection # 2 (87 L) Manufacturer

UNITS -

REQUIRED Yes Yes

GUARANTEED

ABB, AREVA, SIEMENS,REYR OLLE, SEL REL XXX or equiv. Phase comparison Digital microprocessor Percent bias 25 max Yes Yes Yes Yes 10

2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11 2.12 2.13 2.14

Type Function Technology Characteristics Operation time Single and three phase trip Sampling rate A/D conversion - number of bits Alphanumeric display Keypad Front panel visual indication Accuracy Tripping contacts - number - rating voltage current with L/R=40 ms

ms kHz %

Vdc A Vdc A

110 110 -

2.15

Signalling and digital output contacts - number - rating voltage current with L/R=40 ms

TECHNICAL DATA SCHEDULE PROTECTION COMPONENTS DATA

ITEM 2.16 Digital input - number - rating voltage

DESCRIPTION

UNITS Vdc A V Hz Vdc VA VA

REQUIRED 110 1 110(ph - ph) 50 110 -

GUARANTEED

2.17

Analogue Input - AC Current - AC Voltage -Frquency - Auxillary Voltage supply

2.18

Burden - voltage input - current input Digital man-machine interface - number - type (EIA, CCITT) - data rate - protocol - compatibility

2.19

kbits/s -

1 RS 232c 64 max Windows XP, 2xxx,Vister or NT xx Yes

2.20 2.21

Other features - relay failure indication and contact Power supply - voltage - consumption

Vdc W kbits/s -

110 -

2.22

Digital interface for 87L operation - number - type (CCITT, EIA) data rate - modulation - duplex

1 V35,RS 232c as coordinated with multiplexer supplier 64 max Yes

TECHNICAL DATA SCHEDULE PROTECTION COMPONENTS DATA

ITEM 2.22 2.22.1 3.0 3.1

DESCRIPTION Integration in Substation Automation System Serial Interface with adequate Communication Protocol Line main1 and main 2 distance relay Manufacturer

UNITS -

REQUIRED Yes Yes

GUARANTEED

Schweitzer, AREVA, ABB, SIEMENS, REYROLLE, SEL SEL xx, REL 5xx or equivalent Distance phase phase and phase ground Digital microprocessor programmable

3.2 3.3

Type Function

3.4

Technology

3.5

Characteristics

Mho and quadrilateral 4 zones Yes Yes Yes Yes 5( continuous ) 30(for 0.3sec) 110

3.6 3.7 3.8 3.9 3.10 3.11 3.12 3.13 3.14

Operation time Single and three phase trip Sampling rate A/D conversion number of bits Alphanumeric display Keypad Front panel visual indication Accuracy Tripping contacts - number - rating voltage current with L/R=40 ms

ms % A A Vdc

TECHNICAL DATA SCHEDULE PROTECTION COMPONENTS DATA

ITEM 3.15

DESCRIPTION Signalling and digital output contacts - number - rating voltage current with L/R=40 ms Digital input - number - rating voltage Analogue Input - AC Current - AC Voltage -Frquency - Auxillary Voltage supply A V

UNITS A Vdc A Vdc

REQUIRED 110 110 1 110(ph - ph) 50 110 1 RS 232c 64 max Windows XP, 2xxx,Vister or NT xx

GUARANTEED

3.16

3.17

Hz Vdc VA VA kbits/s -

3.18

Burden - voltage input - current input Digital man-machine interface - number - type (EIA, CCITT) - data rate - protocol - compatibility

3.19

3.20

Other features - acceleration/blocking schemes - carrier input/output - directional ground overcurrent - power swing blocking - voltage transformer fuse supervision - fault locator - syncronizing (IRIG-B) - relay failure indication and alarm contact yes yes yes yes yes preferred yes yes

TECHNICAL DATA SCHEDULE PROTECTION COMPONENTS DATA

ITEM 3.21 Power supply - voltage

DESCRIPTION

UNITS

REQUIRED

GUARANTEED

V W -

110 Yes Yes

- consumption 3.22 3.22.1 4.0 4.1 Integration in Substation Automation System Serial Interface with adequate Communication Protocol Circuit breaker failure relay (50 BF) Manufacturer

Schweitzer AREVA, ABB, SIEMENS, REYROLLE, SEL SEL xxx,NCGG, REB 5xx or equivalent Single or three poles breaker failure for single breaker or breaker and half Digital microprocessor programmable Definite time overcurrent Three preferred Yes Yes -

4.2

Type

4.3

Function

4.4

Technology

4.5 4.6 4.7 4.8 4.9 4.10 4.11 4.12 4.13 4.14

Characteristics Operating time Single and three phase trip Sampling rate A/D conversion number of bits Alphanumeric display Keypad and push buttons Front panel visual indication Accuracy Tripping contacts - number

ms kbits/s % -

TECHNICAL DATA SCHEDULE PROTECTION COMPONENTS DATA

ITEM - rating

DESCRIPTION

UNITS A A Vdc A Vdc A Vdc A V Hz Vdc VA kbits/s -

REQUIRED 5(continuous ) 30 (for 0.3 sec) 110 110 110 1 110(ph - ph) 50 110

GUARANTEED

voltage current with L/R=40 ms

4.15

Signalling and digital output contacts - number - rating voltage current with L/R=40 ms Digital input - number - rating Analogue Input - AC Current - AC Voltage -Frquency - Auxillary Voltage supply

4.16

4.17

4.18 4.19

- Burden Digital interface - number - type (EIA, CCITT) - data rate - protocol - compatibility

1 RS 232c 64 max Windows XP, 2xxx,Vister or NT xx

4.20

Other features - timers


s -

yes Yes

number setting range

- relay failure indication and contact 4.21 Power supply - voltage - consumption 4.22 Integration in Substation Automation

V W -

110 Yes

TECHNICAL DATA SCHEDULE PROTECTION COMPONENTS DATA

ITEM System 4.22.1 5.0 5.1

DESCRIPTION

UNITS

REQUIRED

GUARANTEED

Serial Interface with adequate Communication Protocol Shunt reactor differential protection (87 R) Manufacturer

yes

ABB, AREVA , SIEMENS, REYROLLE, SEL RET5xx, or equivalent Current Differential Digital microprocessor programmable 10 typical Three Yes -

5.2 5.3 5.4

Type Function Technology

5.5 5.6 5.7 5.8 5.9 5.10 5.11 5.12 5.13 5.14

Characteristics Operating time Single and three phase trip Sampling rate A/D conversion - number of bits Alphanumeric display Keypad Front panel visual indication Accuracy Tripping contacts - number - rating

ms kHz %

A A V A V

5 (Continuous) 30 (for 0.3 sec) 110 110

voltage current with L/R=40 ms

5.15

Signalling and digital output contacts - number - rating voltage

TECHNICAL DATA SCHEDULE PROTECTION COMPONENTS DATA

ITEM

DESCRIPTION current with L/R=40 ms

UNITS A

REQUIRED -

GUARANTEED

5.16

Digital input - number - rating V A V Hz Vdc VA kbits/s 110 1 110(ph - ph) 50 110 yes Windows XP, 2xxx,Vister or NT xx

5.17

Analogue Input - AC Current - AC Voltage -Frquency - Auxillary Voltage supply

5.18 5.19

- Burden Digital interface - number - type (EIA, CCITT) - data rate - protocol - compatibility

5.20

Other features - relay failure indication and contact Yes

5.21

Power supply - voltage - consumption Vdc W 110 Yes Yes

5.22 5.22.1 6.0 6.1

Integration in Substation Automation System Serial Interface with adequate Communication Protocol Shunt reactor overcurrent protection Manufacturer

ABB, AREVA, SIEMENS, REYOLLE, SEL Digital microprocessor programmable

6.2

Type

TECHNICAL DATA SCHEDULE PROTECTION COMPONENTS DATA

ITEM 6.3 6.4 6.5 6.6 6.7 6.8 6.9 6.10 6.11 6.12 6.13 6.14 Function Technology

DESCRIPTION

UNITS ms kHz/s % A A Vdc A V A Vdc A V Hz Vdc VA

REQUIRED Overcurrent Instantaneous overcurrent 10 max Three Yes Yes 5 (continuous ) 30(for 0.3 sec ) 110 110 110 1 110(ph - ph) 50 110 yes

GUARANTEED

Characteristics Operating time Single and three phase trip Sampling rate A/D conversion - number of bits Alphanumeric display Keypad or push buttons Front panel visual indication Accuracy Tripping contacts - number - rating

voltage current with L/R=40 ms

6.15

Signalling and digital output contacts - number - rating voltage current with L/R=40 ms Digital input - number - rating voltage Analogue Input - AC Current - AC Voltage -Frquency - Auxillary Voltage supply

6.16

6.17

6.18 6.19

- Burden Digital man-machine interface

TECHNICAL DATA SCHEDULE PROTECTION COMPONENTS DATA

ITEM -

DESCRIPTION number type (EIA, CCITT) data rate protocol compatibility

UNITS kbits/s -

REQUIRED RS 232 c Windows XP, 2xxx,Vister or NT xx

GUARANTEED

6.20 6.21

Other features - relay failure indication and contact Power supply - voltage - consumption Integration in Substation Automation System Serial Interface with adequate Communication Protocol Restricted earthfault protection (87N) Manufacturer AREVA, ABB, SIEMENS, REYOLLE, Schweitzer MCAG, RET 5xx, SEL xxx or equivalent High Impedance < 15% Ir Yes Yes Vdc W Yes 110 Yes Yes

6.22 6.22.1 6A.0 6A.1

6A.2

Type

6A.3 6A.4 6A.5 6A.5.1 7.0 7.1

Function / Scheme Sensitivity Integration in Substation Automation System Serial Interface with adequate Communication Protocol Autotransformer differential protection (87T) Manufacturer

AREVA, ABB, Schweitzer, SIEMENS, REYROLLE, SEL

TECHNICAL DATA SCHEDULE PROTECTION COMPONENTS DATA

ITEM 7.2 Type

DESCRIPTION

UNITS -

REQUIRED KBCH xxx, RET 5xx, SELxxx or equivalent Current differential Digital microprocessor Bias/slope 20-40 Three Yes Yes Yes 7,5 5(continuous) 30(for 0.3 sec) 110 110 110 1 110(ph - ph)

GUARANTEED

7.3 7.4 7.5 7.6 7.7 7.8 7.9 7.10 7.11 7.12 7.13 7.14

Function Technology Characteristics Operation time Single and three phase trip Sampling rate A/D conversion - number of bits Alphanumeric display Keypad or push buttons Front panel visual indication Accuracy Tripping contacts - number - rating

ms kHz % A A Vdc A Vdc A Vdc A V

voltage current with L/R=40 ms

7.15

Signalling and digital output contacts - number - rating voltage current with L/R=40 ms Digital input - number - rating voltage Analogue Input - AC Current - AC Voltage

7.16

7.17

TECHNICAL DATA SCHEDULE PROTECTION COMPONENTS DATA

ITEM -Frquency

DESCRIPTION

UNITS Hz Vdc VA VA

REQUIRED 50 110 -

GUARANTEED

- Auxillary Voltage supply 7.18 Burden - voltage input - current input Digital man-machine interface - number - type (EIA, CCITT) - data rate - protocol - compatibility 7.20 Other features - relay failure indication and contact - overfluxing protection - programmable 7.21 Power supply - voltage - consumption 7.22 7.22.1 7A.0 7A.1 Integration in Substation Automation System Serial Interface with adequate Communication Protocol Restricted earthfault protection (87N) Manufacturer

7.19

kbits/s -

1 RS 232c Windows XP, 2000 or NT 4.0

yes yes yes

Vdc W -

110 Yes Yes

AREVA, ABB, Schweitzer, SIEMENS, REYROLLE, SEL MCAG, RET 5xx, SEL xxx or equivalent High Impedance < 15% Ir

7A.2

Type

7A.3 7A.4

Function / Scheme Sensitivity

TECHNICAL DATA SCHEDULE PROTECTION COMPONENTS DATA

ITEM 7A.5 7A.5.1 8.0 8.1

DESCRIPTION Integration in Substation Automation System Serial Interface with adequate Communication Protocol Overcurrent protection (50/51) Manufacturer

UNITS -

REQUIRED Yes Yes

GUARANTEED

AREVA, ABB, Schweitzer or equivalent. ms kHz % MICOM P122 3 phases & neutral prot. digital microprocessor Inverse/inst. 20 min Three Yes Yes 7,5 max

8.2 8.3 8.4 8.5 8.6 8.7 8.8 8.9 8.10 8.11 8.12 8.13 8.14

Type Function Technology Characteristics Operation time Single and three phase trip Sampling rate A/D conversion - number of bits Alphanumeric display Keypad, push buttons or selector switches Front panel visual indication Accuracy Tripping contacts - number - rating

A A Vdc A

5(continuous ) 30(for 0.3 sec ) 110 -

voltage current with L/R=40 ms

8.15

Signalling and digital output contacts - number - rating


voltage

Vdc

110

TECHNICAL DATA SCHEDULE PROTECTION COMPONENTS DATA

ITEM

DESCRIPTION
current with L/R=40 ms

UNITS A

REQUIRED -

GUARANTEED

8.16

Digital input - number - rating

Vdc A V Hz Vdc

110 1 110(ph - ph) 50 110

voltage

1.17

Analogue Input - AC Current - AC Voltage -Frquency - Auxillary Voltage supply

8.18

Burden - voltage input - current input VA VA N/A yes kbits/s 1 RS 232c Windows XP, 2xxx,Vister or NT xx

8.19

Digital man machine interface - number - type (EIA, CCITT) - data rate - protocol - compatibility

8.20

Other features - relay failure indication and contact - inverse time characteristic selection yes yes

8.21

Power supply - voltage - consumption Vdc W 110 Yes Yes

8.22 8.22.1 9.0 9.1

Integration in Substation Automation System Serial Interface with adequate Communication Protocol Distribution feeders protection (50/51/79) Manufacturer

Specify

TECHNICAL DATA SCHEDULE PROTECTION COMPONENTS DATA

ITEM 9.2 9.3 Type Function

DESCRIPTION

UNITS -

REQUIRED Specify 3 phases & neutral prot. With multiple shots recloser digital microprocessor Fast and slow curves inverse/inst. 20 max. Three Yes Yes 7,5 max

GUARANTEED

9.4 9.5

Technology Characteristics

9.6 9.7 9.8 9.9 9.10 9.11 9.12 9.13 9.14

Operation time Single and three phase trip Sampling rate A/D conversion - number of bits Alphanumeric display Keypad, push buttons or selector switches Front panel visual indication Accuracy Tripping contacts - number - rating

ms kHz %

A A Vdc A

5(Continuous ) 30(for 0.3sec ) 110 -

voltage current with L/R=40 ms

9.15

Signalling and digital output contacts - number - rating


voltage current with L/R=40 ms

Vdc A

110 -

9.16

Digital input - number - rating

Vdc

110

voltage

TECHNICAL DATA SCHEDULE PROTECTION COMPONENTS DATA

ITEM 1.17

DESCRIPTION Analogue Input - AC Current - AC Voltage -Frquency - Auxillary Voltage supply A V

UNITS

REQUIRED 1 110(ph - ph) 50 110

GUARANTEED

Hz Vdc

9.18

Burden - voltage input - current input VA VA N/A yes kbits/s 1 RS 232c Windows XP, 2xxx,Vister or NT xx

9.19

Digital man machine interface - number - type (EIA, CCITT) - data rate - protocol - compatibility

9.20

Other features - relay failure indication and contact - inverse time characteristic selection yes yes

9.21

Power supply - voltage - consumption Vdc W 110 yes

9.22

Integration in Substation Automation System

9.22.1 10.0 10.1 10.2

Serial Interface with adequate Communication Protocol Bus differential protection # 1 (87 B) Manufacturer Type

yes

Specify REB5xx (Low Imp.) MCAG xx (High


Imp.)

or equivalent

TECHNICAL DATA SCHEDULE PROTECTION COMPONENTS DATA

ITEM 10.3 10.3.1 10.3.2 Function

DESCRIPTION

UNITS

REQUIRED

GUARANTEED

Low Impedance Protection High Impedance Protection

330kV,132kV yes 33kV yes (330kV, 132kV Option)

10.4 10.4.1 10.4.2 10.5 10.6 10.7 10.8 10.9 10.10 10.11 10.12 10.13 10.14

Technology Digital Microprocessor Electromechanical static Characteristics Operation time Single and three phase trip Sampling rate A/D conversion number of bits Alphanumeric display Keypad, push buttons or selector switch Front panel visual indication Accuracy Tripping contacts - number - rating

ms kHz % Yes option 25 three phases Yes Yes -

A A Vdc A

5(Continuous ) 30(for 0.3sec ) 110 -

voltage current with L/R=40 ms

10.15

Signalling and digital output contacts - number - rating


voltage current with L/R=40 ms

Vdc A

110 -

10.16

Digital input - number - rating -

TECHNICAL DATA SCHEDULE PROTECTION COMPONENTS DATA

ITEM

DESCRIPTION voltage A V

UNITS Vdc

REQUIRED 110 1 110(ph - ph) 50 110

GUARANTEED

10.17

Analogue Input - AC Current - AC Voltage -Frquency - Auxillary Voltage supply

Hz Vdc

10.18

Burden - voltage input - current input VA VA yes kbits/s RS 232c Windows XP, 2xxx,Vister or NT xx

10.19

Digital man-machine interface - number - type (EIA, CCITT) - data rate - protocol - compatibility

10.20

Other features - electronic relay failure indication and contact - stabilizing resistance yes yes

10.21

Power supply - voltage consumption Integration in Substation Automation System Serial Interface with adequate Communication Protocol Overvoltage relay (59): manufacturer type three-phase definite time

Vdc W -

110 yes yes

10.22 10.22.1 11.0 11.1 11.2 11.3 11.4 11.5

%, ms

Specify Yes Yes 95,20 max

- reset ratio/time

TECHNICAL DATA SCHEDULE PROTECTION COMPONENTS DATA

ITEM 11.6 11.7 11.8 11.8.1 12.0 12.1 12.2 12.3 12.4 12.5 12.5 12.5.1 13.0 13.1 13.2 13.3 13.4 13.5 13.6 13.7 13.8 13.8.1

DESCRIPTION - three adjustable independent steps Analogue Input Voltage Integration in Substation Automation System Serial Interface with adequate Communication Protocol Undervoltage relay (27): - manufacturer - type - three-phase - definite time Analogue Input Voltage Integration in Substation Automation System Serial Interface with adequate Communication Protocol Multi-shot auto-reclose relay (79): - manufacturer - type - Multi reclosure - time delay for reclosing and reclaiming - different time delay settings for single or three phases reclosing - single or three poles reclosing - single or double breakers Integration in Substation Automation System Serial Interface with adequate Communication Protocol V

UNITS -

REQUIRED Yes 110 (PH-PH)

GUARANTEED

Yes Yes Specify -

V -

Yes Yes 110 (PH-PH) Yes Yes Specify

Yes Yes yes yes yes yes yes

14.0

Synchronism check relay (25):

TECHNICAL DATA SCHEDULE PROTECTION COMPONENTS DATA

ITEM 14.1 14.2 14.3 14.4 14.5 14.5.1 15.0

DESCRIPTION - manufacturer - type - phase angle difference and frequency slip and voltage difference measurement - LLDB or LBDL schemes Integration in Substation Automation System Serial Interface with adequate Communication Protocol Tripping relay (94): - manufacturer - type self-reset hand-reset flag hi-speed operation number of contacts contact rating voltage current Lockout-trip relay (86): - manufacturer - type - hand-reset flag - hi-speed operation - number of contacts - contact rating voltage current Interposing, signalling relays 74, 48, 3, 52x, 89x...): - manufacturer - type - single-element relay - self-reset -

UNITS Vdc A Vdc A -

REQUIRED Specify MAVS 01, 02 or equivalent yes yes yes yes Specify MVAJ or equivalent Yes Yes Yes 110 Specify MVAJ or equiv. Yes Yes 110 Specify MVAA or equivalent yes yes

GUARANTEED

16.0

17.0

TECHNICAL DATA SCHEDULE PROTECTION COMPONENTS DATA

ITEM

DESCRIPTION - number of "C" contacts - hand-reset flag (alarm only)

UNITS -

REQUIRED yes Specify

GUARANTEED

18.0

Teleprotection interposing relay (85x): - manufacturer - type - hand reset flag - hi-speed - self-reset

MVAA 16 or equivalent yes yes yes Specify

19.0

Trip circuit supervision relay (95): - manufacturer - type - two or one trip coils and protective circuits supervision with circuit breaker in closed and open position - supply voltage supervision Supervision of complete trip circuits in both CB positions (closed & open)

MVAX 31 or equivalent yes

yes yes

20.0 20.1 20.2 20.3 20.4 20.4.1 21.0 21.1

Undercurrent relay (37) - manufacturer - Type - Instantaneous Integration in Substation Automation System Serial Interface with adequate Communication Protocol Neutral capacitors bank overcurrent - Manufacturer - Type - Immunity to harmonics - Tuned on fundamental frequency Specify yes yes Specify yes yes yes

TECHNICAL DATA SCHEDULE PROTECTION COMPONENTS DATA

ITEM 21.2 21.2.1 22.0

DESCRIPTION Integration in Substation Automation System Serial Interface with adequate Communication Protocol Auxiliary relay: - standard socket for rail mounting - interposing relays - supply voltage supervision (27 dc)

UNITS -

REQUIRED yes yes yes S + S CS 1 or equivalent Entrelec or equivalent Specify

GUARANTEED

23.0

Static digital time delay relay (2, 62, 48): - Manufacturer - Type - pick-up time delayed - adjustable delay (0.1-10 sec)

MVTT or equivalent yes yes MG yes yes ABB flexitest or equivalent Entrelec M4/6 or equivalent

24.0

Accessories: mini-moulded circuit breakers fuses and fuse holders neon or led pilot lights test switches or block (voltage, current, dc trip...) - terminal blocks with rail

14.4

Metering components - Data


TECHNICAL DATA SCHEDULE METERING COMPONENTS DATA

ITEM 1.0 1.1

DESCRIPTION Multifunction meter: - manufacturer

UNITS -

REQUIRED Power Measurement, Electro Industries or equivalent

GUARANTEED

1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 1.10 1.11 1.12 1.13

- type 12 bits A/D converter A (3 phases) CL 1,0 V (3 phases) CL 1,0 kW CL 1,0 kVAR CL 1,0 PF CL 1,0 Hz CL 1,0 kW-h CL 0.2 kVAR-h CL 0.2 digital MM interface

yes yes yes yes yes yes yes yes yes RS 232c Windows XP, 2xxx,Vista or NT xx included yes yes Digital display Crompton, RIS or equivalent -

- compatibility

1.14 1.15 1.15.1 2.0

- energy management software Integration in Substation Automation System Serial Interface with adequate Communication Protocol Direct-read metering instruments: - AC bus voltmeter

3.0

4-20 mAcc transducers: - manufacturer AC voltage transducer AC amp transducer AC watt transducer AC var transducer

TECHNICAL DATA SCHEDULE METERING COMPONENTS DATA

ITEM 4.0

DESCRIPTION kW and kVAR counters: - manufacturer - type - kWH/kVARH, CL 0,2 - bidirectional - digital interfaces for remote communication - compatibility

UNITS -

REQUIRED Scientific Columbus or equivalent JEM or equivalent yes yes yes Windows XP, 2xxx,Vista or NT xx

GUARANTEED

5.0

Accessories: - mini-moulded circuit breaker with auxiliary contact - test switches (voltage, current) - terminal blocks and rail

MG or equivalent ABB FT-1 Mulltiamps States or equivalent Entrelec M4/6 or equivalent

14.5

Control Devices - Data

TECHNICAL DATA SCHEDULE CONTROL DEVICES DATA

ITEM

DESCRIPTION

UNITS

REQUIRED

GUARANTEED

1.0

Apparatus control switches Turn-and-push command switch with discrepancy lamp: - circuit breaker command - disconnect switch control Kraus & Naimer, Entrelec CP or equivalent yes yes Kraus & Naimer, Entrelec VY 10 or equivalent yes yes

2.0

On/off selector switch:

- SCADA - auto-reclose

3.0

Auxiliary relay (contact repeaters): - telesignalling - DC voltage supervision (27DC) - position repeaters (89x, 52x)

Phoenix or equivalent Entrelec or equivalent S+S CS 1 or equivalent S+S CS 1 or equivalent yes yes

4.0

Control interposing relay (3C, 3T): - Capacity suitable to manoeuvre apparatus - various "C" contacts

5.0

Signalling and alarm relay: - circuit breaker fault (48) - disconnecting switch fault (48) - signalling and alarm relay (74) Alstom MVTT or equivalent Alstom MVTT or equivalent Alstom MVAA or equivalent yes

6.0

Tap changer control: - momentary push buttons

TECHNICAL DATA SCHEDULE CONTROL DEVICES DATA - position indicator Supplied by transf. Manuf. REQUIRED ABB, EES or equivalent As required As required yes GE, Entrelec or equivalent MG or equivalent GUARANTEED

ITEM 7.0

DESCRIPTION Solid-state or microprocessor based annunciator: - 48 points - 24 points - repeating contact for each input

UNITS -

8.0

Accessories: - neon or led pilot lamps - mini moulded circuit breakers - etc.

14.6

Substation Automation Components Data

TECHNICAL DATA SCHEDULE AUTOMATION - COMPONENTS DATA

ITEM 1.0 1.1 1.2 1.3

DESCRIPTION Bay Control Units (BCUs) Manufacturer Model Similar BCUs/Installations (at voltage level 330kV or higher) have already been in reliable operation for min. two years [evidence & reference list to be attached]. Technology Redundant Power Supply Operating performance

UNITS

REQUIRED

GUARANTEED

ABB, AREVA , SEL or equivalent REC5xx, REC3xx or equivalent yes

1.4 1.5 1.6

Vdc -

Digital microprocessor 110 -

TECHNICAL DATA SCHEDULE AUTOMATION - COMPONENTS DATA 1.7 1.8 1.9 1.10 Alphanumeric display Keypad Front panel visual indication Digital input - number - rating - module type Digital output - number - rating voltage

Vdc -

yes yes yes 110 -

1.11

Vdc A -

110 -

current with L/R = 40 ms

- module type 1.12 Analogue input - module type - number - A/D conversion - number of bits/sample - rating

V A or mA UNITS

12 min 1A / 4-20mA REQUIRED


GUARANTEED

voltage current (CT conn. or via transducer) DESCRIPTION

ITEM

burden

ohms

>500

1.15

Local digital man-machine interfaces - number of ports - type - date rate - protocol - compatibility kbits/s Windows XP, 2xxx,Vista or NT xx

1.16

Remote man-machine interfaces (integration in substation automation

TECHNICAL DATA SCHEDULE AUTOMATION - COMPONENTS DATA system) - number of ports - type - data rate - protocol - compatibility kbits/s Windows XP, 2xxx,Vister or NTxx

2.0 2.1 2.2 2.3 2.4

Station Control Unit (SCU) and MMI Manufacturer Model Industrial Computer Similar SCU/ Installations (at voltage level 330kV or higher) have already been in reliable operation for min. two years [evidence & reference list to be attached]. Redundant Power Supply Enclosure Processor / CPU board Graphics Controller Type Number and Type of Slots ABB, AREVA , SELor equivalent yes yes

2.5 2.6 2.7 2.8 2.9

Vdc -

110V 19 Intel Centrino -

ITEM

DESCRIPTION

UNITS

REQUIRED

GUARANTEED

2.10

Mass Data Storage CD-RW drive Hard Disk, 3 floppy disk Communication Interfaces Ports for connection of the REDUNDANT fibre optic network of the substation automation network Ethernet / Station LAN Ports Modem

2.10 2.10.1

yes

2.10.2 2.11

yes yes

TECHNICAL DATA SCHEDULE AUTOMATION - COMPONENTS DATA 2.11 2.12 2.12 2.13 3.0 3.1 3.2 3.3 3.4 21 TFT Monitor Keyboard and Mouse Colour Laser Printer Event Printer Two Redundant Gateway Computers Manufacturer Model Industrial Computer Similar Gateways / Installations (at voltage level 330kV or higher) have already been in reliable operation for min. two years [evidence & reference list to be attached]. Redundant Power Supply Enclosure Modular Construction / Multiple Protocol Conversion Communication Modules/CPUs with IEC 60870 104 IEC 60870 101 IEC 60870 103 Substation specific protocol Starcouplers Manufacturer ABB, AREVA or equivalent REQUIRED yes
GUARANTEED

yes yes yes yes

ABB, AREVA or equivalent COMxxx or equivalent yes yes

3.5 3.6 3.7 3.8 3.8.1 3.8.2 3.8.3 3.8.4 4.0 4.1

Vdc -

110V 19 yes

yes yes yes yes

ITEM 4.2 4.3 Model

DESCRIPTION

UNITS -

Similar Starcouplers / Installations (at voltage level 330kV or higher) have already been in reliable operation for min. two years [evidence & reference list to be attached]. Redundant Power Supply Applicable for Redundant Fibre Optic Network

4.4 4.5

Vdc -

110V yes

TECHNICAL DATA SCHEDULE AUTOMATION - COMPONENTS DATA 4.6 5.0 5.1 5.2 5.3 5.4 5.5 5.6 6.0 5.1 5.2 5.3 7.0 7.1 7.2 7.3 7.4 7.5 7.6 7.7 7.8 7.9 ITEM 7.10 7.11 7.12 7.13 7.14 Modular Construction GPS System Manufacturer Model Satellite Controlled Clock Power Supply Communication Interfaces Antenna Type Engineering Workstation Manufacturer Model 21 TFT Screen Shunt reactor operation controller, SROC (4) Manufacturer Type Function Technology Characteristics Operation time Single and three phase trip Sampling rate A/D conversion - number of bits DESCRIPTION Alphanumeric display Keypad Front panel visual indication Accuracy Operating contacts - number 64 min ms kHz UNITS % Digital microprocessor <V,>V, <f,>f/t definite time three REQUIRED yes 1
GUARANTEED

yes

Vdc -

110 -

yes

TECHNICAL DATA SCHEDULE AUTOMATION - COMPONENTS DATA 7.15 voltage Vdc 110

Analogue input - number input voltage or current Vdc, mA 16 -

7.16

Digital input - number - rating


Vdc A VA

64 110 -

voltage current with L/R=40 ms

7.17

Main voltage input number

2x3 -

- voltage input 7.18 Analogue output - number - current/burden - settings 7.19 Voltage settings 7.20 under voltage (steps) over-voltage (steps) time delay (steps)

mA, %

4 1, 10 k 0-100

% % s

0,85-1,0 (0,01) 1,04-1,30 (0,01) 0,5-60 (0,10)

Frequency setting under frequency (steps) frequency variation (steps) DESCRIPTION Timer settings for inputs/outputs Average voltage reference integration time (steps) settings for starting settings for operation with time delay s % % s 0-30 (1,0) 0,5-2 2-10% 0-30 (0,1) Hz Hz/s UNITS s 55-60 (0,01) -0,5 to 5,0 (0,01) REQUIRED 0,5-60
GUARANTEED

ITEM 7.21 7.22

TECHNICAL DATA SCHEDULE AUTOMATION - COMPONENTS DATA 7.23 7.24 7.25 Voltage change-over feature with time delay Line open detection Digital man machine interface - number - type (EIA, CCITT) - data rate - protocol 7.26 Other features 7.27 anti-pumping device with timesetting relay failure indication and contact 60 Hz voltage filtering sub and over synchronous freq. filter remote operation signal input min 0-30 Yes Yes Yes Yes kbits/s 1 RS 232c Yes Yes

Power supply - voltage - consumption Vdc W 110 -

8.0 8.1

Synchronized breaker switching controller (34) Manufacturer AREVA, ABB, Snemo or equivalent RPH2, F236,
ICOSTXL or equivalent

8.2 8.3 ITEM 8.4

Type Function DESCRIPTION Technology

UNITS -

Synchro. switching REQUIRED Digital microprocessor Voltage zero detection 0,1 Single
GUARANTEED

8.5 8.6 8.7

Characteristics Operation time Single and three phase operation

ms -

TECHNICAL DATA SCHEDULE AUTOMATION - COMPONENTS DATA 8.8 8.9 8.10 8.11 8.12 8.13 8.14 Sampling rate A/D conversion - number of bits Alphanumeric display Keypad Front panel visual indication Accuracy Operating contacts - number - rating

kHz ms

Yes Yes Yes 2

Vdc A

110 -

voltage current with L/R=40 ms

8.15

Signalling and digital output contacts - number - rating


Vdc A

110 -

voltage current with L/R=40 ms

8.16

Digital input - number - rating

Vdc

110

voltage

8.17

Burden - voltage input - current input VA VA DESCRIPTION - type (EIA, CCITT) - data rate - protocol UNITS kbits/s yes REQUIRED RS 232c GUARANTEED

8.18

Digital man machine interfaces - number

ITEM

8.19

Other features - relay failure indication and contact - control voltage and temperature compensation Yes Yes

TECHNICAL DATA SCHEDULE AUTOMATION - COMPONENTS DATA 8.20 Power supply - voltage - consumption 8.21 Analogue inputs - number - current range - voltage range mA V V W 110 -

9.0 8.1

Transformer Voltage Regulation System Manufacturer Maschinenfabrik Rheinhausen, EBERLE - , REGSys

8.2 8.3

Type Function / Available Schemes

Master Follower & Limiting of Circulating Current


(selectable) via BCD module yes yes

8.4 8.5 8.6

Tap Position-Interface to Transformer Transformer Parallel Operation Serial Interface to Substation Automation System

14.7

Cabinet

TECHNICAL DATA SCHEDULE CABINET DATA

ITEM 1.0

DESCRIPTION Metallic free-standing panels for control and protection: - IP 54 - modular standard (IEC 297) - pad lockable doors - door switched lamps - thermostat/hygrostat controlled heaters - ground busbar - power outlets - telephone outlets - mimic - blank plates - terminal blocks Phoenix or eq. - wiring and accessories - anchoring bolts - bottom plates with EMV cable clands for all control and LV power cables

UNITS -

REQUIRED

GUARANTEED

yes yes yes yes yes yes yes yes yes yes yes yes yes yes

15.1 DIESEL GENERATOR SET 30 kW

TECHNICAL DATA SCHEDULE DIESEL GENERATOR SET 30 kW ITEM 1.0 1.2 1.3 2.0 2.1 2.1.1 2.1.2 2.1.3 2.1.4 2.1.5 2.1.6 2.1.7 2.1.8 2.1.9 2.1.10 2.1.11 2.1.12 DESCRIPTION Manufacturer Model Type Nominal characteristics Engine Manufacturer Type N of cylinders Cylinder arrangement Rated speed Power at substation environmental conditions Max. power at sea level and 20oC Displacement Combustion cycle Compression ratio Temperature deviation factor Governor - type/model - speed regulation for step from no-load to full load - speed regulation, at steady state - isochroneous operation 2.1.13 2.1.14 Starting aid Maintenance - operating time without maintenance - operating time before overhaul h h % % 5 max. 0.5 yes Block heather RPM kW kW cm %
3

UNITS

REQUIRED

GUARANTEED

Diesel 50 (min.) 4 -

TECHNICAL DATA SCHEDULE DIESEL GENERATOR SET 30 kW ITEM 2.1.15 DESCRIPTION Exhaust accessories - silencer - piping - wall thimble - flexible couplers - support - hardware 2.2 2.2.1 2.2.2 Cooling System Type Radiator: - type - capacity (incl. engine) 2.2.3 2.2.4 2.2.5 2.2.6 Water pump type Fan blades diameter Fan motor power Cooling air: - air flow at rated power - air temp. increase at rated power - air outlet size at hook-up 2.27 2.3 2.3.1 2.3.2 2.3.3 2.3.4 Outlet wall coupling with accessories Fuel System Engine injection fuel pump type Other fuel pump type Recommended fuel Fuel consumption at: - 100% rated power - 75% rated power - 50% rated power - 25% rated power 2.3.5 Overall diesel generator efficiency l/h l/h l/h l/h % Diesel ASTM #2 m3/min C mm yes L mm kW Liquid-cooled Mounted on DG set UNITS REQUIRED yes yes yes yes yes yes yes GUARANTEED

TECHNICAL DATA SCHEDULE DIESEL GENERATOR SET 30 kW ITEM 2.4 2.4.1 2.4.2 2.4.3 2.4.4 2.4.5 2.4.6 2.4.7 2.4.8 2.4.9 2.4.10 2.4.11 2.4.12 2.4.13 Alternator Manufacturer Type Model no Voltage Phases Connection Power for substation environmental conditions at power factor Power at sea level and 20 C at power factor Temperature derating factor for temperature of Maximum neutral current Frequency Rated speed Insulation class: - material - temperature rise 2.4.14 Enclosure C F or H IP 62 Drip-proof dust-proof Brushless V KVA KVA % C A Hz 415/240 3 Yn, 4 wires 63 0,8 0,8 50 DESCRIPTION UNITS REQUIRED GUARANTEED

2.4.15 2.4.16

Exciter type Voltage regulator: - type - voltage regulation, for step from noload to full load - voltage regulation at steady state

Solid state 2 max 1 max -

% ohms

2.4.17 2.4.18

Winding resistance Short circuit current: - transient state - steady state

A A

TECHNICAL DATA SCHEDULE DIESEL GENERATOR SET 30 kW ITEM 2.4.19 DESCRIPTION Time constant: - sub-transient - transient 2.4.20 2.4.21 2.4.22 Alternator cooling Engine alternator coupling Bearing: - number - type 2.5 2.5.1 2.5.2 2.5.3 2.5.4 2.5.5 Control Cabinet Manufacturer Type Model no Enclosure Main circuit breaker: - manufacturer - type - model n - voltage - enclosure - rated current - interrupting capacity - shunt trip for protection - auxiliary contacts (for Purchaser use) - padlockable - terminals for cable of 2.5.6 Control and protective devices - digital programmable controller manufacturer type digital interface (RS 232 c) - control features remote/local selector switch start/stop for local or remote

UNITS

REQUIRED

GUARANTEED

s s -

IP 62

V A kA sym. -

Thermal magnetic 415 Moulded case 14 yes 1 N.O. - 1 N.C. yes 4 c - 4/0 AWG

yes yes

TECHNICAL DATA SCHEDULE DIESEL GENERATOR SET 30 kW ITEM


DESCRIPTION running indication (local/remote) manual voltage adjustment dc circuit mini moulded circuit breakers

UNITS -

REQUIRED yes yes yes yes yes yes yes yes yes yes yes yes For remote control For remote control and alarms Lamps for alarms and indication

GUARANTEED

- protection and alarm features emergency stop (local/remote)


overspeed overcrank low oil pressure over temperature of engine low fuel level low coolant level

diesel generator set fault heating element failure - input dry contacts - output dry contacts

- local indication 2.5.7 Instruments: - digital electrical multimeter with RS 232 c interface - speedometer (RPM) - engine water temperature (oC) - engine oil pressure (kPa) - running time meter (hours)

PM 3710 ACM EI Futura + or equivalent yes yes yes yes

TECHNICAL DATA SCHEDULE DIESEL GENERATOR SET 30 kW ITEM 2.6 2.6.1 2.6.2 2.6.3 2.6.4 DESCRIPTION Battery Charger Manufacturer Type Model no Input: - number of phases - rated input voltage - frequency - rated input current 2.6.5 Output: - rated output voltage - floating voltage - equalizing voltage - output current - equalizing charger time - short-circuit withstand 2.6.6 Input breaker: - manufacturer - type - rated voltage - rated current - rated interrupting capacity 2.6.7 Output breaker: - manufacturer - type - rated voltage - rated current - rated interrupting capacity 2.6.8 Instruments and control - dc ammeter - dc voltmeter - equalizing/floating signaling lamps - fault alarm lamp and contact Yes Yes Yes Yes Vdc A kA. 110 10 Vac A kA sym. Moulded case 400 or 220 14 Vdc Vdc Vdc A h Current limited Vac Hz A 415 or 240 50 UNITS REQUIRED GUARANTEED

TECHNICAL DATA SCHEDULE DIESEL GENERATOR SET 30 kW ITEM DESCRIPTION - manual equilizing/floating control buttons 2.6.9 2.7 2.7.1 2.7.2 2.7.3 2.7.4 2.7.5 2.7.6 2.7.7 2.7.8 2.7.9 Enclosure Battery Manufacturer Cell type Number of cells Rated battery voltage Floating cell voltage Equalizing cell voltage Rated A-h capacity at 25C (for 8 hours discharge time) Cell end voltage at 25C (for rated A-h capacity) Discharge current at rated end voltage: - during 1 hour - during 1 minute 2.7.10 Recharging current - for 1 hour - for 10 hours 2.7.11 2.7.12 2.7.13 2.7.14 2.7.15 2.7.16 Number of charging/discharging cycles Internal cell resistance Short circuit current Life expectancy Electrolyte type Accessories: - battery support - electrolyte densimeter - isolated tools - cables and connectors 2.7.17 Characteristics charts or curves to be yes yes yes yes A A ohms A Years 10 acid A A Vdc Vdc Vdc A-h Vdc PbCa UNITS REQUIRED yes IP62 GUARANTEED

TECHNICAL DATA SCHEDULE DIESEL GENERATOR SET 30 kW ITEM supplied: - voltage vs time at rated Ah - current vs time at rated Ah - temperature derating factor for battery capacity 2.8 2.8.1 2.8.2 2.8.3 2.8.4 Fuel tanks Type Capacity Autonomy of diesel generator set Fittings: - filling - venting - gauge - outlet 2.8.5 2.8.6 2.8.7 2.8.8 2.9 2.9.1 2.9.2 2.9.3 2.10 2.10.1 2.10.2 2.10.3 Fuel gauge Low fuel level alarm contact Normal vent kit Fuel transfer pump Manufacturer Model Voltage Capacity Sound Attenuated Enclosure Key lockable access doors Exhaust rain cap and shield Wheather protective design for high temperature ambient and tropical/desertic environment Stainless steel door hinges Access for electrical cable from bottom yes yes yes V L/h in. NPT in. NPT in. NPT in. NPT yes yes yes if necessary L h Double wall 96 min DESCRIPTION UNITS REQUIRED GUARANTEED

2.10.4 2.10.5

yes yes

2.10.6

Oil and water resistant acoustical

yes

TECHNICAL DATA SCHEDULE DIESEL GENERATOR SET 30 kW ITEM material 2.10.7 2.10.8 2.10.9 2.10.10 2.10.11 3.0 3.1 Concrete pad anchors Lifting hooks Daily tank at bottom Steel thickness Noise at full generator power Weight and dimensions (H x L x W) Weight Engine and alternator with exhaust 3.1.1 - weight for service - weight for transport 3.1.2 Control cabinet - weight for service - weight for transport 3.1.3 Battery charger - weight for service - weight for transport 3.1.4 Battery - weight for service - weight for transport 3.1.5 Fuel tank - weight for service - weight for transport 3.2 3.2.1 Dimensions Engine with alternator with exhaust - dimensions for service - dimensions for transport 3.2.2 Control cabinet - dimensions for service - dimensions for transport 3.2.3 Battery charger mm mm mm mm kg kg kg kg kg kg kg kg kg kg mm dB(A) yes yes Yes DESCRIPTION UNITS REQUIRED GUARANTEED

TECHNICAL DATA SCHEDULE DIESEL GENERATOR SET 30 kW ITEM DESCRIPTION - dimensions for service - dimensions for transport 3.2.4 Battery - dimensions for service - dimensions for transport 3.2.5 Fuel tank - dimensions for service - dimensions for transport 3.2.6 4.0 5.0 5.1 5.2 Outline drawings number N/A Standards Manufacturing Quality assurance ASTM D396 IEC 60947-1 ISO 9001 mm mm To be included in the bid mm mm UNITS mm mm REQUIRED GUARANTEED

6.0

Installation

Outdoor desertic/tropical environment

GTP / DATA SHEET FOR TACSR "160" CONDUCTOR


Description
1 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 2 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 3 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9 3.10 3.11 3.12
Maker's Name, Address Country of Origin
Code Name Size / Construction STANDARDS FOR DESIGN Manufacturing and testing Specn reffered for Guidelines Cross sectional area of the Conductor Standard outer Diameter of conductor Sq.mm mm

Units

Required
Specify Specify
TACSR 160mm2 (Galvanised steel core) TAL.30+ST.7/2.60 mm As per customer reffered standards IEC 62004,IEC 1089 & IEC 888 196.4 18.20

Guaranteed

TAL strands after stranding


Diameter Nominal Maximum Minimum Minimum Tensile Stress % Elongation on 250mm Guage Length Maximum resistivity of individual Strand at 20C. Wrapping Test STEEL STRANDS Diameter (a) Nominal (b) Maximum (c) Minimum Minimum Tensile Strength of strand. (a) Before Stranding (b) After Stranding Stress at 1% Elongation % Elongation on 250mm Guage Length Galvanising (a) Minimum mass of zinc coating per sq.m of Uncoated wire surface. (b) Min. no. of twists in a gauge length equal to 100 times diameter of wire which the strand can withstand mm mm mm MPa % -mm2 / Km 2.60 2.63 2.57 152 1.5 28.735 ON 1 X D

mm mm mm

2.60 2.64 2.56

Mpa Mpa Mpa %

1410 1339.5 1280 2.5

gm Nos.

218.5 16

3.13 4 4.1 4.2 4.3 4.4

in the torsion test. Wrap Test and Adhesion Test

on 3 X D and 4 X D Kg Ohm/Km Kg 7447 0.1846 (max) 2234.1

TACSR Stranded Conductor


Min Breaking Load of Conductor D.C. resistance of conductor at 20oC Maximum working tension Continuous maximum current carrying capacity of conductor .
(wind velocity = 0.5m/s, Intensity of Solar Radiation = 900 W/m2, Solar Radiation Absorption Coefficient=0.42)

4.5 4.6 4.7 4.8 4.9 4.10 4.11 4.12 4.13 4.14

In still air at 30C ambient temperature and 75C conductor temperature In still air at 30C ambient temperature and 150C conductor temperature Lay ratio of Conductor 6+1 Steel wire layer TAL 12 Wire Layer TAL 18 Wire LayerTAL 12 Wire Layer Direction of lay for outside layer Co-efficient of linear expansion Final modulus of elasticity Linear mass of Conductor

Ampere Ampere

491 752

/C N/mm2 Kg/Km 732.8

Max - 26 Min - 16 Max - 16 Min - 10 Max - 14 Min - 10 Right Hand 17.8 X 10-6 80000 732.8