Pressure Drop Calculations

Pump Discharge to Radiator Sl.No. 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0 14.0 15.0 16.0 17.0 18.0 19.0 Description Service Pressure Temperature Flow Specific volume Dynamic viscosity Material of the pipe Outside diameter of the pipe Thickness Inside diameter of the pipe Flow area Volumetric flow Flow velocity Reynold's number Surface roughness Assumed friction factor Actual frictionfactor Straight pipe length Fittings Bend/Tee/Valve 180 bend = 5D 90 bend = 5D 90 bend =1.5D 45 bend =1.5D TEE (Straight out) TEE ( side outlet) Gate valve (Open) Gate valve (-closed) Gate Valve (-closed) Gate vavle (-closed) Membrane valve Ball valve (spherical plug Needle valve Butterfly valve (larger then 6") Globe valve Nozzle (suction nozzle on Check valve (in-line ball type) Check valve (swing type) Filter (Y-type and bucket type) Equivalent fittings length 20.0 21.0 TOTAL LENGTH Pressure drop Units bar g C M3/hr m/Kg Kg/m sec mm mm mm m m/sec m/sec mts. Parameter Water 5 35 500 0.001089 7.25E-04 SA 106 Gr.B 323.9 6.35 311.2 0.0761 0.1389 1.83 7.19E+05 0.05 0.01442 0.01442 98.000 L/D 28 16 28 16 20 65 13 39 195 300 200 18 1000 20 300 32 150 135 250 Equivalent length 0.000 0.000 165.558 4.979 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 24.896 0.000 0.000 0.000 84.024 0.000 279.458 377.458 0.2676

Change this value so that the acutal and assumed are equal

mts. Quantity 0 0 19 1 0 0 0 0 0 0 0 0 0 4 0 0 0 2 0

mts. bar g

Aquatherm Engineering Consultants (India) Pvt. Ltd.,