Professional Documents
Culture Documents
Power quality is the measurement of how perfect an electrical voltage/current is at any given point or time The Measurement is in terms of:
Continuity Magnitude
Frequency
Waveform
Equipment Failure
Intangible Losses
Productivity losses
Troubleshooting
Reduced equipment life
A study was performed by European Copper Institute in 2001, covering 1400 sites in 8 countries Any given site in Europe has 5-20% probability of suffering from one or more of the problem listed.
Computer Lockups Flickering screens Flickering lights. Overheating of transformers at moderate load
The Annual losses that Industries in EU face on account of poor power quality is to the tune of 10 Billion Euros The hourly losses experienced by a few businesses in the USA
Airline reservation centers: $67,000 $112,000 ATM network and service fees: $12,000 - $17,000 Brokerage (retail): $5.6 $7.3 million Credit card sales authorizations: $2.2 $3.1 million Telephone ticket sales: $56,000 $82,000 Catalog sales centers (large retailers): $60,000 - $120,000.
Utility
Supply quality Disturbances due to other connected loads
Network
Effect of Network impedance
Load
Non Linearity
Voltage Surge Voltage Swell Overvoltage Blackout Voltage Sag Brownout Flicker Harmonics
- Over voltage that can reach thousands of volts - Lasts less than one cycle - Origin
Voltage Surge
Lightning surges Switching surges
Nearby stroke
Ground potential rise
Voltage Swell
Over-voltage that lasts for a few cycles to a few seconds 20% to 30% increase in line voltage
Surge suppressors may not operate, as magnitude will be less than 2 times
Voltage sag
Line voltage less than 80% of normal voltage Equipment malfunction or shutdown of control circuits Source: faults in the feeders
Fault at F3
Dip to 0% at Load 3 Dip to 64% at Load 2 Dip to 98% at Load 1
Fault at F1
Dip to 0% at Load 1 50% dip for other
loads
Sustained under-voltage Utilities deliberately reduce the voltage to reduce power drawn Brownouts result in
Over heating of compressor motors Loss of microprocessor memory Reduced motor torque, increased stalling Overheating of motors (insulation failure) Tripping of protective devices
Cyclic variation of intensity of lamps Repetitive sags/fluctuation of supply voltage results in flickering Causes
Effects
Harmonics are sinusoidal components of a wave, whose frequencies are integral multiples of the fundamental frequency For the fundamental frequency 50 Hz integral multiples are 2, 3, 4,etc. So, 3rd Harmonic is 3 X 50 Hz = 150 Hz
industries
SMPS
6 P Drive
CFL
12 P Drive
Y 0o 0o 0o 0o 0o
B -120o -240o +120o -360o 0o Negative sequence Zero sequence Positive sequence
Third harmonic
R Y B
Positive sequence
ITHD
< 20 20 - 50 50 - 100
>1000
15.0 %
1.4 %
20.0 %
Triple-N harmonics are additive Neutral current may rise up to 150% to 210% of the phase current
At high frequency eddy current will be high Increased neutral current because of triple-N harmonics In delta circulating currents will be more (3N harmonics)
Heating because of eddy current, skin effect Uneven torque results in mechanical damage of shaft
Distorted voltage
Harmonic current results in harmonic voltage drop, which distorts the supply voltage Higher harmonic frequencies may interfere with the data and communication line that are laid near
Capacitors offer low impedance for higher frequencies So heavy harmonic current results in capacitor damage
Most portable do not measure true RMS value and can underestimate non-sinusoidal current by 40% Frequent tripping of relays and circuit breakers
DC current flow
The effective area of the conductor, available for current flow, reduces as the frequency of the AC current increases. Hence, the resistance of the conductor increases, as the frequency increases
Mal-operation
Nuisance tripping
Trip level set lower than the fundamental value. The relay should trip as the fundamental value is higher than the trip level. But the presence of harmonics has reduced the peak value. Hence the protective relay will not trip.
Trip level set higher than the fundamental value. The relay should not trip as the fundamental value is lower than the trip level. But the presence of harmonics has increased the peak value. Hence the protective relay will trip.
Capacitive Reactance is inversely proportional to the supply frequency Offers a low impedance path to the harmonic currents resulting in harmonic amplification Can be observed through the change in THD levels before and after switching on capacitor banks
Voltage surges
Voltage swell Voltage sag Brownout Flicker Voltage swell Voltage sag Blackout Brownout
Blackout Brownout
Generators
Transformer
Disturbing equipment
Sensitive equipment
Disturbing equipment
Sensitive equipment
Not recommended
Better
Excellent
Harmonic filter
Hybrid filter
Detuned filter
Tuned filter
7%
14%
Harmonic filter comprises of a Reactor (L) in series with a Capacitor (C) Such a filter has a unique resonance frequency FR at which inductive reactance of reactor equals capacitive reactance of capacitor. FR = 1/(2LC)
Detuned or Harmonic Suppression Filters Resonance Frequency FR< 90% of lowest dominant Harmonic frequency Tuned or Harmonic Absorption Filters
Linearity
One of the most important factor that
Q factor
Ratio of the Tuning frequency to the
Bandwidth
52
53