You are on page 1of 7

W A T L O W

Transmitters/Signal
Conditioners
SERIES DX

Watlow’s SERIES DX DeviceNet™


four-channel temperature transmitter
provides high accuracy and the
flexibility of distributed networking in
a compact, DIN-mounted package.
Hundreds of temperature sensors
can now be networked together on a
single DeviceNet™ cable. This
simplifies the installation process
and reduces the cost of wiring labor

Transmitters/Signal Conditioners
and input hardware. The new
transmitter not only saves on
installation costs, but also allows all
of the latest temperature sensor
technologies based on the IEEE
1451.4 format to be accessible to
most PLCs, networks and
LabVIEW™ applications.
The DX transmitter inputs can be
used in any combination
of standard or plug and play IEEE Features and Benefits • Low power consumption; allows
1451.4 RTDs and thermocouples. Easy installation, use and up to 252 sensors to be installed
maintenance via 63 cascaded transmitters on
• Thermocouples: Type J, K, T, N,
one DeviceNet™ network run
E, R, S, B and nonstandard • Network and rotary switch
configurable • Small size enables use of smaller
• RTDs: 2- or 3-wire platinum, 100Ω,
enclosures and lowers the
DIN (0.00385 curve) • Bright, legible status LEDs for
enclosure cost per channel (four
• INFOSENSE-P™ high accuracy channel and network status
sensor inputs in 0.90 in. (22.5 mm)
plug and play IEEE 1451.4 smart • Automatic DIN-rail grounding wide package)
sensors (RTD and thermocouple) • Writable front cover for easy Very high accuracy
• WATCOUPLE thermocouple identification
• 0.5°C (±0.9°F) cold junction
long-life, high accuracy, high • Hot-swappable without having to compensation accuracy for
temperature plug and play IEEE remove adjoining transmitters thermocouples over range of -40
1451.4 smart nonstandard
• No need to install separate power to 70°C (-40 to 158°F)
thermocouples
supply • ± 0.5°C (±0.9°F) transmitter
Lower cost installation accuracy with thermocouple
(significantly lower cost per • ± 0.25°C (±0.5°F) transmitter
channel in multi-channel accuracy with RTD
installation)
Available Options
• Powered from DeviceNet™
• M12 sealed-style metal circular
network (11 to 25VÎ(dc),
male micro DeviceNet™ connector
class 2); no additional cost for
additional power supplies and • Open-style stripped five-wire
additional cabinet space DeviceNet™ connector
• Backplane cascade connection
DeviceNet™ is a trademark of the Open
DeviceNet Vendors Association.

LabVIEW™ is a trademark of National


Instruments Corporation.

129
Transmitters/Signal
Conditioners
SERIES DX Ordering Information—To order, complete the part number on the right with
the information below:
DX4000 __

Connector
B = Backplane connector only
M = M12 sealed style metal circular male
micro DeviceNet™ connector and
backplane connector
S = Open style stripped five-wire DeviceNet™
connector and a backplane connector

Printed manual 22308101

CD manual and EDS file 22307601

Dimensions
Optional Connectors

Channel
2 1

Backplane 1.79 in.


(45 mm)
Connector
4.48 in.
(114 mm)

0.71 in.
(18 mm)

1.57 in.
(40 mm)

4 3 0.90 in.
(23 mm)
4.22 in. 1.15 in.
(107 mm) (29 mm)

4.48 in.
TERMINAL T/C RTD IEEE 1451.4 (114 mm)

R
+ DeviceNet™ Connector Options
- Open Style Connector M12 Male Micro Style
TEDS (Option S) (Option M)
D
2 4 1 5 3 3 2
5
Drain
Can-L
Can-H
V+

V-

4 1
Channel Connector R
+
Removable for Easy -
D
Wiring

130
W A T L O W

Transmitters/Signal
Conditioners
SERIES 5750
Watlow’s SERIES 5750 temperature
transmitters offer remarkably
accurate temperature measurement
and improved reliability which
reduces downtime and costs.
The 5750 SERIES two-wire signal
conditioner is constructed using
surface mount technology and
utilizes digital technology with non-
volatile memory. It is designed to fit

Transmitters/Signal Conditioners
directly into universal aluminum or
universal iron connection heads with
a separate mounting kit.
The transmitter is programmed via a
separate connection cable along with
an easy-to-use Windows®-based
software program. There is no need
to use a separate thermocouple/RTD
calibrator; nor are individual resistors
required.
The SERIES 5750 provides User selectable input types • Response time appr.: 0.5
linearization between temperature seconds
• Thermocouple calibration Types
sensor input signal and the 4-20 mA
B, C, E, J, K, N, R, S and T; RTD • RFI sensitive: 20 - 1000 MHZ,
output signal, ensuring accurate
Pt100, DIN or JIS 10V/m typical <0.1 percent (of end
temperature measurements over a
CE marked value)
wider range.
• Compliant to electromagnet • Permissible ripple of supply:
Contact our customer service
interference 4V p-p
department to integrate this
transmitter into a Watlow Style AR or NAMUR compliant • Long term stability: 0.2 percent
AT thermocouple sensor or a Watlow per year
• Increased safety
Style RR or RT RTD sensor. • Calibration inaccuracy,
No external power supply needed thermocouples: max of 20µ volts
Features and Benefits for ranging or 0.01 percent
Full temperature to thermocouple • Ease of use • Temperature effect: cold junction
signal linearization over the compensation ± 0.5˚C
complete operation temperature Specifications
span • Operating voltage: 8 to 36 volts • Housing: PC, ABS/VO connection
(the SERIES 5750 is protected polyamid / V2
• Ensures signal accuracy
against voltage surges and • Mounting: DIN B or DIN-rail with
Programmable Part #30413301
reverse polarity)
• Ensures greater convenience for • Non-Isolated
• Sensor burn out protection: A
future changes and inventory
pulsed current is continuously
efficiency
checking all sensor leads for
disconnect. The output will go
upscale or downscale.
• Minimum input signal: RTDs:
10˚C, thermocouples: 2mV
Windows® is a registered trademark of the • Operating temperature:
Microsoft Corporation. -40 to +85˚C

131
Transmitters/Signal
Conditioners
SERIES 5750 Ordering Information—To order, complete the part number on the right with
the information below:
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

RTD
1-4. SERIES
5750 = Linearized T/C or RTD
1 2 3 4 5 5. Sensor Type
Standard plugs and jacks 200°C (400°F)
B = Type B T/C N = Type N T/C
C = Type C T/C R = Type R T/C
6

E = Type E T/C S = Type S T/C


7

J = Type J T/C T = Type T T/C


K = Type K T/C O = 3-wire RTD 100Ω
6. Low Temperature Sign
RLoad (Enter + or - sign)
7-9. Low Temperature
10. High Temperature Sign
8.0 - 36VÎ(dc) (Enter + or - sign)
11-14. High Temperature
PC
(Used for field 15. Unit of Measure (°C/°F)
ranging only)
Program cable and software part number 5750-CABLE (Required for optional future
changes)

T/C Standard Dimensions


1.73 in.
(44 mm)
1 2 3 4 5

1.02 in.
0.63 in. (26 mm)
(16 mm)
6
7

0.3 in.
(7 mm)

RLoad

8.0 - 36VÎ(dc)

PC
(Used for field
ranging only) 1.3 in.
(33 mm)

Wiring Diagram
Smart Sense Smart Sense

1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5
* *
- +
Pt100, Pt1000, Pt100, Pt1000, Pt100 "Smart Sense"
T/C
Ni100, Ni1000 Ni100, Ni1000 3-sensor wires
* Smart Sense-wire 4-sensor wires 3-sensor wires * Smart Sense-wire

132
W A T L O W

Transmitters/Signal
Conditioners
SERIES 5900
Watlow’s SERIES 5900 temperature
transmitters offer remarkably
accurate temperature measurement
and improved reliability which
reduces downtime and costs.
The 5900 SERIES two-wire signal
conditioner is constructed using
surface mount technology and
utilizes digital technology with non-
volatile memory. It is designed to fit

Transmitters/Signal Conditioners
directly into universal aluminum or
universal iron connection heads with
a separate mounting kit.
The transmitter is programmed via a
separate connection cable along with
an easy-to-use Windows®-based
software program. There is no need
to use a separate thermocouple/RTD
calibrator; nor are individual resistors
required.
The SERIES 5900 is isolated to
Fits directly into connection head • Sensor burn out protection: A
1500V~(ac) and features full
• Easy to install pulsed current is continuously
linearization between temperature
Programmable checking all sensor leads for
sensor input signal and the 4-20 mA
disconnect. The output will go
output signal. Isolated transmitters • Insures greater convenience for upscale or downscale.
provide isolation from input to output future changes and inventory
thus eliminating ground loops and efficiency • Minimum input signal: RTDs:
other related problems to signal 10˚C, thermocouples: 2mV
User selectable input types
integrity. • Operating temperature:
• Thermocouple calibration Types -40 to 85˚C
Additional options include insulation
B, C, E, J, K, N, R, S and T; RTD
resistance monitoring between • Response time appr.: 0.5
Pt100 and Pt1000 including four-
sensor and ground to prevent seconds
wire
inaccurate measurements due to • RFI sensitive: 20 - 1000 MHZ,
insulation breakdown. Optional insulation resistance
monitoring 10V/m typical <0.1 percent (of end
Contact our customer service value)
department to integrate this • Prevents inaccurate
measurements due to insulation • Permissible ripple of supply:
transmitter into a Watlow Style AR or 4V p-p
AT thermocouple sensor or a Watlow breakdown
Style RR or RT RTD sensor. CE marked • Long term stability: 0.1 percent
per year
Features and Benefits • Compliant to electromagnet
interference • Calibration inaccuracy,
Full temperature to thermocouple thermocouples: max of 20µ volts
signal linearization over the Specifications or 0.01 percent
complete operation temperature • Isolation: 1500VÅ(ac) for one • Temperature effect: cold junction
span minute compensation 0.02 percent C/C
• Ensures signal accuracy • Operating voltage: 6.5 to 36 volts • Housing: PC, ABS/VO connection
Full isolation from input to output (the 5900 is protected against polyamid / V2
voltage surges and reverse
• Eliminates ground loops for high • Mounting: DIN B
polarity)
data integrity

133
Transmitters/Signal
Conditioners
SERIES 5900 Ordering Information—To order, complete the part number on the right with
the information below:
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Input

1-4. SERIES
1 2 3 4 5900 = Linearized T/C or RTD
5901 = 1000Ω RTD
5902 = Isolated, linearized with insulation
resistance monitoring
6

5. Sensor Type
5

Standard plugs and jacks 200°C (400°F)


B = Type B T/C R = Type R T/C
RLoad C = Type C T/C S = Type S T/C
E = Type E T/C T = Type T T/C
J = Type J T/C O = 3-wire RTD
K = Type K T/C 1 = 2-wire RTD
6.5 - 36VÎ(dc)
N = Type N T/C 2 = 4-wire RTD

PC 6. Low Temperature Sign


(Enter + or - sign)
7-9. Low Temperature
10. High Temperature Sign
Standard Dimensions (Enter + or - sign)
11-14. High Temperature
1.73 in.
(44 mm) 15. Unit of Measure (°C/°F)
Program cable and software part number 5900-CABLE

1.02 in.
0.63 in. (26 mm)
(16 mm)

0.3 in.
(7 mm)

1.3 in.
(33 mm)

Wiring Diagram

Smart Sense Smart Sense

1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
* * T2 T1
- + Pt100
Pt100, Pt1000, Pt100, Pt1000, Pt100 "Smart Sense"
T/C
Ni100, Ni1000 Ni100, Ni1000 3-sensor wires Diff temperature
* Smart Sense-wire 4-sensor wires 3-sensor wires * Smart Sense-wire T1 > T2

134
W A T L O W

Transmitters/
Signal Conditioners
System Components Controller or PLC with 4-20mA Input
Transmitter
Typical Wiring Diagrams for
Two-Wire Signal Conditioners 4-20mA -
+
4-20mA
Input
- +
Input
- +
Contoller or PLC

DC
Power
Supply

Transmitters/Signal Conditioners
Controller or PLC with Intergal Power Supply
Transmitter

+ - 4-20mA
+ Input
-
+ DC
Input 4-20mA
- Output

Controller or PLC

Controller or PLC with 1 to 5 Volt Input


Transmitter

4-20mA
-
+ 250 1 to 5
Load Volt
Input
- +
Input
- +
Controller or PLC
DC
Power
Supply

Transmitter and Connection


Head Mounting Options

Connection Heads

Cast Cast Explosion Poly Heads


Signal Conditioner Model and Description Aluminum Iron XP SERIES Pt SERIES

5750, Non-isolated, Non-linearized Mount with kit Does not fit Mount with kit Mount with kit
81501901 81501301 81501201
5900, 5901 and 5902, Isolated, Linearized Mount with kit Does not fit Mount with kit Mount with kit
81501901 81501301 81501201

135