600/1000V STANDARD COPPER CONDUCTORS PVC INSULATED WITH STEEL WIRE

ARMOUR AND PVC SHEATHED OVERALL


CABLE SIZE
CONDUCTOR
NUMBER OF CORES
NOM.
AREA
NEUTRAL 1
2
3
31/2
4
5
7
10 12 19
2
MM
1.5
16
16
20s 20s 20s 20 20 25
2.5
20s 20s
20s 20s 20 25 25 25
4
20s 20
20
20
25 25 32 32
6
20
20
20
10
25
25
25
16
25
25
25
25
16
32
32
32
32
25
25
32
35
16
32
32
32
40
25
32
32
50
25
25
32
32
32
40
70
35
25
32
40
40
40
95
50
25
40
40
50s 50s
120
70
32
40 50s
50
50
150
70
32 50s 50
50
63s
185
95
32
50
50
63s
63
240
120
40
50 63s
63
75s
300
150
40 63s 63
75s
75
300
185
75
400
185
50s 63 75s
90
90
500
50
630
50
800
63s
1000
63
-

27

37

48

25
32
40

32
32

32
40

Metric threads 1.5 mm pitch are standard up to size 75mm. For size above 75mm pitch
would be 2 mm BS 3643 applies only on Brass Cable Glands comply with BS 6121 :
1989.
The following table gives the more popular forms available. (The table is not a size for
size comparison chart. Some taper threads e.g. NPT, BSPT may require larger than
standard entry components to accommodate the taper dimensions

We will mark the glands with any other threads E.G. BW-20L like BW-20L/1/2"NPT

LAND
SIZE

METRIC
(MM)

NPT

PG

BSP

Preferred

Alternate

Preferred

Alternate

Preferred

Alternate

16L
20S
20L
25L
32L
40L
50S
50L
63S
63L
75S
75L
90L

16
20
20
25
32
40
50
50
63
63
75
75
90

3/8"
1/2
1/2
3/4
1
1-1/4
1-1/2
2
2
2-1/2
2-1/2
3
3-1/2

1/2"
3/4
1
1-1/4
1-1/2
-

11
13.5
16
21
29
36
36
42
48
-

9, 13.5
11,16
11,13.5,21
29
42
48
-

3/8"
1/2
1/2
3/4
1
1-1/4
1-1/2
2
2
2-1/2
2-1/2
1-1/2
3

1/2"
3/4
1
1-1/4
1-1/4
3
3-1/2

IMPERIAL
5/8"
3/4
3/4
1
1-1/4
1-1/2
2
2
2-1/2
2-1/2
3
3
3-1/2

NOTE :Other thread types can be supplied at extra charge - details on request.