You are on page 1of 25

MQUINAS ELTRICAS

MANUTENO DE TRANSFORMADORES

Por: Delirose Ramos

O QUE MANUTENO?

MANUTENO A COMBINAO DE TODAS AS AES TCNICAS E ADMINISTRATIVAS, INCLUINDO AS DE SUPERVISO, DESTINADAS A MANTER OU RECOLOCAR UM ITEM EM UM ESTADO NO QUAL POSSA DESEMPENHAR UMA FUNO REQUERIDA. (NBR-5462)

TIPOS DE MANUTENO
CORRETIVA PREVENTIVA

PREDITIVA

DETECTIVA

QUADRO COMPARATIVO

MANUTENO DE TRANSFORMADORES

CONSIDERAES INICIAIS

ALTITUDE DE FUNCIONAMENTO

LIGAES

ATERRAMENTO DO TANQUE

COMPONENTES DE PROTEO E MANOBRA

SINTOMAS DE FALHAS COMUNS

RUDO INTERNO ANORMAL

POSSVEIS CAUSAS ARCO ELTRICO FASE-FASE OU FASE-TERRA

ATUAO DEVE-SE RECUPERAR AS PARTES DANIFICADAS


PELO ARCO OU SUBSTITUIR AS MESMAS, CASO A RECUPERAO NO SEJA MAIS POSSVEL.

INTENSO VAZAMENTO DE LEO

POSSVEIS CAUSAS FALHAS NAS ESTRUTURAS E/OU CONEXES,


PODEM SER CAUSADAS POR IMPACTOS SOFRIDOS PELOS EQUIPAMENTOS, OU CORROSO DO MATERIAL.

ATUAO A INTERVENO DEVE SER IMEDIATA, UMA VEZ


QUE SE O NVEL DO LEO ALCANAR VALORES MUITO BAIXOS, PODE-SE PERDER O EQUIPAMENTO.

DISPOSITIVO DE PRESSO ATUADO POSSVEIS CAUSAS ARCO INTERNO

ATUAO ELIMINAO DO PONTO DE ARCO

REL DE GS ATUADO POSSVEIS CAUSAS LIBERAO DE GS NO LEO DO


TRANSFORMADOR

ATUAO DEPENDE DA NATUREZA DO GS, CASO SEJA


INDICATIVA DE POSSVEL EXISTNCIA DE ARCO, O REPARO DEVE SER REALIZADO IMEDIATAMENTE.

SOBREAQUECIMENTO EXCESSIVO DOS CONECTORES

POSSVEIS CAUSAS MAU-CONTATO NOS TERMINAIS DO


TRANSFORMADOR; ARCO ELTRICO NOS TERMINAIS.

ATUAO EM CASO DE IDENTIFICAO DE ARCO ELTRICO,


A ATUAO DEVER SER IMEDIATA, EM CASO DE MAU-CONTATO, DEVE-SE PROGRAMAR A MANUTENO DO EQUIPAMENTO.

ANLISE DE LEO DO TRANSFORMADOR

GS PREDOMINANTE: ACETILENO OCORRNCIA DE ARCO ELTRICO, INDICA QUE O LEO PODE SER CARBONIZADO.

GS PREDOMINANTE: ETILENO SUPERAQUECIMENTO DO LEO

GS PREDOMINANTE: HIDROGNIO DECOMPOSIO DA GUA ASSOCIADA COM A FERRUGEM; DESCARGAS PARCIAIS NA CELULOSE

GS PREDOMINANTE: MONXIDO DE CARBONO INDICAO DE CELULOSE SUPERAQUECIDA