You are on page 1of 1

C A B L E

A S S E M B L Y

I N S T R U C T I O N

Controller Model: Maple OIT Model:

Koyo DL405 (D4-450 CPU) OIT3100 and OIT4100 Series

Communication Type: RS-422 with DB25 connector at PLC


Use the wiring diagram and illustration to assemble a communication cable for use with a Koyo DL405 PLC (D4-450 CPU, Port 3).
#6 Crimp Lug 18 AWG Green wire

To Chassis Ground
DB25 Backshell

RJ-45 Shielded Plug for round cable and 26 AWG wire 4 Pair 26 AWG Shielded Cable, Category 5 Metric, M2.6 x 0.45 x 12.7 mm Retainer Screws, 2 places

OIT END

Pin 1 DB25P Connector

PLC END NOTES: Twist together 18 AWG green wire and shield wire. Solder 1 wires and insulate with heatshrink to avoid shorting. Connect shield wire to the metal housing of the RJ-45 connector.. 2
1

OIT
RXDRXD+ Return TXDTXD+ 8 1 8 1

Green

To Chassis Ground PLC

RJ-45 7 8 4 2 1

Shield 25P 13 12 7 25 24

TXDTXD+ Signal Ground RXDRXD+

Top

Pin Configuration RJ-45 Plug

1022-0037, Rev 04