SELECTION CHART FOR DOL STARTERS

ML Relays and ML Contactors

(Type C Co-ordination IS8544 (Part1)/IEC 292-1, Type 2 Co-ordination IS13947(Part4/Sec1)/IEC 60947-4-1)


Sr.No.

Motor Rating 415V - 3 Phase

Motor 240V - 1 Phase


HP

kW

In,A

H.P.

kW

In,A

Relay Range Contactor


A

HRC Back-up
Fuse
Rating, A

0.125

0.09

0.4

0.4 - 0.65

ML0

0.15

0.11

0.45

0.4 - 0.65

ML0

0.2

0.15

0.57

0.4 - 0.65

ML0

0.25

0.19

0.7

0.6 - 1

ML0

0.33

0.25

0.88

0.6 - 1

ML0

0.5

0.37

1.2

1 - 1.6

ML0

0.75

0.55

1.6

1.5 - 2.5

ML0

0.75

1.8

1.5 - 2.5

ML0

1.25

0.92

2.1

1.5 - 2.5

ML0

1.5

1.1

2.6

2.5 - 4

ML0

10

11

1.75

1.3

2.5 - 4

ML0

10

12

1.5

3.5

2.5 - 4

ML0

10

2.5

1.8

4.8

4.5 - 6.5

ML0

16

14

2.2

4.5 - 6.5

ML0

16

15

6.2

4.5 - 6.5

ML0

16

0.125

0.11

7
8

0.25

0.18

9
10

13

0.5

0.75

0.4

3.6

0.55

16

0.75

7.5

3.7

7.5

6 - 10

ML0

20

17

1.25

0.9

4.5

6 - 10

ML0

25

18

1.5

9.5

7.5

5.5

11

10 - 16

ML0

25

19

2.25

10

7.5

14

10 - 16

ML1

32

20

12.5

9.3

18

13 - 21

ML1.5

50

21

15

11

21

20 - 32

ML1.5

63

22

17.5

13

24

20 - 32

ML2

63

23

20

15

28

20 - 32

ML2

63

24

25

18.6

35

28 - 42

ML3

80

25

30

22.5

40

28 - 42

ML3

80

14

8/27