SOLKOR R 5KV & 15KV

1 Availability of schematic diagram. 2 After the FDR switched 'OFF', check the pilot resistance ( 2.4K) * Disconnected the pilot wire and re-check the resistance; it will be ( 1.2K). This to confirm the pilot is healthy; and prevent the operation of the solkor relay in far end. In some s/stn. The terminal block not quit clear. 3 Start testing for the relay with necessary connection to measuring the spill current and voltage in pilot. 4 Apply the actual tripping test for the feeder, check for alarm, auto-trip locally and with respect to N.C.C. 5 Re-connect the pilot back to normal after measuring the resistance of pilot cable and confirm that is ( 2.4K) in open and ( 1.2K) when normalized back to normal. 6 After normalizing the FDR. back to normal, the on load current in CT circuits, also check the spill current (mA DC) shall be very small (in micro- amp).