UNIVERSAL GAS SIZING - VALVES IN SERIES

G 0.57 Specific Gravity


T 146 °F 605.69 R (Rankine)
CV1 12.5
Liquid Sizing Coefficients
CV2 11.5
P1 8250 psig Upstream Pressure
C11 37.0
Ratios of Gas Sizing Coefficient and Liquid Sizing Coefficient
C12 22.0
dP 3900 psi Pressure Drop
CVT 8.5 1/CVT2 = 1/CV12 + 1/CV22
C1T 29.8 Ratio of C1 based on Cv
Cg 252.31 Gas Sizing Coefficient
Angle 78.8 use 78.8 degrees
Sine 0.98

2,514,447 scfh
60,346,722 scfd
Q=
60.35 mmscfd
41,907 scfm

Reference: Fisher

Note: If the sine function is unity, flow is choked and the value of sine is set to 1.0

Choked Flow: Also known as "Critical Flow". "This condition exists when at a fixed upstream
pressure the flow cannot be further increased by lowering the downstream pressure."