Transformer-Differential Protection Relay P632

Sub Station :
Model No :
Serial No :
Frequency:

Date
:
Aux.Voltage :
Rated Current:
Version
:

Settings:
Ratings
Capacity
HV side Circuit-A
LV side Circuit B
Connection

220 kv
66 KV

CT Ratios
HV side Circuit-A
LV side Circuit-B

800/1
1000/1

Iref
HV side Circuit-A
LV side Circuit-B
Kamp

0.874 A
0.131 A

HV Side Circuit-A

7.621

LV Side circuit-B

1.143

Relay Settings
Diff.
Id>
m1
m2
Ir m2

0.2
0.2
0.8
1.5

Measurement:
Circuit

Phase

Injected Value(A)

Relay Measured(A)

HV
HV
HV
LV
LV
LV

R
Y
B
R
Y
B

0.131
0.131
0.131
0.874
0.874
0.874

52
52
52
1749
1749
1749

20 % SLOPE :

Characteristic equation for the range 0.5. Id> < IrIr m2


(Id/Iref )=m1. (Ir/Iref) + {(Id>/Iref) . (1- 0.5 x m1) }
Phase
R
Y
B

Circuit-A (I1)
1
1
1

Circuit-B(I2)
0.62
0.62
0.62

Id theoretical
0.38
0.38
0.38

Id actual
0.380
0.383
0.382

80 % SLOPE :
Characteristic equation for the range Ir m2< IR
(Id/Iref )=m2. (Ir/Iref) + {(Id>/Iref) . (1- 0.5 x m1) }+ 1.5 (m1-m2)

Phase
R
Y
B

Circuit-A (I1)
2
2
2

Circuit-C (I2)
1.33
1.33
1.33

Id theoretical
0.67
0.67
0.67

HARMONICS TEEST
2 ND HARMONIC TEST: TRIPPING LESS THAN 10%
5 TH HARMONIC TEST: TRPPING LESS THAN 20%
CONTACT CHECKS

: OK

LED CHECKS

: OK

OPTO CHECKS

:OK

Tested By:

Witnessed By:

Signature:

Signature:

Id actual
0.672
0.671
0.673