You are on page 1of 1

8

11 112.00 110.00

48.00 CLEARANCE PER NOTE #4

48.00 CLEARANCE PER NOTE #4

56.00

NOTES: 1. CUSTOMER PIPING MUST BE SUPPORTED NEAR ALL INTERFACE CONNECTIONS TO ELIMINATE STRAIN. 2. ALL PIPING SUPPORTS ARE NOT SHOWN FOR CLARITY PURPOSES. 3. ALL POLYMERIC DRAIN LINE PIPING TO THIS LOCATION. 4. MINIMUM CLEARANCE TO ANY OBSTRUCTION REQUIRED BY THE NATIONAL ELECTRIC CODE. 5. SHIPPING DIMENSIONS: 144"L x 112"W x 121"H. 6. ESTIMATED SHIPPING WEIGHT: 9,000 LBS, ESTIMATED OPERATING WEIGHT: 11,600 LBS. 7. CONDUIT AND SMALL PIPING RUNS TO FOLLOW STRUCTURAL MEMBERS, WHERE POSSIBLE, TO AVOID CREATING TRIP HAZARDS. 8. TO ACHIEVE THE PROPER BUILDING FOUNDATION DESIGN, AN ENGINEER SHALL BE RETAINED WHO IS FAMILIAR WITH LOCAL BUILDING CODES, SOIL CONDITIONS, AND ANCHORING REQUIREMENTS. 9. BASE PLATE SETTING PRIOR TO PIPING: GROUTING PROCEDURES AND FINAL ALIGNMENT MUST BE IN ACCORDANCE WITH THE XYLEM A-C FIRE PUMP INSTRUCTION MANUAL. 10. INSTALL CHECK VALVE WITH HINGE PINS IN THE VERTICAL POSITION. 11. PRESSURE SENSING LINE DRAINS TO BE PIPED TO THE SKID DRAIN MANIFOLD. ITEMS TO SHIP LOOSE: METERING AND PRESSURE GAUGES.

BOM SYM 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 DESCRIPTION CNTRLR,JOCKEY CNTRLR,ELECTRIC,MAIN DISCONNECT FLOWMETER,GROOVED,GERAND K-500-6 GAUGE,3.5,SS,.25,0-300,DUAL DISP GAUGE,3.5,SS,.25,LM,30-0-30,DUAL DISP HEATER,W/ THERMOSTAT,7.5KW MOTOR,FRAME,NEMA,HORIZ,365TS LOAD CENTER PANEL POWER PAK,15-KVA PUMP, GOULDS,eSV,1-5SV_G PUMP,8100,CL150,6x4x9F,CW SWITCH,TAMPER,SYSTEM SENSOR OSY2 VALVE,AIR RELEASE,175PSI,15A,.5 VALVE,AIR, RELEASE VALVE,BFLY,ANVIL,GEAR,W/TAMPER,UL/ULC,6 VALVE,CHECK,NIBCO,KW-900-W,6 VALVE,CLA-VAL,2050B-4KG1,CL150,3 VALVE,GATE,OSY,NIBCO,F-607-RW,6 WASTE CONE,C.S.,3x5,CL150,CLOSED ------100-200-309 88-001-279 88-001-275 ------80-003-032 --100-210-056 23-003-050 16-003-005 --20-005-385 23-002-225 100-200-454 23-002-525 100-200-404 P/N ITEM QTY 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 1 1 1 1

26.50

CUSTOMER INTERFACE CONNECTIONS: A. SUCTION: FLANGED, 8", CLASS 150#. B. DISCHARGE: FLANGED, 6", CLASS 150#. C. DRAIN: 2" CLASS 150#. PAINT SPECIFICATIONS: PAINT PER XYLEM FLOWTRONEX SPEC FPP-002.

2.00 .00 18 20

72.00

52.38

144.00 142.00

123.19

13.44

2.00 .00

15 121.00

NOT FOR CONSTRUCTION

29.75

11.57

9.63 .00 10661 NEWKIRK STREET DALLAS, TX 75220 800.786.7480 DRN: MAURICIO HERNANDEZ CHK: DATE: 9/5/2012 DATE:

.00

13

19

16

14

12

17

16

16

10

STATION PARAMETERS GPM: 500 INTAKE PSI: 10 DISCHARGE PSI: 40 VOLTAGE: 460 HZ: 60 PHASE: 3

THIS DRAWING AND THE INFORMATION DEPICTED THEREIN IS THE PROPERTY OF XYLEM. COPIES ARE ISSUED IN STRICT 500 GPM WITH BUILDING THRU FLOOR CONFIDENCE AND SHALL NOT BE REPRODUCED OR COPIED, OR USED AS THE BASIS FOR THE MANUFACTURE OR SALE OF REV SIZE SHEET : PRODUCTS WITHOUT PRIOR WRITTEN PERMISSION OF XYLEM. 0 1 /1