Professional Documents
Culture Documents
Table 2.3
19
During the design of outdoor areas, project teams should lay
out buildings, roads, and public spaces on site to protect and
celebrate the presence of on site ecological features. These
features could form a theme for site-wide landscaping
strategies.
The natural systems strategy should outline any activities
that may cause damage to sensitive areas during the
operation and construction phases of the development.
It should identify measures that have been designed into
the scheme and those that will be implemented during the
operation to protect these areas / species, for example,
limited access to mangrove areas and boardwalks provided
for pedestrians to minimise damage to mangrove roots.
The protection strategy should include measures such as:
Design protection measures
Ensuring that work compounds, access tracks etc are not
located in or adjacent to sensitive habitats
Establish temporary fencing around protected areas to
restrict access
Undertake any works near protected areas in a manner so
as to safeguard their integrity
Undertake works considering any critical seasons for
protected species
Some of these measures could be included in the
Construction Environmental Management Plan if prepared as
part of IDP-3.
The Mitigation Strategy report should identify the areas
to be protected and measures adopted to ensure their
protection, as outlined in the Protection Strategy Report. It
should identify the mitigation areas and justication for the
appropriateness for mitigation including:
Area calculations
Identication of appropriate plant nurseries
Continuous monitoring of success or failure of young
plants
Management techniques to encourage establishment. This
should be adapted following any failures.
The Compensation Strategy report should demonstrate
options considered for off site compensation and the
selection criteria for the proposed compensation site.
The report should include measures to ensure ora
establishment as outlined in the mitigation strategy and
protection measures as outlined in the protection strategy.
Consideration should be given to the habitat lost on the
proposed site and the potential to provide enhanced habitat
of a similar type to the habitat lost. The author of this
report should be a qualied ecologist who has experience
in habitat establishment for those particular habitats, for
example, mangrove specialist.
C
o
n
t
e
x
t
20
2.4 Manage natural systems Related Credit: NS-R3: Natural Systems Design & Management Strategy
A Natural Systems Design and Management
Strategy is required to ensure the long-term
survival and prosperity of ecological assets. The
strategy must cover all landscaped areas and
include the management of any on or off-site
protected, mitigated or compensated natural
asset areas. The strategy should promote soil
protection and enhancement, low maintenance
requirements and low demand for resources.
The team should consider using only native
species, and landscapes that do not require
wasteful use of irrigation when developing the
landscaping strategy and Natural Systems Design
and Management Strategy. This will be rewarded
with additional points under options PBRS credits.
The Management Strategy should identify the
seasons during which each activity will be carried
out.
Soil protection
Plant selection should suit existing soils onsite. Where
soil enhancement is required this should be tailored to
the existing soil type. Where soils is brought on site,
this should be protected from erosion, pollution and
increases in salinity. Paths should be provided to avoid
pedestrian compaction of soil. Irrigation should consider the
topography of the site and soil erosion.
Low maintenance requirements
Landscaping should be a combination of hard and soft
landscaping, and should minimise the application of
fertilizers, pesticides and herbicides. Landscaping should
promote low maintenance requirements.
Low demand for resources
Plant selection should reect the microclimate conditions
of the area. Water efcient irrigation systems such as
drip irrigation should be adopted to minimise water
consumption.
Example 2.4: Landscaping images
21
2.5 Assess urban systems Related Credit: LBo-R2: Urban Systems Assessment
An urban systems assessment details the urban context
around the project site, the type of neighbourhood the
building will exist within, and how accessible and integrated
the building will be.
The analysis should be carried out at the start of the project,
before site clearance, to inform project programming,
neighbourhood connectivity and built form.
The end-product of this analysis is the Urban Systems
Assessment Report, and should include a narrative, maps,
and site photos. Site plans or diagrams should be provided at
the Local, Subregional, and Regional scales.
The content of the plans provided should be tailored to the
scale of the plan, i.e. local, sub-regional or regional. Where
facilities are to be provided in the future, this should be
indicated.
Plans provided should document the following at a
minimum:
Community facilities
Public interest areas, such as public beaches, cultural or
heritage landmarks
Street patterns
Public transit facilities, bicycle and pedestrian paths
Utility plots and corridors, such as electricity, gas,
potable water and wastewater
Land uses, such as retail centres, food provision areas,
and areas of food production
Residential zones, centres of employment, and
education facilities
Solar orientation and shading patterns from surrounding
buildings should be shown at the local level.
1
2
3
4
5
6
7
Utility corridor
Bike Path
Pedestrian Path
Transit Stop
Existing Buildings
Utility Building
8
Retail Centre
Example 2.5a: Plan showing local urban systems
C
o
n
t
e
x
t
22
Major Road Corridor
Major Utility Corridor
Community Facility
Cultural Landmark
Transit Stop
Park Area
Residential Area
Existing Buildings
Public Beach
(A regional scale assessment
will describe larger features
such as natural areas, etc.)
Example 2.5b: Plan showing sub-regional urban systems
23
2.6 Identify opportunities + constraints Related Credits:NS-R1: Natural Systems Assessment
Contextual opportunities and constraints are important to
identify to allow the development to take advantage of
special site features and address site challenges effectively.
Information obtained in the Natural Systems Assessment
and in the Urban Systems Assessment informs the
formation of a complete opportunities and constraints
analysis. An example study is shown to the right, illustrating
how Opportunities and constraints can be used to inform
the design of a site.
The opportunities and constraints of the proposed site
will determine the areas that can be developed, the most
appropriate type of development and issues that will
need to be addressed during the design, for example,
contamination and remediation strategies.
Key Performance Indicators (KPIs) should be prepared to
guide the design of the development based on the results
of the opportunities and constraints analysis. The KPIs
should be measurable targets and cover soil, ora, fauna,
microclimate, topography, drainage, targets set to mitigate
identied constraints and areas of site to be protected,
maintained, created or restored.
Examples include:
Percentage increase of protected species / priority
habitats on site through habitat enhancement
Percentage of reuse of soils on site
Views
Pedestrian Link
Infrastructure
Main Traffic Route
Local Traffic Route Prevailing Wind
Sun Path
Example 2.6: Plan showing opportunities + constraints
C
o
n
t
e
x
t
Spiney Tailed Lizard
Burrows
Protected Ghaf Trees
24
3.0 Design outdoor spaces
The impact of a building can be reduced signicantly by
decisions made early in the design process. The relative
location of other buildings, windows, and outdoor areas
ditectly impacts on the amount of energy, water and
materials required to keep a building comfortable.
The buildings orientation and massing has to be planned
in relation to its urban and natural environment. Building
should be designed to reduce internal heat gains and
harness daylight so that their energy demand will be
reduced. This can be achieved by using materials in the
buildings envelope that comply with the minimum U values
specied in credit RE-R1 and also by careful selection the
glazing elements in the facade. When selecting building
materials, the requirements of credit SM-R1 that forbids the
use of chromated copper arsenate (CCA) treated timber and
asbestos containing materials (ACM).
Buildings can also contribute to improve pedestrian comfort
by providing external shading and shielding pedestrians from
prevailing hot winds hence contributing to the requirements
specied in credit LBo-R3. Local weather data sets are
available to analyse how the building elements will perform
Related Credits
NS-R1: Natural Systems Assessment & Protection
LBo-R3: Outdoor Thermal Comfort Strategy
RE-R1: Minimum Energy Performance
SM-R1: Hazardous Materials Elimination
SM-R3: Storage & Collection of Waste & Recyclables
LBi-R2: Smoking Control
and the effect the building will have in its surroundings.
The buildings plot landscape should be designed to protect
and link natural habitat around it. The building should also
be adequately linked to the adjacent streets to facilitate
pedestrian and vehicle movements. In particular, credit SM-
R3 requires to provide access to waste collection vehicles.
Finally, the design of the building outdoor spaces should
meet credit LBi-R2 requirements to designate smoke free
zones around sensitive areas of the building but also to
allocate dedicated external smoking areas.
Useful resources:
Abu Dhabi weather data from EnergyPlus
(http://apps1.eere.energy.gov/buildings/energyplus)
25
Harmonious integration with
surroundings & pedestrian environments
Cool breezes can reduce heat build up in external areas as
well as freshen the air in externally accessible areas. Hot
winds cause unpleasant and uncomfortable conditions
building up heat in external areas, increasing heat load on
the building and increasing pedestrian thermal discomfort.
Understand local wind climate, identifying orientation,
timing and temperature of prevailing winds.
Consider position, form and orientation of nearby
buildings to understand wind movement and how the
external environment is affected.
Use building form and position to best use cool
breezes. This will help to reduce build-up of hot or
stagnant areas at pedestrian level.
Use building form to shelter pedestrian areas from hot
or high speed winds.
Consider the use of external building features as well
as building form and massing to minimize adverse
impacts from wind on the public realm. Features to be
considered include, but are not limited to:
shading devices, e.g. brise-soleil, mashrabiya, etc.
overhangs
breaks in facade continuity
podiums
openings
permeable features
Potential adverse impacts include downwash, corner
accelerations and local wind direction changes amongst
other effects.
3.1 Building layout
The layout of the buildings on the plot has many
implications later in the design process, especially with
regard to energy performance and external shading. The
design team should carefully consider the following:
Optimize natural light but minimise solar
gains
Utilize external shading devices to reduce solar gain,
whilst maintaining external views. For example by
providing horizontal shading on South orientation and
vertical shading on East and West orientations.
Use shadows cast by surrounding buildings to provide
shade and reduce solar gains.
Place windows in shaded areas, recessed into the wall,
or facing North to provide light to indoor spaces.
Use rooights sparingly as these signicantly increase
solar heat gains. Consider using sunpipes or solar-
tubes instead.
1
1
2
3
4
5
6
2
3
Consider the need for mitigation of adverse wind
conditions within the public realm. Potential mitigation
strategies include, but are not limited to:
canopies
wind screens
shelter belts
deployable structures
4
O
u
t
d
o
o
r
Related Credits: LBo-R3: Outdoor Thermal Comfort Strategy
RE-R1: Minimum Energy Performance
26
The building orientation in relation to local winds and
sunpath as well as the inuence of surrounding buildings
and other landscape elements should be considered to
provide an adequate outdoor space that improves the
buildings exterior microclimate and achieves adequate
pedestrian comfort.
In particular for shading, it is required to check that the
shading percentage required by credit LBo-R3 is achieved
on the equinox (21st of March) and the summer solstice
(June 21st ) at 1.00pm over the following elements:
Exterior Surface Parking with more than 10 spaces,
including parking on exposed roof car parks
Public Open Spaces, including privately owned
Pedestrian walkways
Cycle tracks
Playgrounds
The checks can be done using sun altitude and azimuth
data (For Abu Dhabi, the summer solstice alt = 81.4,
azi =-94.6 and for the spring equinox alt = 64.2, azi
= -161.6) or an appropriate software such as 3D CAD
software, e.g. Ecotect, or free 3D tools, such as Sketch up.
Shading can be provided by mature trees or by structures,
such as canopies. If structural elements are used, their outer
surfaces must have a minimum Solar Reectance Index
(SRI) of 29. The SRI is a measure of the roofs ability to
reect solar heat, and the higher it is, the better the surface
is a reecting heat. High SRI can be achieved with light or
reective materials and/or nishes, e.g. some concretes,
light aluminum cladding.
The guidelines in the UPC Urban Street Design manual
can be used for designing the outdoor spaces around the
building. The manual can be downloaded from
http://www.upc.gov.ae/guidelines/urban-street-design-
manual.aspx.
3.2 Outdoor thermal comfort
The following example shows different strategies of how
the required levels of shading can be achieved using
adequate building layouts, natural elements or some
additional construction elements.
Example 3.2a
Use trees to provide
shading to pathway
Building orientation will provide
shade to required areas
Provide external
overhangs
Related Credits: LBo-R3: Outdoor Thermal Comfort Strategy
27
Example 3.2b: Outdoor shading plan
BUILDING
BUILDING
BLOCKS
PARK
PARKING
PLAZA
PLAYGROUND
CANOPY
CANOPY
CANOPY
O
u
t
d
o
o
r
28
3.3 External waste and recycling storage
The central waste and recycling storage room is typically
located in the buildings ground oor or basement and
should be easily accessible from street level by collection
vehicles. It is typically air conditioned, enclosed and located
near loading docks or bays and has doors at least 1.8 m
wide to facilitate material movement and pick up as shown
in examples 3.3a and 3.3b. The room must be sized to
allow for the storage and movement of waste containers.
To reduce the volume of waste and recyclables, and
associated space requirements, compactors or balers are
typically used. Particular attention has to be paid to turning
radii of collection vehicles and vertical and horizontal
clearances required for vehicle manoeuvring. Vehicle
reversing should be avoided if possible. When compactors
are deployed in basements, a minimum local clearance of
typically 5.5 m is required as shown in example 3.3c.
Additional footprint
allowance for storing bins
Additional movement
allowance for
transporting bins
Local height clearance
of typically 5.5m
Storage room located near
loading bays/docks
Double set of doors.
Minimum width of 1.8m
Collection route from
building to waste room
and loading bays/docks
Example 3.3a
Example 3.3b
Example 3.3c
Related Credits
SM-R3: Basic Operational Waste Management
29
3.4 External building materials
As the building and plot areas take shape, it is important
that the appropriate materials are selected for external
structures and facade. There are several requirements to
consider when specifying these materials.
U- values
The materials that comprise the structure and facade of the
building will form its thermal envelope the main barrier
to external heat and solar energy. Keeping the occupied
space cool and comfortable is an easier task with a high
performance envelope.
The U-value is a measure of how much heat passes through
a given material (i.e. how much insulation the material
provides). The project team should specify and build the
building envelope to achieve the lowest possible U values
and in any case achieve the minimum U-value requirements
outlined in RE-R1 which are dened by ASHRAE Standard
90.1-2007, Section 5. For the UAE the relevant climate
zone is zone 1.
The following practices can be used to achieve the required
values:
Provide insulation between the earth and concrete foor
slab to reduce heat from the ground warming the rooms.
Insulate above the roof slab and apply an external fnish in
a light color to reect solar heat.
Include suffcient insulation in the building walls.
In addition to the basic U-value heat transfer reduction the
following factors can also benet the energy and internal
environment:
Thermal mass
Place concrete elements adjacent to the occupied spaces, to
buffer thermal energy and provide a cool surface feel for the
occupant.
Vapor barrier
Provide a barrier to restrict ingress of moisture through the
building walls, oor and roof. This is a critical protective
consideration given the high humidity in the coastal area of
the UAE.
Exterior Surface nishes
Use light colors to reect sunlight and reduce absorption of
solar energy. This will reduce heat build up and gain through
the walls and roof.
Glazing design
Glazing design is important for overall building energy usage,
because windows bring light and heat into occupied spaces.
Credit RE-R1 details the requirements for both windows
insulation, e.g. U values, and radiative heat gain, e.g. solar
heat gain coeffcient (SHGC). The U value requirements will
generally require double glazing coatings while the SHGC
requirements can be achieved with tinted glass or reective
factory applied coatings.
These factors can be specied to the glazing manufacturers;
a wide range of suitable, compliant products are available
within the UAE.
O
u
t
d
o
o
r
Related Credits: RE-R1: Minimum Energy Performance
SM-R1: Hazardous Materials Elimination
30
3.5 Smoke free zones & dedicated external smoking areas
There are several requirements that need to be fullled to
comply with LBi-R2 Smoking Control which include:
Establish smoke free zones around sensitive areas of the
building;
Provide dedicated external smoking areas with
associated facilities; and
Train security staff to enforce smoking policy.
Smoke Free Zones
The design team must rst identify the locations of
entrances, openable windows and air intakes of the project
building, but also of any adjacent existing building that
may be similarly affected. Each of these areas will require
protection by establishing smoke free zones within which
people must not be allowed to smoke at any time.
Care should be taken to accommodate the horizontal
width of each item, for example an air intake, as this can
be substantial and will determine the extent of the smoke
free zone. Example 3.6 is an example of how project teams
should establish the extent of smoke free zones by plotting
loci (shown in red) to the extent required by the Pearl
Building Rating System. These plans or gures can be used
to communicate the extent of the smoke free zone when
training security staff.
Dedicated External Smoking Areas
After plotting the smoke free zones, the design team can
look to establish suitable locations for dedicated external
smoking areas. Care must be taken not to encroach upon
the air intakes, entrances or openings associated with any
adjacent building. Where space is constrained, typically in a
dense urban setting, sharing smoking zones with adjacent
buildings can be considered.
All dedicated external smoking areas must have appropriate
and suitable facilities for collecting ash and cigarette ends.
Consider the nature of the location when deciding upon
whether to install free standing or secure wall mounted
devices to meet this requirement. For example, locations
at grade near to unrestricted high pedestrian trafc public
right of ways should consider wall mounted devices
whereas campus type facilities with restricted public access
can install free standing devices. In any event the external
smoking area must not be located directly within public or
high use pedestrian thoroughfares.
Posters (for example wall, board or bench mounted) or other
suitable media, such as through leaet stands must also be
provided listing the negative health impacts of smoking and
provide details on where to seek assistance for those aiming
to stop smoking.
Residential
People who own or rent apartments within a residential
building can smoke within their apartments, therefore
dedicated external smoking areas may not always be
needed. Where such facilities are to be included, design
teams must follow the guidance detailed above.
Example 3.5: Smoke free and smoking
zones
BUILDING
Main Entrance
Rear Entrance
Openable
Window
Openable
Window
Air Intake
Smoking
Zone
Related Credits:
LBo-R3: Outdoor Thermal Comfort Strategy
31
It is also important to ensure that selected materials do not
contain hazardous components excluded by credit SM-R1.
The design team should be aware of these requirements
while designing exterior spaces.
The prohibition of hazardous materials should also be
written into the project specication documents during
the design stage and followed by the contractor during the
construction stage.
Specify that materials, including walls, insulation, and
interior materials, will not contain asbestos and that all
asbestos containing materials have been removed from
refurbished buildings.
Specify that wood materials exposed to the outside
and within human reach such as shading structures,
playgrounds, and decking will not be treated with
chromated copper arsenate (CCA).
1
2
Example 3.6a: Extract from
specications
In compliance with the Pearl Building Rating
System for Estidama, credit SM-R1 Hazardous
Materials Elimination, the following materials shall
not be used:
1. Asbestos Containing Materials (ACM)
2. Chromated copper arsenate (CCA)-treated
timber, where timber is used for external
structures subject to frequent and intimate
contact. These materials include, but are
not limited to, shading devices, playground
equipment and handrails
3.6 Hazardous materials
O
u
t
d
o
o
r
Related Credits: SM-R1: Hazardous Materials Elimination
32
No Asbestos Containing Material (ACM) is used
and no Chromated Copper Arsenate (CCA)
treated timber is used on external structures
Reective (SRI>29) overhangs to provide
additional shading to walkways
Shaded entrance not aligned with prevailing
hot winds for pedestrian comfort
Use of external building materials that
achieve required U-values provide thermal
mass, provide vapour barrier, and have light
colour nishes
Glazing that maximises daylight whilst
minimizing heat gains
Dedicated external smoking area away from
air intakes and openings
Vehicular access on secondary road
Waste storage at ground level provides
enough space for vehicle manoeuvering
Example 3.6b: Summary of outdoor strategies
33
S
u
b
m
i
s
s
i
o
n
There are many factors to consider when planning the
layout of spaces inside a building. These factors relate to:
energy consumption
visual and thermal comfort
ventilation
daylight
materials emissions
Some factors may conict with others, for example, a space
designed for excellent day lighting may be detrimental to
energy consumption as a result of poor facade decisions.
Occupant comfort is an important consideration, this
includes understanding visual and thermal comfort and as
well as ensuring sufcient fresh air provision. The project
team should also look to reduce the source of material
emissions through low VOC products.
It is important, therefore, to develop a project with the right
blend of carefully considered solutions.
Approach
The layout and position of internal spaces within the
building to suit daylight and ventilation have to be
considered at this stage as per credit RE-R1. It is also
necessary to specify glazing correctly to ensure optimal
trade-off between light ingress and solar transmission.
This design should be done bearing in mind credit LBi-R1,
which requires that all spaces must be ventilated according
to the requirements of the ASHRAE 62.1 2007, or local
code, whichever is more stringent. The consideration of
ventilation strategy is an important factor for both RE-R1
and LBi-R1 credits as they are both affected by natural and
mechanical ventilation system performance.
As in previous steps, materials forbidden by credit SM-R1
(asbestos and chromated copper arsenate treated wood)
should not be specied for indoor spaces. All decisions
affecting the design of the building indoor spaces must be
part of the Integrated Development Strategy.
useful resources:
ASHRAE Standard 55-2004. Thermal environmental conditions for
human occupancy
International Mechanical Code 2009, International Code Council
(http://publicecodes.citation.com/icod/imc/2009/index.htm)
ANSI/ASHRAE Standard 62.1-2007, Ventilation for Acceptable
Indoor Air Quality
Centre of Waste Management, Abu Dhabi. (www.cwm.ae)
Cabinet Resolution No. 39 of 2006 Concerning Prohibiting Import,
Production and Utilization of Asbestos Boards
Related Credits:
SM-R1: Hazardous Materials Elimination
SM-R3: Basic Operational Waste Management
LBi-R1: Healthy Ventilation Delivery
LBi-R2: Smoking Control
RE-R1: Minimum Energy Performance
4.0 Design indoor spaces
Credit LBi-R2 requires residential units or apartments to be
appropriately sealed to eliminate or minimize exposure of
building occupants to the harmful effects of tobacco smoke
from neighbouring apartments. This should be done with
adequate seals and weather-stripping.
I
n
d
o
o
r
34
An observational survey of the building site and its
immediate surroundings shall be conducted to determine
site air quality conditions and local contaminants from
the surrounding environment. The outdoor air quality
investigation shall be documented and reviewed with
building owners or their representative.
All exhausts shall discharge outside the dened public
realm or as dened by local code, whichever is more
stringent in order to maintain air quality. Discharging above
a public realm space can be achieved if vertical separation
is provided, which typically would be a minimum of one
storey above the public realm space.
Minimum fresh air rates to ensure good air quality (for
breathing and removing air contaminants) shall comply
with the minimum thresholds set out in ASHRAE 62.1:2007
using the ventilation rate procedure or local code, whichever
is more stringent.
The shortest distances between outdoor air intakes
(including doors and windows required as part of a
natural ventilation system) and any exhausts or discharge
points should comply with ASHRAE 62.1.2007 or local
code whichever is more stringent. This will avoid cross
contamination and provide good air quality.
Refer to example 4.1 Ventilation Strategy for a graphical
representation of a typical building with associated
minimum air intake seperation distances.
4.1 Ventilation strategy
Example 4.1
min. 5m
min. 5m
min. 7.5m
min. 5m
min. 5m
min. 7.5m
min. 5m
Vent chimneys from combustion
appliances and equipment Cooling tower exhaust
Cooling tower intake
Garage entry
Automobile loading area
Garbage storage +
pick-up area
Thorough fare with high
trafc volume
Public realm
Car park exhaust
Related Credits: RE-R1: Minimum Energy Performance
LBi-R1: Healthy Ventilation Delivery
35
4.2 Smoking Control
Smoking within a building is only permitted
for occupants within residential units, or
apartments. No smoking is permitted within any
and all common areas of the building including car
parks.
To comply with the requirements, each residential unit
must be sealed with impermeable deck to deck partitions
along the whole perimeter of the unit (walls) and vertically
between units (ceilings and oors). All penetrations within
these walls, including those for wiring, pipework, ductwork,
switches, electrical outlets, recessed xtures and risers
must be fully and appropriately sealed. Examples of sealing
processes include caulking or spray foam application. Whilst
the designer should identify suitable materials for sealing
gaps, contractors must ensure that the sealing of gaps is
carried out adequately.
All doors leading from a residential unit to a common area,
such as a corridor, or between residential units must be
weather-stripped. To achieve effective weather-stripping,
the architect must design and the contractor must ensure
that gaps around doors are not so large that weather
stripping cannot provide an adequate seal.
Related Credits: LBi-R2: Smoking Control
I
n
d
o
o
r
36
4.3 Internal waste and recycling storage
Waste and recyclables generated by activities undertaken
in a building is known as operational waste. The amount of
this material generated depends on the building use, (e.g.
ofce, residential) and should be managed prociently. This
can be achieved by following the Reduce, Reuse, Recycle
principle to minimise economic costs and environmental
impacts.
A building-level management strategy for waste and
recyclables should be created by the design team and
implemented by the facilities management team to achieve
the minimum requirements of the Pearl Building Rating
System. The strategy must:
Estimate the quantities anticipated using the building
waste calculator tool available from the Estidama web
site.
Review the existing and planned materials collection
and treatment infrastructure for the building location by
contacting, the Centre of Waste Management (www.
cwm.ae)
Document the intended waste collection company or
companies and the recycling or disposal facilities
Provide enough space to segregate waste into:
Green container for recyclable plastics, glass and
metals;
Blue container for recyclable paper and cardboard;
Black container for non recyclable and non
compostable waste; and
An optional container may be provided for
compostable organic waste (if there is suitable
treatment available)
Where the above recycling measures meet the
mandatory requirements for landll and incineration
diversion, the remainder residual waste can be
allocated to landll and incineration.
Describe the logistics of materials movement within
the building to ensure the residents maximum carrying
distance is less than 30 m and is optimised for every
building user.
Describe how waste and recyclables will be collected
by external collection vehicles for transportation to
adequate treatment or disposal facilities.
Waste and recyclables generated in the building should be
stored on each building oor before being taken to a central
storage facility for the whole building. From there it will
be collected for transport to the appropriate treatment or
disposal facility.
The oor transfer rooms should be clearly indicated, well
ventilated, easy to clean and located near service lifts
or waste chutes, in common areas of the buildings but
separated from them. Each room should be sized according
to:
Expected generation on each oor. This can be worked
out by apportioning the total building waste and
recyclables generation to each oor area.
Container type. Typically these have capacities of 120
to 240 litres;
Collection frequency to the central storage room. This
will be dened by the buildings facilities manager and
it is typically daily or even more often.
1
2
3
4
Example 4.3: Depictions of storage room
connection
Waste and recyclables storage area (internal connection)
Waste and recyclables storage area (externalconnection)
5
6
1
2
3
Related Credits
SM-R3: Basic Operational Waste Management
37
The lighting, shading and ventilation strategies established early in the design process will reduce
the requirements for building systems. Careful detailing of systems to provide cool, comfortable and
efcient performing indoor spaces can further reduce the buildings environmental impact.
5.0 Design building systems
Approach
For credit LBi-R1, the building must comply with ventilation
requirements set out in ASHRAE Standard 62.1-2007, or
local code, whichever is more stringent.
Energy
The design of the building HVAC and lighting systems is
driven by the requirements outlined in ASHRAE Standard
90.1- 2007. Compliance with RE-R1 is achieved by a 12%
improvement in Proposed Design Energy Performance when
compared with the Baseline Design Energy Performance.
This improvement is demonstrated through dynamic
simulation modelling to simulate energy performance
as outlined by the Performance Rating Methodology in
Appendix G of ASHRAE 90.1-2007.
Credit RE-R2 requires energy submetering, whereby
installed meters are to be clearly labeled and provided
in easily accessible locations. They must measure,
as a minimum, 90% of the estimated annual energy
consumptions of each fuel type (electricity, gas, etc)
for all energy end use categories, in both Landlord and
Tenant areas. Metering is also required for all onsite energy
generating systems and large plant items.
Water
Efcient water xtures and metering are covered by credits
PW-R1 and PW-R2. Estidama requires specic ows rates
for water xtures, ttings, and appliances. As with energy
meters, water meters must be easily accessible and clearly
labeled, to sub-meter the buildings external water use.
These must have a pulsed output and be capable of remote
monitoring.
Related Credits
LBi-R1: Healthy Ventilation Delivery
LBi-R3: Legionella Prevention
PW-R1: Minimum Interior Water Use Reduction
PW-R2: Water Monitoring
RE-R1: Minimum Energy Performance
RE-R2: Energy Monitoring & Reporting
RE-R3: Ozone Impacts of Refrigerants & Fire Suppression Systems
SM-R3: Basic operational waste management strategy
Materials and Waste
SM-R3 requires waste generated in the building to be
stored on each building oor before being taken to a central
waste storage for the whole building from where it will be
collected to the appropriate treatment or disposal facility.
Credit IDP-R1 requires decisions regarding the design of
MEP and waste to be agreed on in integrated development
workshops.
Credit RE-R3 species that only refrigerants and re
suppression systems with an ozone depletion potential
(ODP) of zero can be used for any purpose onsite.
useful resources
ASHRAE Handbook of Fundamentals 2009.
ASHRAE Standard 62.1-2007 Ventilation for Acceptable Indoor Air
Quality/ASHRAE/IESNA 90.1 2007: Energy Standard for Buildings
Except Low- Rise Residential Buildings.
UNIFORM PLUMBING CODE of Abu Dhabi Emirate 2009,
Environment Agency Abu Dhabi.
S
y
s
t
e
m
s
38
Air conditioning and mechanical ventilation
Although the cooling requirements of a building will be
reduced by minimizing heat gain through windows and
other external surfaces, energy must also be used to
condition spaces in Abu Dhabis climate. Efcient system
performance is therefore a critical factor in achieving
reductions in energy usage.
For most buildings the performance of the air-conditioning
system is based upon:
The efciency of energy conversion from electricity
to cooling, typically provided by localized units, central
chillers or district cooling
The effectiveness of the fans providing air to the
spaces, both fresh and recirculated air
The selection of appropriate sensors and controls for
various system elements in different zones
The response of the system to variation in thermal
loads and occupant requirements
The inclusion of energy recovery, performance
modulation and other efciency measures.
There are requirements for all aspects of system
performance outlined by ASHRAE Standard 90.1-2007.
However in order to achieve the target performance
required by credit RE-R1 it will be necessary to demonstrate
improvement beyond the levels dened in Standard 90.1-
2007.
Lighting
Good lighting design can reduce energy usage internally and
externally. Internal lighting energy is restricted on a basis of
power used per unit area. Power allowance is based on the
building type or the space type classication as outlined in
Standard 90.1-2007. Example performance for the building
type classication is shown in table 5.1.
5.1 Energy system
Renewables
The use of onsite renewable energy sources to contribute
towards the building load is encouraged. Renewable
technologies should be designed to integrate with proposed
building design, HVAC systems and lighting.
In addition to reducing the energy consumed by lighting
systems, good use of controls and sensors can increase
energy savings and reduce the cooling load required.
Examples of lighting controls include:
Occupancy sensors
Daylight sensors
Dimmable controls
Programmable time controls
External lighting is also restricted on the basis of power
use, either per unit area or per linear meter as dened by
Standard 90.1-2007 for various functions. Furthermore
external lighting should be controlled to ensure that it is not
operational during daylight hours, which will reduce energy
wastage.
Table 5.1
Related Credits: RE-R1: Minimum Energy Performance
LBi-R1: Healthy Ventilation Delivery
39
Metering facilities should be provide to allow the energy
performance of the building to be recorded. This monitoring
will provide an understanding of the use in energy
within the building as well as providing scope for future
improvements. RE-R2: Energy Monitoring & Reporting has
the following requirements:
All meters provided are to be clearly labeled and easily
accessible
90% of estimated annual energy consumption of
each fuel type to be monitored. For ofce, retail and
multi-residential buildings, the equipment and systems
described in Table 5.2a should be submetered
Separate meters to be provided for plant exceeding the
loads shown in Table 5.2b
Written commitment from building owner to supply all
energy monitoring data if requested by Estidama
Capability to provide hourly, daily, weekly, monthly
and annual energy consumption for each end-use and
compare consumption for the different time frames
Landlord and Tenant areas to be separately metered as well
as any on site energy generating systems. All metering
requirements are to be documented within the tenant
guidelines as part of IDP-R2 Tenant Fit-Out Design &
Construction Guide.
For Tenant spaces, the following metering categories are to
be followed:
Non-Residential: tenant area metering requirements for
ofce;
Residential (spaces used primarily for living and/or
sleeping): tenant area metering requirements for multi-
residential.
Schools are assumed to be solely landlord controlled and
therefore there are no additional requirements for tenant
areas.
5.2 Energy metering
1
2
3
4
5
Guidance
GIL 65: Metering Energy Use in New Non-Domestic Buildings
CIBSE TM39 2009: Building Energy Metering
Table 5.1 Table 5.2a
Table 5.2b
S
y
s
t
e
m
s
Related Credits: RE-R2: Energy Monitoring & Reporting
40
Refrigerant
Many of the refrigerants currently used in air conditioning
systems cause damage to the ozone layer. The ozone layer
protects the earths surface from damaging radiation. This
environmental impact can be reduced by the appropriate
selection of refrigerants and re suppression systems with
a zero ozone depletion potential (ODP).
RE-R3 requires that refrigerants and gaseous re
suppression systems installed within the plot have a zero
ozone depletion potential.
This would require avoiding refrigerants such as HCFC-22,
which even though will not be banned until 2015 within the
UAE, it is required that it is not used due to it still having an
ODP. Refrigerants with an ODP of zero are required such as
HFC-134a.
5.3 Refrigerant
Table 5.3
Related Credits: RE-R3: Ozone Impacts of Refrigerants & Fire
41
Optimize interior water consumption
Interior water consumption within a building is attributed
to xtures and appliances such as taps, toilets, washing
machines etc. Large water savings can be made by using
low ow xtures and high efciency appliances.
PW-R1 sets a minimum standard for xture ow rates and
appliance efciencies. These ow rates are as follows:
To comply with PW-R1, a project must demonstrate that
the proposed buildings interior potable water consumption
is less than or equal to the baseline building interior potable
water consumption based on the ow rates detailed within
the adjacent table. This must be demonstrated by utilizing
the PBRS Water Calculator v1.1 available from www.
estidama.org.
The calculator allows the project to trade between ow
rates so that the efciency of certain xtures/appliances
may be relaxed only if others are improved. This ensures
that the overall proposed building interior potable water
consumption is less than or equal to the baseline.
The next few pages contain snapshots of the PBRS Water
Calculator v1.1. This will help the design team select
appropriate xtures and demonstrate compliance with the
Estidama requirements.
5.4 Water xtures
Fixture/Appliance Unit Rate
Kitchen Taps liters/minute 6.0
Bathroom Washbasin
Taps
liters/minute 6.0
Toilets Dual Flush liters/ush 6.0/4.0
Bidets liters/minute 6.0
Shower Head liters/minute 9.5
Ablution Fixtures liters/minute 6.0
Dishwashers liters/place setting 1.3
Washing Machines liters/kg of dry
load
8.5
Table 5.4
S
y
s
t
e
m
s
Related Credits: PW-R1: Minimum Interior Water Use Reduction
42
Example 5.4: Building water calculator output
Fill in detailed information on the water xture uses in
the building and compare them with the baseline
Fill in detailed
information on the
different building
uses such as ofce,
residential, etc.
Step 5 is the same as step 4 but with non-residential and
residential building types not included by default in the calculator
Fill in internal water usage.
Fill in external water usage
43
Summary of the different elements of the water balance
Fill in detailed information on the building plot irrigation,
water features, etc. and compare them with the baseline
Fill in detailed information on heat rejection equipment
Fill in information on the summed total of all
external water features and swimming pools
S
y
s
t
e
m
s
44
Summary of compliance with required credits
and number of points awarded in optional credits
Graphical summary of water demand
for different building uses
Summary of water demand for different building uses
Numerical summary of water demand
for different building uses
Graphical summary of water balance. Ideally building
waste water should balance with exterior demands.
45
Water metering
PW-R2 requires easily accessible and clearly labelled water
meters to be provided and capable of monitoring all exterior
water consumption. The following must be seperately sub-
metered where present:
Irrigation Systems
Heat Rejection
Swimming Pools
Water Features
The meters are also required to have data logging capability
and be connected to a central monitoring system so that
the exterior water consumption may be recorded. This, and
a better understanding of both interior and exterior water
use will help determine areas of high water consumption,
identify leaks quickly, and pursue opportunities to save
water.
Example 5.5: Diagram of water monitoring
5.5 Water metering
S
y
s
t
e
m
s
Related Credits: PW-R2: Water Monitoring
46
5.6 Legionella
Legionnaires disease is a potentially fatal form of
pneumonia which principally affects those who are
susceptible due to age, illness, immunosuppression,
smoking etc.
HSE Approved Code of Practice (ACoP) L8: Legionnaires
Disease The Control of Legionella Bacteria in Water
Systems applies to plant and water systems which may
present a particular risk potential by releasing a spray or
aerosol during operation or when being maintained.
Relevant water based systems include but are not limited
to:
Water systems incorporating a cooling tower or an
evaporative condenser.
Hot and cold water systems.
Other plant and systems containing water which is likely
to exceed 20C and which may release a spray or aerosol
during operation OR during maintenance.
Humidifers.
Air washers.
Spa baths and Pools.
Car / bus washes.
Wet scrubbers.
Fountains and Water features (Indoor and Outdoor).
Sprinkler and hose reel systems.
Roles and responsibilities
The design engineers should support the Client in
developing guidance including design and operational intent.
HSE ACoP L8 requires the owner to appoint an operations
manager who should ensure that all responsibilities are
clearly dened and formally allocated. The owner is also
responsible to ensure that control procedures are carried
out to the standard required to prevent the growth of
legionella bacteria.
Related Credits: LBi-R3: Legionella Prevention
47
Legionella Management Plan
At all stages adequate measures should be implemented
to minimise the risk of contamination. A Legionella
Management Plan must be developed at the outset of the
project and should address the following:
1. Identify and assess the risk in the design and operation of
the building to assess the level of risk associated with water
systems. If the risks are insignicant, no further action
needs be taken, other than periodical reassessment in case
anything changes in the system.
2. Manage the risk: management responsibilities, training
and competence. If a risk is identied, proper controls
must be introduced and documented within the Legionella
Management Plan. Risks can be controlled by careful
planning, management policy, competent staff and
adherence to proper control strategies.
3. Prevent or control the risk from exposure to legionella
bacteria. Consideration should be given to:
Ensure that the release of water spray is properly
controlled.
Keep the system and the water in it clean.
Avoid conditions that favour the growth of
legionella and other micro-organisms, water
stagnation and materials encouraging growth.
Treat water to either kill legionella (and other
micro-organisms), limit their ability to grow or
biocidal treatment if applicable
Continually monitor all water where sources of
legionella could occur.
Easy access for inspection, draining, dismantling
and cleaning to all systems.
4. Record keeping of maintenance and documentation.
Records need to be kept of the scheme and who is
responsible for managing that scheme, these should also be
kept with the results of the routine monitoring.
5.Ensure that information from manufacturers, importers,
suppliers and installers provide guidance and include risks to
users.
S
y
s
t
e
m
s
48
49
S
u
b
m
i
s
s
i
o
n
Estidama design submission at building permit application
IDP-R1: Integrated Development Strategy
Team structure listing team members and their roles
Narrative summarizing initial vision, objectives and targets set jointly by the project team
Process chart for the IDP developed at project inception, listing design milestones and planned workshops
Methodology for ensuring appropriate stakeholders are involved, including construction team, commissioning agent, potential tenants, building operators and relevant
regulatory authorities and permit agencies
Meeting minutes, action items and team member responsibilities from key workshops held as part of the IDP
Implementation strategy for achieving transition between project stages and project packages
IDP-R3: Basic Commissioning
CV of Commissioning Agent
Contract with the Commissioning Agent
Commissioning Plan clearly indicating commissioning requirements for the project, including: Owners Project Requirements and Basis of Design narrative
NS-R1 Natural Systems Assessment
Natural Systems Assessment Report including: Narrative, Maps, Site photographs that must clearly identify the extent of different habitats and/or other signicant natural
system features
Review of the site against Environmental Policy Statements included in Plan 2030
CV of appointed suitably qualied environmental professional
S
u
b
m
i
s
s
i
o
n
50
NS-R2 Natural Systems Protection
Supporting calculations, summarizing total site area, protection area and/or mitigation area/compensation area in hectares
Construction strategy to protect sensitive habitats and protected species from construction impacts
Details of the appointed suitably qualied ecological consultants professional status, if different to the consultant details provided in NS-R1
Strategy 1: Protection Strategy Report which identies the potential risks to the Natural Systems assets from development and inform setback requirements, including:
Narrative and maps which detail the boundaries of the assets
Extent of habitats and species to be protected
Limits of development, buffer areas and setbacks (Works areas must be clearly identied on an aerial photograph of existing conditions)
Any features of ecological value to be lost
Strategy 2: Mitigation Strategy Report which details the reasons for requiring mitigation for loss of habitat and includes:
Narrative and maps of the area of natural system assets to remain protected
The area and value of habitat to be lost to development
The area allocated for re-establishment
Limits of development, buffer areas and setbacks (Works areas must be clearly identied on an aerial photograph of existing conditions)
A strategy for habitat re-establishment, including source of plant stock and establishment of soil base
Five year strategy for on-going management and monitoring following completion of construction, including conrmation of management organization
Strategy 3: Compensation Strategy Report which details the reasons for requiring compensation for loss of habitat and includes:
Narrative and maps of the area of natural system asset to remain protected;
The area and value of habitat to be lost to development;
Limits of development, buffer areas and setbacks (Works areas must be clearly identied on an aerial photograph of existing conditions);
Details on the compensation area allocated for re-establishment, including site location and conrmation of approval to establish habitat;
Estidama design submission at building permit application
51
Strategy for habitat re-establishment, including source of plant stock and establishment of soil base; and
Five year strategy for on-going management and monitoring following completion of construction, including conrmation of management organization.
NS-R3 Natural Systems Design and Management Strategy
Natural Systems Design and Management Strategy that includes:
Plans and drawings illustrating layout and design of landscaped and habitat areas
Details of soft and hard landscaped areas
Details and justication of plant selection (ensuring that only native and adaptive drought and saline tolerant species are specied for habitat areas)
Details of soil strategy for testing, protection, enhancement and maintenance
Irrigation strategy
Details of landscape maintenance procedures including fertilizer, herbicide and pesticide application
Details of specic establishment, maintenance and protection requirements for sensitive areas
Details of monitoring requirements
Details of the appointed suitably qualied environmental consultants professional status, if different to the consultant details provided in NS-R1
LBo-R1 Plan 2030
A letter from the UPC conrming that the proposed development is:
Located within an established Urban Growth Boundary
Did not require signicant variance or special relief from Plan 2030, Development Code and/or Area Plan for approval
LBo-R2 Urban Systems Assessment
CV of the appointed suitably qualied professional
S
u
b
m
i
s
s
i
o
n
Estidama design submission at building permit application
S
u
b
m
i
s
s
i
o
n
52
Urban Systems Assessment report including:
Urban System Assessment report including narrative, maps and site photographs that must clearly identify the existing site conditions
LBo-R3 Outdoor Thermal Comfort Strategy
Plan and tabulated results showing achievement of % of shading of applicable spaces at 1:00pm clock time on the Equinox and Summer Solstice
Extracts from specications relating to the SRI of all cover elements
Outdoor Thermal Comfort Strategy report highlighting all measures contributing to improving the buildings exterior microclimate including:
Narrative and drawings of the public realm spaces and priority shade areas
LBi-R1 Healthy Ventilation Delivery
Documentation of an observational study of local air quality including photographs of surrounding sources of pollutant emissions
Mechanical system drawings marked-up to clearly show distances between air intake points and exhaust air or other discharge points and the distances from the air
exhaust points to any dened public realm areas
Narrative describing how the mechanical design system meets the Credit Requirements, including description of mechanical ventilation system
Spreadsheet calculations of fresh air ventilation rates based on the ventilation rate procedure for all zones
LBi-R2 Smoking Control
Written commitment from the building owner/developer that there will be a no smoking policy operated within the building (or common areas for residential buildings or
additionally for school grounds) by inclusion in Contracts of Sale and Lease/Rent Agreements that smoking will be banned by future owners and tenants
Extracts from specications and/or drawings indicating the locations of posted signage stating that the entire building is a no smoking environment and detailing the
negative health impacts of smoking installed in all dedicated external smoking areas
Drawings indicating the location of dedicated outside smoking areas and facilities for collecting ash and cigarette ends which clearly indicate their distance from
entrances, operable windows and air intakes
For residential units, provide specications for weather-stripping of doors and drawings that highlight impermeable deck to deck partitioning
Estidama design submission at building permit application
53
LBi-R3 Legionella Prevention
Narrative and drawings of the air conditioning systems regardless of whether water-based cooling towers are present or not. The Narrative must explain the approach to
Legionella Management, or conrm no water-based systems are present
Narrative and drawings of the projects other water-based systems
Legionella Management Plan for the treatment of Legionella in the projects water-based systems
PW-R1 Minimum Interior Water Use Reduction
Building Water Calculator conrming that the buildings predicted interior potable water consumption will be no greater than the baseline building interior potable water
consumption using efciency measures only
Brief narrative describing all proposed water conservation strategies
Extracts from specications for all proposed xtures and ttings indicating ow rates and ow regulation systems
PW-R2 Exterior Water Monitoring
Brief narrative describing how the requirements of the credit will be achieved
Extracts from specications and MEP drawings clearly indicating the type, extent and locations of all metering, and central monitoring system
List of all exterior uses and corresponding metering equipment
RE-R1 Minimum Energy Performance
Energy Model Template summarizing the dynamic energy simulation, conrming that the minimum requirements of this credit will be achieved
RE-R2 Energy Monitoring
Brief narrative describing how the requirements of the credit will be achieved
Energy system schematics illustrating the proposed metering strategy conrming that the required level of metering will be achieved
Extracts from specications and MEP layout design drawings clearly indicating the type, extent and locations of all metering, and the central monitoring system
Estidama design submission at building permit application
S
u
b
m
i
s
s
i
o
n
54
RE-R3 Ozone Impacts of Refrigerants & Fire Suppression Systems:
Brief narrative describing how the project meets the credit requirements
Specication extracts for all proposed refrigerants and gaseous re suppression systems conrming ODP of each refrigerant and gas is zero
SM-R1 Hazardous Materials Elimination
Extracts from specications indicating that no ACMs or CCA-treated timber are to be used in the project as per the Credit Requirements
Where portions of the project are reused from an existing building:
Results of a hazardous materials survey documenting the existence, if any, of ACMs in the building. It is recommended to follow internationally recognized standards
such as ASTM E 256-04 Comprehensive Building Asbestos Surveys or similar standards
Where ACMs were found, Asbestos removal and disposal plan
SM-R2 Basic Construction Waste Management
CDWMP conforming to the Credit Requirements
Schedule of items to be recycled/salvaged
SM-R3 Basic Operational Waste Management
Operational Waste Strategy that includes:
A narrative summarizing options researched and selected to meet the diversion targets. The strategy must address waste minimization, storage, collection, and
treatment and links to private or municipal and regional infrastructure and programs
Calculations documenting projected waste quantities for the development during operation on an annual basis. Waste benchmarks may be obtained from the Centre
of Waste Management, waste audits of similar buildings or literature research. References must be clearly listed
Drawing(s) indicating location of the storage/disposal facilities and vehicle access areas designed to ensure adequate space for maneuvering delivery and waste
removal vehicles
Waste transfer inventory outlining the intended receiver of waste. This should include information indicating that the carrier, recycling and disposal facilities are
licensed
Estidama design submission at building permit application
55
useful resources:
Environment Agency of Abu Dhabi: Technical Guidance Document:
Development of Construction Environmental Management Plan
(CEMP) Onshore.
ISO 14000: 2004 Family of Standards on Environmental
management systems.
Cibse TM 31. Building log building toolkit.
Once all the design has been completed, the process of
constructing the building will start. This step covers the
construction process from the potential demolition of
existing structures to the completion of a new building.
During this process, it will be necessary to maintain
communication between the members of the design team,
contractors, and developers, to ensure that the building
is built to the correct design specications. This will be
facilitated by the IDP process and the implementation
strategy agreed at the beginning of the design process.
Approach
Estidama credit SM-R2 requires that 30% of the demolition
and construction waste be salvaged or recycled by weight.
This means the contractor needs to prepare a construction
and demolition waste management plan before demolition
begins. This plan is to be supported by the Building Waste
Calculator that is available from the Estidama website.
During construction, documents will need to be collected
by a designated responsible person from the contractor
who will work with the PQP to conrm the target has been
achieved.
Similarly, compliance with credit RE-R1 requires that
good quality materials performing according to design
specications are used and that good construction practices
are followed to ensure the fabric and system performance
levels modeled are actually achieved.
Credit SM-R1 requires guaranteeing that hazardous
materials do not make their way into the project. There can
be no asbestos or exposed wood treated with chromated
copper arsentate.
6.0 Build building
Related Credits: SM-R2: Basic Construction Waste Management
RE-R1: Minimum Energy Performance
B
u
i
l
d
56
Before starting any demolition or construction, it is
necessary to develop a construction and demolition (C&D)
waste management plan. This should incorporate:
Estimates of waste generation. The Building Waste
Calculator will help to estimate the type and amount
of waste expected for the project. This can be
downloaded from the Estidama website.
A destination for each waste type leaving the site. For
example, specify that aggregates will be transported
to the municipal C&D recycling facility, or that t-out
leftovers will be disposed to landll.
Identication of materials to be salvaged or recycled.
At least 30% of the estimated waste generation by
weight has to be salvaged or recycled.
A location for storing waste on-site during
construction. This should be conveniently located near
the area where construction materials are delivered
and has to be large enough to allow for separating at
least aggregates and other waste streams.
An example of the above is shown here. These elements
should be updated with information compiled during
construction.
On-site waste segregation area
Example 6.1a Schedule of items reclaimed/recycled
6.1 Construction waste management
1
2
3
4
Total waste generated: 585 tonnes
Total waste landfilled: 211 tonnes (36.1%)
Total waste diverted: 374 tonnes (63.9%)
LANDFILLED C&D WASTE CALCULATION IN TONNES
Landfill material description Landfill hauler or location Quantity of landfilled waste
General waste March 2010 Al Dhafra Landfill 15
General waste April 2010 Al Dhafra Landfill 31
General waste May 2010 Al Dhafra Landfill 70
General waste June 2010 Al Dhafra Landfill 65
Pallets April 2010 Al Dhafra Landfill 10
Pallets May 2010 Al Dhafra Landfill 5
Pallets June 2010 Al Dhafra Landfill 15
DIVERTED C&D WASTE CALCULATION IN TONNES
Diverted/recycled material description Diversion/recycling hauler or location
Quantity of diverted /
recycled waste
Concrete from demolition March 2010 Municipal C&D plant 150
Concrete from demolition April 2010 Municipal C&D plant 200
Metal March 2010 Local metal recycler 4
Metal April 2010 Local metal recycler 3
Metal May 2010 Local metal recycler 1
Metal June 2010 Local metal recycler 1
Construction and Demolition Waste:
585 tonnes
36.1%
63.9%
Landfilled
Salvaged/
Recycled
SALVAGED C&D WASTE CALCULATION IN TONNES
Diverted/recycled material description Diversion/recycling hauler or location
Quantity of diverted /
recycled waste
Spandrel panels from faade June 2010 Reused in new building 15
Related Credits: SM-R2: Basic Construction Waste Management
57
Enter details of
existing building
(if applicable)
Enter details of proposed
building. Use the Mixed
use option for buildings
with more than one use
Enter waste generation
details for the building
use. Default values can be
overridden if required
Enter construction and demolition
waste management procedures.
Default capture rates can
be overridden if required
Example 6.1b: Building waste calculator
Enter operational waste
management procedures
In step 1 enter project details and then follow these
instructions.
B
u
i
l
d
58
Summary of construction
and demolition as well as
operational waste estimates
and diversion from landll
and incineration rates
Summary of compliance with
required credits in the Stewarding
Material Section of the Pearl
Building Rating System
Summary of operational waste
estimates in numerical format
Summary of operational waste
estimates in graphical format
Summary of construction and
demolition waste estimates in
numerical format
Summary of construction and
demolition waste estimates in
graphical format
59
Finishing construction is not quite the last step in an
Estidama project. Key to ensuring sustainability is to
verify the building will perform according to the design
specications. The performance of the structure and
building systems should be evaluated, and occupants should
be informed how to operate and maintain the building for
best results.
Approach
Credit IDP-R3 requires a Competent Professional to verify
the building performs as designed to protect occupant health
and provide comfort and ongoing building efciency. Credit
IDP-R2 requires all the Integrated Development Strategy
created as part of the IDP-R1credit is clearly communicated
using a tenant t-out design and construction guide. This
tenant t out guide provides essential technical information
such as design requirements, materials for the t out
design and construction and submittal for Landlord approval
to ensure that compliance with the requirements will be
checked by the developer. The envelope and systems should
comply with the requirements of credit RE-R1.
Information collected from the energy and water sub-
meters required by credits RE-R2 and PW-R2 credits can be
used to ensure optimum operation.
Although credit IDP-R3 is completed after construction,
it should be started earlier in the design process. Some
systems need to be tested before installation. Note that
the person who conducts the verication can be from a
company involved in the design process, but the individual
who veries cannot be directly involved in the project for
any other purpose.
7.0 Verify performance
Related Credits: IDP-R2: Tenant Fit-Out Design & Construction guide
IDP-R3: Basic commissioning
V
e
r
i
f
y
60
7.1 Commissioning
The Basic Commissioning aims to ensure that the building
performs as designed to protect occupant health , provide
comfort and ongoing building efciency. An independent
commissioning agent, reporting to the project owner, with
at least 2 years commissioning experience, should be
engaged as part of the project design team throughout the
design stages.
The commissioning process must cover, at a minimum, the
following systems:
Heating, ventilation, air conditioning, refrigeration
On-site energy generation (including co-generation)
Building Management System
Lighting and lighting controls
Domestic hot and cold water systems
On-site water treatment systems including swimming
pools (if applicable)
Automated control features such as blinds
Within the building log book the following sections would
be normally expected:
Annual review & updates to the log book
Purpose & responsibilities
Links to other key documents
Main contacts
Commissioning, handover & compliance
Overall building design
Summary of areas / occupancy
Summary of main MEP plant
Overview of controls / BEMs
Builder user information (requirement dependent on
building typology)
Metering, monitoring & targeting strategy
Building performance records
Summary of maintenance requirements
Major alterations
Results of in-use investigations (requirement dependent
on building typology)
Appendices - All relevant certicates / tests
(requirement dependent on building typology).
A commissioning plan should include the following
Commissioning program overview
List of systems and assemblies included in
commissioning process and activities
Commissioning team and responsibilities
Management , communication and reporting of
commissioning process
Overview of commissioning process activities through
the design including:
- Design and construction document review
- Basis of Design review
- Owners project requirements
- Submittals documentation and process
- Functional performance test development and
implementation