You are on page 1of 3

No.

Date
Time
Event(s)
---------------------------------------------------------------------------------------------------1 xx-xxx-xxxx 09:03:00.000 1
(51GW2) Inv. Time Ground Overcurrent Picked Up
(87T) Phase Differential Current - Phase B Operated
(87T) Phase Differential Current - Phase C Operated
INPUTS:
OUTPUTS: 1,4,5,7,8
W1 Currents: 2.10 A (A), 0.79 A (B), 9.20 A (C)
W2 Currents: 2.32 A (A), 3.45 A (B), 2.63 A (C), 22.84 A (N)
W3 Currents: 0.27 A (A), 0.33 A (B), 0.28 A (C), 0.00 A (N)
PARA W1 SE TIENE UNA RTC EN FASE A, B Y C DE 240:1
PARA W2 SE TIENE UNA RTC EN FASE A, B Y C 2400:1 Y EN IN DE 160:1
PARA W3 SE TIENE UNA RTC EN FASE A, B Y C DE 160:1

Pgina 1 de 3

Oscilograma 50FI, con 3296 amp.

Pgina 2 de 3

Pgina 3 de 3