VOLTECH ENGINEERS PVT. LTD.

TEST REPORT FOR VACUUM


CIRCUIT BREAKER
CLIENT : M/S VOLTTECH ENGINEERING WORKES DATE :26.11.2013
PROJECT : JINDAL STEEL AND POWER LTD RAIGARH Sheet No.: 1 of 2

Test Performed by: VEPL Witnessed by: VOLTTECH Witnessed by: JSPL
Name :Mr.T.Balaji Name : Name :
Designation : Senior
commissioning Engineer
Designation : Designation :
Signature &
Date
Signature &
Date
Signature &
Date

1. Equipment Details

Make : ABB
Sl. No. : 1VYN02021300796
Rated Current : 2000 A
Rated voltage : 36KV
Short Circuit breaker current : 31.5 KA rms
Short Circuit current duration : 3 Sec
Short Circuit making current : 79 KApk
Closing coil Supply Voltage : 110V DC
Tripping coil Supply Voltage : 110V DC
Motor Supply Voltage : 110V D
Type : 3AK 6532-A
Mfg Year : 2013

2. Feeder Name : Incomer-1
3. Location : FES 33KV Switch Board (Panel No-01)
4. General Inspection : Ok

5. Insulation Resistance Test: (Using 5000V Meggar)

i. Open Condition:

Terminal Values
R-R >100G
Y-Y >100G
B-B >100G










VOLTECH ENGINEERS PVT. LTD.
TEST REPORT FOR VACUUM
CIRCUIT BREAKER
CLIENT : M/S VOLTTECH ENGINEERING WORKES DATE :26.11.2013
PROJECT : JINDAL STEEL AND POWER LTD RAIGARH Sheet No.: 2 of 2

Test Performed by: VEPL Witnessed by: VOLTTECH Witnessed by: JSPL
Name :Mr.T.Balaji Name : Name :
Designation : Senior
commissioning Engineer
Designation : Designation :
Signature &
Date
Signature &
Date
Signature &
Date



ii. Close Condition:

Terminal Values
R ph-Earth >100G
Y ph- Earth >100G
B ph- Earth >100G
R ph-Y ph >100G
Y ph-B ph >100G
B ph-R ph >100G


6. Contact Resistance Test:

Terminal Values
R-R 18.0
Y-Y 20.6
B-B 19.3



7. Timer Interval Test:

Operations R ph-R ph Y ph-Y ph B ph-B ph
Close 64 ms 63 ms 64 ms
Open 27 ms 27 ms 27 ms
Close-Open 39 ms 39 ms 41 ms



8. Closing Coil Resistance :16.40M
9. Tripping Coil Resistance-1 :10.86M
10. Tripping Coil Resistance-2 : 16.0M







VOLTECH ENGINEERS PVT. LTD.
TEST REPORT FOR VACUUM
CIRCUIT BREAKER
CLIENT : M/S VOLTTECH ENGINEERING WORKES DATE :26.11.2013
PROJECT : JINDAL STEEL AND POWER LTD RAIGARH Sheet No.: 3 of 2

Test Performed by: VEPL Witnessed by: VOLTTECH Witnessed by: JSPL
Name :Mr.T.Balaji Name : Name :
Designation : Senior
commissioning Engineer
Designation : Designation :
Signature &
Date
Signature &
Date
Signature &
Date



11. Operational Check:

a. Manual
Close OK
Open OK
b. Electrical
Close OK
Open OK
Protection Tripping OK


12. Functional Check:

ON-OFF Indication OK
Spring charge Limit Switch OK
CB Aux. contacts OK
Trip circuit healthy OK
Antipumping function OK








13. Remarks: Breaker Check found ok