GHAYATHI COMMUNITY HOSPITAL SEHA-G/TEN/44/2009

Abu Dhabi - UAE Section 15050


Burt Hill Project No. 10710.00 Basic Mechanical Materials and Methods
Technical Specifications Tender Documents
Book V Mechanical Works Date of Issue: 16
th
February 2011

BURT , HILL Page 6 of 22

1. Shall consist of radiographic inspection to comply with B.S. 2600 and B.S.2910.
Non-destructive testing shall be carried out by a specialist company approved by the
Engineer, but paid by the Contractor.
2. Radiographic tests shall be performed on a minimum of 5% of the welds sized
150mm or smaller. Radiographic tests shall be performed on a minimum of 10% of
the welds of piping measuring 160mm or larger. Ultrasonic tests shall be performed
on the remaining balance of the welds.
3. The specialist company shall provide a report on the radiographic tests which have
been made, including an interpretative results section. The report and films shall be
handed to the Engineer.
4. The material of the image quality indicator shall be radiographically similar to that of
the filler metal under examination.
5. The use of X-Ray and Gamma Radiation sources shall be in strict accordance with the
requirements of the lonizing Radiation (Sealed Sources) Regulations. The required
radiographic sensitivity shall not be more than 2, and the required image details shall
be readily seen on each radiograph.
6. Radiographs which do not comply with this requirement, whatever the cause, shall be
unacceptable and the weld in question shall be re-examined at no cost to the Owner.
7. All interested parties shall be advised well in advance where and when radiographic
tests are to be conducted, in order that appropriate precautions may be taken.
1.7 DELIVERY, STORAGE, AND HANDLING
A. Deliver pipes and tubes with factory-applied end caps. Maintain end caps through shipping,
storage, and handling to prevent pipe end damage and to prevent entrance of dirt, debris, and
moisture.
B. Store plastic pipes protected from direct sunlight. Support to prevent sagging and bending.
1.8 COORDINATION
A. Arrange for pipe spaces, chases, slots, and openings in building structure during progress of
construction, to allow for mechanical installations.
B. Coordinate installation of required supporting devices and set sleeves in poured-in-place
concrete and other structural components as they are constructed.
C. Coordinate requirements for access panels and doors for mechanical items requiring access
that are concealed behind finished surfaces. Access panels and doors are specified in
Division 8 Section "Access Doors and Frames."