You are on page 1of 314

This presentation is being brought to you

by:
ASHRAE India Chapter and Xylem, Inc.

Large Chilled Water System


Design Seminar

Presented by:
Larry Konopacz, Manager of Training & Education
Bell & Gossett Little Red Schoolhouse
Saturday, September 21, 2013

Large Chilled Water System Design Seminar


The Production Loop

Chilled Water Sources


Chillers
Cooling towers
Free-Cooling &
Waterside Economizer
Thermal Storage
Water Source Heat Pumps

Whats a Ton?

I Ton Ice =
2000 LB;
1LB Ice =
144 Btu;
1 Ton ice =
288,000 Btu

Rule of 24
12,000 Btu/h = 500 x gpm x tF = 1 ton
gpm/ton = 12,000/(500 x tF)
= 24/tF

What Types of Chillers


are Available?
Compressor

Centrifugal
Rotary screw
Reciprocating
Absorption

Condenser

Evaporator

Refrigeration Cycle
Expansion Device

Hot Water

Liquid Flow

Vapor Flow

Condenser
Water Pump

Compressor
Motor

Load

Evaporator

Low Pressure Zone

Cool Water

High Pressure Zone

Condenser

Cooling
Tower

Supply
Water

Return
Water
Chilled
Water
Pump

Where is What Used?


Large chilled water plants - centrifugal
Mid-range size - rotary screw
Smaller chilled water applications reciprocating
Inexpensive source of steam or other
energy source - absorption
Combinations of the above

Chiller Piping - Evaporator Side


C

Chiller 2

Chiller 1

Return

Common Pipe

Supply

Typical Piping Method


Chiller 3
Chiller 2
Triple
Duty

Chiller 1
Supply

Triple
Duty
Common
Pipe

Return

Adding Pump Redundancy


Chiller 2

Triple
Duty

Chiller 1
Supply

Triple
Duty
Common
Pipe

Return

Headered Primary Pumps


Actuated Control Valve
Chiller 3
Chiller 2
Piped for
Standby
Pumps

Supply
Triple
Duty

Chiller 1

Common
Pipe
Triple
Duty

Return

Chiller Piping - Condenser Side


Cooling

SRS

Towers

SRS

SRS

Pumps
Triple Duty
Condenser

Condenser
Condenser

Multi-celled Cooling Tower


Condenser
Condenser
Condenser
Multi-cell Cooling Tower
Triple
Duty

SRS

Standby Pump

Tower Equalization
Cooling Towers

Equalization
Line

Condenser

Condenser

SRS

Triple Duty
Condenser

Cooling Tower Piping Practices


Fill all sections of pipe to purge air.
Size piping at a minimum of 2 fps to
move free air bubbles to tower.
All piping installed below system purge
level.

Condenser Water Piping Above Grade


System Purge Level

SRS

Overhead Piping Concerns

Piping manifolds can result in low velocities.


Low velocity will allow air to be released.
Air trapped in piping increases head required.
Piping installed above purge level compounds
problem.
Unpurged areas are potential sources of
problems when pumps are turned on.

Elevated Suction Piping Concerns

Condenser water pump difficult to purge.


At start-up a manual air vent may be required.
During operation air will again accumulate.
Automatic air vent may not work.
If above the basin fill level, the result is
cavitation.

Improper Piping Above Basin Level


System Purge Level

Basin Fill Level

Multi-tower System, Properly Piped


System Purge Level

SRS

Tower Piping Observations


At part load reduced velocities in headers may
allow air to be released.
Idle pumps will accumulate air that should be
released prior to starting the pump.
Tower basins should be elevated to ensure
positive pressure under all flow conditions.
Pump casings should be fitted with automatic
air vents.

Condenser Head Pressure Control


With centrifugal chillers a minimum supply
water temperature is needed to:
Maintain optimum efficiency
Maintain a minimum pressure differential
between condenser and evaporator
Prevent pressure imbalance

Hermetic Compressor Guidelines

Condenser water temperature > 75 F.


Establish 75 F within 15 minutes.
N/O condenser water throttling valve.
Three-way bypass valve can be used.
Constant condenser water flow.
Water temperature control through fan
modulation, or other methods.

Open Compressor Guidelines

Condenser water temperature > 55 F.


Three-way bypass valve can be used.
Constant condenser water flow.
Water temperature control through fan
modulation, or other methods.

Cooling Towers

Air in

Air out

Water In

Water out

Induced Draft, Counter-flow Tower


Air Out

Water in

Air in

Water out

Air in

Forced Draft, Cross-flow Tower


Air Out

Air in

Air in

Water out
Water in

Dynamic Relationship of Load,


Approach, and Range
Temperature

Range
(R F)
Approach
(F)

Wet bulb F

Heat Load = L x R

L lb/min of water

Load

L lb/min of water

Hot water F

Cold water F

Water Flow

Tower Size Relationships


Variables:
Heat Load (Varies Directly)
Range (Varies Inversely)
Approach (Varies Inversely)
Wet-bulb Temperature (Varies Inversely)
Varying any of these variables will affect
the size of the tower.

Types of Free-Cooling
(Waterside Economizer)
Air Out

Water in
Air in

Air in

Water out

Earth Contact

Evaporative

Earth Contact Characteristics


Usually indirect.
Cooling medium and load separated by heat
exchanger.
Stable temperatures.
Water temperature limitations.
Water treatment and pumping costs.
Environmental concerns.

Heat Exchangers

How do they work?


Thin plates are stamped with
a unique chevron pattern and
assembled in a frame
Four holes punched in the
plate corners form a
continuous tunnel which acts
as a distribution manifold for
the inlet and outlet of each
fluid

How do they work?


Each plate has a gasket that
confines the fluid to the port
or to the heat transfer area of
the plate
Units are built to order with a
standard 150 psi ASME Code
stamped design or to custom
designs

Earth Contact - Summer Cycle

C
O
N
D

TOWER

E
V
A
P

GPX

H
E
A
T

E
X
C
H

LOAD

Triple Duty
Sediment Removal
Separator

Triple Duty

Earth Contact - Winter Cycle

C
O
N
D

TOWER

E
V
A
P

GPX

H
E
A
T

E
X
C
H

LOAD

Triple Duty
Sediment Removal
Separator

Triple Duty

Evaporative Characteristics
Heat rejection device (tower) exists.
As temperature declines, opportunity
arises.
Higher sensible vs. latent loads
Leaving water temperature approaches
42 F.
Freeze protection may be required.

Freeze Protection

Sump heaters.
Close temperature control.
Accurate water level control.
Prevention of moist air recirculation.
External piping freeze protection.

Evaporative Cooling - Direct

C
O
N
D

TOWER

E
V
A
P

LOAD

Triple Duty
Sediment Removal
Separator

Single Tower, Summer Cycle

Triple Duty

Evaporative Cooling - Direct

NOT RECOMMENDED
C
O
N
D

TOWER

E
V
A
P

Triple Duty
Sediment Removal
Separator

* Alternate location of SRS, depending on


system conditions

Single Tower, Winter Cycle

LOAD

Triple Duty

Evaporative Cooling - Indirect

C
O
N
D

TOWER

E
V
A
P

GPX

H
E
A
T

E
X
C
H

LOAD

Triple Duty
Sediment Removal
Separator

Single Tower/GPX, Summer Cycle

Triple Duty

Evaporative Cooling - Indirect

C
O
N
D

TOWER

E
V
A
P

GPX

H
E
A
T

E
X
C
H

LOAD

Triple Duty
Sediment Removal
Separator

Single Tower/GPX, Winter Cycle

Triple Duty

Temperature Cross and Approach


TEMP.
DEG. F

57= T1

CH. WATER
52= t2
7F TEMPERATURE
CROSS

45= T2

COND. WATER

3F COOLING
APPROACH
42= t1

EXCHANGER
LENGTH

Heat Transfer Area vs Approach


COND. WATER
EWT LWT FLOW

CH. WATER
EWT LWT FLOW

LMTD
DEG F

AREA EXCH.
SQ.FT. MODEL

COST
INDEX

42

52

1000

57

45

834

3.92

1390

GPX807

1.00

42

52

1000

58

46

834

4.93

1135

GPX807

0.85

42

52

1000

59

47

834

5.94

975

GPX807

0.76

Temperatures are in F

Flow is in USGPM

Heat exchanger selection based on max pressure drop of 7 psi


10/3.92=2.55

Approach = 3F

10/4.93=2.03

Approach = 4F

10/5.94=1.69

Approach = 5F

Production Source - Thermal Storage

Application Criteria
Economics
Storage Media
Storage Technologies
System Configurations

Application Criteria

High maximum load.


Significant premium for peak demand.
Incentives.
Limited space available.
Limited electrical capacity.
Back-up or redundancy required.

Storage Media
Chilled Water
Ice Harvesting
External/Internal Ice Melt

Stratified Chilled Water System


T
Load
Variable volume
distribution
pump

Warm

Vent

Storage

Pressure sustaining
and check valve

Cool
Constant volume
primary pump

Chiller

Temperature Stratification
Top 0
Depth of tank, ft

-5
-10

Thermocline

-15

Bottom -20
30

40

50

60

Temperature, F

70

Use of Pressure Sustaining Valves


Load
Distribution
pump

Primary
pump

Chiller

Transfer

Pump

Direction
control
valves

Vent
Warm

Pressure sustaining
and check valve

Storage

Cool
Constant volume
primary pump

Incorporating Heat Exchangers


Load T
Variable volume
secondary
pump

Heat
Exchanger

Variable volume
primary
pump
Warm

Vent
Storage

Cool
Constant volume
primary pump

Pressure sustaining
and check valve

Chiller

Ice Harvesting System


Section Section Section Section
1
3
4
2
Ice harvester
chiller

Load

Ice water
Chilled water
pump

recirculation

pump

External Melt Ice Storage

Discharging Mode
Charging Mode

Encapsulated Ice Storage


Charge and Discharge Modes
Charging Mode

Discharging Mode
Ice

Cold glycol

Ice

Warm glycol

Water

Full Storage Strategy


Chiller on

Charging
Storage

Charging
Storage
Chiller off

Tons

Cooling load
(met by storage)
Chiller meets load directly

Time of Day

Partial Storage - Load Leveling


Charging
Storage

Cooling load
(met by storage)

Tons

Chiller runs continuously


Cooling load
(met by chiller)

Time of Day

Charging
Storage

Partial Storage - Demand Limiting


Reduced on-peak demand
Charging
Storage

(met by storage)

Tons

Cooling load

(met by chiller)
Time of Day

Charging
Storage

Production Source - Water Source Heatpumps

Growing market segment


System temperature range 40 - 90 F
Energy added below 40 F (heat)
Heat removed above 90 F (cooling
tower)

Heat Pump Cycles - Water Source


Supply

System Water

Return
Air Coil

Water Coil

Air Coil

Water Coil

(Evaporator)

(Condenser)

(Condenser)

(Evaporator)

Cool
Air

Warm
Air

Compressor

Reversing

Valve

Capillary

Air Conditioner Cooling

Refrigerant
Loop

Compressor

Reversing

Valve

Capillary

Air Conditioner Heating

Design Considerations
Use slow closing two-way valves for
each zone
Good system balance required
Use staged c/s or v/s pumps
Use with cooling towers and GPX
Use with closed circuit cooling towers

Heat Pump-Water Source Schematic


Compression
Tank
Cooling
Tower

Water Source
Heat Pump

Buffer
Tank
( Optional )

Gasketed
Plate Heat
Exchanger

Water Source
Heat Pump

Water Source
Heat Pump

Water Source
Heat Pump

Water Source
Heat Pump

Water Source
Heat Pump

Water Source
Heat Pump

Water Source
Heat Pump

Water Source
Heat Pump

Heat Pump-Water Source Schematic


Closed Circuit Cooler
Heat Rejecter

Water Source
Heat Pump

Buffer
Tank
( Optional )

Compression
Tank

Water Source
Heat Pump

Water Source
Heat Pump

Water Source
Heat Pump

Water Source
Heat Pump

Water Source
Heat Pump

Water Source
Heat Pump

Water Source
Heat Pump

Water Source
Heat Pump

Comments?
Questions?
Observations?

Large Chilled Water System Design Seminar


Variable Volume Distribution

Variable flow through coil


Constant flow through system

Variable flow through coil


Variable flow through system

Three Way Valve

Two Way Valve

Three-Way Valve Systems

Low return temperatures


Balance problems
Increased flow at part load
Extra chillers to provide flow at low t
Chillers operate at high kW/ton

C
H
I
L
L
E
R

Two-Way Valve System with


Chiller Bypass

C
H
I
L
L
E
R

A Problem
We want:
a. variable volume, to save pumping
costs at part load,
b. constant flow through the chiller to
protect it.

A Solution
a. constant flow primary system for the chillers
b. variable flow secondary system for the load

Primary-Secondary Terms
Supply
Primary Loop
Production

Secondary Loop
Distribution
C
H
I
L
L
E
R

C
H
I
L
L
E
R

C
H
I
L
L
E
R

Primary-Secondary
Common Pipe
Return

Fundamental Idea

Secondary
Pump

Primary
Pump

Tee
A

Tee
B

Low pressure drop in the common pipe

Primary-Secondary Pumping
The idea is based on:
Conservation of Mass
Conservation of Energy

Law of the Tee: Diversion


50 GPM

100 GPM

50 GPM

Law of the Tee: Mixing


100 GPM

60 GPM

40 GPM

No Secondary Flow

Secondary
Pump
Off

A
100 GPM @ 45F
Primary
Pump

100 GPM @ 45F

100 GPM @ 45F

Primary = Secondary

100 GPM @ 45F

100 GPM @ 55F

Pump On

A
100 GPM @ 45F

B
0 GPM

100 GPM @ 55F

Primary > Secondary

50 GPM @ 45F

50 GPM @ 55F

Pump On

Mixing at Tee B

100 GPM @ 45F

100 GPM @ 50F


50 GPM @ 45F

Primary < Secondary

200 GPM @ 55F

200 GPM @ 50F

Pump

On

100 GPM @ 45F


Mixing at Tee A

100 GPM @ 55F


100 GPM @55F

Control Valve in Secondary

Two-way Valve

Primary-Secondary Pumping
Supply
Primary Loop
Production

Secondary Loop
Distribution
C
H
I
L
L
E
R

C
H
I
L
L
E
R

C
H
I
L
L
E
R

Primary-Secondary
Common
Return

Common Pipe Design Criteria


Use the flow of the largest chiller
Chiller staging at half of this flow is
common

Head loss in common <1 1/2 ft


Distribution pipe size is often used where
reductions would be inconvenient

Three pipe diameters between tees


Excessive length increases total head loss

Low velocities in system piping

Design of the Common Pipe


Secondary
Constant Speed
Pumps

Supply

Chiller 1

Chiller 2

Chiller 3

Pump
Controller
Common

Return

10 dia.

Common Pipe Configurations

Secondary System Curve


Control Valves
Closing
H1
H2

Control Valves
Opening

H3

Head

Flow

F1

F2

F3

Typical System
Distribution
Production

45F
To Loads

Chiller 1, on

Chiller 2, off

Secondary Pumps
1500 gpm each

Common
1500 gpm
each
From Loads

Production = Distribution
CHWS Temp
45oF

1500

1500

Chiller 2, off

Chiller 1, on

Secondary
Pumps

1500

Common -- No Flow
0

1500

1500
ECW Temp
55oF

CHWR Temp
55oF

Distribution > Production


CHWS Temp
47.5oF

2000
1500

Chiller 2, off

Chiller 1, on

Secondary
Pumps

2000
Mixing (1500 @ 45) + (500 @ 55)

Common -- 500
1500

2000
ECW Temp
55oF

CHWR Temp
55oF

Check Valve in Common?


Supply
>1500 GPM
>1500 GPM
@ 47.5oF

Chiller 1, on

Chiller 2, off

0 GPM

Be Careful!

Common
Return
>1500 GPM

>1500 GPM
@ 55oF

What can we do?


Supply

Linear
Function

Step
Function
Chiller 1

Chiller 2

Chiller 3

Primary/Secondary
Common
Distribution
Production

Return

Typical Load Profile


30
25
% Time

20
15
10
5
0
0-10

30-40
60-70
% Load

90-100

Multiple Chillers
Chiller 1
Chiller 2

80

% Load

60
40
20

1
25

50

2
75

% Time

100

Chiller 1, 40%

Chiller 2, 60%

100

What else can we do?


Reset Supply Temperature
Lower chiller set point when mixing occurs to
maintain a constant temperature to the system.
Allows us to mix colder water and maintain supply
temperature to secondary. (coils)

Expect increases in cost of chiller operation at


lower set point: 1-3% per degree of reset.
Adds to control complexity.
Delays start of the next chiller.

Production > Distribution


P/S Chiller Bridge - Front Loaded Common
(Flow in GPM)

CHWS Temp
45oF

3000

Chiller1, on

Chiller 2, on

Secondary
Pumps
2100

Common -- 900
1500

Mixing (2100 @ 55) + (900 @ 45)


1500

2100
ECW Temp
52oF

CHWR Temp
55oF

Loading a Chiller
A chiller is a heat transfer device. Like
most equipment, it is most efficient at
full load.
To load a chiller means:
Supply it with its rated flow of water
Insure that water is warm enough to permit
removal of rated Btu without freezing the
water

Chiller Performance Curve


1.1
1.0

KW per Ton

0.9
0.8
0.7
0.6
0.5
10 20

30

40 50 60 70
Percent Load

80 90 100

Typical Load Profile


30
25
% Time

20
15
10
5
0
0-10

30-40
60-70
% Load

90-100

60/40 Chiller Split to Help Minimize


Low Part Load Operation
Chiller 1
Chiller 2

80

% Load

60
40
20

1
25

50

2
75

% Time

100

Chiller 1, 40%

Chiller 2, 60%

100

Three Unequally Sized Chillers


Chiller 1 or Chiller 2
and

Chiller 3

and

Chiller 2

80
60

% Load
40
Chiller 3
20

Chiller 1
or

Chiller 2

25

50

75

100

% Time

Chiller 1, 40%

Chiller 1

Chiller 2, 40%

Chiller 3, 60%

100

Approaching Flow = Load

% Load

Time

Applying a Variable Speed Chiller


100
Ch 1

75

% Flow

Ch 1

Ch 2

50
Ch 1

Ch 2

Ch 3

Ch 3

Ch 4

25
Ch 2
Ch 1

25

50

75

% Load

100

Back Loaded Common


To Loads

Chiller 1

Chiller 2

Chiller 3

Common

From loads

Production = Distribution
CHWS Temp
45oF

1500

1500

Chiller 1, on

Chiller 2, off

Common
0 Flow

Secondary
Pumps
1500

1500

1500

CHWR Temp
55oF

Distribution > Production


CHWS Temp
47.5oF

Mixing (1500 @ 45) + (500 @ 55)

500
Chiller 1, on

Chiller 2, off

Common
500 gpm

Secondary
Pumps

1500

2000

1500

2000

500
CHWR Temp
55oF

Production > Distribution


CHWS Temp
45oF
900

1500

Chiller 1, on

Chiller 2, on

Common
900

600

1500 GPM
@ 49oF

900 GPM
@ 45oF

Secondary
Pumps

1500

2100

1500 GPM
@ 55oF

600 GPM
@ 55oF

Mixing (900 @ 45) + (600 @ 55)

2100
CHWR Temp
55oF

Maximize Free Cooling


Secondary
Pumps
PrimarySecondary
Common

Supply

Free Cooling

Chiller 2

Chiller 3

Pump
Controller

Return

Primary-Secondary System

Secondary
Pumps

Supply

Chiller 1

Chiller 2

Chiller 3

Pump
Controller
PrimarySecondary
Common

Return

Pump Horsepower Comparison


150

Constant Flow Primary Pumps, only


125

BHP

100

75

Secondary Pumps +
50

Primary Pumps = V/V


25

25

50

75

Design Coil Flow


%

100

2012 ASHRAE Handbook - HVAC Systems and Equipment, p 44.11

Constant vs Variable Volume


150
140

Constant Flow, C/S Pump


(3 Way Valve)

C/S Pump
(2 Way Valve)

130
120

Base
Design
HP %

Pump Over-headed by 150%

110
100

Constant Flow, C/S Pump


(3 Way Valve)

90

Pump Head Matched


to System @
Design Flow

80
70
60

% Full Load 50
(Design) HP 40
30
20
10
0

10 20 30 40 50 60 70 80 90 100

% Flow

Impact of Piping Length and Overheading


350

300

250
c/s @ 1.0
Yearly Operating Cost x $1000

c/s @ 1.25

200

c/s @ 1.50
c/s @ 2.0
150

100

50

0
0

1000

2000

3000

4000

5000

Pipe Length, Feet

6000

7000

8000

9000

Always Size the Pump to the System!


But...
Uncertainties
Coils
Control valves
Primary data

Lead times

Dealing With an Overheaded Pump


Throttle at the discharge valve
Limits on the valve

Flow balance & trim pump impeller


Required by ASHRAE/IES 90.1

Additional Concerns
Pump Protection at minimum flow
Chiller Staging and De-staging
instrumentation.

Pump Protection

Minimum recommended flow from ESP Plus = 900 gpm

Bypass Options
1. Establish a minimum flow equal to or greater than
the minimum required to protect the pump.
2. Install a bypass at the end of the mains with a
balance valve to set minimum flow.
3. Install a bypass at ends of zones.
4. In retrofits, leave a three way valve at the end of the
system.
5. Use P or flow sensing to open pump bypass only
when needed.
6. V/S pumps are not as big a problem because of
lower head at reduced flow.

System Bypass Options


3

Secondary
Constant Speed
Pumps

Supply

Chiller 1

Chiller 2

Chiller 3

Pump
Controller

6
Primary
Secondary
Common

Return

Chiller Staging Instrumentation


Production

TS-S

TP-S

FS

FP

To Loads

Chiller 1, on

Chiller 2, off

Secondary/Pumps

Distribution
Common

TP-R

TS-R
From Loads

Common Pipe Flow Indication


Distribution
Production
To Loads

Flow Switches

Chiller 1

Chiller 2

Secondary/Pumps

Common

From Loads

Comments?
Questions?
Observations?

Large Chilled Water Design Seminar


Variable Speed Pumping

Why variable speed?


1. When should I use it?
2. How does it work?
3. What about variable primary flow?

Typical operating load profile


30%

20%
15%

5%
2%

3%

15%

5%

3%

2%

Bell & Gossett 70V


1970s

Adjustable Frequency Drives


Rectifier section
converts AC to DC
several varieties available

Inverter section
forms a synthetic sine wave
several varieties available
maintains a controlled frequency/voltage ratio

Requires an automatic control system


Adds to the initial cost of the system

Affinity Laws
1. Capacity varies as the RPM change ratio:
FLOW 2 = FLOW 1 ( SPEED2 / SPEED 1)
2. Head varies as the square of the RPM change ratio:
HEAD 2 = HEAD 1 (SPEED 2 / SPEED 1)

3. Brake horsepower varies as the cube of the RPM change ratio:


BHP 2 = BHP 1 (SPEED 2 / SPEED 1)

Affinity Laws for Centrifugal Pumps


100

Percent

90
80

Flow

70

Head

60

Horsepower

50
40
30
20
10
0
0

10

20

30

40

50

60

70

Flow/Speed, Percent

80

90

100

Theoretical Savings
120
110

Pump Curves

100

90%

100% Speed

110
100

Design

90

90
80%

80

Head

70

70
70%

60
50

60
50

60%

40

HP Draw
50%

30

40%

30

Head
20
BHP

10 30%
0

0 10 20

40

Flow
30 40

50

60

70 80

% Design Flow

10
0
90 100

% BHP

% Head

80

20

120

Required Differential Pressure

P Sensor/Transmitter
25 Ft. Head

System Curve
& V/S Control System
110
25 FT Differential Head
Maintained Across Load
(Set Point)

80
60

Overall
system curve

40

Distribution
piping head
loss curve

20
0

200

400

600

800

1000 1200 1400

Flow

Set Point
Pump TDH

Head

100

1600

Effect of Constant* Set Point


110

As the valve closes,


the pump slows down

100
80

Pump TDH

Head

Set point,
25 FT

Control curve

60
Overall system curve
40
Distribution
piping head
loss curve

20
0
0

200

400

600

800

1000

1200

1400

1600

Flow

*Whats Constant?

Pump
Initial Speed

Control Curve
B

Head, H
(feet)
Pipe, Fitting
Friction Loss

Flow, Q
(gpm)

Q2 Q1

Decrease in Heat Load Results in Troom < T set point


Causes Two Way Valves to Throttle Flow

Pump
Curve

Speed 1
B
Speed 2

Control Curve
A

Head, H
(feet)

Pipe, Fitting
Friction Loss

Flow, Q
(gpm)

Q3 Q2

Q1

Decrease in Pump Speed Reduces Flow, Reduces Error

Control Curve

Speed 1

Head
(ft)
Final Speed

Pipe, Fitting
Friction Loss

Flow, Q
(gpm)

Q4

Q1

System Operation on Control Curve at Lower Speed

Variable vs Constant Head Loss


Constant Head Loss
Variable Head Loss
Supply
C
H
I
L
L
E
R

C
H
I
L
L
E
R

C
H
I
L
L
E
R

Pump
Controller

Adjustable Freqy. Drives

Return

Variable Head Loss Ratio


C/S, Constant Flow System

Base 100

Pump Head Matched to


System at Design Flow

90
80

Percent Design BHP

C/S, Variable Flow

V/S, 0% Variable Hd Loss, 100% Constant Hd

70
V/S, 25% Variable Hd Loss, 75% Constant Hd

60
50

V/S, 50% Variable Hd Loss, 50% Constant Hd

40

V/S, 75% Variable Hd Loss, 25% Constant Hd

30
V/S, 100% Variable Hd Loss, 0% Constant Hd

20
10
0

10

20 30 40

50 60 70 80 90

% Flow

100

Variable Head Ratio w/


Overheading
Constant Flow, C/S Pump
(3 Way Valve)

150
140

C/S Pump
(2 Way Valve)

130
120

Base
Design
HP %

Pump OHeaded by 150%

110
Constant Flow, C/S Pump

100

(3 Way Valve)
90

Pump HD Matched
to System @
Design Flow

80
70
60

% Full Load
(Design) HP

50
* 25/75 Means:
25 % Variable HD Loss
75 % Constant HD Loss

40
30
20
10
0

10

20

30 40

50 60

70 80 90

100

V/S Curves
120

50 %

110

60 % 70 %
80 % 85 % % Efficiency
85 %
80 %

100

100 %

90

Head, Feet

80

90 %

70

% Speed Curves
80 %

60
50

70 %

40

Constant
Efficiency
Curve

60 %

30

50%

20

40 %
30 %

10
0

100 200

300 400

500

GPM
600

700 800

900 1000

Efficiency Changes
50 %

120

60 %

110

70 % 80 %
% Efficiency
85 %
85 %
80 %

100

100 %

90

Head, Feet

80

90 %

70

% Speed Curves
80 %

60
50

70 %

40

Constant
Efficiency
Curve

60 %

30

50%
20

40 %

10
0

30 %
0

100 200

300 400

GPM
500

600

700

800

900 1000

Minimum Drive Speed


50 %

120

60 %

110

% Efficiency
70 % 80 %
85 %
85 %
80 %

100

100 %

90

Head, Feet

80

90 %

70

% Speed Curves
80 %

60
50

70 %

40

Constant
Efficiency
Curve

60 %

30

50%
20

40 %

10
0

30 %
0

100 200

300 400

GPM
500

600

700

800

900 1000

Multiple Pump System Staging


Constant Differential Head Loss
Variable Head Loss
Supply
C
H
I
L
L
E
R

C
H
I
L
L
E
R

C
H
I
L
L
E
R

Pump
Controller

Adjustable Freqy. Drives

Return

Parallel V/S Operation

Pump 1

Pumps 1 & 2

Control Curve

1770 RPM
1450 RPM

1150 RPM
600 RPM

900 RPM

Pumps 1, 2 & 3

Variable Speed Pumping Equipment


3f , 60 Hz Power
(Control Agent)

Set Point
(Input Signal)

Technologic
Pump
Controller

Feedback
Signal

Sensor/
Transmitter

Set Point
+/- error

Adjustable
Frequency
Drive
(Controlled Device)

3f, Variable Frequency


Variable Voltage

Controlled
Variable

System

The Controlled Variable Determines the Type of Sensor

Pressure
Differential
Pressure
4-20
ma
signal
Temperature
Differential
Temperature
Flow

Pump
Controller

3f , 60 Hz Power
(Control Agent)

Set Point
(Input Signal)

Technologic
Pump
Controller

Feedback
Signal

Sensor/
Transmitter

Set Point
+/- error

Adjustable
Frequency
Drive
(Controlled Device)

3f, Variable Frequency


Variable Voltage

Controlled
Variable

System

Technologic Pump
Controller
Controls pumps and drives
Accept set point, analyze sensor input
PID function
Pump staging
Pump alternation
Recognize and react to component failure
Provide message display
Central management system link
Safeguard system

PID Control

Eliminates offset from set point


Allows for timely speed change
Handles large, sudden disturbances
Prevents oscillation and over-damping

3f , 60 Hz Power
(Control Agent)

Set Point
(Input Signal)

Technologic
Pump
Controller

Feedback
Signal

Sensor/
Transmitter

Set Point
+/- error

Adjustable
Frequency
Drive
(Controlled Device)

3f, Variable Frequency


Variable Voltage

Controlled
Variable

System

Adjustable Frequency Drive


Constant
Voltage &
Frequency
Power

Rectifier
Section

Direct
Current

Inverter
Section

Some important issues:


Rectifier and Inverter Design
Drive Efficiency
RFI and EMI Noise
Audible Noise
Size and Cost
Manual drive bypass

Variable
Voltage &
Frequency
Power

Pump
Motor

Typical Efficiency Range


Variable Speed Drives
120

Efficiency, %

100

60

Currently Available
AFDs
Typical Older AFDs

40

Other Types

80

20
0
0

20

40

60

Design Speed, %

80

100

Pump and Motor

The Pump
Minimum Flow
Minimum Speed
Inverter Duty
Motors
Motor Couplers

Maintaining Minimum Flow


120
100 % Speed

110
100
90

Head

80
70
60
30% Speed

50
40
30
20
10
0

10

20

30

40

50

% Flow

60

70

80

90

100

EPDM couplers on variable-speed pumps

Failed Hytrel Coupler from a Variable


Speed Pump

Variable Flow
Through
The Evaporator

Primary-Secondary System
Constant Differential Head Loss
Variable Head Loss
Supply
C
H
I
L
L
E
R

C
H
I
L
L
E
R

C
H
I
L
L
E
R

Pump
Controller

Adjustable Freqy. Drives

Return

Primary-Secondary
Common Practice.
Why?
Protection.
Nuisance shutdowns.
Freezing.
Costly downtime.

Variable Primary Flow


Flow Meter, option

DP Sensor

C
H
I
L
L
E
R

C
H
I
L
L
E
R

DP Sensor

C
H
I
L
L
E
R

DP Sensor

DP Sensor

Two-position Control Valves

Modulating
Valve

AFD

AFD

AFD

Controller

Whats different?
Primary pumps only
Flow meters or p sensors at each
chiller.
Two-position isolation valves at each
chiller
Minimum flow bypass with a modulating
control valve.
Smarter controller.

Alternative #1

Minimum Flow Bypass at Chillers


Minimum Chiller Flow
Minimum Pump flow

Ganged Pumps

FLOW
METER

SUPPLY

F
SIGNAL
TO TECH

DP
SENSOR
DP
SENSOR

DP
SENSOR

CHILLER

DP
SENSOR

CHILLER

DP
SENSOR

CHILLER

SIGNAL
TO TECH
SIGNALS
TO TECH

SIGNAL
TO TECH

SIGNALS
TO TECH

SIGNALS
TO TECH

TDV

TDV

TDV

T
NOTE:
ALL SENSOR
SIGNALS WIRED TO
TECHNOLOGIC
5500

RETURN
AFD

AFD

AFD
ISOLATION VALVE
CHECK VALVE
F FLOWMETER/TRANSMITTER
T TEMPERATURE SENSOR

BYPASS:
FOR SYSTEMS WITH
EXTENDED LIGHT
LOADS/WEEKEND
SHUTDOWNS. SET
BALANCE VALVE
FOR LOW FLOW TO
REDUCE THERMAL
STRATIFICATION
AND ALLOW QUICK
START UP AFTER
SHUT DOWN.

Monitoring Chiller Flow


P sensors - Technologic controller ensures the chiller
is in proper working condition by monitoring each
working chillers differential pressure. Flow through the
chiller is calculated using the values defined in the user
setup.
OR
Flow sensors - Technologic controller ensures the chiller
is in proper working condition by monitoring each
working chillers flow rate.

Technologic 5500
Initial programming is
crucial.
Must use accurate data
from the chiller
manufacturer.
Start-up coordination
should include the BMS
too.

Technologic 5500 Control Variables


1. Monitor zone differential pressure sensors,
compare actual values to the required set points.
Pump speed is modulated to maintain set point.
Pump staging will occur as required to meet set point.

Control sequence is exactly as described earlier.

Technologic 5500 Control Variables


2. Determine if the minimum flow requirements are
being met for all working chillers.
Prevents freeze-up or chiller low-flow trips
If chiller flow is too low, controller opens minimum flow
bypass valve in programmed increments. Size the valve
for system p.
Requests de-staging action from the chiller control
system or BMS.
Allows for operator intervention, decision making.
Required by code in some areas.

Ganged pumps allow operation of two chillers with one


pump.

Technologic 5500 Control Variables


3. Monitors chiller flow rate to prevent operation
above the maximum flow for the chillers and the
pumps.
Excess chiller flow generates a request to stage on an
additional chiller. Minimum flow bypass valve is closed.
Operator or BMS intervention required.
Ganged pumps allow operation of one chiller, two
pumps.
Optional system flow meter provides end-of-curve
protection for the pumps

Alternative #2
Bypass at End of System
Minimum chiller flow
Minimum pump flow
Ganged Pumps

FLOW
METER

SUPPLY

F
SIGNAL
TO TECH

DP
SENSOR

DP
SENSOR

CHILLER

DP
SENSOR

CHILLER

SIGNALS
TO TECH

CHILLER

DP
SENSOR

SIGNAL
TO TECH

SIGNALS
TO TECH

DP
SENSOR

SIGNAL
TO TECH

SIGNALS
TO TECH

TDV

TDV

TDV

T
NOTE:
ALL SENSOR
SIGNALS WIRED TO
TECHNOLOGIC
5500

RETURN
AFD

AFD

AFD
ISOLATION VALVE
CHECK VALVE
F FLOWMETER/TRANSMITTER
T TEMPERATURE SENSOR

Alternative #2
Minimum flow bypass valve is controlled
to protect both the pumps and the
chillers.
Pump requires >25% BEP flow
Minimum flow of largest chiller

Size the bypass valve using the zone


p.
Best for systems with extended light
loads or weekend shut-down.

Alternative #3

Primary pumps piped directly to chillers.


More common in retrofit systems.
Easier for applying un-equally sized
chillers in parallel.

FLOW
METER

SUPPLY

F
SIGNAL
TO TECH

DP
SENSOR
DP
SENSOR

CHILLER

DP
SENSOR

DP
SENSOR

CHILLER

DP
SENSOR

CHILLER

SIGNAL
TO TECH

SIGNALS
TO TECH

SIGNALS
TO TECH

TDV

SIGNAL
TO TECH

SIGNALS
TO TECH

TDV

TDV

T
NOTE:
ALL SENSOR
SIGNALS WIRED TO
TECHNOLOGIC
5500

RETURN
AFD

AFD

AFD
ISOLATION VALVE
CHECK VALVE
F FLOWMETER/TRANSMITTER
T TEMPERATURE SENSOR

BYPASS:
FOR SYSTEMS WITH
EXTENDED LIGHT
LOADS/WEEKEND
SHUTDOWNS. SET
BALANCE VALVE
FOR LOW FLOW TO
REDUCE THERMAL
STRATIFICATION
AND ALLOW QUICK
START UP AFTER
SHUT DOWN.

Pump Selection
Equal size pumps.
Redundancy.
Parts.
Maintenance.

Unequal size pumps.


Control issues.
Flow issues.
Premature failure, large pump at low flow.

Chiller Selection
Equal size chillers.
Redundancy.
Parts.
Maintenance.

Unequal size chillers.


Control issues.
Flow issues
Additional equipment.

Design Considerations
Size bypass for minimum flow of largest chiller.
Minimum building load?

Size bypass modulating valve


for system p, if its installed near the chillers
for zone p, if its out in the system.

Program the controller with the chiller p set


points for minimum and maximum chiller flow.
Verify with chiller manufacturer.

Design Considerations
Sequence chillers based on p or temperature
sensors.
Use accurate, calibrated flow meter or p sensors
at each evaporator
Allow for operator training.
Initial
On-going

Consider this design if:


System flow can be reduced by 30%.
System can tolerate modest changes in water
temperature.
Operators are well trained.
Demonstrates a greater cost savings.
High proportion of operating hours at:
Part load.
Full load with low entering condenser water.

Turn-down Ratio
Chiller manufacturers publish 3 - 11 fps
evaporator velocity range (typically).
You may have to increase your
acceptable head loss targets, use more
pump head.
Nominal base of 7 fps desirable.
Variation of 1 to 2 fps.
Work with the manufacturer.

Rate of Change*
Maximum rate of flow change, % design flow per minute
Source

Vapor Compression

Absorption

#1

4-12

**

#2

20-30

2-5

#3

**

30

#4

**

#5

**

1.67

*Table 2-2
ARTI-21CR/611-20070-01, 2004, Bahnfleth & Peyer
** Information not provided

Do not use if:


Supply temperature is critical.
Three-way valves are used throughout.
Existing controls are old, inaccurate.
Operators are unlikely to operate the
system as designed.

Supply Water Temperature


Dependant on :
System volume.
Rate of flow change.

Application specific.
Consider thermal storage

Operator Ability
Within operators ability?.
Commercial buildings may not have well
qualified operators.

Training is mandatory.
Initial
Periodic, in view of operator turnover.

Start-Up & Shut-down


In systems that start-up and shut-down, it
may be advisable to anticipate, and
avoid, rapid changes in flow as control
valves all tend to act together.
Control system, BMS, manual
procedures.
Use slow opening/closing valves at the
chiller, 60-90 seconds.(?)

Controls Complexity
Additional controls for the chillers
Additional controls the pumps.
Pumps operate on flow, temperature, and
P.
Chiller P.

Sensor Calibration
Multiple sensors control:
Flow.
Temperature.
Delta p

Maintenance.
Calibration.

Summary
Evaluate all the options.
Read some articles:
Variable Primary Flow CHW: Potential Benefits and Application Issues
by Bahnfleth and Peyer. Pennsylvania State University, ARTI21CR/611-20070-01
Chilled Water System for University Campus by Stephen W. Duda, PE,
ASHRAE Journal May, 2006

Another tool for the toolbox.

Comments?
Questions?
Observations?

Large Chilled Water System Design Seminar


Primary-Secondary-Tertiary Pumping Systems

Primary-Secondary-Tertiary
Zone C

Zone A
Zone B

C
H
I
L
L
E
R

C
H
I
L
L
E
R

Variable Speed Pump

Direct Pumped Zones


Zone A

Zone B

WRONG !

C
H
I
L
L
E
R

C
H
I
L
L
E
R

DP Controller

Zone C

Constant Demand Zones


Zone A

Zone B

WRONG !

C
H
I
L
L
E
R

C
H
I
L
L
E
R

Zone C

Hard set valve

Automatic
Flow Control
Valve

Primary-Secondary-Tertiary
Zone C

Zone A

RIGHT !

C
H
I
L
L
E
R

Zone B

C
H
I
L
L
E
R

Variable Speed Pump

Three Different Buildings


A has coils selected for 44F.
B has coils selected for 45F.
C has coils selected for 46F.
Therefore, the supply water temperature
must be at least 44F for A.
But what about B and C?

Primary-Secondary-Tertiary
can be even more useful
Zone C

Zone A
Zone B

C
H
I
L
L
E
R

C
H
I
L
L
E
R

?
Optional Variable
Speed Pump

Temperature Sensor Locations


Load

Load

Load

T1
Tertiary
Zone
Pump

MV

MV

MV

T4 T1

Common

T2

T2

T3
Pumped
Chilled
Water
Supply

Circuit Setter

Chilled
Water
Return

T3

T4

Tertiary Bridge
Load

Load

Load

MV

MV

MV

T1
Tertiary
Zone
Pump

T4

Common

T2
T3

Pumped
Chilled
Water
Supply

Tertiary Bridge
Chilled
Water
Return

Temperature Sensor Locations


Load

Load

Load

T1
Tertiary
Zone
Pump

MV

MV

MV

T4 T1

Common

T2

T2

T3
Pumped
Chilled
Water
Supply

Chilled
Water
Return

T3

T4

ADVANTAGES
1. Permits operating at highest allowable zone temperature
2. Maximizes coil flow rate, good film coefficients
3. Maximizes flow rate through each control valve
4. Ensures good humidity control
5. Minimizes the amount of coil reheat

DISADVANTAGES
1. Temperature of return water is unknown
2. Temperature of return water to chiller may be too high
3. Will not recognize increased supply water temperature

T2 Operation
Load

T1
Tertiary
Zone
Pump

MV

Load

MV

Load

MV

T4 T1

Common

T2

T2

T3
Pumped
Chilled
Water
Supply
Chilled
Water
Return

T3 T4

ADVANTAGES
1. Maintains chilled water return temperature at setpoint
2. Will not overload the chiller

DISADVANTAGES
1. No control of zone supply water temperature
2. Could lose humidity control
3. Will not recognize increased supply water temperature

T3 Operation
Load

Load

Load

T1
Tertiary
Zone
Pump

MV

MV

MV

T4

Common

T1

T2

T2

T3
Pumped
Chilled
Water
Supply

Chilled
Water
Return

T3 T4

ADVANTAGES
1. There are no perceived advantages at this location

DISADVANTAGES
1. Little, if any, valve modulation unless it is set to
close on sensing supply temperature lower than
permissible in the zone

T4 Operation
Load

Load

Load

T1
Tertiary
Zone
Pump

MV

MV

MV

T4
T1

Common

T2

T2

T3
Pumped
Chilled
Water
Supply

Chilled
Water
Return

T3

T4

ADVANTAGES
1. Maximizes coil flow rate
2. Ensures good humidity control

DISADVANTAGES
1. Temperature of return water is unknown
2. Temperature of return water to chiller may be too high
3. Will not recognize increased supply water temperature

No single sensor location


satisfies all design criteria
SO........

Applying Zone Valve Controller


Load

Load

Load

MV

MV

MV

T1

T2

T1
Tertiary
Zone
Pump

Common

T2

T3
Pumped
Chilled
Water
Supply

Chilled
Water
Return

T3

Control Algorithm
1. Temperature control to the zone (T1 sensing).
2. If T1 is satisfied, return water temperature to the chiller
plant (T2 sensing).
3. Monitor secondary chilled water supply temperature
(T3 sensing) for temperature increase due to secondary
return water recirculation or temperature decrease due to
chiller leaving water temperature reset.
4. Reference point for automatic reset and T (T2 - T3)
control (T3 sensing).

So what?
Satisfy zone cooling requirement at the
maximum possible supply temperature
Minimize secondary flow rate
Optimize return water temperature

3-way Valve Application

Tertiary
Pump

Chiller Plant

Secondary Pumps

Tertiary
Pump

Tertiary
Pump

Problems
Bypass returns cold water to chillers,
reduces system t.
Linear valve characteristics can cause
increased flow at part load.
Balancing required in bypass pipe and
coil-to-coil.
High cost per ton at the chiller.

3-way Valve System


Load

MV

Load

MV

Load

MV

T1

T1

Common
Flow
Meter

T3

Small
By-Pass

Secondary Supply
Secondary Return

T2

T2

T3

Multi-zone Application
Zone 1

Zone 2

Zone 3

Terminal
Unit Balance
Valve

Terminal
Unit Control
Valve

Zone 4
Zone
(Tertiary)
Pump

Zone Supply
Temperature
T1

T1
Chiller Supply
Temperature

T3

Common

GPX

Flow
Meter

C
h
i
l
l
e
r

Common
T3

]e

C
Distribution
o
(Secondary)
m
Pumps
m
o Rolairtrol
n

Return
Water
Temperature

Zone Bias
Control Valve

T2
C
h
i
l
l
e
r

T1
Common

T3

T3

3D Valves
C
h
i
l
l
e
r

T1

T2

T2

T2

District Cooling Application

Individual building temperature control


Static pressure isolation
Return water temperature control
Btu/hr totalization
Outdoor temperature reset
Independent operation

District Cooling Application


with GPX
Independent pressure control
HVAC fluid isolation

VPF Application
Zone 1

Zone 2

Zone 3

Terminal
Unit Balance
Valve

Terminal
Unit Control
Valve

Zone 4
Zone
(Tertiary)
Pump

Zone Supply
Temperature
T1

T1
Chiller Supply
Temperature

T3

GPX

Flow
Meter

Common

C
h
i
l
l
e
r

Common
T3

Zone
Balance
Valve

Rolairtrol

Return
Water
Temperature

Zone Bias
Control Valve

T2
C
h
i
l
l
e
r

T1
Common

T3

T3

3D Valves
C
h
i
l
l
e
r

T1

T2

T2

T2

Comments?
Questions?
Observations?

Large Chilled Water System Design Seminar


Primary-Secondary Zone Pumping Systems

Primary-Secondary Zone Pumping

Zone A

C
H
I
L
L
E
R

C
H
I
L
L
E
R

Zone B

Supply

Return

Zone C

Shared Piping

Zone A

C
H
I
L
L
E
R

C
H
I
L
L
E
R

Zone B

Supply

Shared Pipe
Return

Zone C

Shared Piping

Zone A

C
H
I
L
L
E
R

C
H
I
L
L
E
R

Zone B

Supply

Shared Pipe
Return

Zone C

Present and Future Piping


1500 gpm

Flow :
Current = 3000
Future = 4500

C
H
I
L
L
E
R

C
H
I
L
L
E
R

Zone A

1500 gpm

(1500 gpm)

Zone B

Zone C

Supply
Current = 1500
Future = 3000

Current = 0
Future = 1500
Return

Future Zone C

Zone A Requirements
(1500 gpm)

1500 gpm @ 80 (1500 gpm)

Zone A

Zone B

Zone C

4500 gpm*
A1 Supply

A2
A Zone A
Pressure drop:A to A1+B to B1
Present = 20.8
*Future = 45.2
B1
Return
B 4500 gpm*

A3

B2

B3

Zone A Calculations
Table 9-1 Zone A calculations
Zone A (A to A1 + B to B1)
Pipe Size
Pressure Drop - ft / 100 ft
Equivalent Length
(supply & return)
Pressure drop
Zone pressure drop
Total pressure drop

Future Flow @ 4500 gpm


14
2.26

Present Flow @ 3000 gpm


14
1.04

1000 ft x 2 = 2000 ft
45.2 ft
80 ft
125.2 ft

1000 ft x 2 = 2000 ft
20.8 ft
80 ft
100.8 ft

Pump Selection @ 1500 gpm

1510-6G @ 56.4 hp = 75 hp*

1510-6G @ 45.8 hp = 60 hp*

Note: 15 hp additional for future requirements


* Nominal horsepower motor for NOL pump

Zone B Requirements
(1500 gpm)

1500 gpm @ 80 1500 gpm @ 80

Zone B

Zone A

4500 gpm*
A

3000 gpm*
A1 Supply

Pressure drop: Zone B


AtoA1+ BtoB1 + A1toA2 + B1toB2
Present =20.8
9.0
*Future = 45.2
33.4 B1

B 4500 gpm*

Zone C

A2

Return
3000 gpm*

A3

B2

B3

Zone B Calculations
Table 9-2 Zone B calculations
Zone B(A1to A2+B1 to B2)
Pipe Size
Pressure Drop - ft / 100 ft
Equivalent Length
(supply & return)
Pressure drop
Previous pressure drop
Zone pressure drop
Total pressure drop

Future Flow @ 3000 gpm


12
1.67

Present Flow @ 1500 gpm


12
0.45

1000 ft x 2 = 2000 ft
33.4 ft
45.2 ft
80 ft
158.6 ft

1000 ft x 2 = 2000 ft
9.0 ft
20.8 ft
80 ft
109.8 ft

Pump Selection @ 1500 gpm

1510-6G @ 71.4 hp = 100 hp* 1510-6G @ 49.6 hp = 60 hp*

Note: 40 additional hp required for future requirements


* Nominal horsepower motor for NOL pump

Zone C Requirements
1500 gpm @ 80 1500 gpm @ 80

Zone B

Zone A

4500 gpm
A

1500 gpm

3000 gpm
A1 Supply

Zone C

A3

A2

Pressure drop: Zone C


AtoA1+ BtoB1 + A1toA2 + B1toB2 + A2toA3+ B2toB3
Present = 45.2 + 33.4
+ 21.4
Future = Present

B1

B 4500 gpm

1500 gpm @ 80

Return
3000 gpm

B2

B3
1500 gpm

Zone C Calculations
Zone C (A2 to A3 + B2 to B3) Future Flow @ 1500 gpm
Present Flow @ 0 gpm
Pipe Size
10
Pressure Drop - ft / 100 ft
1.07
Equivalent Length
(supply & return)
1000 ft x 2 = 2000 ft
Pressure drop
21.4 ft
Previous pressure drop
78.6 ft
(A to A2, B to B2)
Zone pressure drop
80 ft
Total pressure drop
180.0 ft
Pump Selection @ 1500 gpm 1510-6G @ 82.7 hp = 125 hp*; Note: 50 hp more
than Zone A

Zone Pumping Summary


Summary
Zone A
Zone B
Zone C
Total

Present Requirement
Future Requirement
Duty Pump Standby Pump Duty Pump Standby Pump
1 @ 75 hp
1 @ 75 hp
1 @ 75 hp
1 @ 75 hp
1 @ 100 hp
1 @ 100 hp 1 @ 100 hp
1 @ 100 hp
1 @ 125 hp
1 @ 125 hp
2 @ 175 hp
2 @ 175 hp 3 @ 300 hp
3 @ 300 hp
4 @ 350 hp
6 @ 600 hp

* Nominal horsepower motor for NOL pump

Pressure Diagram - Zone Pumped


System
Zone
Pump A

Zone
Pump B

Zone
Pump C

Load
Friction
Loss
0

Friction Loss
Supply Header
Friction Loss
Return Header

Primary-Secondary Equivalent
1500 GPM

1500 GPM

3000 GPM A1 1500 GPM A2

(1500 GPM)

A3

Supply

Chiller 1

Chiller 2

Chiller 3

Pump
Controller

AFDs

B
3000 GPM

B1

Return B2
1500 GPM

B3

P-S Calculations
Primary-Secondary pressure drop calculation:
Pipe Segment
A to A1 + B to B1
A1 to A2 + B1 to B2
A2 to A3 + B2 to B3
Zone B
Total

Pressure Drop
Present, feet
20.8
9.0
DNA
80.0
109.8

Pipe Segment
A to A1 + B to B1
A1 to A2 + B1 to B2
A2 to A3 + B2 to B3
Zone C
Total

Pressure Drop
Future, feet
45.2
33.4
21.4
80.0
180

P-S Calculations
Distribution pump selection:
Present = 3000 gpm @ 109.8 feet, increase impeller to 13.5 for future head requirements:
2 @ VSCS 8x10x17L @ 111.0 hp 125 NOL
1 @ VSCS 8x10x17L @ 111.0 hp 125 NOL, standby
Total
3 Pumps
375 NOL, Total
Future = 4500 gpm @ 180 feet:
3 @ VSCS 8x10x17L @ 114.4 hp 375 NOL
1 @ VSCS 8x10x17L @ 114.4 hp 125 NOL
Total
4 Pumps
500 NOL

Comparison
Zone Pumping
Present
350 hp

Future
600 hp

P/S Pumping
Present
375 hp

Future
500 hp

Primary-Secondary Zone
Pumping Cautions
Excessive initial horsepower
Initial equipment investment
Future considerations
Reduced Horsepower

Comments?
Questions?
Observations?

Large Chilled Water System Design Seminar


Variable Speed Sensor Selection and Location

Direct Return Piped System

Supply

Chiller 1

Chiller 2

Chiller 3

Pump
Controller

AFDs
Return

Differential
Pressure
Sensor

Single Point Pressure Sensor


Supply

WRONG!
Chiller 1

Chiller 2

Chiller 3

Single
Point
Pressure
Sensor

AFDs

Pump
Controller
Return

Control Curve Using Single Point


Pressure Sensor
90
80

Shut-off head

Design Point

70

Constant Pressure

60

Head, FT

50

1750 RPM
(Maximum rpm)

40
30

1480 RPM
(Minimum rpm)

20
10
0

200 400

600 800

1000 1200 1400 1600

Flow, gpm

Single Point Pressure Sensor


in a CHW System
A rise in the average water temperature
results in a net expansion of the water.
This net expansion volume flows into
the compression tank, raising the
system pressure.
The pump slows down.

What if?
Zone A

Zone B

P Sensor here
Supply

C
H
I
L
L
E
R

C
H
I
L
L
E
R

C
H
I
L
L
E
R

AFDs

Pump
Controller
Return

Zone C

Sensor Across Mains At Pump


Whats the set point?
Its the greatest branch and distribution
piping head loss calculated at design
flow. In other wordsdesign head.

What will the flow be in each zone?


Determined by the zone path CV

Differential Pressure Sensor


at the Pump
90
80

Design Point

70
60

Head, FT

50

Maximum rpm

40
30
20

Minimum rpm

10
0

200 400

600 800

1000 1200 1400 1600

Flow, gpm

Variable Head Loss Ratio


C/S, Constant Flow System

Base 100

Pump Head Matched to


System at Design Flow

90
80

Percent Design BHP

C/S, Variable Flow

V/S, 0% Variable Hd Loss, 100% Constant Hd

70
V/S, 25% Variable Hd Loss, 75% Constant Hd

60
50

V/S, 50% Variable Hd Loss, 50% Constant Hd

40

V/S, 75% Variable Hd Loss, 25% Constant Hd

30
V/S, 100% Variable Hd Loss, 0% Constant Hd

20
10
0

10

20 30 40

50 60 70 80 90

% Flow

100

Coil or Valve?

25 Head

Maximizing Variable Head Loss


Constant Head Loss
Variable Head Loss
Supply

Chiller 1

Chiller 2

Chiller 3

Pump
Controller

AFDs
Return

Differential
Pressure
Sensor

Control Area
Zone 2
20 ft

Zone 1
20 ft

DP Sensor
C
H
I
L
L
E
R

C
H
I
L
L
E
R

C
H
I
L
L
E
R

Pump
Controller

AFDs

Pressure Drops in Piping (Table 11-1)


P AB+EF

P Zone 1

20FT

20FT

P BC+DE P Zone 2
20FT

20FT

TDH = P AB + EF + BC + DE + P ZONE 2 = 60 FT

Control Area Calculation


Table 11-2 Control Area Calculation
Friction Friction P
TDH
Flow
Flow
Friction Friction P
Loss Zone 2
Zone 1 Zone 2
Loss
Loss Zone 1 Loss
BC+DE Zone 2
AB+EF Zone 1
40
20
20
20
45
0 gpm 600 gpm
5
0
25
5
20
20
30
300 gpm 300 gpm
5
5
20
0
0
20
25
600 gpm
0 gpm
5
20
20
0
0
20
20
0 gpm
0 gpm
0
0
40
20
20
20
60
600 gpm 600 gpm
20
20

What pump head is required at:


zero flow?
full flow?
less than full flow?

Control Area
60
50
40
Head, FT

30
20

Lower Limit
Upper Limit
Single Point

10
0
0

100

300

500 600 900 1100 1200


Flow, gpm

So What...?
Staging pumps in a closed loop HVAC
system by flow alone may not work
because of different head requirements
for a given flow.
Wire to water pump efficiency
calculations at part load depend heavily
on the assumptions made about the
nature and shape of the control curve.

Single Sensor, Including


Balance Valve Pressure Drop
Zone 2
20 ft

Zone 1
25 ft

B (50)

E (10)
F

What do you mean...?


The head loss across the coil and the
wide open valve in zone 1 is 25 feet at
full flow.
If thats true, then we need to add an
extra 15 feet of head loss in the balance
valve to insure adequate flow out to
Zone 2 when the Zone 1 valve is wide
open.

Set Point, Zone 1, 40 ft


Flow Zone 1

Flow Zone 2

Friction Loss

Friction Loss

Head Required

Setpoint -

AB+EF

BC+DE

Zone 2

Friction Loss

0 gpm

600 gpm

20

20

300 gpm

300 gpm

30

600 gpm

0 gpm

40

Excess head means wasted energy

Sensor Location
Zone 2

Zone 1

DP Sensor
C
H
I
L
L
E
R

C
H
I
L
L
E
R

C
H
I
L
L
E
R

Pump
Controller

AFDs

Single Sensor in Zone 2


Zone 1 requires 600 gpm at 25 ft
Zone 2 requires 600 gpm at 20 ft

Flow
Zone 1
0 gpm
300 gpm
600 gpm

Flow
Zone 2
600 gpm
300 gpm
0 gpm

Friction Loss

Friction Loss

Friction Loss

AB+EF

Zone 1

BC+DE

5
5
5

0
6.25
25

20
5
0

P Zone1,
Available
40
25
20

Inadequate head for Zone 1

P Avail Friction Loss


Zone 1
40
13.75
-5

Sensor in Zone 1
Zone 1 requires 600 gpm at 25 ft
Zone 2 requires 600 gpm at 20 ft

Flow Zone 1
0 gpm
300 gpm
600 gpm

Flow Zone 2
600 gpm
300 gpm
0 gpm

Friction Loss
AB+EF
5
5
5

Friction Loss
BC+DE
20
5
0

Head Required

Zone 2
20
5
0

Inadequate flow in Zone 2

Setpoint Friction Loss


5
20
25

What can we do...?

In this system:
Single sensor in Zone 2 at 20 ft fails to
provide adequate flow only when
load in Zone 2 < 50% and
load in Zone 1 > 75%

Is this a predictable, recurring situation?


manual adjustment
programming

Add a second sensor

Applying Multiple Sensors


Zone A

Zone B

Supply

DP Sensors
C
H
I
L
L
E
R

C
H
I
L
L
E
R

C
H
I
L
L
E
R

AFDs

Pump
Controller
Return

Zone C

Use Multiple Sensors?


Load
Similarity
Priority
Diversity

One building or several


Redundancy
First cost vs operating cost

The Active Zone


Zone set points do not have to be the
same.
Technologic pump controller scans all
zones often, comparing process
variable to set point in each case.
Pumps are controlled to satisfy the
worst case.
What happens to the rest of the zones?

Effect of Sensor Location


Zone 1

Zone 2

A
OR

E
F

Multiple Sensors & Setpoints


Multiple sensors, set point across Zone 1, = 25 FT and setpoint across Zone 2 = 20 FT, (Table 11-6)
Flow
Flow
Friction Loss
Minimum
Friction Loss
Minimum
P
P
Zone Zone
AB+EF
Reqd
BC+DE
Reqd
Zone1
Zone 2
1
2
Available
Available
P Zone 1,
P Zone2
0
600
5
0
40
20
20
20
300
300
5
6.25
25
5
5
20
600
0
5
25
25
0
0
25

Row 1. Sensor 2 is controlling, Zone 1 is over pumped.


Row 3. Sensor 1 is controlling, Zone 2 is over pumped.
Total pump head required:
row 1 45 ft
row 2 30 ft
row 3 30 ft

Reverse Return Piped System

Supply

C
H
I
L
L
E
R

Return

Reverse Return Systems


If all the circuits are the same length,
will the pump still change speed?
Suppose a coil with a high p
requirement and another with a lower p
requirement are served by the same
reverse return piping system. OK?
If the coils are serving different sides of
the building, could we have a problem?

Tertiary Piped System

Zone A

C
H
I
L
L
E
R

Zone B

Zone C

C
H
I
L
L
E
R

Return

Zone Piped System

Zone A

C
H
I
L
L
E
R

C
H
I
L
L
E
R

Zone B

Supply

Return

Zone C

Summary
Give priority to the needs of the branch.
The rule of sensor location is simple and easy
to apply:
If you have to use a single sensor, put it across
the critical branch.
Whats the critical branch?
Its the same one that determined the pump head.

As weve seen, the analysis is more important


than the rule.

Comments?
Questions?
Observations?

Large Chilled Water System Design Seminar


Achieving Hydronic System Balance

Systems Approach
Control M

Load

Distribution

Air Management

Verification
Philosophy
Source

Systems Approach
All components work together as team
Components interact and work as well as we
understand them

A collection of mismatched components will


not perform as expected
Owner, engineer, architect, contractor, and
operators are part of the system too!

Hydronic Balancing
We worry about balance because:
Load calculations are approximate
Piping circuitry analysis is approximate
Control valve selection is approximate
Approximations will lead to underflow and
overflow situations

Results of overflow or underflow


Design Dt cannot be achieved
Supply temperature controller hunts (?)
Sequence of operation can be upset.

For example:
Published by
ASHRAE &
Hydraulic
Institute
DarcyWeisbach
Equation.
Add 15%!

What Is Balancing?
Its test, adjust & balance
Test: The system, now built, is verified in
operation to perform to the expected level.
What do we measure?
temperature, flow, pressure drop, energy
consumption.

What do we test with?


Can we test with what is installed?
Can we obtain accurate readings?

Adjust
Adjust: tested in operation, the system is
found lacking and needs fine tuning.
What level of adjustment, and for what
purpose?
Create comfort conditions
Minimize energy consumption
Prevent equipment damage

How do we adjust?

Balance
Balance is often interpreted to mean 10%
of design flow.
This generalization may or may not yield
satisfactory heat transfer required for
comfort conditions

Redefining Balance
Evaluate System Operation
If the goal is occupant comfort, then heat
transfer becomes the key concern.
We control heat transfer as a sensible
temperature control process between controller,
control valve and coil
Analysis should account for interaction of all key
components, and how they affect the rest of the
system

Balanced Hydronic Systems


All terminals receive enough flow to produce
satisfactory heat transfer (97.5% - 102.5%)
At design conditions, all terminals receive
satisfactory flow with the pump in a specified
range of operation
Under temperature control modulation to
match load, circuit flow does not exceed
design flow accuracy

Chilled Water Coil Flow vs. Heat Transfer


120%

Total

45
40

100%

80%

30

Sensible
25
60%

Latent
40%

20
15
10

20%
5
0%
0%

20%

40%

60%

80%

100%

120%

140%

% Flow
30H X 46W 10 FPI / 4 Row 30 GPM / 10T 85 DB/ 71 WB Ent 45 EWT 15 Circuits 3/8 Tube 4000 CFM Nominal 10 Ton Rating

160%

180%

0
200%

Waterside T (F)

% Heat Emission

35

Chilled Water Coil Flow vs. Emission


100
90
80
70
60
50
40
30
20
10

80%

100%

30H X 46W 10 FPI / 4 Row 30 GPM / 10T 85 DB/ 71 WB Ent 45 EWT 15 Circuits 3/8 Tube 4000 CFM Nominal 10 Ton Rating

97%

Flow Tolerance 97% Design HT


10%

15%

20%

Heating

260
240
220
200
180
160
140
120
100
80
70 16
60
50
40
0

5%

Cooling

Supply Water Temperature F

-0 / +10%

10

12

14

16

18

20

22

Suggested Flow Tolerance (%)

24

Balancing, The Obvious Answer


Maximum branch flows need to be controlled
Balancing valves are one solution
Pressure independent flow control is another
method
Systems perspective needs to be
maintained; pipe, valves, calculations.

Pressure Dependent Balancing Valve

Pressure Dependent Balancing Valve


140

Head (Feet)

120
100
80
60
40
20
0
0

50

100

150

Flow (USGPM)

200

250

Pressure Independent Flow Limiting Valve


Orifice is sized for
the design flow

Cartridge

Cartridge Operation
Flow

Flow

P1

P2

P1 is low
Cartridge Opens
P1 - P2 = Constant

P1

P2

P1 is high
Cartridge Closes
P1 - P2 = Constant

Pressure Independent Flow Limiting Valve


Fixed
Orifice

Flow in GPM

Control Range

Design Flow

Differential Pressure in PSI

Accuracy
Range

Pressure Independent Flow Limiting Valve


2 sizes available
.18 to 45.46 GPM

Externally adjustable flow limiting balance valves

Pressure Independent Control Valves


2 sizes available
.13 to 37 GPM

Externally adjustable flow limiting balance valve and


a modulating control valve

Its more than just balancing valves


Piping system decisions:
Usually have a choice between two size pipes
Varied methods of pipe head loss calculation

Have to account for safety factors, aging


Control valve selection: may not get the exact flow
coefficient you need.
Have to have a way to validate (test) and make
adjustments (branch & system)
It takes some judgment and experience.

Design Criteria For Piping


ASHRAE recommends:
Velocity

Consider:
Branch to riser pressure
drops should be 2:1 or
General 4 -10 fps
greater
Mechanical rm. 6 -15 fps
Direct return circuits in
Maximum velocity
variable speed / variable
1500 hr/yr 15 fps
flow hydronic circuits
3000 hr/yr 13 fps
require much more
6000 hr/yr 10 fps
attention to detail and
Pressure drop
control
sequence
1.0 to 4.0 ft / 100 ft.

ASHRAE 90.1-2010
CHAPTER 6

HEATING, VENTILATING, AND AIR CONDITIONING


SECTION 6.5
Prescriptive Path
TABLE 6.5.4.5 Piping System Design Maximum Flow Rate in GPM
Operating Hours/Year

<2000 Hours/Year

<2000 and <4400 Hours/Year

>4400 Hours/Year

Nominal Pipe Size, in.

Other

Variable Flow/
Variable Speed

Other

Variable Flow/
Variable Speed

Other

Variable Flow/
Variable Speed

120

180

85

130

68

110

180

270

140

210

110

170

350

530

260

400

210

320

410

620

310

470

250

370

740

1100

570

860

440

680

1200

1800

900

1400

700

1100

10

1800

2700

1300

2000

1000

1600

12
Maximum Velocity for Pipes
over 12 in. Size

2500

3800

1900

2900

1500

2300

8.5 fps

13.0 fps

6.5 fps

9.5 fps

5.0 fps

7.5 fps

Piping System Design Maximum Flow Rate


Friction Loss Rate Comparison
Friction Loss Rate
Operating
Hours/Year

<2000 and <4400


Hours/Year

<2000 Hours/Year

Nominal Pipe
Friction
Size, in.
Other Loss Rate
(GPM) (Ft/100 Ft)
120
10.01
2 1/2
180
7.26
3
350
6.55
4
5
410
2.84
6
740
3.47
1200
2.2
8
1800
1.52
10
2500
1.18
12

Variable
Friction
Speed Loss Rate
(GPM) (Ft / 100 Ft)
180
21.78
270
15.78
530
14.56
620
6.25
1100
7.44
1800
4.79
2700
3.3
3800
2.63

Other
(GPM)
85
140
260
310
570
900
1300
1900

>4400 Hours/Year

Friction
Variable
Friction
Loss Rate Speed Loss Rate
(Ft / 100 Ft) (GPM) (Ft / 100 Ft)
5.2
130
11.66
4.5
210
9.74
3.72
400
8.46
1.67
470
3.68
2.11
860
4.63
1.27
1400
2.95
0.82
2000
1.86
0.7
2900
1.57

Other
(GPM)
68
110
210
250
440
700
1000
1500

Friction
Variable
Friction
Loss Rate Speed Loss Rate
(Ft / 100 Ft) (GPM) (Ft / 100 Ft)
3.42
110
8.48
2.86
170
6.51
2.48
320
5.52
1.12
370
2.34
1.3
680
2.96
0.79
1100
1.86
0.5
1600
1.21
0.45
2300
1.01

Velocity
Operating
Hours/Year
Nominal Pipe
Size, in.
Other
(GPM)
120
2 1/2
3
180
350
4
410
5
6
740
1200
8
1800
10
2500
12

<2000 and <4400


Hours/Year

<2000 Hours/Year

Velocity
(ft/sec)
8.04
7.81
8.82
6.57
8.22
7.7
7.32
7.17

Variable
Speed
(GPM)
180
270
530
620
1100
1800
2700
3800

Velocity
(ft/sec)
12.06
11.72
13.36
9.94
12.22
11.55
10.98
10.89

Other
(GPM)
85
140
260
310
570
900
1300
1900

Velocity
(ft/sec)
5.69
6.08
6.55
4.97
6.33
5.78
5.29
5.45

Variable
Speed
(GPM)
130
210
400
470
860
1400
2000
2900

>4400 Hours/Year

Velocity
(ft/sec)
8.71
9.12
10.08
7.53
9.55
8.98
8.13
8.31

Other
(GPM)
68
110
210
250
440
700
1000
1500

Velocity
(ft/sec)
4.56
4.78
5.29
4.01
4.89
4.49
4.07
4.3

Variable
Speed
(GPM)
110
170
320
370
680
1100
1600
2300

Velocity
(ft/sec)
7.37
7.38
8.07
5.93
7.55
7.06
6.51
6.59

SYSTEM SYZER
Flow/Pressure Drop

ASHRAE 90.1 max


pipe size information

Estimated annual
energy cost based
on pipe size
Note that cost is based on a constant load it is
independent of the info in ASHRAE frame

Branch to Riser Pressure Drop Ratio


Ratio, Branch To
Distribution
4
2
1

% Design Flow
In End Circuit
95
90
80

And it falls off much more below 1:1

Branch:Riser Pressure Drop Ratio

Head

100%

Pump head constant


Improved

Distance From Pump

Branch:Riser Pressure Drop Ratio


constant
Reduced pump head

Head

100%

Distance From Pump

Issue: System Curve


When we have many paths, we have many
system curves depending upon which valves
are open.
In VS/VF systems, the pump flow changes
as the control valves modulate. The pump
speed adjusts to those changes.

A much larger system


Friction
Velocity
Loss
(FPS)
(Feet)
4.48
14.34
2.77
11.86
1.41
9.08
0.78
7.17
0.45
5.77
0.18
3.99

Flow
(USGPM)

Pipe
Size

5000

12
14
16
18
20
24

5500

14
16
18
20
24

3.33
1.7
0.94
0.54
0.22

13.04
9.99
7.89
6.35
4.39

6000

14
16
18
20
24

3.94
2.01
1.11
0.64
0.26

14.23
10.89
8.61
6.92
4.79

Reynolds
Friction
Flow Type
Number
Factor
1172764
1066660
933291
829403
743901
618839

Transition
Transition
Transition
Transition
Transition
Transition

0.014
0.0139
0.0138
0.0138
0.0138
0.0138

1173326
1026626
912343
818292
680723

Transition
Transition
Transition
Transition
Transition

0.0138
0.0137
0.0136
0.0136
0.0137

Transition
Transition
Transition
Transition
Transition

0.0137
0.0136
0.0135
0.0135
0.0136

1279992
1119949
995283
892682
742607

Balanced
Flow
Coefficient Available
CV
P
Branch

Set Point = 20 Ft

10

340

20

1000

287

28

1000

253

36

1000

229

44

1000

211

52

1000

196

60

1000

10
CV

CV

CV

e
CV

d
CV

32

Total

CV

24

4
C

16

4
D

4
A

6000@68

40
b

Branch
Flow

Branch = 20
Risers = 48
Ratio = 0.4

70.0

60.0

50.0

Head (Feet)

40.0

30.0

20.0

Inner Valves Close Head


Outer Valves CLose
System Curve
10.0

0.0
0.0

1000.0

2000.0

3000.0

4000.0

5000.0

6000

Flow (USGPM)

Q2
h2 h1 Min Control Head
Q1

2:1 BRPDR
70.0

10

10

CV

G
.83
F

60.0

Head (Feet)

50.0

.83
E
.83
D

40.0

.83
C
.83
B

30.0

20.0

Out Valves Close Head


Inner Valves Close
System Curve

0.0
1000.0

2000.0

3000.0

Flow (USGPM)

4000.0

5000.0

g
CV

1.7

CV

3.4

6000.0

.83
f

5.1

.83
e
.83
d

6.8

.83

3
CV

4
CV

c
CV

8.5

.83
b

.83

10.0

0.0

.83
A
a
6000 @ 30

Plot of Valve & Head Combinations 6000 GPM @ 30


2:1 Branch Riser Pressure Drop Ratio (BRPDR)

Variable Primary Flow System


4

VFD

6000 GPM
@88 Ft Hd

10

10

1
2
2

40
2

24
E

10

10

10

32
F

10

10

10

8
C

20

These Must Be Balanced!

0
B

10

10

10

10

16
D

Control Area for Variable Flow-Variable Speed Primary Distribution System


120.0

Valve 6 Closed

Valve 6 & 5
Closed

100.0

Valve 6,5,4,3
Closed

80.0

Valve 6,5,4
Closed

All Open

Head (Feet)

Valve 6,5,4,3,2
Closed

60.0

40.0
Valve 1 Closed
All Closed

Valve 1,2 Closed

20.0

System Curve
Inboard
Outboard

Valve 1,2,3 Closed


Valve 1,2,3,4 Closed
Valve 1,2,3,4,5 Closed

0.0
0

1000

2000

3000
4000
Flow (GPM)

5000

6000

7000

Thoughts On Selection
Coil pressure drop dominates system
controllability.
Control valve selection with = 0.5
Balancing valves: provide trim
Use as much PD as possible in control valves
Absorb the rest at the balancing valve.

Use independent flow measurement


Triple Duty Valve
Pump
Circuit Setters

Summary: Why Test & Balance?


Load calculations can be inaccurate causing
excess flow
Pipe and fitting predicted losses will vary from
actual performance
Aging factors / fouling will actually occur many years in
the future
Safety factors result in pump over-heading, improper
pump selection and over flow.

Control valve sizing is not exact.


Systems are not built as designed.

Additional Resources

Questions?
Thanks for Attending!
http://www.bellgossett.com
Resources & Tools
XylemKnowsH2o

http://mediasite.xyleminc.com
Our Representative in your area.

You might also like