You are on page 1of 22

Table 1

Design Response Spectra

Spectral Values Calculation - (Based on IBC 2003 - Section 1615.1.4)


The user shall input the cells shown in:

Spectral Respnse Acceleration for Mapped Maximum Considered Earthquake (MCE)

1.1 Short Period


1.2 Period

Site Class

Site coefficient

0.2 sec

Ss

0.186

(Ref SAES-A-112, Table-1)

1 sec

S1

0.053

(Ref SAES-A-112, Table-1)

3.1 Short Period


3.2 Period

1 sec

(Ref SAES-A-112, Table-1


note.4 or Soil report if available)

Fa

1.20

(Ref ASCE 7-05, Table 11.4-1)

Fv

1.70

(Ref ASCE 7-05, Table 11.4-2)

Adjusted MCE Spectral Response Acceleration Parameters :

4.1 Short Period


4.2 Period

1 sec

SMS = Fa * Ss

0.2232 g

(Ref ASCE 7-05, Eqn 11.4-1)

SM1 = Fv * S1

0.0901 g

(Ref ASCE 7-05, Eqn 11.4-2)

Design Spectral Response Accelerations Parameters

5.1 Short Period


5.2 Period

1 sec

SDS = 2/3 * SMS

0.1488 g

(Ref ASCE 7-05, Eqn 11.4-3)

SD1 = 2/3 * SM1

0.0601 g

(Ref ASCE 7-05, Eqn 11.4-3)

Design Response Spectrum


6.1

To = 0.2 * SD1/SDS

0.08073 s

6.2

Ts = SD1/Sds

0.40367 s

6.3 Long Period Transition Period


6.4 Fundamental Period of Equip/Str.

TL=

6.000

s
s

Design Spectral Response Accelerations, Sa


a)

b)

c)

d)

T < To
Sa = SDS 0.4 + 0.6 T/T0

0.1488 {0.4+0.6*T / 0.08073}

T0 < T < Ts
Sa = SDS

0.1488

Ts < T < TL
Sa = SD1 / T

0.0601
T

TL < T
Sa = SD1. TL / T2

0.3604
T2

Based on:
Site Class
SDS

0.1488

SD1

0.0601

(Ref ASCE 7-05 Table 11.6-1)


Category(for SDS)
(Ref ASCE 7-05 Table 11.6-2)
Category(for SD1)

Seismic Design Category


Most critical of either category case above controls

=
=

A
A

EV

0.2 SDS

0.0298 D
1.0EV

0.0298

LC 2B :

1.2 + 1.0EV

1.2298 D

1.2 (Ds + Do + Af) + (1.6 W o

LC 4A :

0.9 - (1.0EV)

0.8702 Ds

0.9 (Ds + Do) + 1.2 Af + 1.0

LC 4A :

0.9 - (1.0EV)

0.8702 Do

0.9 (Ds + Do) + 1.2 Af + 1.0

LC 4B :

0.9 - 0.9(1.0EV)

0.8732 Ds

0.9 (Ds + De) + 1.0 Ee

LC 4B :

0.9[0.6 - 1.0EV]

0.5132 Do

0.9 (Ds + De) + 1.0 Ee

0.160
0.140
0.120
0.100
Axis Title

0.080
0.060

Sa

0.040
0.020
0.000
0.00

1.00

2.00

3.00
Axis Title

4.00

5.00

6.00

7.00

0
C

Ss
0.186
1.2

Table-1)

0.25
1.2
Ss

Table-1)

Table-1
port if available)

A
B
C
D

0.25
0.8
1
1.2
1.6

0.5
0.8
1
1.2
1.4

0.75
0.8
1
1.1
1.2

1
0.8
1
1
1.1

1.25
0.8
1
1
1

Table 11.4-1)

2.5

1.7

1.2

0.9

0.9

Table 11.4-2)

Sec. 11.4.7Sec. 11.4.7Sec. 11.4.7Sec. 11.4.7Sec. 11.4.7

Eqn 11.4-1)

Eqn 11.4-2)

Eqn 11.4-3)

Eqn 11.4-3)
0
C

Ss
0.053
1.7

0.1

0.2

0.1
1.7
S1
0.3

0.4

0.5

A
B
C
D
E

0.8
1
1.7
2.4
3.5

0.8
1
1.6
2.0
3.2

0.8
0.8
0.8
1
1
1
1.5
1.4
1.3
1.8
1.6
1.5
2.8
2.4
2.4
Sec. 11.4.7Sec. 11.4.7Sec. 11.4.7

Load
Factor

(Ds + Do + Af) + (1.6 W or 1.0 Eo)

1.2300

(Ds + Do) + 1.2 Af + 1.0 Eo

0.8710

(Ds + Do) + 1.2 Af + 1.0 Eo

0.8710

(Ds + De) + 1.0 Ee

0.8740

(Ds + De) + 1.0 Ee

0.5140

Sa

7.00

ASCE Seismic Load Calculation : Base Shear Equation


Occupancy Category
Importance Factor
Soil site class

=
=
=

I
1.0
C

Spectral Acceln. (short period)

SS

0.186

Spectral Acceln. (1 second)


Structure Height

S1
hn

=
=

0.053
4.0

Fa
Fv

=
=

1.20
1.70

Site Coefficients

Maximum Spectral Response Accelerations:


SMS
SM1

=
=
=
=

Fa * SS
0.223
Fv * S1
0.090

Design Spectral Response Accelerations for Short and 1-Second Periods :

SDS
SD1

=
=
=
=

2/3 * SMS
0.149
2/3 * SM1
0.060

Seismic Design Category:

Category(for SDS)
Category(for SD1)
Use Category

=
=
=

A
A
A

Fundamental Period:

Period Coefficient

Ct

0.0488

Period Exponent

x
Ta

0.75
Ct * (hn)X

Approx. Period

0.138
Upper Limit Coef.

Cu

Period maximum

T(max)

1.7
C u * Ta

0.235
0.138

Tmodel
T

=
=

0.138

2.50

Fundamental Period
Period from model
Choose Period
Seismic Design Factors and Coefficients:

Response Modifier

CS
CS(max)
CS(min)

=
=
=
=
=

SDS /(R/I)
0.060
SD1/{(R/I)*T}
0.174
0.044*SDS*I 0.01
0.010

CS

0.060

e Shear Equation

(Ref ASCE 7-05, Table 1.5.1 and 1.5.2)


(only for temporary facilities 4 years lifetime)
(Ref SAES-A-112, Table-2 note.4 or Soil report if available)
(Ref SAES-A-112, Table-2)

(Ref SAES-A-112, Table-2)


Tank Effluent height

(Ref ASCE 7-05, Table 11.4-1)


(Ref ASCE 7-05, Table 11.4-2)

(Ref ASCE 7-05, Eqn 11.4-1)


(Ref ASCE 7-05, Eqn 11.4-2)

(Ref ASCE 7-05, Eqn 11.4-3)


(Ref ASCE 7-05, Eqn 11.4-3)

(Ref ASCE 7-05 Table 11.6-1)


(Ref ASCE 7-05 Table 11.6-2)
Most critical of either category case above controls

( Ref ASCE 7-05 Table 12.8-2)


(Ref ASCE 7-05 Table 12.8-2)
(Ref ASCE 7-05 Eqn. 12.8-7)

sec
(Ref ASCE 7-05 Table 12.8-1)

sec
sec
sec
sec

(Ref ASCE 7-05 Section 12.8.2)


(T = Ta <= Cu*Ta, ASCE 7-05 Section 12.8.2)
From Staad.Pro (Structural Analysis)

(Ref ASCE 7-05 Table 12.2.1 or 13.6.1 or 15.4.2)


for nonstructural i.e. Tank, Pump

(Ref ASCE 7-05 Eqn. 12.8-2)

/{(R/I)*T}

044*SDS*I 0.01

(Ref ASCE 7-05 Eqn. 12.8-3)


(Ref ASCE 7-05 Eqn. 12.8-5)

CS(min) <= CS <= CS(max)

orary facilities 4 years lifetime)