You are on page 1of 87

Job Information

Engineer

Checked

Approved

Included in this printout are data for:


Design Group

Design Brief

Member 7 - Main Steel Summary

Distance

Span

Moment

As Req.

As' Req.

Design Code

Members

Summary: the member is safe

Member M7 Span 1

Detailed ACI Design Requirements

Section Property: 250 x 449


Span Length
Width
Covers:

= 2.912

= 250 mmDepth

Rectangular section
= 450 mm

Top = 40 mm Bottom = 40 mm Side = 40 mm

Member M7 Span 1

Detailed ACI Main Reinforcement

Hogging: at 0.200 m from the start of the member


Moment applied to section

= 115.19 kNm

Effective depth of tension reinforcement

= 388 mm

Depth to compression reinforcement

d'

= 87 mm

Limit for compression steel

Rnt

= 4.78

Rn

= (Mu/bd2)

= 3.40

As

= (M/fy z)

= 1343.5 mm2

Tension Bars provided

= 2#25

Actual area of tension reinforcement

= 1020 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 1.05 %

Minimum horizontal distance between top bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between top bars

= 100 mm

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)

= 458.18 mm

10.6.4

Largest actual space between tension bars

= 126 mm

Actual neutral axis depth in section

= 85.38 mm

Moment capacity of section

= 90.73 kNm
NOT OK

Sagging: at 2.912 m from the start of the member


Moment applied to section

= 139.89 kNm

Effective depth of tension reinforcement

= 368 mm

Depth to compression reinforcement

d'

= 62 mm

Limit for compression steel

Rnt

= 4.78

Rn

= (Mu/bd2)

= 4.60

As

= (M/fy z)

= 1812.8 mm2

Tension Bars provided

= 3#25 2#25

Actual area of tension reinforcement

= 2550 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 2.77 %

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)
Largest actual space between tension bars

= 458.18 mm
= 63 mm

Actual neutral axis depth in section

= 184.87 mm

Moment capacity of section

= 182.44 kNm
OK

Member M7 Span 1

10.6.4

Detailed ACI Span / Depth Check

Basic span / depth ratio


Strength modification factor

= 21.00
= 0.4 + fy / 700

Hence, modified span / depth ratio


Actual span / depth ratio

9.5.2.1
= 0.79
= 16.65

= 6.47

OK

Member M7 Span 1

Detailed ACI Shear Reinforcement

High shear zone: 0.200 m to 1.775 m


Actual spacing of ties, s

= 150 mm

Design axial force, Nu

= -28.68 kNm

Shear force, Vu

= 137.30 kN

Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 69.94 kN

required (Av/s)

R11.5.7

= (Vu - Vc/fytd)

= (137303.24 - 0.85 69942.67/0.85 275 387.8)

Av, min

= 0.062 fc'(bws/fyt) = 38.7 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

= 47.7 mm2

= 142.0 mm2

area of links provided (2#10), Av


Maximum spacing of ties

= 194 mm11.5.5.1&11.5.5.3
OK

High shear zone: 1.775 m to 2.911 m


Actual spacing of ties, s

= 175 mm

Design axial force, Nu

= -28.68 kNm

11.2&11.3

= 858.8 mm2/m

Shear force, Vu

= 76.61 kN

Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 69.94 kN

required (Av/s)

R11.5.7

= (Vu - Vc/fytd)

11.2&11.3

= (76610.21 - 0.85 69942.67/0.85 275 387.8)= 189.3 mm2/m

Av, min

= 0.062 fc'(bws/fyt) = 45.2 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

= 55.7 mm2

= 142.0 mm2

area of links provided (2#10), Av


Maximum spacing of ties

= 194 mm11.5.5.1&11.5.5.3
OK

Member M7 Span 2

Detailed ACI Design Requirements

Section Property: 250 x 449


Span Length
Width
Covers:

= 1.113

= 250 mmDepth

Rectangular section
= 450 mm

Top = 40 mm Bottom = 40 mm Side = 40 mm

Member M7 Span 2

Detailed ACI Main Reinforcement

Sagging: at 2.912 m from the start of the member


Moment applied to section

= 139.62 kNm

Effective depth of tension reinforcement

= 368 mm

Depth to compression reinforcement

d'

= 62 mm

Limit for compression steel

Rnt

= 4.78

Rn

= (Mu/bd2)

= 4.59

As

= (M/fy z)

= 1808.6 mm2

Tension Bars provided

= 3#25 2#25

Actual area of tension reinforcement

= 2550 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 2.77 %

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)
Largest actual space between tension bars

= 458.18 mm
= 63 mm

Actual neutral axis depth in section

= 184.87 mm

Moment capacity of section

= 182.44 kNm
OK

Member M7 Span 2

Detailed ACI Span / Depth Check

Basic span / depth ratio


Strength modification factor

= 21.00
= 0.4 + fy / 700

Hence, modified span / depth ratio


Actual span / depth ratio
OK

Member M7 Span 2

9.5.2.1
= 0.79
= 16.65

= 2.47

10.6.4

Detailed ACI Shear Reinforcement

High shear zone: 2.911 m to 4.024 m


Actual spacing of ties, s

= 175 mm

Design axial force, Nu

= -24.09 kNm

Shear force, Vu

= 76.76 kN

Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 70.84 kN

required (Av/s)

R11.5.7

= (Vu - Vc/fytd)

11.2&11.3

= (76761.79 - 0.85 70836.63/0.85 275 387.8)= 182.6 mm2/m

Av, min

= 0.062 fc'(bws/fyt) = 45.2 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

= 55.7 mm2

area of links provided (2#10), Av


Maximum spacing of ties

= 194 mm11.5.5.1&11.5.5.3
OK

Member M7 Span 3

Detailed ACI Design Requirements

Section Property: 250 x 449


Span Length
Width
Covers:

= 1.800

= 250 mmDepth

Rectangular section
= 450 mm

Top = 40 mm Bottom = 40 mm Side = 40 mm

Member M7 Span 3

Detailed ACI Main Reinforcement

= 142.0 mm2

Sagging: at 4.025 m from the start of the member


Moment applied to section

= 82.62 kNm

Effective depth of tension reinforcement

= 388 mm

Depth to compression reinforcement

d'

= 62 mm

Limit for compression steel

Rnt

= 4.78

Rn

= (Mu/bd2)

= 2.44

As

= (M/fy z)

= 929.4 mm2

Tension Bars provided

= 2#25

Actual area of tension reinforcement

= 1020 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 1.05 %

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 100 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)

= 458.18 mm

Largest actual space between tension bars

= 126 mm

Actual neutral axis depth in section

= 73.95 mm

Moment capacity of section

= 89.97 kNm
OK

Hogging: at 5.625 m from the start of the member


Moment applied to section

= 221.44 kNm

Effective depth of tension reinforcement

= 388 mm

Depth to compression reinforcement

d'

= 87 mm

Limit for compression steel


Rn

= (Mu/bd2)

Rnt

= 4.78

= 6.54

Rn > Rnthence compression steel required.


As'

= (M'n/Eu(1 - d'/c) (d - d'))

= 920.8 mm2

10.6.4

Tension Bars provided

= 2#25

Actual area of tension reinforcement

= 1020 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 1.05 %

Compression Bars provided

= 3#25 3#25
= 3060 mm2

Actual area of compression reinforcement


Actual % of compression reinforcement

= 3.16 %

Minimum horizontal distance between top bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between top bars

= 100 mm

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)
Largest actual space between tension bars

= 458.18 mm
= 126 mm

Actual neutral axis depth in section

= 85.38 mm

Moment capacity of section

= 90.73 kNm
NOT OK

Member M7 Span 3

Detailed ACI Span / Depth Check

Basic span / depth ratio


Strength modification factor

= 21.00
= 0.4 + fy / 700

Hence, modified span / depth ratio


Actual span / depth ratio

9.5.2.1
= 0.79
= 16.65

= 4.00

10.6.4

OK

Member M7 Span 3

Detailed ACI Shear Reinforcement

High shear zone: 4.024 m to 5.625 m


Actual spacing of ties, s

= 80 mm

Design axial force, Nu

= -20.53 kNm

Shear force, Vu

= 204.94 kN

Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 71.53 kN

required (Av/s)

R11.5.7

= (Vu - Vc/fytd)

= (204937.07 - 0.85 71531.24/0.85 275 387.8)

Av, min

= 0.062 fc'(bws/fyt) = 20.7 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

= 25.5 mm2

area of links provided (2#10), Av


Maximum spacing of ties

= 97 mm 11.5.5.1&11.5.5.3
OK

Member M7 Span 4

Detailed ACI Design Requirements

Section Property: 250 x 449


Span Length
Width
Covers:

= 1.800

= 250 mmDepth

= 142.0 mm2

Rectangular section
= 450 mm

Top = 40 mm Bottom = 40 mm Side = 40 mm

11.2&11.3

= 1590.1 mm2/m

Member M7 Span 4

Detailed ACI Main Reinforcement

Hogging: at 6.025 m from the start of the member


Moment applied to section

= 189.76 kNm

Effective depth of tension reinforcement

= 388 mm

Depth to compression reinforcement

d'

= 87 mm

Limit for compression steel


Rn

= (Mu/bd2)

Rnt

= 4.78

= 5.61

Rn > Rnthence compression steel required.


As'

= (M'n/Eu(1 - d'/c) (d - d'))

Tension Bars provided

= 431.3 mm2
= 2#25

Actual area of tension reinforcement

= 1020 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 1.05 %

Compression Bars provided

= 3#25 3#25
= 3060 mm2

Actual area of compression reinforcement


Actual % of compression reinforcement

= 3.16 %

Minimum horizontal distance between top bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between top bars

= 100 mm

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)
Largest actual space between tension bars

Actual neutral axis depth in section

= 458.18 mm
= 126 mm

= 85.38 mm

10.6.4

Moment capacity of section

= 90.73 kNm
NOT OK

Sagging: at 7.625 m from the start of the member


Moment applied to section

= 89.32 kNm

Effective depth of tension reinforcement

= 388 mm

Depth to compression reinforcement

d'

= 62 mm

Limit for compression steel

Rnt

= 4.78

Rn

= (Mu/bd2)

= 2.64

As

= (M/fy z)

= 1012.0 mm2

Tension Bars provided

= 2#25

Actual area of tension reinforcement

= 1020 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 1.05 %

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 100 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)
Largest actual space between tension bars

= 458.18 mm
= 126 mm

Actual neutral axis depth in section

= 73.95 mm

Moment capacity of section

= 89.97 kNm
OK

Member M7 Span 4

Detailed ACI Span / Depth Check

10.6.4

Basic span / depth ratio


Strength modification factor

= 21.00
= 0.4 + fy / 700

Hence, modified span / depth ratio


Actual span / depth ratio

9.5.2.1
= 0.79
= 16.65

= 4.00

OK

Member M7 Span 4

Detailed ACI Shear Reinforcement

High shear zone: 6.025 m to 7.624 m


Actual spacing of ties, s

= 90 mm

Design axial force, Nu

= -24.92 kNm

Shear force, Vu

= 190.22 kN

Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 70.67 kN

required (Av/s)

R11.5.7

= (Vu - Vc/fytd)

= (190220.70 - 0.85 70674.86/0.85 275 387.8)

Av, min

= 0.062 fc'(bws/fyt) = 23.2 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

= 28.6 mm2

area of links provided (2#10), Av


Maximum spacing of ties

= 97 mm 11.5.5.1&11.5.5.3
OK

Member M7 Span 5

Detailed ACI Design Requirements

Section Property: 250 x 449


Span Length

= 1.200

= 142.0 mm2

Rectangular section

11.2&11.3

= 1435.7 mm2/m

Width
Covers:

= 250 mmDepth

= 450 mm

Top = 40 mm Bottom = 40 mm Side = 40 mm

Member M7 Span 5

Detailed ACI Main Reinforcement

Sagging: at 8.825 m from the start of the member


Moment applied to section

= 131.13 kNm

Effective depth of tension reinforcement

= 368 mm

Depth to compression reinforcement

d'

= 62 mm

Limit for compression steel

Rnt

= 4.78

Rn

= (Mu/bd2)

= 4.31

As

= (M/fy z)

= 1676.7 mm2

Tension Bars provided

= 3#25 2#25

Actual area of tension reinforcement

= 2550 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 2.77 %

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)
Largest actual space between tension bars

= 458.18 mm
= 63 mm

Actual neutral axis depth in section

= 184.87 mm

Moment capacity of section

= 182.44 kNm
OK

10.6.4

Member M7 Span 5

Detailed ACI Span / Depth Check

Basic span / depth ratio


Strength modification factor

= 21.00
= 0.4 + fy / 700

Hence, modified span / depth ratio


Actual span / depth ratio

9.5.2.1
= 0.79
= 16.65

= 2.67

OK

Member M7 Span 5

Detailed ACI Shear Reinforcement

Minimum links zone: 7.624 m to 7.849 m


Actual spacing of ties, s

= 150 mm

Design axial force, Nu

= -21.21 kNm

Shear force, Vu

= 59.44 kN

Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 71.40 kN

Vu Vc

only nominal ties required

11.1.1

Av, min

= 0.062 fc'(bws/fyt) = 38.7 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

= 47.7 mm2

= 142.0 mm2

area of links provided (2#10), Av


Maximum spacing of ties

= 194 mm11.5.5.1&11.5.5.3
OK

Minimum links zone: 7.849 m to 8.824 m


Actual spacing of ties, s

= 175 mm

11.2&11.3

Design axial force, Nu

= -21.21 kNm

Shear force, Vu

= 51.47 kN

Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 71.40 kN

Vu Vc

only nominal ties required

11.1.1

Av, min

= 0.062 fc'(bws/fyt) = 45.2 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

= 55.7 mm2

= 142.0 mm2

area of links provided (2#10), Av


Maximum spacing of ties

= 194 mm11.5.5.1&11.5.5.3
OK

Member M7 Span 6

Detailed ACI Design Requirements

Section Property: 250 x 449


Span Length
Width
Covers:

= 3.000

= 250 mmDepth

Rectangular section
= 450 mm

Top = 40 mm Bottom = 40 mm Side = 40 mm

Member M7 Span 6

Detailed ACI Main Reinforcement

Sagging: at 8.825 m from the start of the member


Moment applied to section

= 131.53 kNm

Effective depth of tension reinforcement

= 368 mm

Depth to compression reinforcement

d'

= 62 mm

Limit for compression steel

Rnt

= 4.78

11.2&11.3

Rn

= (Mu/bd2)

= 4.33

As

= (M/fy z)

= 1682.9 mm2

Tension Bars provided

= 3#25 2#25

Actual area of tension reinforcement

= 2550 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 2.77 %

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)

= 458.18 mm

Largest actual space between tension bars

= 63 mm

Actual neutral axis depth in section

= 184.87 mm

Moment capacity of section

= 182.44 kNm
OK

Hogging: at 11.625 m from the start of the member


Moment applied to section

= 187.62 kNm

Effective depth of tension reinforcement

= 388 mm

Depth to compression reinforcement

d'

= 87 mm

Limit for compression steel


Rn

= (Mu/bd2)

Rnt

= 4.78

= 5.54

Rn > Rnthence compression steel required.


As'

= (M'n/Eu(1 - d'/c) (d - d'))

Tension Bars provided

= 398.2 mm2
= 2#25

Actual area of tension reinforcement

= 1020 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 1.05 %

10.6.4

Compression Bars provided

= 3#25 3#25
= 3060 mm2

Actual area of compression reinforcement


Actual % of compression reinforcement

= 3.16 %

Minimum horizontal distance between top bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between top bars

= 100 mm

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)
Largest actual space between tension bars

= 458.18 mm
= 126 mm

Actual neutral axis depth in section

= 85.38 mm

Moment capacity of section

= 90.73 kNm
NOT OK

Member M7 Span 6

Detailed ACI Span / Depth Check

Basic span / depth ratio


Strength modification factor

= 21.00
= 0.4 + fy / 700

Hence, modified span / depth ratio


Actual span / depth ratio
OK

Member M7 Span 6

Detailed ACI Shear Reinforcement

9.5.2.1
= 0.79
= 16.65

= 6.67

10.6.4

High shear zone: 8.824 m to 9.466 m


Actual spacing of ties, s

= 175 mm

Design axial force, Nu

= -16.66 kNm

Shear force, Vu

= 78.01 kN

Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 72.28 kN

required (Av/s)

R11.5.7

= (Vu - Vc/fytd)

11.2&11.3

= (78010.42 - 0.85 72283.38/0.85 275 387.8)= 182.8 mm2/m

Av, min

= 0.062 fc'(bws/fyt) = 45.2 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

= 55.7 mm2

= 142.0 mm2

area of links provided (2#10), Av


Maximum spacing of ties

= 194 mm11.5.5.1&11.5.5.3
OK

High shear zone: 9.466 m to 11.625 m


Actual spacing of ties, s

= 90 mm

Design axial force, Nu

= -16.66 kNm

Shear force, Vu

= 160.17 kN

Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 72.28 kN

required (Av/s)

R11.5.7

= (Vu - Vc/fytd)

= (160173.56 - 0.85 72283.38/0.85 275 387.8)

Av, min

= 0.062 fc'(bws/fyt) = 23.2 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

area of links provided (2#10), Av


Maximum spacing of ties

= 28.6 mm2

= 142.0 mm2
= 194 mm11.5.5.1&11.5.5.3

OK

11.2&11.3

= 1089.2 mm2/m

Member M7 Span 7

Detailed ACI Design Requirements

Section Property: 250 x 449


Span Length
Width
Covers:

= 3.000

= 250 mmDepth

Rectangular section
= 450 mm

Top = 40 mm Bottom = 40 mm Side = 40 mm

Member M7 Span 7

Detailed ACI Main Reinforcement

Hogging: at 12.025 m from the start of the member


Moment applied to section

= 163.03 kNm

Effective depth of tension reinforcement

= 388 mm

Depth to compression reinforcement

d'

= 87 mm

Limit for compression steel


Rn

= (Mu/bd2)

Rnt

= 4.78

= 4.82

Rn > Rnthence compression steel required.


As'

= (M'n/Eu(1 - d'/c) (d - d'))

Tension Bars provided

= 18.4 mm2
= 2#25

Actual area of tension reinforcement

= 1020 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 1.05 %

Compression Bars provided

= 3#25 3#25
= 3060 mm2

Actual area of compression reinforcement


Actual % of compression reinforcement

= 3.16 %

Minimum horizontal distance between top bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between top bars

= 100 mm

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)

= 458.18 mm

Largest actual space between tension bars

10.6.4

= 126 mm

Actual neutral axis depth in section

= 85.38 mm

Moment capacity of section

= 90.73 kNm
NOT OK

Sagging: at 14.825 m from the start of the member


Moment applied to section

= 132.08 kNm

Effective depth of tension reinforcement

= 368 mm

Depth to compression reinforcement

d'

= 62 mm

Limit for compression steel

Rnt

= 4.78

Rn

= (Mu/bd2)

= 4.34

As

= (M/fy z)

= 1691.3 mm2

Tension Bars provided

= 3#25 2#25

Actual area of tension reinforcement

= 2550 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 2.77 %

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)
Largest actual space between tension bars

= 458.18 mm
= 63 mm

10.6.4

Actual neutral axis depth in section

= 184.87 mm

Moment capacity of section

= 182.44 kNm
OK

Member M7 Span 7

Detailed ACI Span / Depth Check

Basic span / depth ratio


Strength modification factor

= 21.00
= 0.4 + fy / 700

Hence, modified span / depth ratio


Actual span / depth ratio

9.5.2.1
= 0.79
= 16.65

= 6.67

OK

Member M7 Span 7

Detailed ACI Shear Reinforcement

High shear zone: 12.025 m to 13.900 m


Actual spacing of ties, s

= 90 mm

Design axial force, Nu

= -21.11 kNm

Shear force, Vu

= 151.34 kN

Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 71.42 kN

required (Av/s)

R11.5.7

= (Vu - Vc/fytd)

= (151338.93 - 0.85 71417.44/0.85 275 387.8)

Av, min

= 0.062 fc'(bws/fyt) = 23.2 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

= 28.6 mm2

11.2&11.3

= 999.8 mm2/m

= 142.0 mm2

area of links provided (2#10), Av


Maximum spacing of ties

= 194 mm11.5.5.1&11.5.5.3
OK

High shear zone: 13.900 m to 14.824 m


Actual spacing of ties, s

= 175 mm

Design axial force, Nu

= -21.11 kNm

Shear force, Vu

= 79.75 kN

Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 71.42 kN

required (Av/s)

R11.5.7

= (Vu - Vc/fytd)

11.2&11.3

= (79751.27 - 0.85 71417.44/0.85 275 387.8)= 210.1 mm2/m

Av, min

= 0.062 fc'(bws/fyt) = 45.2 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

= 55.7 mm2

area of links provided (2#10), Av


Maximum spacing of ties

= 194 mm11.5.5.1&11.5.5.3
OK

Member M7 Span 8

Detailed ACI Design Requirements

Section Property: 250 x 449


Span Length
Width
Covers:

= 1.200

= 250 mmDepth

Rectangular section
= 450 mm

Top = 40 mm Bottom = 40 mm Side = 40 mm

Member M7 Span 8

= 142.0 mm2

Detailed ACI Main Reinforcement

Sagging: at 14.825 m from the start of the member


Moment applied to section

= 131.70 kNm

Effective depth of tension reinforcement

= 368 mm

Depth to compression reinforcement

d'

= 62 mm

Limit for compression steel

Rnt

= 4.78

Rn

= (Mu/bd2)

= 4.33

As

= (M/fy z)

= 1685.5 mm2

Tension Bars provided

= 3#25 2#25

Actual area of tension reinforcement

= 2550 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 2.77 %

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)
Largest actual space between tension bars

= 458.18 mm
= 63 mm

Actual neutral axis depth in section

= 184.87 mm

Moment capacity of section

= 182.44 kNm
OK

Member M7 Span 8

Detailed ACI Span / Depth Check

10.6.4

Basic span / depth ratio


Strength modification factor

= 21.00
= 0.4 + fy / 700

Hence, modified span / depth ratio


Actual span / depth ratio

9.5.2.1
= 0.79
= 16.65

= 2.67

OK

Member M7 Span 8

Detailed ACI Shear Reinforcement

High shear zone: 14.824 m to 16.024 m


Actual spacing of ties, s

= 175 mm

Design axial force, Nu

= -16.71 kNm

Shear force, Vu

= 69.26 kN

Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 72.27 kN

required (Av/s)

R11.5.7

= (Vu - Vc/fytd)

11.2&11.3

= (69261.64 - 0.85 72274.36/0.85 275 387.8)= 86.4 mm2/m

Av, min

= 0.062 fc'(bws/fyt) = 45.2 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

= 55.7 mm2

area of links provided (2#10), Av


Maximum spacing of ties

= 194 mm11.5.5.1&11.5.5.3
OK

Member M7 Span 9

Detailed ACI Design Requirements

Section Property: 250 x 449


Span Length

= 1.800

= 142.0 mm2

Rectangular section

Width
Covers:

= 250 mmDepth

= 450 mm

Top = 40 mm Bottom = 40 mm Side = 40 mm

Member M7 Span 9

Detailed ACI Main Reinforcement

Sagging: at 16.025 m from the start of the member


Moment applied to section

= 80.49 kNm

Effective depth of tension reinforcement

= 388 mm

Depth to compression reinforcement

d'

= 62 mm

Limit for compression steel

Rnt

= 4.78

Rn

= (Mu/bd2)

= 2.38

As

= (M/fy z)

= 903.5 mm2

Tension Bars provided

= 2#25

Actual area of tension reinforcement

= 1020 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 1.05 %

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 100 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)
Largest actual space between tension bars

= 458.18 mm
= 126 mm

Actual neutral axis depth in section

= 73.95 mm

Moment capacity of section

= 89.97 kNm
OK

10.6.4

Hogging: at 17.625 m from the start of the member


Moment applied to section

= 213.18 kNm

Effective depth of tension reinforcement

= 388 mm

Depth to compression reinforcement

d'

= 87 mm

Limit for compression steel


Rn

Rnt

= (Mu/bd2)

= 4.78

= 6.30

Rn > Rnthence compression steel required.


As'

= 793.2 mm2

= (M'n/Eu(1 - d'/c) (d - d'))

Tension Bars provided

= 2#25

Actual area of tension reinforcement

= 1020 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 1.05 %

Compression Bars provided

= 3#25 3#25
= 3060 mm2

Actual area of compression reinforcement


Actual % of compression reinforcement

= 3.16 %

Minimum horizontal distance between top bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between top bars

= 100 mm

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)
Largest actual space between tension bars

= 458.18 mm
= 126 mm

Actual neutral axis depth in section

= 85.38 mm

Moment capacity of section

= 90.73 kNm
NOT OK

10.6.4

Member M7 Span 9

Detailed ACI Span / Depth Check

Basic span / depth ratio


Strength modification factor

= 21.00
= 0.4 + fy / 700

Hence, modified span / depth ratio


Actual span / depth ratio

9.5.2.1
= 0.79
= 16.65

= 4.00

OK

Member M7 Span 9

Detailed ACI Shear Reinforcement

High shear zone: 16.024 m to 17.625 m


Actual spacing of ties, s

= 90 mm

Design axial force, Nu

= -12.86 kNm

Shear force, Vu

= 198.18 kN

Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 73.02 kN

required (Av/s)

R11.5.7

= (Vu - Vc/fytd)

= (198182.20 - 0.85 73022.98/0.85 275 387.8)

Av, min

= 0.062 fc'(bws/fyt) = 23.2 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

area of links provided (2#10), Av


Maximum spacing of ties

= 142.0 mm2
= 97 mm 11.5.5.1&11.5.5.3

OK

Member M7 Span 10

= 28.6 mm2

11.2&11.3

= 1501.5 mm2/m

Detailed ACI Design Requirements

Section Property: 250 x 449


Span Length
Width
Covers:

= 1.800

= 250 mmDepth

Rectangular section
= 450 mm

Top = 40 mm Bottom = 40 mm Side = 40 mm

Member M7 Span 10

Detailed ACI Main Reinforcement

Hogging: at 18.025 m from the start of the member


Moment applied to section

= 190.32 kNm

Effective depth of tension reinforcement

= 388 mm

Depth to compression reinforcement

d'

= 87 mm

Limit for compression steel


Rn

= (Mu/bd2)

Rnt

= 4.78

= 5.62

Rn > Rnthence compression steel required.


As'

= (M'n/Eu(1 - d'/c) (d - d'))

Tension Bars provided

= 440.1 mm2
= 2#25

Actual area of tension reinforcement

= 1020 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 1.05 %

Compression Bars provided

= 3#25 3#25
= 3060 mm2

Actual area of compression reinforcement


Actual % of compression reinforcement

Minimum horizontal distance between top bars

= 3.16 %

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between top bars

= 100 mm

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)

= 458.18 mm

Largest actual space between tension bars

10.6.4

= 126 mm

Actual neutral axis depth in section

= 85.38 mm

Moment capacity of section

= 90.73 kNm
NOT OK

Sagging: at 19.625 m from the start of the member


Moment applied to section

= 91.78 kNm

Effective depth of tension reinforcement

= 388 mm

Depth to compression reinforcement

d'

= 62 mm

Limit for compression steel

Rnt

= 4.78

Rn

= (Mu/bd2)

= 2.71

As

= (M/fy z)

= 1042.6 mm2

Tension Bars provided

= 3#25

Actual area of tension reinforcement

= 1530 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 1.58 %

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)
Largest actual space between tension bars

= 458.18 mm
= 63 mm

10.6.4

Actual neutral axis depth in section

= 110.92 mm

Moment capacity of section

= 129.00 kNm
OK

Member M7 Span 10

Detailed ACI Span / Depth Check

Basic span / depth ratio


Strength modification factor

= 21.00
= 0.4 + fy / 700

Hence, modified span / depth ratio


Actual span / depth ratio

9.5.2.1
= 0.79
= 16.65

= 4.00

OK

Member M7 Span 10

Detailed ACI Shear Reinforcement

High shear zone: 18.025 m to 19.624 m


Actual spacing of ties, s

= 90 mm

Design axial force, Nu

= -19.51 kNm

Shear force, Vu

= 192.04 kN

Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 71.73 kN

required (Av/s)

R11.5.7

= (Vu - Vc/fytd)

= (192036.98 - 0.85 71729.37/0.85 275 387.8)

Av, min

= 0.062 fc'(bws/fyt) = 23.2 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

= 28.6 mm2

11.2&11.3

= 1445.9 mm2/m

= 142.0 mm2

area of links provided (2#10), Av


Maximum spacing of ties

= 97 mm 11.5.5.1&11.5.5.3
OK

Member M7 Span 11

Detailed ACI Design Requirements

Section Property: 250 x 449


Span Length
Width
Covers:

= 1.112

= 250 mmDepth

Rectangular section
= 450 mm

Top = 40 mm Bottom = 40 mm Side = 40 mm

Member M7 Span 11

Detailed ACI Main Reinforcement

Sagging: at 20.737 m from the start of the member


Moment applied to section

= 134.78 kNm

Effective depth of tension reinforcement

= 368 mm

Depth to compression reinforcement

d'

= 62 mm

Limit for compression steel

Rnt

= 4.78

Rn

= (Mu/bd2)

= 4.43

As

= (M/fy z)

= 1732.9 mm2

Tension Bars provided

= 3#25 2#25

Actual area of tension reinforcement

= 2550 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 2.77 %

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)

= 458.18 mm

Largest actual space between tension bars

= 63 mm

Actual neutral axis depth in section

= 184.87 mm

Moment capacity of section

= 182.44 kNm
OK

Member M7 Span 11

Detailed ACI Span / Depth Check

Basic span / depth ratio


Strength modification factor

= 21.00
= 0.4 + fy / 700

Hence, modified span / depth ratio


Actual span / depth ratio

9.5.2.1
= 0.79
= 16.65

= 2.47

OK

Member M7 Span 11

Detailed ACI Shear Reinforcement

High shear zone: 19.624 m to 19.850 m


Actual spacing of ties, s

= 150 mm

Design axial force, Nu

= -15.71 kNm

Shear force, Vu

= 61.73 kN

Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 72.47 kN

required (Av/s)

R11.5.7

= (Vu - Vc/fytd)

11.2&11.3

10.6.4

= (61725.31 - 0.85 72468.92/0.85 275 387.8)= 1.4 mm2/m

Av, min

= 0.062 fc'(bws/fyt) = 38.7 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

= 47.7 mm2

= 142.0 mm2

area of links provided (2#10), Av


Maximum spacing of ties

= 194 mm11.5.5.1&11.5.5.3
OK

Minimum links zone: 19.850 m to 20.736 m


Actual spacing of ties, s

= 175 mm

Design axial force, Nu

= -15.71 kNm

Shear force, Vu

= 54.56 kN

Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 72.47 kN

Vu Vc

only nominal ties required

11.1.1

Av, min

= 0.062 fc'(bws/fyt) = 45.2 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

= 55.7 mm2

area of links provided (2#10), Av


Maximum spacing of ties

= 194 mm11.5.5.1&11.5.5.3
OK

Member M7 Span 12

Detailed ACI Design Requirements

Section Property: 250 x 449


Span Length
Width
Covers:

= 2.913

= 250 mmDepth

= 142.0 mm2

Rectangular section
= 450 mm

Top = 40 mm Bottom = 40 mm Side = 40 mm

11.2&11.3

Member M7 Span 12

Detailed ACI Main Reinforcement

Sagging: at 20.737 m from the start of the member


Moment applied to section

= 135.09 kNm

Effective depth of tension reinforcement

= 368 mm

Depth to compression reinforcement

d'

= 62 mm

Limit for compression steel

Rnt

= 4.78

Rn

= (Mu/bd2)

= 4.44

As

= (M/fy z)

= 1737.7 mm2

Tension Bars provided

= 3#25 2#25

Actual area of tension reinforcement

= 2550 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 2.77 %

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)

= 458.18 mm

Largest actual space between tension bars

= 63 mm

Actual neutral axis depth in section

= 184.87 mm

Moment capacity of section

= 182.44 kNm
OK

Hogging: at 23.450 m from the start of the member


Moment applied to section

= 150.52 kNm

10.6.4

Effective depth of tension reinforcement

= 388 mm

Depth to compression reinforcement

d'

= 87 mm

Limit for compression steel

Rnt

= 4.78

Rn

= (Mu/bd2)

= 4.45

As

= (M/fy z)

= 1836.2 mm2

Tension Bars provided

= 2#25

Actual area of tension reinforcement

= 1020 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 1.05 %

Minimum horizontal distance between top bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between top bars

= 100 mm

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)
Largest actual space between tension bars

= 458.18 mm
= 126 mm

Actual neutral axis depth in section

= 85.38 mm

Moment capacity of section

= 90.73 kNm
NOT OK

Member M7 Span 12

Detailed ACI Span / Depth Check

Basic span / depth ratio


Strength modification factor

= 21.00
= 0.4 + fy / 700

Hence, modified span / depth ratio

9.5.2.1
= 0.79
= 16.65

10.6.4

Actual span / depth ratio

= 6.47

OK

Member M7 Span 12

Detailed ACI Shear Reinforcement

High shear zone: 20.736 m to 21.616 m


Actual spacing of ties, s

= 175 mm

Design axial force, Nu

= -11.46 kNm

Shear force, Vu

= 79.68 kN

Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 73.30 kN

required (Av/s)

R11.5.7

= (Vu - Vc/fytd)

11.2&11.3

= (79679.75 - 0.85 73296.30/0.85 275 387.8)= 191.7 mm2/m

Av, min

= 0.062 fc'(bws/fyt) = 45.2 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

= 55.7 mm2

= 142.0 mm2

area of links provided (2#10), Av


Maximum spacing of ties

= 194 mm11.5.5.1&11.5.5.3
OK

High shear zone: 21.616 m to 23.450 m


Actual spacing of ties, s

= 90 mm

Design axial force, Nu

= -11.46 kNm

Shear force, Vu

= 149.39 kN

Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 73.30 kN

required (Av/s)

R11.5.7

= (Vu - Vc/fytd)

= (149390.15 - 0.85 73296.30/0.85 275 387.8)

Av, min

= 0.062 fc'(bws/fyt) = 23.2 mm2

(11-13)

11.2&11.3

= 960.7 mm2/m

(0.35 bws) / fyt

= 28.6 mm2

= 142.0 mm2

area of links provided (2#10), Av


Maximum spacing of ties

11.5.6.3

= 194 mm11.5.5.1&11.5.5.3
OK

Member M7 Span 13

Detailed ACI Design Requirements

Section Property: 250 x 449


Span Length
Width
Covers:

= 3.350

= 250 mmDepth

Rectangular section
= 450 mm

Top = 40 mm Bottom = 40 mm Side = 40 mm

Member M7 Span 13

Detailed ACI Main Reinforcement

Hogging: at 23.850 m from the start of the member


Moment applied to section

= 41.07 kNm

Effective depth of tension reinforcement

= 388 mm

Depth to compression reinforcement

d'

= 62 mm

Limit for compression steel

Rnt

= 4.78

Rn

= (Mu/bd2)

= 1.21

As

= (M/fy z)

= 443.5 mm2

Tension Bars provided

= 2#25

Actual area of tension reinforcement

= 1020 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 1.05 %

Minimum horizontal distance between top bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between top bars

= 100 mm

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 100 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)

= 458.18 mm

Largest actual space between tension bars

10.6.4

= 126 mm

Actual neutral axis depth in section

= 65.60 mm

Moment capacity of section

= 89.88 kNm
OK

Sagging: at 23.850 m from the start of the member


Moment applied to section

= 3.69 kNm

Effective depth of tension reinforcement

= 388 mm

Depth to compression reinforcement

d'

= 62 mm

Limit for compression steel

Rnt

= 4.78

Rn

= (Mu/bd2)

= 0.11

As

= (M/fy z)

= 38.6 mm2

Tension Bars provided

= 2#25

Actual area of tension reinforcement

= 1020 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 1.05 %

Minimum horizontal distance between top bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between top bars

= 100 mm

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 100 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)

= 458.18 mm

Largest actual space between tension bars

10.6.4

= 126 mm

Actual neutral axis depth in section

= 65.60 mm

Moment capacity of section

= 89.88 kNm
OK

Hogging: at 26.800 m from the start of the member


Moment applied to section

= 70.25 kNm

Effective depth of tension reinforcement

= 388 mm

Depth to compression reinforcement

d'

= 62 mm

Limit for compression steel

Rnt

= 4.78

Rn

= (Mu/bd2)

= 2.08

As

= (M/fy z)

= 780.2 mm2

Tension Bars provided

= 2#25

Actual area of tension reinforcement

= 1020 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 1.05 %

Minimum horizontal distance between top bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between top bars

= 100 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)
Largest actual space between tension bars

= 458.18 mm
= 126 mm

Actual neutral axis depth in section

= 73.95 mm

Moment capacity of section

= 89.97 kNm
OK

10.6.4

Member M7 Span 13

Detailed ACI Span / Depth Check

Basic span / depth ratio


Strength modification factor

= 21.00
= 0.4 + fy / 700

Hence, modified span / depth ratio


Actual span / depth ratio

9.5.2.1
= 0.79
= 16.65

= 7.44

OK

Member M7 Span 13

Detailed ACI Shear Reinforcement

Minimum links zone: 23.850 m to 26.800 m


Actual spacing of ties, s

= 175 mm

Design axial force, Nu

= 5.74 kNm

Shear force, Vu

= 50.20 kN

Vc = 0.17 [1 + (Nu/14 Ag)] fc' bw d

= 75.80 kN

Vu Vc

only nominal ties required

11.1.1

Av, min

= 0.062 fc'(bws/fyt) = 45.2 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

area of links provided (2#10), Av


Maximum spacing of ties

= 142.0 mm2
= 194 mm11.5.5.1&11.5.5.3

OK

Member M7 Span 14

= 55.7 mm2

11.2&11.3

Detailed ACI Design Requirements

Section Property: 250 x 449


Span Length
Width
Covers:

= 2.913

= 250 mmDepth

Rectangular section
= 450 mm

Top = 40 mm Bottom = 40 mm Side = 40 mm

Member M7 Span 14

Detailed ACI Main Reinforcement

Hogging: at 27.200 m from the start of the member


Moment applied to section

= 129.98 kNm

Effective depth of tension reinforcement

= 388 mm

Depth to compression reinforcement

d'

= 87 mm

Limit for compression steel

Rnt

= 4.78

Rn

= (Mu/bd2)

= 3.84

As

= (M/fy z)

= 1543.5 mm2

Tension Bars provided

= 2#25

Actual area of tension reinforcement

= 1020 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 1.05 %

Minimum horizontal distance between top bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between top bars

= 100 mm

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)

= 458.18 mm

10.6.4

Largest actual space between tension bars

= 126 mm

Actual neutral axis depth in section

= 85.38 mm

Moment capacity of section

= 90.73 kNm
NOT OK

Sagging: at 29.913 m from the start of the member


Moment applied to section

= 133.79 kNm

Effective depth of tension reinforcement

= 368 mm

Depth to compression reinforcement

d'

= 62 mm

Limit for compression steel

Rnt

= 4.78

Rn

= (Mu/bd2)

= 4.40

As

= (M/fy z)

= 1717.7 mm2

Tension Bars provided

= 3#25 2#25

Actual area of tension reinforcement

= 2550 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 2.77 %

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)
Largest actual space between tension bars

= 458.18 mm
= 63 mm

Actual neutral axis depth in section

= 184.87 mm

Moment capacity of section

= 182.44 kNm
OK

Member M7 Span 14

10.6.4

Detailed ACI Span / Depth Check

Basic span / depth ratio


Strength modification factor

= 21.00
= 0.4 + fy / 700

Hence, modified span / depth ratio


Actual span / depth ratio

9.5.2.1
= 0.79
= 16.65

= 6.47

OK

Member M7 Span 14

Detailed ACI Shear Reinforcement

High shear zone: 27.200 m to 29.075 m


Actual spacing of ties, s

= 150 mm

Design axial force, Nu

= -21.04 kNm

Shear force, Vu

= 141.34 kN

Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 71.43 kN

required (Av/s)

R11.5.7

= (Vu - Vc/fytd)

= (141337.91 - 0.85 71430.55/0.85 275 387.8)

Av, min

= 0.062 fc'(bws/fyt) = 38.7 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

= 47.7 mm2

= 142.0 mm2

area of links provided (2#10), Av


Maximum spacing of ties

= 194 mm11.5.5.1&11.5.5.3
OK

High shear zone: 29.075 m to 29.912 m


Actual spacing of ties, s

= 175 mm

Design axial force, Nu

= -21.04 kNm

11.2&11.3

= 889.4 mm2/m

Shear force, Vu

= 71.63 kN

Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 71.43 kN

required (Av/s)

R11.5.7

= (Vu - Vc/fytd)

11.2&11.3

= (71627.55 - 0.85 71430.55/0.85 275 387.8)= 120.4 mm2/m

Av, min

= 0.062 fc'(bws/fyt) = 45.2 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

= 55.7 mm2

= 142.0 mm2

area of links provided (2#10), Av


Maximum spacing of ties

= 194 mm11.5.5.1&11.5.5.3
OK

Member M7 Span 15

Detailed ACI Design Requirements

Section Property: 250 x 449


Span Length
Width
Covers:

= 1.112

= 250 mmDepth

Rectangular section
= 450 mm

Top = 40 mm Bottom = 40 mm Side = 40 mm

Member M7 Span 15

Detailed ACI Main Reinforcement

Sagging: at 29.913 m from the start of the member


Moment applied to section

= 133.41 kNm

Effective depth of tension reinforcement

= 368 mm

Depth to compression reinforcement

d'

= 62 mm

Limit for compression steel

Rnt

= 4.78

Rn

= (Mu/bd2)

= 4.39

As

= (M/fy z)

= 1711.8 mm2

Tension Bars provided

= 3#25 2#25

Actual area of tension reinforcement

= 2550 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 2.77 %

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)
Largest actual space between tension bars

= 458.18 mm
= 63 mm

Actual neutral axis depth in section

= 184.87 mm

Moment capacity of section

= 182.44 kNm
OK

Member M7 Span 15

Detailed ACI Span / Depth Check

Basic span / depth ratio


Strength modification factor

= 21.00
= 0.4 + fy / 700

Hence, modified span / depth ratio


Actual span / depth ratio
OK

Member M7 Span 15

9.5.2.1
= 0.79
= 16.65

= 2.47

10.6.4

Detailed ACI Shear Reinforcement

High shear zone: 29.912 m to 31.024 m


Actual spacing of ties, s

= 175 mm

Design axial force, Nu

= -16.72 kNm

Shear force, Vu

= 70.79 kN

Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 72.27 kN

required (Av/s)

R11.5.7

= (Vu - Vc/fytd)

11.2&11.3

= (70792.53 - 0.85 72272.41/0.85 275 387.8)= 103.3 mm2/m

Av, min

= 0.062 fc'(bws/fyt) = 45.2 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

= 55.7 mm2

area of links provided (2#10), Av


Maximum spacing of ties

= 194 mm11.5.5.1&11.5.5.3
OK

Member M7 Span 16

Detailed ACI Design Requirements

Section Property: 250 x 449


Span Length
Width
Covers:

= 1.800

= 250 mmDepth

Rectangular section
= 450 mm

Top = 40 mm Bottom = 40 mm Side = 40 mm

Member M7 Span 16

Detailed ACI Main Reinforcement

= 142.0 mm2

Sagging: at 31.025 m from the start of the member


Moment applied to section

= 83.08 kNm

Effective depth of tension reinforcement

= 388 mm

Depth to compression reinforcement

d'

= 62 mm

Limit for compression steel

Rnt

= 4.78

Rn

= (Mu/bd2)

= 2.46

As

= (M/fy z)

= 935.0 mm2

Tension Bars provided

= 2#25

Actual area of tension reinforcement

= 1020 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 1.05 %

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 100 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)

= 458.18 mm

Largest actual space between tension bars

= 126 mm

Actual neutral axis depth in section

= 73.95 mm

Moment capacity of section

= 89.97 kNm
OK

Hogging: at 32.625 m from the start of the member


Moment applied to section

= 212.02 kNm

Effective depth of tension reinforcement

= 388 mm

Depth to compression reinforcement

d'

= 87 mm

Limit for compression steel


Rn

= (Mu/bd2)

Rnt

= 4.78

= 6.27

Rn > Rnthence compression steel required.


As'

= (M'n/Eu(1 - d'/c) (d - d'))

= 775.3 mm2

10.6.4

Tension Bars provided

= 2#25

Actual area of tension reinforcement

= 1020 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 1.05 %

Compression Bars provided

= 3#25 3#25
= 3060 mm2

Actual area of compression reinforcement


Actual % of compression reinforcement

= 3.16 %

Minimum horizontal distance between top bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between top bars

= 100 mm

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)
Largest actual space between tension bars

= 458.18 mm
= 126 mm

Actual neutral axis depth in section

= 85.38 mm

Moment capacity of section

= 90.73 kNm
NOT OK

Member M7 Span 16

Detailed ACI Span / Depth Check

Basic span / depth ratio


Strength modification factor

= 21.00
= 0.4 + fy / 700

Hence, modified span / depth ratio


Actual span / depth ratio

9.5.2.1
= 0.79
= 16.65

= 4.00

10.6.4

OK

Member M7 Span 16

Detailed ACI Shear Reinforcement

High shear zone: 31.024 m to 32.625 m


Actual spacing of ties, s

= 90 mm

Design axial force, Nu

= -13.05 kNm

Shear force, Vu

= 199.26 kN

Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 72.99 kN

required (Av/s)

R11.5.7

= (Vu - Vc/fytd)

= (199255.28 - 0.85 72986.08/0.85 275 387.8)

Av, min

= 0.062 fc'(bws/fyt) = 23.2 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

= 28.6 mm2

area of links provided (2#10), Av


Maximum spacing of ties

= 97 mm 11.5.5.1&11.5.5.3
OK

Member M7 Span 17

Detailed ACI Design Requirements

Section Property: 250 x 449


Span Length
Width
Covers:

= 1.800

= 250 mmDepth

= 142.0 mm2

Rectangular section
= 450 mm

Top = 40 mm Bottom = 40 mm Side = 40 mm

11.2&11.3

= 1513.7 mm2/m

Member M7 Span 17

Detailed ACI Main Reinforcement

Hogging: at 33.025 m from the start of the member


Moment applied to section

= 191.31 kNm

Effective depth of tension reinforcement

= 388 mm

Depth to compression reinforcement

d'

= 87 mm

Limit for compression steel


Rn

= (Mu/bd2)

Rnt

= 4.78

= 5.65

Rn > Rnthence compression steel required.


As'

= (M'n/Eu(1 - d'/c) (d - d'))

Tension Bars provided

= 455.2 mm2
= 2#25

Actual area of tension reinforcement

= 1020 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 1.05 %

Compression Bars provided

= 3#25 3#25
= 3060 mm2

Actual area of compression reinforcement


Actual % of compression reinforcement

= 3.16 %

Minimum horizontal distance between top bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between top bars

= 100 mm

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)
Largest actual space between tension bars

Actual neutral axis depth in section

= 458.18 mm
= 126 mm

= 85.38 mm

10.6.4

Moment capacity of section

= 90.73 kNm
NOT OK

Sagging: at 34.625 m from the start of the member


Moment applied to section

= 89.32 kNm

Effective depth of tension reinforcement

= 388 mm

Depth to compression reinforcement

d'

= 62 mm

Limit for compression steel

Rnt

= 4.78

Rn

= (Mu/bd2)

= 2.64

As

= (M/fy z)

= 1011.9 mm2

Tension Bars provided

= 2#25

Actual area of tension reinforcement

= 1020 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 1.05 %

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 100 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)
Largest actual space between tension bars

= 458.18 mm
= 126 mm

Actual neutral axis depth in section

= 73.95 mm

Moment capacity of section

= 89.97 kNm
OK

Member M7 Span 17

Detailed ACI Span / Depth Check

10.6.4

Basic span / depth ratio


Strength modification factor

= 21.00
= 0.4 + fy / 700

Hence, modified span / depth ratio


Actual span / depth ratio

9.5.2.1
= 0.79
= 16.65

= 4.00

OK

Member M7 Span 17

Detailed ACI Shear Reinforcement

High shear zone: 33.025 m to 34.624 m


Actual spacing of ties, s

= 90 mm

Design axial force, Nu

= -25.19 kNm

Shear force, Vu

= 191.02 kN

Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 70.62 kN

required (Av/s)

R11.5.7

= (Vu - Vc/fytd)

= (191019.08 - 0.85 70623.53/0.85 275 387.8)

Av, min

= 0.062 fc'(bws/fyt) = 23.2 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

= 28.6 mm2

area of links provided (2#10), Av


Maximum spacing of ties

= 97 mm 11.5.5.1&11.5.5.3
OK

Member M7 Span 18

Detailed ACI Design Requirements

Section Property: 250 x 449


Span Length

= 1.200

= 142.0 mm2

Rectangular section

11.2&11.3

= 1445.0 mm2/m

Width
Covers:

= 250 mmDepth

= 450 mm

Top = 40 mm Bottom = 40 mm Side = 40 mm

Member M7 Span 18

Detailed ACI Main Reinforcement

Sagging: at 35.825 m from the start of the member


Moment applied to section

= 131.98 kNm

Effective depth of tension reinforcement

= 368 mm

Depth to compression reinforcement

d'

= 62 mm

Limit for compression steel

Rnt

= 4.78

Rn

= (Mu/bd2)

= 4.34

As

= (M/fy z)

= 1689.8 mm2

Tension Bars provided

= 3#25 2#25

Actual area of tension reinforcement

= 2550 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 2.77 %

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)
Largest actual space between tension bars

= 458.18 mm
= 63 mm

Actual neutral axis depth in section

= 184.87 mm

Moment capacity of section

= 182.44 kNm
OK

10.6.4

Member M7 Span 18

Detailed ACI Span / Depth Check

Basic span / depth ratio


Strength modification factor

= 21.00
= 0.4 + fy / 700

Hence, modified span / depth ratio


Actual span / depth ratio

9.5.2.1
= 0.79
= 16.65

= 2.67

OK

Member M7 Span 18

Detailed ACI Shear Reinforcement

High shear zone: 34.624 m to 34.849 m


Actual spacing of ties, s

= 150 mm

Design axial force, Nu

= -25.19 kNm

Shear force, Vu

= 145.26 kN

Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 70.62 kN

required (Av/s)

R11.5.7

= (Vu - Vc/fytd)

= (145257.46 - 0.85 70623.53/0.85 275 387.8)

Av, min

= 0.062 fc'(bws/fyt) = 38.7 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

area of links provided (2#10), Av


Maximum spacing of ties

= 47.7 mm2

= 142.0 mm2
= 194 mm11.5.5.1&11.5.5.3

OK

Minimum links zone: 34.849 m to 35.824 m

11.2&11.3

= 940.2 mm2/m

Actual spacing of ties, s

= 175 mm

Design axial force, Nu

= -21.39 kNm

Shear force, Vu

= 52.24 kN

Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 71.36 kN

Vu Vc

only nominal ties required

11.1.1

Av, min

= 0.062 fc'(bws/fyt) = 45.2 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

= 55.7 mm2

area of links provided (2#10), Av


Maximum spacing of ties

= 142.0 mm2
= 194 mm11.5.5.1&11.5.5.3

OK

Member M7 Span 19

Detailed ACI Design Requirements

Section Property: 250 x 449


Span Length
Width
Covers:

= 3.000

= 250 mmDepth

Rectangular section
= 450 mm

Top = 40 mm Bottom = 40 mm Side = 40 mm

Member M7 Span 19

Detailed ACI Main Reinforcement

Sagging: at 35.825 m from the start of the member


Moment applied to section

= 132.38 kNm

Effective depth of tension reinforcement

= 368 mm

Depth to compression reinforcement

d'

= 62 mm

11.2&11.3

Limit for compression steel

Rnt

= 4.78

Rn

= (Mu/bd2)

= 4.35

As

= (M/fy z)

= 1695.9 mm2

Tension Bars provided

= 3#25 2#25

Actual area of tension reinforcement

= 2550 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 2.77 %

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)

= 458.18 mm

Largest actual space between tension bars

= 63 mm

Actual neutral axis depth in section

= 184.87 mm

Moment capacity of section

= 182.44 kNm
OK

Hogging: at 38.625 m from the start of the member


Moment applied to section

= 185.18 kNm

Effective depth of tension reinforcement

= 388 mm

Depth to compression reinforcement

d'

= 87 mm

Limit for compression steel


Rn

= (Mu/bd2)

Rnt

= 4.78

= 5.47

Rn > Rnthence compression steel required.


As'

= (M'n/Eu(1 - d'/c) (d - d'))

Tension Bars provided

= 360.6 mm2
= 2#25

Actual area of tension reinforcement

= 1020 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 1.05 %

10.6.4

Compression Bars provided

= 3#25 3#25
= 3060 mm2

Actual area of compression reinforcement


Actual % of compression reinforcement

= 3.16 %

Minimum horizontal distance between top bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between top bars

= 100 mm

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)
Largest actual space between tension bars

= 458.18 mm
= 126 mm

Actual neutral axis depth in section

= 85.38 mm

Moment capacity of section

= 90.73 kNm
NOT OK

Member M7 Span 19

Detailed ACI Span / Depth Check

Basic span / depth ratio


Strength modification factor

= 21.00
= 0.4 + fy / 700

Hence, modified span / depth ratio


Actual span / depth ratio
OK

Member M7 Span 19

9.5.2.1
= 0.79
= 16.65

= 6.67

10.6.4

Detailed ACI Shear Reinforcement

High shear zone: 35.824 m to 36.465 m


Actual spacing of ties, s

= 175 mm

Design axial force, Nu

= -17.09 kNm

Shear force, Vu

= 77.44 kN

Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 72.20 kN

required (Av/s)

R11.5.7

= (Vu - Vc/fytd)

11.2&11.3

= (77444.53 - 0.85 72200.68/0.85 275 387.8)= 177.3 mm2/m

Av, min

= 0.062 fc'(bws/fyt) = 45.2 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

= 55.7 mm2

= 142.0 mm2

area of links provided (2#10), Av


Maximum spacing of ties

= 194 mm11.5.5.1&11.5.5.3
OK

High shear zone: 36.465 m to 38.625 m


Actual spacing of ties, s

= 90 mm

Design axial force, Nu

= -17.09 kNm

Shear force, Vu

= 159.61 kN

Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 72.20 kN

required (Av/s)

R11.5.7

= (Vu - Vc/fytd)

= (159607.66 - 0.85 72200.68/0.85 275 387.8)

Av, min

= 0.062 fc'(bws/fyt) = 23.2 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

area of links provided (2#10), Av


Maximum spacing of ties

= 28.6 mm2

= 142.0 mm2
= 194 mm11.5.5.1&11.5.5.3

OK

11.2&11.3

= 1083.7 mm2/m

Member M7 Span 20

Detailed ACI Design Requirements

Section Property: 250 x 449


Span Length
Width
Covers:

= 3.000

= 250 mmDepth

Rectangular section
= 450 mm

Top = 40 mm Bottom = 40 mm Side = 40 mm

Member M7 Span 20

Detailed ACI Main Reinforcement

Hogging: at 39.025 m from the start of the member


Moment applied to section

= 163.24 kNm

Effective depth of tension reinforcement

= 388 mm

Depth to compression reinforcement

d'

= 87 mm

Limit for compression steel


Rn

= (Mu/bd2)

Rnt

= 4.78

= 4.82

Rn > Rnthence compression steel required.


As'

= (M'n/Eu(1 - d'/c) (d - d'))

Tension Bars provided

= 21.6 mm2
= 2#25

Actual area of tension reinforcement

= 1020 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 1.05 %

Compression Bars provided

= 3#25 3#25
= 3060 mm2

Actual area of compression reinforcement


Actual % of compression reinforcement

= 3.16 %

Minimum horizontal distance between top bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between top bars

= 100 mm

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)

= 458.18 mm

Largest actual space between tension bars

10.6.4

= 126 mm

Actual neutral axis depth in section

= 85.38 mm

Moment capacity of section

= 90.73 kNm
NOT OK

Sagging: at 41.825 m from the start of the member


Moment applied to section

= 130.22 kNm

Effective depth of tension reinforcement

= 368 mm

Depth to compression reinforcement

d'

= 62 mm

Limit for compression steel

Rnt

= 4.78

Rn

= (Mu/bd2)

= 4.28

As

= (M/fy z)

= 1662.9 mm2

Tension Bars provided

= 3#25 2#25

Actual area of tension reinforcement

= 2550 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 2.77 %

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)

= 458.18 mm

10.6.4

Largest actual space between tension bars

= 63 mm

Actual neutral axis depth in section

= 184.87 mm

Moment capacity of section

= 182.44 kNm
OK

Member M7 Span 20

Detailed ACI Span / Depth Check

Basic span / depth ratio


Strength modification factor

= 21.00
= 0.4 + fy / 700

Hence, modified span / depth ratio


Actual span / depth ratio

9.5.2.1
= 0.79
= 16.65

= 6.67

OK

Member M7 Span 20

Detailed ACI Shear Reinforcement

High shear zone: 39.025 m to 40.900 m


Actual spacing of ties, s

= 90 mm

Design axial force, Nu

= -28.75 kNm

Shear force, Vu

= 150.85 kN

Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 69.93 kN

required (Av/s)

R11.5.7

= (Vu - Vc/fytd)

= (150850.76 - 0.85 69929.68/0.85 275 387.8)

Av, min

= 0.062 fc'(bws/fyt) = 23.2 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

= 28.6 mm2

11.2&11.3

= 1008.4 mm2/m

= 142.0 mm2

area of links provided (2#10), Av


Maximum spacing of ties

= 194 mm11.5.5.1&11.5.5.3
OK

High shear zone: 40.900 m to 41.824 m


Actual spacing of ties, s

= 175 mm

Design axial force, Nu

= -28.75 kNm

Shear force, Vu

= 79.26 kN

Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 69.93 kN

required (Av/s)

R11.5.7

= (Vu - Vc/fytd)

11.2&11.3

= (79263.06 - 0.85 69929.68/0.85 275 387.8)= 218.7 mm2/m

Av, min

= 0.062 fc'(bws/fyt) = 45.2 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

= 55.7 mm2

area of links provided (2#10), Av


Maximum spacing of ties

= 194 mm11.5.5.1&11.5.5.3
OK

Member M7 Span 21

Detailed ACI Design Requirements

Section Property: 250 x 449


Span Length
Width
Covers:

= 1.200

= 250 mmDepth

Rectangular section
= 450 mm

Top = 40 mm Bottom = 40 mm Side = 40 mm

Member M7 Span 21

= 142.0 mm2

Detailed ACI Main Reinforcement

Sagging: at 41.825 m from the start of the member


Moment applied to section

= 129.90 kNm

Effective depth of tension reinforcement

= 368 mm

Depth to compression reinforcement

d'

= 62 mm

Limit for compression steel

Rnt

= 4.78

Rn

= (Mu/bd2)

= 4.27

As

= (M/fy z)

= 1658.0 mm2

Tension Bars provided

= 3#25 2#25

Actual area of tension reinforcement

= 2550 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 2.77 %

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)
Largest actual space between tension bars

= 458.18 mm
= 63 mm

Actual neutral axis depth in section

= 184.87 mm

Moment capacity of section

= 182.44 kNm
OK

Member M7 Span 21

Detailed ACI Span / Depth Check

10.6.4

Basic span / depth ratio


Strength modification factor

= 21.00
= 0.4 + fy / 700

Hence, modified span / depth ratio


Actual span / depth ratio

9.5.2.1
= 0.79
= 16.65

= 2.67

OK

Member M7 Span 21

Detailed ACI Shear Reinforcement

High shear zone: 41.824 m to 43.024 m


Actual spacing of ties, s

= 175 mm

Design axial force, Nu

= -24.60 kNm

Shear force, Vu

= 70.93 kN

Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 70.74 kN

required (Av/s)

R11.5.7

= (Vu - Vc/fytd)

11.2&11.3

= (70928.39 - 0.85 70738.44/0.85 275 387.8)= 119.1 mm2/m

Av, min

= 0.062 fc'(bws/fyt) = 45.2 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

= 55.7 mm2

area of links provided (2#10), Av


Maximum spacing of ties

= 194 mm11.5.5.1&11.5.5.3
OK

Member M7 Span 22

Detailed ACI Design Requirements

Section Property: 250 x 449


Span Length

= 1.800

= 142.0 mm2

Rectangular section

Width
Covers:

= 250 mmDepth

= 450 mm

Top = 40 mm Bottom = 40 mm Side = 40 mm

Member M7 Span 22

Detailed ACI Main Reinforcement

Sagging: at 43.025 m from the start of the member


Moment applied to section

= 76.98 kNm

Effective depth of tension reinforcement

= 388 mm

Depth to compression reinforcement

d'

= 62 mm

Limit for compression steel

Rnt

= 4.78

Rn

= (Mu/bd2)

= 2.28

As

= (M/fy z)

= 860.9 mm2

Tension Bars provided

= 2#25

Actual area of tension reinforcement

= 1020 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 1.05 %

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 100 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)
Largest actual space between tension bars

= 458.18 mm
= 126 mm

Actual neutral axis depth in section

= 73.95 mm

Moment capacity of section

= 89.97 kNm
OK

10.6.4

Hogging: at 44.625 m from the start of the member


Moment applied to section

= 219.31 kNm

Effective depth of tension reinforcement

= 388 mm

Depth to compression reinforcement

d'

= 87 mm

Limit for compression steel


Rn

Rnt

= (Mu/bd2)

= 4.78

= 6.48

Rn > Rnthence compression steel required.


As'

= 887.9 mm2

= (M'n/Eu(1 - d'/c) (d - d'))

Tension Bars provided

= 2#25

Actual area of tension reinforcement

= 1020 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 1.05 %

Compression Bars provided

= 3#25 3#25
= 3060 mm2

Actual area of compression reinforcement


Actual % of compression reinforcement

= 3.16 %

Minimum horizontal distance between top bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between top bars

= 100 mm

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)
Largest actual space between tension bars

= 458.18 mm
= 126 mm

Actual neutral axis depth in section

= 85.38 mm

Moment capacity of section

= 90.73 kNm
NOT OK

10.6.4

Member M7 Span 22

Detailed ACI Span / Depth Check

Basic span / depth ratio


Strength modification factor

= 21.00
= 0.4 + fy / 700

Hence, modified span / depth ratio


Actual span / depth ratio

9.5.2.1
= 0.79
= 16.65

= 4.00

OK

Member M7 Span 22

Detailed ACI Shear Reinforcement

High shear zone: 43.024 m to 44.625 m


Actual spacing of ties, s

= 90 mm

Design axial force, Nu

= -20.73 kNm

Shear force, Vu

= 199.66 kN

Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 71.49 kN

required (Av/s)

R11.5.7

= (Vu - Vc/fytd)

= (199663.01 - 0.85 71491.33/0.85 275 387.8)

Av, min

= 0.062 fc'(bws/fyt) = 23.2 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

area of links provided (2#10), Av


Maximum spacing of ties

= 142.0 mm2
= 97 mm 11.5.5.1&11.5.5.3

OK

Member M7 Span 23

= 28.6 mm2

11.2&11.3

= 1532.2 mm2/m

Detailed ACI Design Requirements

Section Property: 250 x 449


Span Length
Width
Covers:

= 3.250

= 250 mmDepth

Rectangular section
= 450 mm

Top = 40 mm Bottom = 40 mm Side = 40 mm

Member M7 Span 23

Detailed ACI Main Reinforcement

Hogging: at 45.025 m from the start of the member


Moment applied to section

= 232.90 kNm

Effective depth of tension reinforcement

= 388 mm

Depth to compression reinforcement

d'

= 87 mm

Limit for compression steel


Rn

= (Mu/bd2)

Rnt

= 4.78

= 6.88

Rn > Rnthence compression steel required.


As'

= (M'n/Eu(1 - d'/c) (d - d'))

Tension Bars provided

= 1097.9 mm2
= 2#25

Actual area of tension reinforcement

= 1020 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 1.05 %

Compression Bars provided

= 3#25 3#25
= 3060 mm2

Actual area of compression reinforcement


Actual % of compression reinforcement

Minimum horizontal distance between top bars

= 3.16 %

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between top bars

= 100 mm

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)

= 458.18 mm

Largest actual space between tension bars

10.6.4

= 126 mm

Actual neutral axis depth in section

= 85.38 mm

Moment capacity of section

= 90.73 kNm
NOT OK

Sagging: at 48.075 m from the start of the member


Moment applied to section

= 211.51 kNm

Effective depth of tension reinforcement

= 363 mm

Depth to compression reinforcement

d'

= 62 mm

Limit for compression steel


Rn

= (Mu/bd2)

Rnt

= 4.78

= 7.15

Rn > Rnthence compression steel required.


As'

= (M'n/fy (d - d'))

Tension Bars provided

= 941.7 mm2
= 3#25 3#25

Actual area of tension reinforcement

= 3060 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 3.38 %

Compression Bars provided

= 2#25
= 1020 mm2

Actual area of compression reinforcement


Actual % of compression reinforcement

= 1.13 %

Minimum horizontal distance between top bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between top bars

= 100 mm

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)

= 458.18 mm

Largest actual space between tension bars

= 63 mm

Actual neutral axis depth in section

= 147.90 mm

Moment capacity of section

= 227.18 kNm
OK

Member M7 Span 23

Detailed ACI Span / Depth Check

Basic span / depth ratio


Strength modification factor

= 21.00
= 0.4 + fy / 700

Hence, modified span / depth ratio


Actual span / depth ratio

9.5.2.1
= 0.79
= 16.65

= 7.22

OK

Member M7 Span 23

Detailed ACI Shear Reinforcement

High shear zone: 45.025 m to 48.074 m


Actual spacing of ties, s

= 90 mm

Design axial force, Nu

= -39.21 kNm

Shear force, Vu
Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 194.76 kN
= 67.89 kN

11.2&11.3

10.6.4

required (Av/s)

= (Vu - Vc/fytd)

R11.5.7

= (194757.39 - 0.85 67892.45/0.85 275 387.8)

Av, min

= 0.062 fc'(bws/fyt) = 23.2 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

= 28.6 mm2

= 142.0 mm2

area of links provided (2#10), Av


Maximum spacing of ties

= 97 mm 11.5.5.1&11.5.5.3
OK

Member M7 Span 24

Detailed ACI Design Requirements

Section Property: 250 x 449


Span Length
Width
Covers:

= 2.750

= 250 mmDepth

Rectangular section
= 450 mm

Top = 40 mm Bottom = 40 mm Side = 40 mm

Member M7 Span 24

Detailed ACI Main Reinforcement

Sagging: at 48.075 m from the start of the member


Moment applied to section

= 207.30 kNm

Effective depth of tension reinforcement

= 363 mm

Depth to compression reinforcement

d'

= 62 mm

Limit for compression steel


Rn

= (Mu/bd2)

Rn > Rnthence compression steel required.

Rnt
= 7.01

= 4.78

= 1511.9 mm2/m

As'

= 885.1 mm2

= (M'n/fy (d - d'))

Tension Bars provided

= 3#25 3#25

Actual area of tension reinforcement

= 3060 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 3.38 %

Compression Bars provided

= 2#25
= 1020 mm2

Actual area of compression reinforcement


Actual % of compression reinforcement

= 1.13 %

Minimum horizontal distance between top bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between top bars

= 100 mm

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)

= 458.18 mm

Largest actual space between tension bars

= 63 mm

Actual neutral axis depth in section

= 147.90 mm

Moment capacity of section

= 227.18 kNm
OK

Hogging: at 50.825 m from the start of the member


Moment applied to section

= 188.00 kNm

Effective depth of tension reinforcement

= 388 mm

Depth to compression reinforcement

d'

= 87 mm

Limit for compression steel


Rn

= (Mu/bd2)

Rnt

= 4.78

= 5.56

Rn > Rnthence compression steel required.


As'

= (M'n/Eu(1 - d'/c) (d - d'))

= 404.1 mm2

10.6.4

Tension Bars provided

= 2#25

Actual area of tension reinforcement

= 1020 mm2

Minimum area of tension reinforcement

= 0.51 % 10.5

Actual % of tension reinforcement

= 1.05 %

Compression Bars provided

= 3#25 3#25
= 3060 mm2

Actual area of compression reinforcement


Actual % of compression reinforcement

= 3.16 %

Minimum horizontal distance between top bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between top bars

= 100 mm

Minimum horizontal distance between bottom bars

= 33 mm 3.3.2(c)&7.6.1

Smallest actual horizontal space between bottom bars

= 37 mm

Maximum spacing of tension bars, s


= 380 (280/fs) - 2.5cc 300(280/fs)
Largest actual space between tension bars

= 458.18 mm
= 126 mm

Actual neutral axis depth in section

= 85.38 mm

Moment capacity of section

= 90.73 kNm
NOT OK

Member M7 Span 24

Detailed ACI Span / Depth Check

Basic span / depth ratio


Strength modification factor

= 21.00
= 0.4 + fy / 700

Hence, modified span / depth ratio


Actual span / depth ratio

9.5.2.1
= 0.79
= 16.65

= 6.11

10.6.4

OK

Member M7 Span 24

Detailed ACI Shear Reinforcement

High shear zone: 48.074 m to 50.824 m


Actual spacing of ties, s

= 90 mm

Design axial force, Nu

= -32.60 kNm

Shear force, Vu

= 184.38 kN

Vc = 0.17 [1 + (0.29 Nu/Ag)] fc' bw d

= 69.18 kN

required (Av/s)

R11.5.7

= (Vu - Vc/fytd)

= (184377.77 - 0.85 69179.43/0.85 275 387.8)

Av, min

= 0.062 fc'(bws/fyt) = 23.2 mm2

(11-13)

(0.35 bws) / fyt

11.5.6.3

area of links provided (2#10), Av


Maximum spacing of ties

= 28.6 mm2

= 142.0 mm2
= 97 mm 11.5.5.1&11.5.5.3

OK

11.2&11.3

= 1385.3 mm2/m

You might also like