You are on page 1of 16

The Inspection Guide

Periodic Inspection

Welcome to the Bureau Veritas inspection guide, which provides information


on a range of services to facilitate mechanical and electrical, as well as health,
safety and environmental service compliance.

Contents
Introduction

03

Regulations 04
- General health and safety
- Work equipment
- Lifting
- Electrical
- Pressure systems
- Power presses and machinery
- Local Exhaust Ventilation (LEV)

Lifting Operations and Lifting Equipment Regulations (LOLER)

09

Power presses and process machinery

09

Pressure System Safety Regulation (PSSR)

10

Electrical

11

Health Safety and Environment Services


- Health and safety at work
- Control of Substances Hazardous to Health (COSHH)
- Fire risk assessment

12
12
13
14

Contact details

16

Powerful solutions for forward-thinking organisations


Bureau Veritas is one of the worlds leading professional service companies, with a comprehensive
range of conformity assessment and certification solutions spanning diverse market sectors. Our
global network of experts provides clients with the guidance and support to achieve, maintain and
demonstrate full compliance with their quality, health and safety, environment (QHSE) and social
responsibility requirements.
Our clients are progressive organisations who depend on us to deliver powerful, tailored, yet costeffective solutions.

A unique portfolio of services


Our full range of compliance related services
are highlighted below:

Management systems and permits


HSE compliance management
HSE management tools
HSE training services
Asbestos
Indoor air and water hygiene
Periodic inspection and testing of electrical
installations (Fixed and PAT)
Examination of lifts and lifting equipment
to LOLER and PUWER
Examination of pressure vessels to PSSR
Examination of local exhaust ventilation
equipment to the COSHH Regulations.

We also offer a full suite of quality, health,


safety and environmental services:

Vendor inspection and audit


Risk and safety assessments
Asset integrity management
Industrial product certification
Health, safety and fire risk management
Environmental studies and impact
assessment
Sustainability and corporate social
responsibility
Supply chain studies.

The Engineering Technical Specialists (ETS);


directed by our senior engineering team,
provide clients with the following compliance
verification and technical assurance services:

PUWER assessment
CE marking
Type approval
Machinery directive works
Pre purchase Inspections
Failure mode and life cycle trend analysis
Lift management programmes
Expert witness
Technical training
Written schemes of examination
PSSR - Design inspections and repair
verification

Full details of all our services can be found on


our website at

www.bureauveritas.co.uk/portfolio

Regulations
General health and safety
The Health & Safety at Work Act (HSAW) 1974 (1978 in Northern Ireland) covers all work places
and defines the obligation of all employers and employees to ensure a safe working environment.
Employers are required to assess risks and have policies and procedures in place to control those
risks. Whilst inspections are not a requirement under this legislation, they are recognised as part of
providing a safe working environment.

Work equipment
The Provision and Use of Work Equipment Regulations (PUWER) 1998 (1999 in Northern Ireland)
covers all work equipment and any activity involving the equipment including starting, stopping,
programming, setting, transporting, repairing, modifying, maintaining, servicing and cleaning. Users
must carry out PUWER assessments and make sure that all equipment is both safely installed and
safe to use. Regular inspections must be carried out by a competent person and documented. Our
qualified team of Engineer-Surveyors are well equipped to carry out the inspections for you.
In addition to these general pieces of legislation, there are specific regulations which apply to
particular types of equipment, as follows:

Lifting
The key piece of legislation concerning lifting equipment is the Lifting Operations and Lifting
Equipment Regulations (LOLER) 1998 (1999 in Northern Ireland). LOLER covers all working
equipment with a lifting function. It applies in addition to PUWER, to offer adequate safeguards to
people working with lifting equipment. The user is required to:

use a competent person to plan lifting operations


ensure that the equipment is suitable
ensure that the lifting operation will not endanger people in the vicinity
assess requirements for inspections of the lifting equipment and accessories
have regular thorough examinations carried out by a suitably competent person.

Note that LOLER applies not only to the equipment itself, but also to the safe operation of that
equipment.

Timing of inspections
Following the installation of new plant and machinery the requirements for initial examination vary
according to the regulations which apply. The prudent approach, and our recommendation, is that all
equipment is examined by a competent person following its installation / commissioning and before
it is first put into use. There are certain circumstances where this is a mandatory requirement, if you
require guidance on a specific situation then please contact us for advice.

Frequency of inspections
Lifting equipment which lifts people

6 months

Lifting accessories, including shackles, hooks, chains, fittings etc

6 months

All other lifting equipment including cranes and loading equipment

12 months

In accordance with an examination scheme


In all cases a risk assessment should be undertaken to ensure the examination frequency
is appropriate

LOLER definitions:

Accessory for lifting work equipment for attaching loads to machinery for lifting
Lifting equipment work equipment for lifting or lowering loads including attachments for
anchoring, fixing or supporting it
Work equipment any machinery, appliance, apparatus, tool or installation for use at work

Electrical
The Electricity at Work Regulations (EAWR) 1989 (1991 in Northern Ireland) are made under the
Health and Safety at Work Act 1974. The regulations require that employers as duty holders must
provide a safe working environment with regard to all electrical equipment and systems, regardless
of when they were manufactured, installed or brought into use.
The employer, self-employed and employee all have duties and obligations in complying with the
requirements of the regulations, which apply to all places of work, with no exemptions. All electrical
systems must be maintained in a safe condition and an important aspect of such maintenance is
periodic inspection and testing.

Fixed electrical wiring inspection and testing


To meet the requirements of the IET wiring regulations all electrical systems, from the main intake
through to the final fixed appliances and accessories, must be inspected and tested on a regular
basis. The frequency of this testing is dependent on the type of premises and varies between three
months and five years.
Many companies struggle to complete the testing using in-house personnel due to lack of time,
resources and knowledge of this specialised field.

Portable electrical appliance testing


As part of our comprehensive service, Bureau Veritas are able to carry out all inspection and testing
on your portable electrical appliances. Results can be presented in hard copy, CD format or web
based reporting, with a summary of items inspected and tested together with the test results and
details of items that failed.

Risk assessments of fixed electrical installations


A risk assessment analyses the physical condition of the electrical installation and determines the
various levels of risk present both to staff and property. Identifying the levels and locations of risks
throughout an installation enables you to deal immediately with any previously unknown dangerous
situations. You will also be able to plan a maintenance / repair programme that spreads both the
workload and costs in a phased manner whilst targeting the high-risk areas first.

Tracing / labelling and scheduling of electrical installations


To assist with maintenance, we are able to generate detailed electrical distribution drawings and
distribution board schedules. These can be issued in any size and on computer disk in CAD form.
individual circuits can also be labelled for identification purposes if required.

Thermographic surveys
As part of fixed wiring inspection and testing programmes, or as a specific service, we can, with the
use of thermal imaging, identify problems before they cause breakdowns or become major safety
issues. In the vast majority of cases this can be done without any disruption to power supply. Regular
thermographic surveying can result in major cost savings through early identification of hotspots
and potential breakdowns.

Electrical safety auditing


Bureau Veritas can provide independent audits to assess your companys compliance with relevant
codes of practice and regulations. The audit provides a true picture of areas where staff may be
at risk due to lack of procedures for working with or around electrical equipment. It also seeks
to establish that all relevant documentation and test results are available, together with random
visual inspections of the site. The results of such auditing can help to reduce insurance premiums.

Emergency lighting inspection and test


Bureau Veritas tests and inspects emergency lighting to ensure compliance with BS 5266, which
comprises identification of the types of light, a duration test, the correct signage and the quantity
and placement of each light. On completion of the inspection and test a full report, NICEIC
certificate and system log (as required by BS 5266) are issued to confirm compliance.

Further electrical services offered include:

electrical load analysis


high voltage testing and maintenance
public entertainment licensing testing.
Lightening Protection systems inspection and testing

Pressure systems
The Pressure Systems Safety Regulations (PSSR) 2000 (2004 in Northern Ireland) require pressure
systems to be inspected in accordance with a written scheme of examination.
The pressure systems safety regulations deal with plant containing a relevant fluid which is defined
by the regulations as:

a gas > 0.5 bar


steam at any pressure.

The range of equipment covered by PSSR is extensive and includes compressed air systems, boilers,
refrigeration, air conditioning plant and others. Plant not containing a relevant fluid is still subject
to certain regulations under PSSR. To ensure compliance, we recommend this type of plant, typically
hot water boilers, is inspected also.
Following an assessment, a written scheme of examination must be drawn up by a competent
person, and must include a definition of the items included in the system and details of frequency
of inspection.
Inspection procedures normally include both a thorough examination (with the system being shut
down and vessels opened up) and a working examination of the system under normal operation.
Inspection intervals may vary according to the application of the system(s). The intervals shown in
the table are those recommended by the Safety Assessment Federation (SAFed).

Power presses and machinery


Requirements for inspections of power presses are covered in Part 4 of PUWER the safe Use
of power presses. This requires that power presses with automatic, photo-electric or interlocking
guards are thoroughly examined every 6 months. Power presses with fixed guards or enclosed tools
should be thoroughly examined every 12 months.
Process machines with guards should also be inspected regularly, although intervals are not
specified.
For paper guillotines and injection moulding machines, there are guidance notes which recommend
periodic safety inspections.
Other guarded machinery is covered in Part 2 of PUWER and should also be inspected regularly.
Although intervals are not specified, the frequency is determined by the risk from deterioration.

Local Exhaust Ventilation (LEV)


There are three sets of Regulations, which require employers to operate and maintain LEV
equipment:

The Control of Substances Hazardous to Health Regulations 2002


Control of Lead at Work Regulations 2002
The Control of Asbestos Regulations 2012.

The COSHH regulations aim to ensure the safety of all people who deal with hazardous substances.
Employers need to assess the risks associated with the handling and use of hazardous substances
and eliminate the risks where possible.
To meet the requirements of these regulations employers are required to ensure that local exhaust
ventilation is thoroughly examined and tested by a competent person.

Lifting operations and lifting equipment regulations


Periodic inspection
Equipment

Periodicity (months)

Governing Regulation(s)

Notes

Escalators and moving walks

PUWER

Inspection under workplace regulations


SAFed guidelines 2011

Excavators

12

PUWER

Excavators fall under PUWER if used only for


excavating but must comply with LOLER if
used for any form of lifting

Builders hoists

12

LOLER / PUWER

Cranes and lifting equipment

12

LOLER / PUWER

In all cases, 12 months will be reduced to 6



months if used for lifting persons

Forklift trucks

12

LOLER / PUWER

Goods, lifts and hoists

12

LOLER / PUWER

Passenger lifts

LOLER / PUWER

Lifting accessories

LOLER / PUWER

Lorry loader cranes

12

LOLER / PUWER

Motor vehicle lifting tables

LOLER / PUWER

Power presses and process machinery


Periodic inspection
Equipment

Periodicity (months)

Governing regulation(s)

Notes

Power presses and press


brakes

PUWER

12 months where press has fixed guards only


or enclosed tool

Paper cutting guillotines

Metal cutting guillotines

Plastic injection moulding


machines

12

Process machinery

Depends on
machinerys hazards

Pressure system safety regulation


Periodic inspection
PSSR requires a written scheme that has to have a nominated periodicity for the type of inspections required.

Equipment

Periodicity (months)

Governing regulation(s)

Notes

Compressed air systems

26

PSSR

Normally inspected at 24 month frequency

Steam boilers and boilers


> 100C

14

PSSR

Normally inspected at 12 month frequency

Refrigeration and air


conditioning systems

48

PSSR

Steam generation equipment


(autocalves etc)

14

PSSR

Normally inspected at 12 month frequency

Steam receiving plant

26

PSSR

Normally inspected at 24 month frequency

Other pressure systems

12 - 120

PSSR

Dependent on vessel type, contents and


application

Electrical
Periodic inspection

10

Equipment

Periodicity (months)

Governing regulation(s)

Notes

Electrical installations and


equipment

3 - 60

EAWR 1989. BS7671:


Requirements for Electrical
Installations (17th editions
IET wiring regulations)

Frequency varies according to the type of


installation and may be determined by local
licensing requirements for places of public
entertainment. Generally industrial premises
are 36 months and commercial premises are 60
months. Local licensing authorities may require a
12 month frequency for places where the general
public use for entertainment or leisure

Quarries

6 - 12

EAWR 1989 & Electrical


Safety in Quarries

The quarry operator should have a maintenance


scheme in place to increase the full inspection and
testing regime of every 6 months

Inspection and testing


of Portable Electrical
Appliances (PAT)

3 - 60

EAWR 1989. IET code of


practice for In-service
Inspection and Testing of
Electrical Equipment. HS
(G) 107 maintaining portable
and transportable electrical
equipment

Frequency varies according to the type of


equipment and environment. Risk assessment
should be carried out to set the inspection and
testing regime. Guidance on frequency is given in
IET Code of Practice for In-service Inspection and
Testing of Electrical Equipment

Electrical
Periodic inspection continued
Equipment

Periodicity (months)

Governing regulation(s)

Notes

Inspections of electromechanical plant and


machinery

12-24

EAWR and PUWER

Frequency varies according to usage and


environmental condition in which plant is operating
(eg temperature, moisture, dust, corrosive,
weather conditions variations in load etc).

Petroleum installations

12 months or as
required by local
licensing authorities

EAWR 1989. Association for


Petroleum and Explosives
Administration (AEPA) and
The Institute of Petroleum
(IP) guidance for the design,
construction, modification
and maintenance of petrol
filling stations

Hazardous areas (explosive


atmosphere)

12

EAWR 1989. BSEN60079


Explosive Atmospheres.
ATEX through DSEAR
(Dangerous Substances
and Explosive Atmosphere
Regulations 2002)

Types of inspections varies from a visual to full


detailed inspection and testing. Year 1 to be
detailed inspection and testing with years 2 & 3
visual inspection depending upon condition of
equipment and its usage

Emergency lighting

6 - 12

BS5266 Code of Practice for


the Emergency Lighting of
Premises

Full testing to be carried out every 12 months.


Every 6 months all system to be tested for
function. Generally Bureau Veritas will carry out 12
monthly tests

Lightning protection

12

BSEN62305 Protection
Against Lightning. BS7430
Code of Practice for Earthing

11

Health safety and environment services


Health and safety at work

Periodic inspection
Equipment

Periodicity (months)

Governing regulation(s)

Notes

General H&S risk


assessment and
compliance audit

Review annually

HSAW 1974, Management


of HSAW 1999 (Reg 3),
regulatory, reform order
2005 (Reg 9)

The employer or person in control of the property/operation must


carry out a H&S risk assessment and a compliance audit at the
same time. We check the status in relation to approx 44 H&S
statutory requirements

Noise

Initial

Control of Noise at Work


Regulations 2005

Carry out risk assessment under Regulation 5

Health & Safety Policy

Review annually

HSAW 1974

Is the Health & Safety Policy held current and up to date?. How
is it made available to staff?. Review procedures and advice as
appropriate

Information, instruction
and training

Review annually

HSAW 1974

Insure that suitable induction and specific health and safety


training is given to enable members of staff to carry out their
roles and responsibilities safely

Permit to Work

Review annually

Management of Health and


Safety at Work Regulations
1997

Review any format and specific controls to high risk operations.


Identify any areas overlooked which permit control will benefit
the client to improve safety and risk

Confined spaces

Review annually

Confined Spaces
Regulation 1997

Identify and undertake any work activity under confined space is


complying with the regulation

DSE (Display Screen


Equipment)

Review when
any significant
changes arise in the
workstation set up or
staff health

Health & Safety (Display


Screen Equipment)
Regulations 1992

Ensure all DSE is undertake and review on a regular base

Manual handling
assessments

Review annually

Manual Handling
Operations Regulations
1992

Assess work activities in the work place which involves staff


moving materials and assess whether such manual handling is a
risk and necessary. Provide advise as required

Provision for first aid

Review annually

Health & Safety (First Aid)


Regulation 1981

Check the first aid coverage, training, facilities and provision to


ensure it is adequate for the needs of the client

Personal protective
equipment

As per manufactures
instructions

Personal Protective
Equipment at Work
Regulations 1992

Assess work activities in the work place which exposes staff to


high risk of injury that require further protection from harm.
Check the equipment is appropriate and in good order. Provide
advice as required

DDA Regulation and keep


only the 2005

The DDA requires service providers and all workplaces to make


reasonable adjustments to overcome physical features, which
obstruct the less able

Provision for disabled


persons

12

Vibration risk
assessment

Annually or if work
requirements change

Control of Vibration at
Work Regulation 2005

Ascertain if a vibration risk assessment is required or review if


one has been carried out. Provide advice as appropriate. Under
Regulation 6, carry out a risk assessment

Working at height risk


assessment

Annually

Working at Height
Regulations 2005

Ascertain if a working at height risk assessment is required or


review if one has been carried out. Provide advice as appropriate

Control of Substances Hazardous to Health (COSHH)

Periodic inspection
Equipment

Periodicity (months)

Governing regulation(s)

Notes

CMR (Carcinogenic
Mutagenic and Reprotoxic)

Initial

COSHH

Undertake regulation and carry out a risk


assessment of any material on site and
implement any changes suitable

Initial asbestos survey

Initial

Produce an asbestos
management plan

Initial

Control of Asbestos Regulations


2012, Regulation 4 (L127 ACoP)

Approved code of practice L143; would


not apply to buildings constructed after
November 1999. Buildings surveyed to
MDHS 100 and HSG 264

Review of the asbestos


management plan

12

Re - Inspection of asbestos
materials

3 - 12

According to the condition of the material

Management of asbestos
record

Ongoing

Tracking incidences and changes on a


database

Monitoring services
Equipment

Periodicity (months)

Governing regulation(s)

Notes

Air monitoring and 4 stage


clearance for asbestos

On request

Guidance notes HSG247/


HSG248

Reassurance air monitoring and the removal


or encapsulation of asbestos; ad hoc

Project management

On request

Legionella

Initial

COSHH. ACOP L8

Legal requirement to carry out a risk


assessment and review at least once every
2 years

Local exhaust ventilation


dust fume / vapour extraction

14

COSHH. Regulation 6&9


guidance note HSG 258

6 monthly for metal dust


6 monthly in non-ferrous foundries

Local exhaust ventilation


shot blast units

COSHH. Regulation 6&9


guidance note HSG 258

Independent project management and


observation on behalf of the client

13

Fire risk assessment

Periodic inspection
Equipment

Periodicity (months)

Governing regulation(s)

Notes

Fire Risk Assessment

12 months / property
changes

Applicable to all equipment:

Should be reviewed following the expiry of time


recommended for remedial work arising from the
previous assessment

The Regulatory Reform (Fire


Safety) Order 2005 (England
and Wales)

Maintenance and testing of


emergency lighting

Monthly / 6 months /
annual

Fire extinguishers

12

Fire exit routes and fire


exits

Daily

Fire alarm systems

Weekly / 6 months /
annual

Test alarm weekly from manual call-points


sequential through the building. All other actions
should be undertaken by a competent engineer

Smoke and heat detectors

12

Ensure that all part of fire alarm and detective


system are serviced and tested in accordance of
the recommendation in the fire risk assessment

Sprinklers

Weekly / 6 months /
annual

Test weekly by operation of test valve. All other


actions should be undertaken by a competent
engineer

Dry / wet risers

6 months / annual

The visual inspection may be done in-house, but


the annual pressure test should be undertaken by
a competent engineer

Hosereels

6 months / annual

The 6 monthly visual inspection may be done


in-house, but the annual pressure test should be
undertaken by a competent engineer

Fire drill

6 months / annual

Drills should be conducted not less than annually


for low to medium office / shop type risks, and not
less than 6 monthly for hotels and buildings to
which the public have access, or as recommended
in the fire risk assessment

The Fire Safety Regulations


2006 (Scotland)
The Fire Safety Regulations
2010 (Northern Ireland)

Carry out inspection of all emergency lights


Ensure that a suitable number and type of
extinguishers are provided and they are serviced
by an approved contractor
Carry out checks of all fire exits and fire exit
routes - record findings

We have endeavoured to ensure details are accurate. No responsibility can be accepted for any errors or omissions.

14

Fire risk assessment

Periodic inspection continued


Equipment

Periodicity (months)

Governing regulation(s)

Notes

Ventilation and smoke


extraction systems

Tested weekly if
interfaced with fire
alarm systems

Applicable to all equipment:

Serviced annually by competent engineers

Smoke curtains

Tested weekly if
interfaced with fire
alarm systems

The Regulatory Reform (Fire


Safety) Order 2005 (England
and Wales)

Serviced annually by competent engineers

Fire / smoke dampers

Tested weekly if
interfaced with fire
alarm systems

The Fire Safety Regulations


2012 (Scotland)

Serviced annually by competent engineers

The Fire Safety Regulations


2010 (Northern Ireland)

Staircase pressurisation

Tested weekly if
interfaced with fire
alarm systems

Serviced annually by competent engineers

Fire suppression systems

6 months / annual

Serviced annually by competent engineers / room


integrity when material change takes place

Fire hydrants on site

12

Serviced annually by competent engineers

15

Our geographical network

Global QHSE provider


Established: 1828
Coverage: 140 countries
Locations: 1,330 offices and laboratories
Employees: 61,600
Aberdeen

Servicing UK clients in:


Grangemouth
Glasgow

Newcastle Upon Tyne


Belfast

Durham

Dublin
Warrington

Birmingham

Hull

Manchester

Great Yarmouth

Milford Haven
Harlow
London

Witham
Canvey Island

Banking and international finance


Food supply chain
Government and public sector
Marine and shipping
Metals and minerals
Nuclear
Oil and gas
Power and utilities
Property
Refining and processing
Retail and consumer products
supply chain

Transport and infrastructure


Wind: onshore and offshore

Americas

270 offices and labs


16,300 employees

Europe, Middle East and Africa

Asia-Pacific

670 offices and labs


23,600 employees

390 offices and labs


21,700 employees

FSC
t: 0845 600 1828 e: info@uk.bureauveritas.com w: www.bureauveritas.co.uk

BR/IGB/0414

Plymouth

You might also like